Professional Documents
Culture Documents
Revision: 03
The content of this document material is a property of Haya Water. No part of this document in whole or in part,
may be reproduced in any form, by photocopy, microfilm, scanning or any other means, or incorporated into any
information retrieval system, electronic or mechanical, without the written permission of Haya water Management.
i Revision History
The following is a brief summary of the most recent revisions to this document. Details of all revisions
prior to these are held on file by the issuing department.
Revision
Date Scope / Remarks
No.
0 13/04/2006 Document approved and issued
01 01/06/2008 To incorporate Tender Board and Veolia comments
02 31/12/2010 To incorporate latest changes as per current International standards.
03 xx/xx/2016 Updated as part of the Haya Water Technical Standards Upgrading project
HAYA Water
M/s Halcrow on Behalf of Haya Water Asset Management / Projects / O&M
Suleiman Al Qasmi
Document No: AM-ENG-WDM-05 Issue Date: 29/09/2016
TABLE OF CONTENTS
1. Introduction .................................................................................................................10
1.1. Purpose ....................................................................................................................10
1.2. Scope .......................................................................................................................10
1.3. Objective ..................................................................................................................10
1.4. Distribution/Target Audience ..................................................................................10
1.5. Review and Improvement........................................................................................10
1.6. Definitions ................................................................................................................10
1.7. Abbreviations........................................................................................................... 11
2. Sewage Treatment Plants ...........................................................................................15
2.1. Sewage Treatment Plant Location ..........................................................................15
2.2. Raw Sewage Characteristic ....................................................................................15
2.3. Treated Effluent Quality ..........................................................................................18
2.3.1. Treated Effluent Quality as per Concession Agreement ...................................18
2.3.2. Treated Effluent Quality as per MECA Standard ................................................18
2.3.3. Treated Effluent Quality for Marine Discharge...................................................20
2.3.4. Treated Effluent Quality Discharge to Wadi’s ....................................................22
2.4. Design Considerations ............................................................................................22
2.4.1. Hydraulic Design .................................................................................................24
2.4.2. Organic Design ....................................................................................................25
2.4.3. Design by Analogy...............................................................................................26
2.4.4. Shock Effects .......................................................................................................26
2.4.5. Flow Equalisation ................................................................................................26
2.4.6. Conduits and Piping ............................................................................................26
2.5. Plant Arrangement ...................................................................................................27
2.5.1. Arrangement of Units ..........................................................................................27
2.5.2. Flow Division and Control ...................................................................................27
2.5.3. Location Plan .......................................................................................................27
2.5.4. General Layout.....................................................................................................27
2.5.5. Detailed Drawings and Calculations ..................................................................27
2.5.6. Unit Bypasses ......................................................................................................28
2.5.7. Unit Dewatering, Flotation Protection, and Plugging ........................................28
2.6. Essential Facilities...................................................................................................28
2.6.1. Power Failure .......................................................................................................28
1. Introduction
1.1. Purpose
i. The purpose of this document is to communicate the technical requirements and preferences of
the Client for the particular system or equipment, or both.
1.2. Scope
i. The scope of this Manual is to provide technical guidance to the Designer regarding key system
elements. This Manual shall be applicable to all Client projects, and shall be read in conjunction
with the relevant standard Specification of all other documents of any Contract requirements or
Particular Specification (or both). Any clause in this Manual which relates to Works or materials
not required by any particular Contract shall be deemed not to apply.
ii. The contents of this document shall be read in conjunction with all Haya Water Technical
Specifications. Compliance with the contents of Haya Water Technical Specifications shall be an
integral requirement of this document.
1.3. Objective
i. The objective of this Manual is to ensure that all designs are carried out to a uniform high
standard, in line with the Client’s intentions and best international practices. Incorporating the
requirements and criteria of this Manual will ease the Client’s technical review and approval
process in the implementation of projects.
ii. This Manual is intended for use by Designers who are knowledgeable and experienced in the
design of wastewater collection, transfer, and treatment processes. The Designers need to be
fully familiar with the contents of this Manual.
iii. Requirements and criteria included in this Manual are not purported to cover all design
conditions. This Manual is a guide and not meant to preclude the use of experienced engineering
judgement for specific design situations. Designers shall address all necessary aspects for their
particular project in consultation with the Engineer, and any proposed deviations from this Manual
must be discussed and agreed upon with the Engineer prior to commencement of the Works.
