PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR

Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

LV PANEL TESTING AND COMMISSIONING PROCEDURE

1. GENERAL INSPECTION
2. EARTH CONTINUITY TEST
3. INSULATION RESISTANCE TEST (BEFORE HV TEST)
4. HI-POT TEST
5. INSULATION RESISTANCE TEST (AFTER HV TEST)
6. AMMETER CALIBRATION TEST REPORT
7. VOLTMETER CALIBRATION TEST REPORT
8. BREAKER TEST REPORT (INCOMER & OUTGOING)
9. FUNCTIONAL TEST
10. ENERGIZE PROCEDURE

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

1. VISUAL INSPECTION AND GENERAL CHECKS:


The Inspection of the LVAC Panels has been carried out as per the Erection Control Form
S. NO DETAILS OBSERVATION / RESULT
1. Dimensions Check
2. Paint Finish (Internal/External) & Thickness
3. Size of Main horizontal Busbar.
4. Availability of Earth bar or earth Strip
5. Bus bar R, Y, B Phase Identification
6. Check Firmness of connection- in Torque Wrench method
7. Door Handles, locks, keys & Hinges
8. Mimic diagram, Nameplates, labels, stickers etc.
9. Earthing of doors Found Ok
10. Make, Rating and Type of Components Found Ok
11. Identification of Components Found Ok
12. Manual Operation of ACB / MCCB Found Ok
13. Check the Proper Tightness of Busbar (Torque Wrench) Found Ok
14. Cable Terminations Found Ok
15. The arrangement as per the SLD Found Ok
Document No:

2. EARTH CONTINUITY TEST:

S.NO DESCRIPTION STATUS


1 Ensure that the Panel/circuit under test is isolated from the supply. Found Ok
Using a Multi Meter check the continuity of all Earth points with the
2 Found Ok
Earth bar.

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

3. INSULATION RESISTANCE TEST (Before HV Test):


As per IEC 60439-1 The-insulation resistance test shall be conducted on a power circuit with 1000V
Megger Instrument. The insulation resistance value (Megger value) is recorded.
Description Applied Voltage (DC) Withstand Time IR value Remarks
R- (Y+B+N+E) * 1 kV 60 Sec 2.60 GΩ
Busbar
Y- (R+B+N+E) 1 kV 60 Sec 2.48 GΩ
Healthy
B- (Y+R+N+E) 1 kV 60 Sec 2.56 GΩ
Found is Ok.
N- (R+Y+B+E) 1 kV 60 Sec 18.6 MΩ

4. HIGH VOLTAGE TEST FOR 415V LVAC BOARD


*Applied voltage: 2.0 kV (80 % FAT Value i.e. 2.5 kV)
Description Applied Voltage (AC) With Stand Time Leakage Current(mA) Remarks
R- (Y+B+N+E) 2 kV 60 Sec 1.658
Busbar
Y- (R+B+N+E) 2 kV 60 Sec 1.702
Healthy
B- (Y+R+N+E) 2 kV 60 Sec 1.672 Found is Ok.
N- (R+Y+B+E) 2 kV 60 Sec 9.827

5. INSULATION RESISTANCE TEST (After HV Test):


Description Applied Voltage (DC) Withstand Time IR value Remarks
R- (Y+B+N+E) 1 kV 60 Sec 2.68 GΩ
Busbar
Y- (R+B+N+E) 1 kV 60 Sec 2.72 GΩ
Healthy
B- (Y+R+N+E) 1 kV 60 Sec 2.60 GΩ Found is Ok.
N- (R+Y+B+E) 1 kV 60 Sec 10.7 MΩ

Note: **When applying HV voltage to Rϕ, short and ground the other Phases and Neutral with Earth.
Also, similarly vice versa for other Phases as mentioned in the above table.

Insulation Resistance Acceptance Criteria:


Test & Acceptance as per IEEE C57.152 Clause# 7.2.13
1MΩ/kV system voltage is acceptable.

