Ref - Nb-Uts-Lvs-0002
Ref - Nb-Uts-Lvs-0002
List of Content
2 CT Details …………………………………………………………………………………………….... 2
4. Phase Pickup…………………………………………………………………………………….. 2
13 Instruments Used……………………………………………………………………………………. 7
14 Remarks………………………………………………………………………………………………… 7
1. RELAY DETAILS:
Make : SIEMENS Relay Designation : F871(87NL)
MLFB : 7SR1102-1MA77-1CA0/FF Firmware Revision : 2436S81127R4k
Nominal Current : 5.0 Amp Parameter Set Version : V04.95.00
Relay Sl.No. : BF2010527504 Auxiliary Volt. : 30 V DC
IP Address : Rated Frequency : 50 Hz
Final setting Doc Ref Drawing & Sheet (A4)P16-20027-UTS-
: :
No. No. 0120-P001 / 55
2. CT DETAILS:
Rated Primary Current : 1600 A
Rated Secondary Current : 5 A
3. Metrosil(NLR) Test:
= 0.31702 mA
Sl.N
Applied Voltage(V) Expected (mA) Measured(mA)
o
1 50 <0.0198 0.04
2 75 <0.1002 0.07
Sl.N
Applied Voltage(V) Expected (mA) Measured(mA)
o
6 175 <2.9715 0.84
7 200 <5.0693 1.37
50 1Ph-1 (87NL-1)
Phase
Pickup current (A) Trip Time @2 x setting (msec)
R 0.995
Y 0.995
B 0.995
INs 0.996
Acceptance Norm
Tolerance for Pickup ±3 % of setting value or 1 % of nominal current at INom = 1 A or 5 A
Trip Time Tolerance ±1 % of setting value or 10 ms + Reaction time 30mSec of Setting Value.
4.2.VOLTAGE INJECTION:
50 1Ph-1
Phase
Pickup Voltage Voltage Across Measured Trip Time @2 x Cal. V
(V) Resistor (V) Current(A) Pickup (msec)
Acceptance Norm
Tolerance for Pickup ±3 % of Vcalc value.
Trip Time Tolerance ±1 % of setting value or 10 ms + reaction time 30mSec of Setting Value
6.BINARY INPUT:
7.BINARY OUTPUT:
BO5 Spare OK
8.LED INDICATION:
9.FUNCTION KEY:
10.FUNCTION CHECKS:
Functional Checks:
SL.No. Function Description Tested( )
11.1 Tripping of HV Trip Coil-1 on LV REF Trip OK
11.2 Tripping of LV Trip Coil on LV REF & Trip OK
11.3 Tripping of K311(86) relay on LV REF Trip OK
11.4 Test Block Operation checked for protection tripping. OK
11.5 Test Block Operation checked for CT Isolation/shorting. OK
11.6 Final Settings downloaded to Relay after Test OK
11.7 Relay found healthy OK
11.INSTRUMENTS USED:
2. Multimeter
14.REMARKS:
1. CURRENT MEASREMENTS:
Phase in Which Injected Current Primary Current Read on Power Monitoring System (PMS)
Current is injected in Sec ( A) IL1 IL2 IL3 ILo
(A)
R-N 5.0
Y-N 5.0
B-N 5.0
R-Y-B 5.0
B. VOLTAGE: 415/110 V
Phase in Which Injected Current Primary Voltage Read on Power Monitoring System in Volt
Current is injected in Sec ( V) (PMS)
(V) V1 V2 V3 Vo
R-N 63.5
Y-N 63.5
B-N 63.5
R-Y-B 110
C. POWER MEASUREMENT:
D. REMARKS:
Energy meter Found Healthy : YES / NO