1.6. Definitions
i. Client/Owner: Oman Wastewater Services Company (Haya Water) for whom the Works are to
be undertaken
ii. Owner Representative/Engineer: The firm or company named in the Contract as appointed by
the Client to supervise and administer the Contract
iii. Consultant: The firm or company selected by the Client to prepare the Particular Specification
(the Contract documents) for a given project
iv. Contractor: The company or organisation responsible for the provision of the Works and who
have entered into a Contract with the Client
v. Designer: Any person carrying out design activities for or on behalf of any of the parties
mentioned previously. A person involved in any changes to existing or proposed Works shall be
deemed to be a Designer.
vi. Site: The land allocated for the Works
vii. Project Documents: All documents associated with and applicable to the Contract
viii. Particular Specification: The Specification associated with the Contract and prepared at the
time of the project by the Engineer specifically for that application
ix. Technical definitions related to this Specification are to be found within the appropriate technical
clauses in the document.
1.7. Abbreviations
2D Two-Dimensional
BS British Standard
Cl2 Chlorine
DO Dissolved Oxygen
DS Dry Solids
EC Electrical Conductivity
N Nitrogen
NH3 Ammonia
NH4 Ammonium
NO3 Nitrate
NOD Nitrogenous Oxygen Demand
PE Population Equivalent
TE Treated Effluent
UV Ultraviolet
Units of Measurement
° Degree
μm Micrometre
°C Degree Celsius
D Day
G Gram
kg Kilogram
kPa Kilopascal
kW Kilowatt
kWh Kilowatt-Hour
L Litre
m2 Square Metre
m3 Cubic Metre
min Minute
mJ/cm2 Millijoule per Square Centimetre
mL Millilitre
mL/g Millilitre per Gram
m2 Square Metre
m3 Cubic Metre
mm Millimetre
m/s Metre per Second
nm Nanometre
sec Second
W Watt
designer for reference purpose; however, designer shall obtain the updated data along with
historic data for a robust system design.
ii. Unless otherwise the raw sewage quality is not specified, the following values of parameters shall
apply as minimum design guideline for process design of the Plant as listed in Table 1.
iii. The temperature of sewage, as observed, undergoes a variation from less than 20 oC in winter
and up to 35 oC in summer. The Designer shall liaise closely with the Client to determine the plant
inlet design values of various parameters taking into consideration the previous existing operating
plant data.
iv. For Fat, Oil & Grease raw sewage characteristics; the Designer shall consider the sewerage
catchments networks covers the commercial, food and beverages outlets which may have higher
values of FOG than the minimum values shown in the Table 1. For such cases, the Designer
shall obtain Client’s agreement for adopted design value for the FOG parameter.
Inert Solids % 20
Air Temperature oC 15 - 60
Humidity % 0-100
v. The Designer shall use the following characteristics for the treatment of influent Raw Sewage
received by Tankers to STP are listed in Table 2, based on flow-proportioned composite samples
collected over 4 days of twenty four hours and analysed in accordance with Standard Methods for
the Examination of Water and Wastewater (21st Edition), and an analysis of historic data from Al
Ansab STP Tanker Discharge Facility.
Design Values
Parameters Unit
Maximum Minimum Average
Fluoride as F mg/L 14 10 12
Temperature ºC 35 20 26
Table 3: Minimum Treated Effluent Quality in Accordance with the Concession Agreement
Biological Oxygen Demand (BOD5) (5d @ 20ºC) mg/L < 15 Daily Note 1
Chlorine Residual (at Distribution Point) 0.3 < x < 1.0 Daily Note 1
ii. Chlorine residual concentrations shall be between 0.3 and 1.0 mg/L at distribution point.
Maximum allowable concentrations at the STP point of discharge are up to 3.0 mg/L to allow for
degradation in the distribution network.
a) Note 1: Compliance shall be based on 7-day moving averages for all constituents except
Faecal Coliforms, Chlorine Residual, and Helminths Ova. No more than two daily
composite samples per month are permitted to exceed one or more of the previous
performance standards.
b) Note 2: No more than five daily composite samples per month permitted to exceed one or
more of the previous performance standards.
c) Note 3: The average of the daily composite samples taken during a month shall not to
exceed the performance standard.
d) Note 4: Testing is only required where sludge shall be made available for reuse.
2.3.2. Treated Effluent Quality as per MECA Standard
i. Additionally, any treatment process selected shall be capable of treating effluent to meet the
effluent quality Class “A” or “B” as specified in the Ministerial Decision 145/1993 dated 13 June
1993 by Ministry of Environment and Climate Affaires, covering wastewater reuse and discharge
to land (see Table 4).
ii. The more stringent of the previous two standards shall be used in the design and compliance of
the quality levels (for example, the Fat, Oil and Grease requirement of 0.5 mg/L [as per Ministerial
Decision 145/1993] shall be the applicable output quality compared to 5 mg/L in the Concession
Agreement).
iii. Similarly, considering MD 145/1993 Regulations of Nitrates as Nitrate (NO 3) < 50 mg/L, the limit
for Nitrates considered as Nitrogen (as N) which shall be < 11.3 mg/L, requiring a sewage
treatment plant to be designed for a substantial level of denitrification to achieve this standard.