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

7. AMMETER CALIBRATION:
7.1 NB-CAS-MDB-001 INCOMER MAIN -1 Ammeter Calibration:
Make : HOBUT CT Ratio : 250/5 A
Type : D96LMC Range : 0-250 A
Injected Primary Current Expected Meter Current Ammeter Reading
% Error
in Amps (R-Y-B) in Amps in Amps (R-Y-B)
50 50 50 0.0
100 100 100 0.0
150 150 150 0.0
200 200 200 0.0
250 250 250 0.0
CT Star with Single Point Earthing : ok
% of Error = (Actual Reading – Expected Reading) / (Full scale Reading) *100
Ammeter Found Healthy : YES / NO

7.2 NB-CAS-MDB-0001 MAIN 2 INCOMER Ammeter Calibration:

Make : HOBUT CT Ratio : 250/5 A


Type : D96LMC Range : 0-250 A
Injected Primary Current Expected Meter Current Ammeter Reading
% Error
in Amps (R-Y-B) in Amps in Amps (R-Y-B)
50 50 50 0.0
100 100 100 0.0
150 150 150 0.0
200 200 200 0.0
250 250 250 0.0
CT Star with Single Point Earthing : ok
% of Error = (Actual Reading – Expected Reading) / (Full scale Reading) *100
Ammeter Found Healthy : YES / NO

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

7.3 NB-CAS-MDB-0001 (Q10 Outgoing Feeder) Ammeter Calibration:

Make : HOBUT CT Ratio : 100/5 A


Type : D96LMC Range : 0-100 A
Injected Primary Current Expected Meter Current Ammeter Reading
% Error
in Amps (R-Y-B) in Amps in Amps (R-Y-B)
20 20 20 0.0
40 40 40 0.0
60 60 60 0.0
80 80 80 0.0
100 100 100 0.0
CT Star with Single Point Earthing : ok
% of Error = (Actual Reading – Expected Reading) / (Full scale Reading) *100
Ammeter Found Healthy : YES / NO

7.4 NB-CAS-MDB-0001 (Q11 Outgoing Feeder) Ammeter Calibration:

Make : HOBUT CT Ratio : 100/5 A


Type : D96LMC Range : 0-100 A
Injected Primary Current Expected Meter Current Ammeter Reading
% Error
in Amps (R-Y-B) in Amps in Amps (R-Y-B)
20 20 20 0.0
40 40 40 0.0
60 60 60 0.0
80 80 80 0.0
100 100 100 0.0
CT Star with Single Point Earthing : ok
% of Error = (Actual Reading – Expected Reading) / (Full scale Reading) *100
Ammeter Found Healthy : YES / NO

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

7.4 NB-CAS-MDB-0001 (Q12 Outgoing Feeder) Ammeter Calibration:


Make : HOBUT CT Ratio : 120/5 A
Type : D96LMC Range : 0-120 A
Injected Primary Current Expected Meter Current Ammeter Reading
% Error
in Amps (R-Y-B) in Amps in Amps (R-Y-B)
20 20 20 0.0
40 40 40 0.0
60 60 60 0.0
80 80 80 0.0
100 100 100 0.0
120 120 120 0.0
CT Star with Single Point Earthing : ok
% of Error = (Actual Reading – Expected Reading) / (Full scale Reading) *100
Ammeter Found Healthy : YES / NO

8.VOLTMETER CALIBRATION:
8.1 INCOMER -M1 - Voltmeter Calibration:
Make : HOBUT VT Ratio :-
Type : D96LMC Range : 0-500 V
Measured Voltage Frequency
Phase Injected Voltage Injected
R-Y Y-B B-R (HZ)
R-N 240 240 0 240 50.0
Y-N 240 240 240 0 50.0
B-N 240 0 240 240 50.0
R-Y-B-N 415 415 415 415 50.0
Voltmeter Found Healthy : YES / NO

8.2 INCOMER -M2 - Voltmeter Calibration:


Make : HOBUT VT Ratio :-
Type : D96LMC Range : 0-500 V
Measured Voltage Frequency
Phase Injected Voltage Injected
R-Y Y-B B-R (HZ)
R-N 240 240 0 240 50.0
Y-N 240 240 240 0 50.0
B-N 240 0 240 240 50.0
R-Y-B-N 415 415 415 415 50.0

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

Voltmeter Found Healthy : YES / NO

13. BREAKER TEST REPORT


PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Main -1 Incomer
Rated Current (In) 250 A
IR Range 0.4 -1.0
IR Setting 0.8
Long
Current Injected (A) 0.8*250*5= 625
Time 1000A
A
L Trip time (Sec) 10.783 10.824 10.076
S.C Characteristic Range 0.4 – 1.0
Short S.C curve Setting 5
Time Current Injected (A) 1800
S Trip Time (Sec) 2.01 2.02 1.92
ZCT set at 300mA / 0.8S Found Ok
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Main -2 Incomer
Rated Current (In) 250 A
IR Range 0.4 -1.0
IR Setting 0.8
Long
Current Injected (A) 0.8*250*5= 625
Time 1000A
A
L Trip time (Sec) 11.066 11.674 10.983
S.C Characteristic Range 0.4 – 1.0
Short S.C curve Setting 5
Time Current Injected (A) 1800
S Trip Time (Sec) 1.98 1.92 1.92
ZCT set at 300mA / 0.8S Found Ok
Manual Close/Trip from Push Button Found Ok

