You are on page 1of 1

Breaker Setting (IR) Normal Rating Injected current Long Time Manufacturer

Rating 0.63-1 (A) (Seconds) Trip Time


1 50 50*5 250 23.44
50 A 0.8 40 40*5 200 23.76
0.63 31.5 31.5*5 158 23.75
1 63 63*5 315 26.31
63 A 0.8 50 50*5 250 27.51 7-38 Sec
0.63 39.6 39.6*5 198 28.36
1 100 100*5 500 21.68
100 A 0.8 80 80*5 400 21.81
0.63 63 63*5 315 21.57
1 125 125*5 750 16.58
125 A 0.8 100 100*5 500 16.07 8-40 Sec
0.63 78.7 78.7*5 394 16.83
1 20 20*5 100 22.96
20 A 0.8 16 16*5 80 23.96
0.63 12.6 12.6*5 63 23.73
4-15 Sec
1 32 32*5 160 16.24
32 A 0.8 25.6 25.6*5 128 14.33
0.63 20.1 20.1*5 100 16.59