Thus, the technology selected and designs shall meet the combined concentration of Total
Nitrogen (as N) = Organic N + Ammonia (NH3) + Ammonium (NH4) + Nitrogen Dioxide (NO2)
+ NO3 shall be < 15 mg/L to meet the Total Nitrogen limits.
2.3.3. Treated Effluent Quality for Marine Discharge as per Ministerial Decision 159/2005
i. Apart from the compliance for Class “A” Effluent as previous, the system shall also have to deal
with excess TE during winter months, when the treated water demand falls drastically for
landscape irrigation. This necessitates disposal of excess TE to the sea in the initial years or
during less demand of TE.
ii. As the Concession Agreement does not specify effluent quality to be discharged into the sea,
Haya Water shall follow the effluent quality requirements set out in Ministerial Decision 159/2005
“Regulations for the Discharge of Liquid Effluents to the Marine Environment”. Effluent quality
discharged into a marine environment must be capable of meeting this standard. The TE quality
requirement is provided in Table 5.
Table 5: Ministerial Decision 159/2005 – Regulations for the Discharge of Liquid Effluents
to the Marine Environment (Unofficial Translation)
iii. Particular attention is given to the parameters highlighted as follows for effluent discharged to the
sea as these differ from the water quality parameters in Table 2 for Class “A” effluents:
a) Ammonia (as N) : 1.0 mg/L
b) Nitrate (as N) : 3.4 mg/L
c) Phosphorous : 2.0 mg/L
d) Total Chlorine : 0.4 mg/L
v. As a basis of design, all treatment plant processes and equipment shall be designed and sized as
per Section 01 General, taking into account future hydraulic flows and organic loads.
2.4.1. Hydraulic Design
2.4.1.1. New System
i. The design for sewage treatment plants shall be based on average per capita household
consumption of 245L/capita or as specified in Haya Water latest updated Master Plan.
ii. Unless water usage data or other justification upon which to better estimate flow is provided, the
previous values shall be updated by the Designer for any changes that a more realistic rate of
water consumption, and in turn, the sewage generation.
iii. The following flows for the design year shall be identified and used as a basis for designing
wastewater treatment units, and other wastewater handling facilities.
a) Design Average Flow: The design average flow is the average of the daily volumes to
be received for a continuous 12-month period, expressed as a volume per unit time.
However, the design average flow for facilities having critical seasonal high hydraulic
loading periods (for example, recreational areas, campuses, and industrial facilities) shall
be based on the daily average flow during the seasonal period.
b) Design Maximum Day Flow: The design maximum day flow is the largest volume of flow
to be received during a continuous 24-hour period, expressed as a volume per unit time.
c) Design Peak Hourly Flow: The design peak hourly flow is the largest volume of flow to
be received during a 1-hour period, expressed as a volume per unit time.
d) Design Peak Instantaneous Flow: The design peak instantaneous flow is the
instantaneous maximum flow rate to be received.
iv. Peak factors on design shall be considered based on the following reference data
v. Allowance shall be made for recycled liquors within the proposed plant or wastewater received by
Tankers. For non-domestic flows, the design load shall be the actual peak period discharge plus
10 percent.
2.4.1.2. Existing System
i. Where there is an existing system, the volume and strength of existing flows shall be determined.
The determination shall include both dry weather and wet weather conditions. At least 1 year's
flow data shall be taken as the basis for the preparation of a hydrograph for analysis to determine
the following types of flow conditions of the system:
a) The annual average daily flow as determined by averaging flows over 1 year, exclusive of
inflow due to rainfall
b) The minimum daily flow as determined by observing 24 hours flows during dry weather
c) Wet weather peak flows as determined by observing 24 hour flows during a period of 1
year
d) Peak hourly flows as determined by observing the maximum hydraulic load to the plant
e) Industrial wastewater flows as determined by flow data, including water use records, for
each of the industries contributing to the sewer system
vii. Data from similar municipalities may be utilised in the case of new systems. However, thorough
investigation that is adequately documented shall be provided for review to establish the reliability
and applicability of such data.
viii. The shock effects of high concentrations and diurnal peaks for short periods of time on the
treatment process shall be considered.
2.4.2.2. Existing Systems
i. When an existing treatment Works is to be upgraded or expanded, the organic design shall be
based upon the actual strength of the wastewater as determined from the measurements from
the Client’s laboratory, with an appropriate increment for growth.
ii. The raw sewage characteristics analysed by the Client’s laboratory will be available from
Laboratory Information Management System (LIMS) on various existing operating plants, and the
Designer shall use this data to optimise plant design. The LIMS data provides historic data to the
Designer for reference purpose only; however, the Designer shall obtain the updated data along
with historic data for a robust system design.
2.4.3. Design by Analogy
i. If suitable, data from similar plants may be used in the design of new systems where raw data is
not available.
2.4.4. Shock Effects
i. The shock effects of high concentrations and diurnal peaks for short periods of time on the
treatment process, particularly for small treatment plants, shall be considered.
2.4.5. Flow Equalisation
i. Facilities for the equalisation of flows and organic shock load shall be considered at all plants
which are critically affected by surge loadings. See Clause 5, Flow Equalisation, for further
details.
2.4.6. Conduits and Piping
i. All piping shall comply with details in the Technical Standard Specification – Mechanical
Section 06 – Piping and Accessories (AM-ENG-SS-03-06).
ii. Pipe and accessories used for conduits shall conform to the standard Specification of the
American Water Works Association (AWWA) or equivalent. In general, the following factors shall
be considered in designing conduits:
a) Carrying capacity
b) Maximum pressures
c) Present and future water hammer
d) Hydraulic grade
e) Traffic loads
f) Laying conditions
g) Expansion and contraction
h) Anchorage at bends and joints
i) Depth of cover
a) Location, dimensions, plan views, sections and elevations of all existing and proposed
plant facilities
b) Elevations of high and low water level of disposal point to which the plant effluent is to be
discharged
c) Type, size, pertinent features, and operating capacity of all pumps, blowers, motors, and
other mechanical devices
d) Minimum, design average, and peak hourly hydraulic flow in profile, including details of all
chemical flows, backwashes, and recycle streams
e) Adequate description of any features not otherwise covered by the Specification.
f) Detailed process flow diagrams for liquid and solid streams, process air, chemical, plant
utility water, foul air to odour control system and plant drainage.
g) Mass and flow balances of all processes and process streams
h) Piping and instrumentation design (P&ID) diagrams showing all relevant process
equipment, piping, main valves, and control instrumentation.
i) Detailed pipe and route and cable route diagrams, sections.
2.5.6. Unit Bypasses
i. Properly located and arranged bypass structures and piping shall be provided so that each unit of
the plant can be removed from service independently.
ii. The bypass design shall facilitate plant operation during unit maintenance and emergency repair
so as to minimize deterioration of effluent quality and ensure rapid process recovery upon return
to normal operational mode.
iii. Bypassing shall be accomplished through the use of duplicate or multiple treatment units in any
stage if the design peak instantaneous flow can be handled hydraulically with the largest unit out
of service.
iv. The actuation of all bypasses shall require manual action by operating personnel. All power-
actuated bypasses shall be designed to permit manual operation in the event of power failure,
and shall be designed so that the valve shall fail as is, upon failure of the power supply.
v. A fixed high water level bypass overflow shall be provided in addition to a manually or power
actuated bypass.
2.5.7. Unit Dewatering, Flotation Protection, and Plugging
i. The plant shall have suitable means such as drains or sumps to completely dewater each unit to
an appropriate point in the process.
ii. Due consideration shall be given to the possible need for hydrostatic pressure relief to prevent
flotation of structures.
iii. Pipes subject to plugging shall be provided with a means of mechanical cleaning or flushing.
treatment process or biomass may be adversely affected due to oxygen depletion and septic
conditions. The specific need for emergency power facilities shall be decided upon in conjunction
with the Client.
ii. The need for standby power and the extent of equipment requiring operation by standby power
must be individually assessed for each sewage treatment plant. Some of the factors which must
be considered in making the decisions regarding standby power and the processes to be
operated by the standby power equipment are as follows:
a) Reliability of primary power source
b) Number of power feeder lines supplying grid system, number of alternate routes within
the grid system, and the number of alternate transformers through which power shall be
directed to the STP
c) Whether sewage enters the plant by gravity or is pumped
d) Type of treatment provided
e) Pieces of equipment which may become damaged or overloaded following prolonged
power failure
f) Assimilation capacity of the receiving waters and ability to withstand higher pollution
loadings over short time periods
g) Other uses of the receiving water
iii. Each specific installation shall provide for the following considerations:
a) Means for illuminating and ventilating working areas to ensure safe working conditions
b) Standby power source, or equivalent, to power pumps, motorized valves, and control
panels that are necessary to maintain the sewage flow through the treatment plant
2.6.1.2. Power for Aeration
i. Standby power generation for aeration equipment is not generally required for activated sludge
processes. However, where there is a history of long-term power outages (> 4 hours), auxiliary
power for minimum aeration of the activated sludge shall be provided.
2.6.1.3. Power for Disinfection
i. Where required, continuous disinfection shall be provided during power outages.
ii. Continuous de-chlorination may be required for chlorine dosing systems.
2.6.2. Water Supply
i. An adequate supply of potable water, under pressure, shall be provided for sanitary and drinking
purposes use in the laboratory and for general cleanliness around the plant. No piping or other
connections shall exist in any part of the treatment Works, which, under any conditions, might
cause the contamination of a potable water supply.
ii. If intended for additional use, the chemical quality shall be checked for suitability for its intended
use such as in heat exchangers, chlorinators, or similar components.
iii. The municipal water system and the potable water piping system within the treatment building
shall be protected from the potential backflow of sewage due to backpressure with the use of
certified backflow prevention devices. In this case, the minimum devices to be used on the
building water service lines shall be a reduced pressure zone backflow preventer.
iv. For protection of water users within the building, appropriate vacuum breakers (including break
tanks), as determined by the Engineer, shall be installed on any threaded water connection.
There shall be no connection made to the potable water supply within the treatment building
between the reduced pressure zone backflow preventer and the street source.
2.6.2.2. Sanitary Facilities
i. Toilet, shower, lavatory, and lockers facilities shall be provided in sufficient numbers and
convenient locations to serve the expected plant personnel.
ii. Floor surfaces shall be sloped adequately to a point of drainage.
2.6.3. Flow Measurement and Location
2.6.3.1. General
i. Flow measurement facilities with indicating, totalising, and recording flow measurement shall be
provided to measure the minimum following flows:
a) Plant influent or effluent flow
b) Excess flow treatment facility discharges (to be advised by the Client on a site-by-site
basis)
c) Other flows required to be monitored under the provisions of the discharge permit
ii. All other flows such as return activated sludge, waste activated sludge, mixed liquor recirculation,
recirculation of TE, recycled filtrate water, or sludge liquors required for plant operational control
and flows that are to be accounted for in deriving the TE flow where there is no effluent flow
monitoring, service water, wash water, and chemical solutions shall be measured.
iii. Flow measurement equipment including approach and discharge conduit configuration and
critical control elevations shall be designed to ensure that the required hydraulic conditions
necessary for accurate measurement are provided. Conditions that must be avoided include
turbulence, eddy currents, air entrainment, and similar conditions that upset the normal hydraulic
conditions that are necessary for accurate flow measurement.
iv. Magnetic flow meters on piped flows shall be located, or the pipe designed, such that the part of
the pipe where the meter is located is flooded and in line with the manufacturer’s
recommendations.
v. Where meters are periodically removed, valving and bypass pipework shall be provided.
vi. Measurement of full flow to treatment (FFT) at the point of flow separation shall be provided at a
minimum for all works; this shall provide instantaneous flows and record daily maximum and
minimum flows and average daily flows (midnight to midnight), expressed as m 3/day.
vii. Storm and emergency overflows shall have event recorders which measure the duration of the
spilling event and overflow rate. These shall log the date, time, and duration of spills in hours for a
minimum of 5 years (this may be done via a telemetry system).
viii. Where instantaneous flow measurements are not required to be displayed, then such flow
measurement devices and their incumbent structures shall not be provided.
2.6.3.2. Accuracy
i. The measurements of flow to full treatment with accuracy of up to ±8 percent shall be provided.
2.6.3.3. Design Considerations
i. Where a standing wave flume is provided, it shall be designed and constructed in accordance
with the requirements of British Standard (BS) 3680, Part 4C: 1981. The flume and associated
channels shall be designed to operate over the full range of flows without being drowned.
ii. Where a V-notch weir is provided, it shall be designed and constructed in accordance with the
requirements of BS 3680, Part 4B: 1986. This type of measuring device shall only be used to
monitor final effluent.
iii. Where a magnetic flow meter is provided, it shall comply with the requirements of BS EN ISO
6817 and be appropriately sized and positioned in accordance with the manufacturer’s
recommendations to achieve the specified accuracy. The flow meter shall operate under all flow
conditions.
2.6.3.4. Specific Requirements
i. There shall be a level hard-standing adjacent to the flow measurement facility for access.
ii. V-notch weirs and standing wave flumes shall be preceded by an area of laminar flow for the
installation of an ultrasonic level detector with a data logger.
iii. Where practical, the plate with a V-notch weir shall be mounted within a flow measuring chamber,
which shall include sampling facilities and have a removable lightweight access cover. There
shall be a facility to clean and remove any settled matter that may accumulate upstream of the
plate.
2.6.4. Monitoring and Sampling Equipment
i. Influent and effluent composite sampling equipment shall be provided, where necessary, to meet
discharge permit monitoring requirements. Composite sampling equipment shall also be
provided, as needed, for influent sampling and for monitoring plant operations.
ii. The influent sampling point shall be located downstream of the screens and grit removal, and
prior to any process return flows.
iii. All sampling points shall be appropriately signposted and labelled, and have an easy and safe
access. They shall be arranged so that a representative sample can be obtained safely.
iv. On-line monitoring instrumentation shall be provided in accordance with the consent conditions.
v. Final selection of additional on-line monitoring shall be subject to risk assessment, automation
requirements, and value engineering.
vi. The overall level and location of on-line sampling equipment shall be agreed upon in conjunction
with the Client.
2.6.5. Laboratory Facilities
i. The Client operates a central laboratory and conducts sampling and analysis of parameters to
meet the Concession Agreement requirements of various STPs.
ii. Generally the treatment plant shall include a laboratory for making the necessary analytical
determinations and operating control tests, except for those plants utilising only processes not
requiring laboratory testing for plant control and where satisfactory offsite laboratory provisions
are made to meet the permit monitoring requirements. For plants where a fully equipped
laboratory is not required, the requirements for utilities, fume hoods, and similar components may
be reduced.
iii. The laboratory shall have sufficient size, bench space, equipment, and supplies to perform all
self-monitoring analytical Works required by discharge permits, and to perform the process
control tests necessary for good management of each treatment process included in the design.
iv. The facilities and supplies necessary to perform analytical work to support industrial waste control
programs shall normally be included in the same laboratory. The laboratory arrangement shall be
sufficiently flexible to allow future expansion should more analytical work be needed. Laboratory
instrumentation and size shall reflect treatment plant size, staffing requirements, process
complexity, and applicable certification requirements. Experience and training of plant operators
shall also be assessed in determining treatment plant laboratory needs.
v. The Designer shall liaise closely with the Client to understand the specific laboratory facility
requirements for the STP. The Table 6, Table 7, Table 8 and Table 9 shows indicative lists of
Laboratory facility requirements;
Indicative
Particulars Specification
Quantity
pH Meter Digital with Electrodes pH 1.0 to 14.0 1 1 No.
Heating Oven, Temperature (250 oC) 600 x 600 x 450 mm 2 1 No.
Muffle Furnace temp. (1,200oC) 50 x 150 x 350 mm 1 1 No.
BOD Incubator with Digital Display 10 ft.3 1 1 No.
Incubator 600 x 600 x 450mm 1 1 No.
Hot Plate Cap (3 kW) 2 ft. x 1 ½ ft. 1 1 No.
Heating Metals 120 oC 4 1 No.
Refrigerator (286L / 300L) 1 1 No.
pH Comparator with Disc. - 1 1 No.
Chemical Pan (Single Pan) Sensitivity: 0.01mg 1 No.
Chemical Pan (Double Pan) – Electrical Operated Sensitivity: 0.01 mg 1 No.
Spectrochem-photometer - 1 1 No.
DO Meter Digital 0 – 15 mg/L 1 1 No.
Water Distillation Plant 4 L/hr 1 1 No.
Pipette Washer - Stainless Steel - 1 No.
Pipette Drieter - Stainless Steel - 1 No.
Sieve Set - 1 No.
Sieve Set Vibrator (Speed & Timer Control) - 1 No.
Kjeldehl Digestion with 6 Hot Plates & Regulator - 1 No.
i. The following items of protective clothing or equipment shall be available and utilised for all
operations or procedures where their use will minimise injury hazard to personnel:
a) Self-contained breathing apparatus, recommended for protection against chlorine
b) Chemical workers’ goggles or other suitable goggles (safety glasses are insufficient)
c) Face masks or shields for use over goggles
d) Dust mask to protect the lungs in dry chemical areas
e) Rubber gloves
f) Rubber aprons with leg straps
g) Rubber boots (leather and wool clothing shall be avoided near caustics)
2.7.4. Warning System and Signs
i. Facilities shall be provided for automatic shutdown of pumps and sounding of alarms when failure
occurs in a pressurised chemical discharge line.
ii. Warning signs requiring use of goggles shall be located near chemical stations, pumps, and other
points of frequent hazard.
2.7.5. Dust Collection
i. Dust collection equipment shall be provided to protect personnel from dusts injurious to the lungs
or skin and to prevent polymer dust from settling on walkways which become slick when wet.
2.7.6. Eyewash Fountains and Safety Showers
i. Eyewash fountains and safety showers utilising potable water shall be provided on each floor
level or Works locations involving hazardous or corrosive chemical storage, mixing (or slaking),
pumping, metering, or transportation unloading. These facilities are to be as close as practical to
points of chemical exposure. They are to be fully operable during all weather conditions.
ii. Safety showers and eye wash facilities shall be provided to the requirements of American
National Standards Institute (ANSI) Z 358.1: 1998.
iii. Showers shall be located no more than 15 m distant from the chemical delivery area.
iv. Storage tanks of 1,200 litre capacity shall be provided unless a guaranteed supply of potable
water of at least 1.25 l/s is available at pressures of 20 to 50 psi (140 to 345 kPa).
v. Heating shall be provided such that showers provide an on-demand supply of water at a
temperature between 15 and 38oC.
vi. Drainage shall be provided in and around safety showers to contain all water within the shower
area. (Showers shall be run and emptied monthly.) Showers shall drain directly to sumps/drains
and not via open areas.
2.7.7. Hazardous Chemical Container Identification
i. The identification and hazard warning data included on shipping containers, when received, shall
appear on all containers (regardless of size or type) used to store, carry, or use a hazardous
substance. Wastewater and sludge sample containers shall be adequately labelled. Suitable
labels to identify a wastewater sample as a hazardous substance are as follows:
a) “RAW SEWAGE WASTEWATER Sample point No.____”
b) “Contains Harmful Bacteria”
c) “May contain hazardous or toxic material. Do not drink or swallow”
3. Preliminary Treatment
Spacing 25 mm
3.2.2.1.v.a...1. Invert
i. The screen channel invert shall be 75 to 150 mm below the invert of the incoming sewer.
3.2.2.1.i.a...1. Flow Distribution
i. Entrance channels shall be designed to provide equal and uniform distribution of flow to the
screens.
ii. Screen installations are to be sized to treat all flows with one unit out of service.
iii. Screens are to be provided with bypass channels sized to take the maximum potential flow to the
Works. Each bypass channel shall be clear flow with no screen.
3.2.2.1.iii.a...1. Return Flows
i. All Works drains, storm returns, and sludge liquors shall normally be returned downstream of the
coarse screens.
3.2.2.1.i.a...1. Cleaning
i. The screen shall have automatic mechanical cleaning except at sites without a power supply, in
which case, the bar screen shall be designed to pass 150 percent of the maximum design flow
when clean, and have easy access for cleaning. This shall include a mechanical device for the
removal of screenings from the screen and depositing the screenings to a screenings handling
system, as a minimum requirement.
ii. Hoisting or lifting equipment may be necessary depending on the depth of pit and amount of
screenings or equipment to be lifted.
iii. Manually cleaned screening facilities shall include an accessible platform from which the operator
shall rake screenings easily and safely. Mechanically cleaned screen channels shall be protected
by guardrails and deck gratings.
iv. Suitable drainage facilities shall be provided for both the platform and the storage area.
3.2.2.1.iv.a...1. Screen Wash Water
i. Wherever possible, treated final effluent rather than potable water shall be utilised for screen
wash water.
ii. Where final effluent is used, covers shall be provided to eliminate the aerosol effect.
iii. If it is not possible to use final effluent, any wash water used on a spray bar shall first be passed
through a duplex filter system. The duplex filter shall be installed to match the screen requirement
and located at the point of use.
iv. The use of screened crude sewage shall be avoided wherever possible.
v. If screened crude sewage cannot be avoided, then a deluge wash system shall be used.
Duty/standby pumps of the cutter type shall be provided.
vi. If high volumes are fat are present, then a deluge system (unfiltered) must be avoided.
vii. The wash water pressure shall be appropriate to the particular screen type, boosted locally if this
is greater than the normal site-wide wash water pressure.
3.2.2.1.vii.a...1. Access and Ventilation
i. Screens located in pits more than 1.2 m deep shall be provided with stairway access. Appropriate
ventilation provisions shall be provided.
ii. Screening devices, installed in a building where other equipment or offices are located, shall be
isolated from the rest of the building, be provided with separate outside entrances, and be
provided with a separate and independent fresh air supply.
iii. Fresh air shall be forced into enclosed screening device areas or into open pits more than 1.2 m
deep. Dampers shall not be used on exhaust or fresh air ducts, and fine screens or other
obstructions shall be avoided to prevent clogging. Where continuous ventilation is required, at
least 12 complete air changes per hour shall be provided. The air change requirements shall be
based on 100 percent fresh air.
3.2.2.1.iii.a...1. Railings and Gratings
i. Manually cleaned screen channels shall be protected by guardrails and deck gratings, with
adequate provisions for removal or opening to facilitate raking.
3.2.2.1.i.a...1. Electrical Equipment, Fixtures, and Controls
i. Electrical equipment, fixtures, and controls in the screening area where hazardous gases may
accumulate shall meet the requirements of the National Electrical Code for Class I, Division 1,
Group D, locations.