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q1 (NFB-CAS-K-03A)
Rated Current (In) 32A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A)
Time 100.8
(0.63*32)*5=100.8 A
L Trip time (Sec) 9.0980 10.0587 10.3176
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (32*0.63)*12*3=
Time 726
726A
S Trip Time (mSec) 43.00 48.00 47.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q2 (NFB-CAS-K-03B)
Rated Current (In) 32A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A)
Time 100.8
(0.63*32)*5=100.8 A
L Trip time (Sec) 10.0926 10.1005 10.0564
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (32*0.63)*12*3=
Time 726
726A
S Trip Time (mSec) 45.00 52.00 56.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q3 ( NFB-CAS-PACU-001A)
Rated Current (In) 50A
Long IR Range 0.63-1

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

IR Setting 0.63
Current Injected (A) (0.63*50)*5=158
Time 158A
A
L Trip time (Sec) 21.267 20.768 21.945
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (50*0.63)*12*3=
Time 1134
1134A
S Trip Time (mSec) 38.00 48.00 39.00
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q4 ( NFB-CAS-PACU-001B)
Rated Current (In) 50A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*50)*5=158
Time 158A
A
L Trip time (Sec) 23.023 28.188 22.875
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (50*0.63)*12*3=
Time 1134
1134A
S Trip Time (mSec) 48.00 50.00 52.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q5 (SPARE)
Rated Current (In) 32A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A)
Time 100.8
(0.63*32)*5=100.8 A
L Trip time (Sec) 11.987 12.098 12.066
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (32*0.63)*12*3=
Time 726
726A
S Trip Time (mSec) 58.00 53.00 55.00
Manual Close/Trip from Push Button Found Ok

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q6 (SAPRE)
Rated Current (In) 63A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*63)*5=
Time 199 A
199.8 A
L Trip time (Sec) 22.786 22.067 22.978
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (63*0.63)*12*3=
Time 1429
1429A
S Trip Time (mSec) 37.00 47.00 47.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q7 (NB-CAS-WRO-001)
Rated Current (In) 63A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*63)*5=
Time 199 A
199.8 A
L Trip time (Sec) 22.532 22.546 22.543
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (63*0.63)*12*3=
Time 1429
1429A
S Trip Time (mSec) 42.00 43.00 48.00
7ZCT set at 100mA / 0.8S Found Ok
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q8 (SPARE)
Rated Current (In) 63A

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*63)*5=
Time 199 A
199.8 A
L Trip time (Sec) 20.876 21.976 20.762
Ii Range 6-12
Short Ii Setting 12
Time Current Injected (A) (63*0.63)*12*3=
1429
1429A
S Trip Time (mSec) 45.00 40.00 43.00
8ZCT set at 100mA / 0.8S Trip to MCCB Found Ok
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q9 (UPS BYPASS)
Rated Current (In) 100A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*100)*5=
Time 315 A
315 A
L Trip time (Sec) 32.097 30.978 30.987
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (100*0.63)*12*2=
Time 1512
1512A
S Trip Time (mSec) 60.00.00 63.00 58.00
9ZCT set at 100mA / 0.8S trip to MCCB Found Ok
Manual Close/Trip from Push Button Found Ok

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q10 (NFB-CAS-UPS-0001)
Rated Current (In) 100A
IR Range 0.63-1
IR Setting 0.8
Long
Current Injected (A) (0.8*100)*5= 400
Time 400 A
A
L Trip time (Sec) 19.936 19.576 20.034
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (100*0.8)*12*2=
Time 1920
1920A
S Trip Time (mSec) 45.00 47.00 45.00
10ZCT set at 100mA / 0.8S trip to MCCB Found Ok
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q11 (NFB-CAS-UPS-0001)
Rated Current (In) 100A
IR Range 0.63-1
IR Setting 0.8
Long
Current Injected (A) (0.8*100)*5= 400
Time 400 A
A
L Trip time (Sec) 23.067 24.065 25.333
Short Ii Range 6-12
Time Ii Setting 12

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

Current Injected (A) (100*0.8)*12*2=


1920
1920A
S Trip Time (mSec) 48.00 48.00 46.00
11ZCT set at 100mA / 0.8S trip to MCCB Found Ok
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q12 (SPARE)
Rated Current (In) 125A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*125)*5=
Time 394 A
394 A
L Trip time (Sec) 26.097 25.078 25.980
Ii Range 6-12
Ii Setting 6
Short
Current Injected (A) (125*0.6)*6*3=
Time 1418
1418A
S Trip Time (mSec) 50.00 56.00 59.00
12ZCT set at 100mA / 0.8S trip to MCCB Found Ok
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q13 (NFB-CAS-SP-001 A/B)
Rated Current (In) 20A
Long IR Range 0.63-1
Time IR Setting 0.63
Current Injected (A) (0.63*20)*5=63 63A

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

A
L Trip time (Sec) 13.293 14.097 15.078
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*0.63)*12*3=454
Time 454
A
S Trip Time (mSec) 60.00 62.00 59.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q14 (NFB-CAS-EF-001 A)
Rated Current (In) 20A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*20)*5=63
Time 63A
A
L Trip time (Sec) 19.045 16.097 15.983
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*0.63)*12*3=454
Time 454
A
S Trip Time (mSec) 67.00 58.00 67.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q15 (NFB-CAS-EF-001 B)
Rated Current (In) 20A
Long IR Range 0.63-1

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

IR Setting 0.63
Current Injected (A) (0.63*20)*5=63
Time 63A
A
L Trip time (Sec) 18.426 17.898 19.977
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*0.63)*12*3=454
Time 454
A
S Trip Time (mSec) 66.00 58.00 65.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q16 (NB-CAS-CRE-001)
Rated Current (In) 32A
IR Range 0.63-1
Long IR Setting 1.00
Time Current Injected (A) (1*32)*5=160 A 160 A
L Trip time (Sec) 11.326 12.097 11.955
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (32*1.0)*12*3=
Time 1152
1152A
S Trip Time (mSec) 45.00 46.00 48.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

Panel Tag NB-CAS-MDB-0001


Breaker Tag Q17 (NFB-CAS-PACU-001 A)
Rated Current (In) 20A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*20)*5=63
Time 63A
A
L Trip time (Sec) 17.261 18.564 17.786
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*0.63)*12*3=454
Time 454
A
S Trip Time (mSec) 58.00 56.00 57.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q18 (SPARE)
Rated Current (In) 20A
IR Range 0.63-1
Long IR Setting 1.0
Time Current Injected (A) (1*20)*5=100 A 100A
L Trip time (Sec) 11.326 11.897 11.954
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*1.0)*12*3=720
Time 720 A
A
S Trip Time (mSec) 43.00 46.00 45.00
Manual Close/Trip from Push Button Found Ok

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q19 (NB-CAS-FACP-001)
Rated Current (In) 20A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*20)*5=63
Time 63A
A
L Trip time (Sec) 18.784 18.670 16.789
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*0.63)*12*3=454
Time 454
A
S Trip Time (mSec) 45.00 47.00 48.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q20 (NFB-CAS-FEP-001 A)
Rated Current (In) 20A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*20)*5=63
Time 63A
A
L Trip time (Sec) 14.926 15.078 15.987
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*0.63)*12*3=454
Time 454
A
S Trip Time (mSec) 56.00 48 58.00
Manual Close/Trip from Push Button Found Ok

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q21 ( NFB-CAS-ACCU-001)
Rated Current (In) 50A
IR Range 0.63-1
IR Setting 1.0
Long
Current Injected (A) (1.0*50)*5=250
Time 250
A
L Trip time (Sec) 21.461 22.087 21.768
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (50*1.0)*12*3=
Time 1800
1800A
S Trip Time (mSec) 48.00 50.00 52.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q22 ( NFB-CAS-ACCU-002)
Rated Current (In) 50A
IR Range 0.63-1
IR Setting 1.0
Long
Current Injected (A) (1.0*50)*5=250
Time 250
A
L Trip time (Sec) 25.098 26.0978 24.987
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (50*1.0)*12*3=
Time 1800
1800A
S Trip Time (mSec) 45.00 55.00 58.00
Manual Close/Trip from Push Button Found Ok

