Project Name: Peñasquito Pyrite Leach 000 509 F76014

Contract Number: HT-7446 15 Jan 2015


Project Location: Zacatecas, México Page 1 of 1

LOW VOLTAGE POWER CABLE INSTALLATION & TEST RECORD


Tag Description: Tag No.:
P. O. No.: Construction Contractor: Turnover System:
Work Package:  ICA Fluor  Subcontractor Sub – System:
Dwg.: Status Legend: OK, PL (Punch List), NA Area / Unit:

Note: This form is to be used for cable voltages greater than 30V and up to and including 750V
ICA Fluor ICA Fluor
Activities Status
Construction Quality
Cable tray is free of sharp edges & cable size, type, voltage, location, segregation,
2. installation and routing is in accordance with drawings
Cable is adequately secured and supported without kinks and proper spacing
4. maintained between power & instrument cables as per specifications and code
Verify cable voltage rating & cable pulling temperature are as per specifications and
6. manufacturer’s maximum pulling tension has not been exceeded
8. Cable connectors are the correct type, size and correctly installed
10. Cable ends sealed after cutting
12. Grounding and bonding is correct as per design drawings
14. Check bending radius is within manufacturer recommendations
Cable tag identification is correct according to drawings, project specifications and
16. is installed at transits and penetrations
18. Confirm mechanical protection is installed as required
Check there is no damage to cores, termination chamber layout is satisfactory, core
20. tag identification is correct and that crimped fittings, when specified, are satisfactory
22. Confirm spare cores are dressed to conform to design drawings and specifications
24. Continuity in all cores, ground and armour
26. Check all enclosure covers have been replaced and no bolts are missing
28. Confirm CSA identification
Insulation Resistance Test completed (*Acceptable value is minimum 100 Megohms”)
Cable Wire Or Cable Insulation
Insulation Resistance
Rating Length Size From To (Megohms)*

30. Notes: 1. Perform Insulation Resistance Test (megohm) between each conductor and ground
and conductor to conductor. Test between each conductor and shield for multiconductor
cables with shielded conductors. Record lowest reading for each cable.
2.Use 1000V test setting for cables rated 600 volts to 1000 volts.
Test Equipment Model Serial number / ID number: Calibration Due Date:

Module Installation
Cable coil length verified Source User
42. per cable schedule. □ (From) end □ (To) End □ Both Ends
Coiled cable is properly preserved for weather and properly secured for module
44. shipment in accordance with installation details or vendor preservation procedure.
Notes:
ICA Fluor Construction ICA Fluor Quality
Name: Name:

Signature: Signature:

Date: Date: