You are on page 1of 3

Free Service Coupon

eFSR Details
S.SHIVA
MAGIEC Code EBU22939 MAGIEC Name eFSR ID EFSR220343390
ENTERPRISES
Engine Serial I-BR-SGLI-ENB- I-BR-SGLI-ENB-
N2A22A22831 Site Id Comm Site ID
Number 9022 9022
Reliance Digital Date And Time
Customer Name Platform & Project Application Genset 30-Mar-2022 17:11
Attended
Service Limited
I-BR-SGLI-ENB-
Site Name Location Belwatiya Cluster / District Purba Champaran
9022

26.8063342/84.5122
Circle / State Bihar DG Supplied By NA Lat / Log
79
Engine Model GEN2185GMC2_SF Engine KVA 10 Running Hour 80
PIU Running Hrs

Engine Serial Number Site Condition - Pre-Service Hour Meter Reading


Ticket Details
Ticket Registered
Ticket Number SR22033898154 on date 30-Mar-2022 Type of Service FSC
MAGIEC Job Ref
Details Free Service Coupon No. 23412
Air System
Inner Element Outer Element
Air System Type Dry OK OK
Primary Secondary
Condition of
OK Condition of Hoses OK
Vaccume Indicator
Clean Wire mesh YES Oil Bath Replaced YES Element NA
Lub System
Qty.of Oil Filled
Oil Level Replaced 5.50
(Ltr.)
Oil Leakage NO No image

Oil Level in FIP Replaced Oil Filter Replaced


Cooling System
Coolant Level OK Coolant Leakage NO
Condition of
Condition of Recovery Bottle & No image
Radiator Cap OK Its Hose OK
Connection

1
Condition of Radiator
Radiator Cleanliness Check
fins & Clean Using OK
blower
No image
Gap Between Cowl Coolant
& Radiator (Visual OK Temperature(Deg. 75.00
Check) Cen)
Condition of Hoses Condition Of Fan Condition Exhaust
OK belt OK Bellow OK

Fuel System
Fuel Filter Primary Not Due Fuel Pipe OK
Fuel Filter
Not Due Fuel Leakage NO
Secondary No image
FIP Feed Pump
Diesel Tank Closed Found Clean
filter
Engine Electrical System
Battery Charging
Battery Available 14
Voltage(V)
Battery Electrolite Battery AH Rating
Level OK (AH) 88

Specififc Gravity of Alternator Charging Available And


Battery 1.22
Unit Working Fine

Condition of
Wiring Harness OK Alternator Bracket OK OK
terminal
Main Alternator & AMF Panel
Condition of
Alternator & Load Cable Meters, Lamps on
Terminal Box OK condition in Main OK OK
Panel For
Condition alternator Functionality
Check Cable
Check The Check Operation Of
OK Connections & OK Working
Controller Setting AMF
Earthing
Automation Solenoid Pulse
Automation LLOP Operation OK 05:00
Functional Corrected
All Safeties
True HWT Operation OK GSU Operation OK
connected to PIU
Main Alternator Main Alternator
earthing - Body Connected earthing - Neutral Connected
Radiator Water
OK Solenoid Operation Solenoid
Level Switch
Condition of 4ST Solenoid Pulse /
Switch OK PIU Stop timing 05:00
Check Genset
Check Genset
OK Overload 42
Overload Setting Setting(amp)
General Check
Output Voltage(AC Engine RPM On
Single phase Engine RPM Max 1500.00 1485
Volts) Load
Visibility of Smoke
Normal Frequency (Hz) 49.50 Oil Pressure (Bar) 3.50
colour
Condition &
Output Voltage Load Opening of
[R/Y/B] 230.00 Current[R/Y/B] 22.00 Breather Tube Vent OK
outside Canopy

Sr.No. Spare Part Code Spare Part Name Qty Failed Part
Recommendation
Not Applicable Important Info NA
for Overhaul

2
Is Tapping Setting
Done

No image No image No image

Customer
representative nitesh kumar Designation NA Phone No 9709845236
Name
Satisfied with the
Job Done. YES
Customer Remark /
Experience Customer representative Photograph. Customer representative Signature.

satisfied by work

Magiec
representative ashok kumar Phone No 9771458596 Next PM Due Date 28-06-2022
Name
Magiec
representative Magiec representative Signature
Remarks

pm done

Engine Sr. : N2A22A22831 / eFSRId : / Hours : / eFSR start Date&Time : 30-Mar-2022 12:00 AM / ServerSaveTime : 30-Mar-2022 05:11 PM / LAT26 : 26.8063342 /