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q23 ( NFB-CAS-ACCU-003)
Rated Current (In) 50A
IR Range 0.63-1
IR Setting 1.0
Long
Current Injected (A) (1.0*50)*5=250
Time 250
A
L Trip time (Sec) 23.098 24.098 24.067
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (50*1.0)*12*3=
Time 1800
1800A
S Trip Time (mSec) 56.00 57.00 57.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q24 ( NFB-CAS-ACCU-004)
Rated Current (In) 50A
IR Range 0.63-1
IR Setting 1.0
Long
Current Injected (A) (1.0*50)*5=250
Time 250
A
L Trip time (Sec) 25.089 26.098 24.034

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (50*1.0)*12*3=
Time 1800
1800A
S Trip Time (mSec) 67.00 56.00 48.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q25 (NFB-CAS-BP-001/002)
Rated Current (In) 20A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*20)*5=63
Time 63A
A
L Trip time (Sec) 16.241 15.678 16.987
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*0.63)*12*3=454
Time 454
A
S Trip Time (mSec) 50.00 62.00 66.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

Breaker Tag Q26 (NFB-CAS-PACU-001B )


Rated Current (In) 20A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*20)*5=63
Time 63A
A
L Trip time (Sec) 16.576 16.875 16.976
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*0.63)*12*3=454
Time 454
A
S Trip Time (mSec) 55.00 60.00 54.00
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q27 (SPARE)
Rated Current (In) 20A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A) (0.63*20)*5=63
Time 63A
A
L Trip time (Sec) 12.056 11.923 11.766
Ii Range 6-12
Ii Setting 12
Short
Current Injected (A) (20*0.63)*12*3=454
Time 454
A
S Trip Time (mSec) 66.00 67.00 65.00
Manual Close/Trip from Push Button Found Ok

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q28 ( NB-CAS-LPNL-0001)
Rated Current (In) 125A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A)
Time 394A
(0.63*125)*5=394 A
L Trip time (Sec) 26.336 25.546 25.678
Ii Range 6-12
Ii Setting 10
Short
Current Injected (A) (0.63*125)*10*2=
Time 1575
1575A
S Trip Time (mSec) 80.00 77.00 74.00
28ZCT set at 100mA / 0.8S trip to MCCB Found Ok
Manual Close/Trip from Push Button Found Ok

PHASE REFERENCE R Y B
Panel Tag NB-CAS-MDB-0001
Breaker Tag Q29 ( SPARE)
Rated Current (In) 125A
IR Range 0.63-1
IR Setting 0.63
Long
Current Injected (A)
Time 394A
(0.63*125)*5=394 A
L Trip time (Sec) 30.045 30.055 31.065
Ii Range 6-12
Ii Setting 10
Short
Current Injected (A) (0.63*125)*10*2=
Time 1575
1575A
S Trip Time (mSec) 82.00 78.00 76.00
29ZCT set at 100mA / 0.8S trip to MCCB Found Ok

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

Manual Close/Trip from Push Button Found Ok

15. MCCB FUNCTIONAL TEST -NB-FWF-CP-02 (SET@ 200A)

INCOMER M1 INCOMER M2
BREKAER
OPEN/CLOSE ✔ ❌
❌ ✔

Breaker Open/Close Possible :✔


Breaker Open/Close Not Possible : ❌

16.ENERGIZATION PROCEDURE:
Ensure LVAC Incomer -1,2, Bus Coupler Breakers are in Open Position, then Energies Auxiliary
Transformer -1,2 by closing the respective HV Circuit Breakers.
1.Check supply connected at both incoming, Voltage level and phase sequence.
2.Check the presence of the mechanical protectors preventing any accidental contact with Live Parts.
3.Open the outgoing circuit breakers.
4.Supply Distribution Board via the Auxiliary Transformers check for voltage and correct phase sequence
and Polarities.
5.Upstream of all circuit breakers indictors and protections.
6.Check the distribution board alarm information return up to the output terminal blocks.

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date
PROJECT TITLE: NEW NAVAL BASE PROJECT/NPP0050 Manufacturer: AL BIDDA SWITCHGEAR
Name of Substation/Panel : NB-FWF-CAS-0001 ( COMPRESSED AIR ROOM )

PHASE SEQUENCE CHECK:


Phase Sequence Remarks
R–Y–B
Y–B–R
B–R-Y
PLACING INTO SERVICE:
1. Energization of the LVAC board after closing of the main circuit-breaker.
2. Check that all necessary protective and signaling devices are in services.
3. Close all outgoing circuit-breaker, when necessary, after checking of the corresponding power cable.
4. Phase out supplies with reference supply.

SUB CONTRACTOR: AYT CONTRACTOR: QBC PMC: REQ


Signatur Signatur Signatur
eName eName eName
Date Date Date