3.2.2.1.i.a...1. Process Control and Operating Regime
i. The cleaning cycle shall be automated.
ii. Automatic controls shall be supplemented by a manual override.
iii. The frequency and duration of this cycle shall initially be set to Contractors’ parameters during
commissioning; however, provision shall be made within the control system for operator
intervention to adjust the time clock settings or manually (or both) initiate a cleaning cycle in
addition to the level control operation of the screen.
iv. Screen control shall be on an upstream level, with timer over-ride. Mat formation is to be
discouraged as this can contribute to “hair-pinning”.
v. Multiple screens shall be sized as duty/standby, but shall be controlled to run as duty/duty.
vi. Screen installations shall be sized to treat all flows with one unit out of service.
vii. Screens shall be provided with bypass channels sized to take the maximum potential flow to the
Works. Each bypass channel shall be clear flow with no screen.
viii. Screens shall run continuously on loss of control level or signal.
ix. Screens shall stop on failure of screenings conditioner.
x. Screens shall stop on failure of screen wash water provision.
3.2.3. Fine Screens
i. The use of static wedge wire, band, drum, and step screens shall all be considered appropriate
for use with fine screening applications.
ii. The Designer shall determine in conjunction with the Client the most appropriate fine screening
device for use on a particular project.
iii. Unless otherwise stated, the term “fine screen” shall imply a 6 mm or less, two-directional screen.
If the downstream main wastewater treatment process is based on a membrane bioreactor, then
the requirement of a secondary screen and the size of the screen shall be based on the
recommendations of the membrane manufacturer to meet the system design requirements.
iv. The design guidance provided in Table 11 shall be used for the design of fine screens:
c) Where there are a number of combined sewer overflows (CSOs) and detention tanks in
the catchment, an additional 10 percent shall be included in addition to the design
blinding factor.
d) Where there is a flat catchment prone to deposition, an additional 10 percent shall be
included in addition to the design blinding factor.
e) Where there is a history of screens problems due to quantity of rag presented, an
additional 10 percent shall be included in addition to the design blinding factor.
f) Where the flow to the screen is pumped, an additional 10 percent shall be included.
xv. The maximum blinding factor to be used shall be 60 percent.
3.2.3.1 Process Control and Operating Regime
i. Automatic controls shall be supplemented by a manual override.
ii. The cleaning cycle shall be automated.
iii. The frequency and duration of this cycle shall initially be set to Contractors’ parameters during
commissioning; however, provision shall be made within the control system for operator
intervention to adjust the time clock settings or manually (or both) initiate a cleaning cycle in
addition to the level control operation of the screen.
iv. Multiple screens shall be sized as duty/standby, but shall be controlled to run as duty/duty.
v. Screens shall run continuously on loss of control level or signal.
vi. Screens shall stop on failure of screenings conditioner.
vii. Screens shall stop on failure of screen wash water provision.
viii. The appropriate handling system shall be sized to take 100 percent of the design screenings load
received at the Works based on a peaking factor of 50.
ix. Lauder channels are not considered suitable for coarse screen applications.
x. Macerator systems are not considered suitable for coarse screens due to the nature of the large
debris encountered.
xi. Screw conveyors are considered more appropriate for all applications where screens are external
and may contribute to site odour.
xii. Where screws are being considered, the maximum length of any one screw shall not exceed 20
m.
xiii. Where screw conveyors are used for screening transfer, full standby shall be provided. If there
are two screens, there shall be two conveyors with each conveyor capable of taking the full load
from both screens.
xiv. Conditioning units suffer from excess wear due to carry-over of stones, so the inclusion of a stone
trap is a requirement. Ideally, there shall be provision for continuous removal of stones using a
screw auger system.
xv. Design of screenings handling systems, bagging units, and disposal facilities including bins and
skips shall be capable of working with standard bins, skips, and similar components.
xvi. Screening receptacles shall be designed to contain a minimum of 1 day's screenings, at
maximum production rate.
xvii. Screenings skips shall have concrete hard standing (with steel slide rails), with drainage into
return liquor system, and wash down facilities.
xviii. Crash barriers are required to protect plant from skip and skip vehicle.
xix. Skip delivery lorries shall have direct access to the set down point, as skip shunting is not
allowed.
xx. The feasibility of providing a facility to feed screenings directly to a skip in the event of a
conditioning plant failure shall be considered.
xxi. A facility to include protection from the elements where skips are removed less frequently than
once a week shall be considered.
xxii. A suitable system to prevent rainwater ingress and odour nuisance shall be provided. Where the
use of “wheely bins” are agreed upon with the Client, as appropriate, due recognition shall be
made of manual handling to minimise risk of operator injury and fully account for collection and
disposal arrangements.
xxiii. Where skips are required to be positioned in a building, there shall be a suitable skip positioning
system provided. Drainage of the skip loading area connected to the foul system shall be
provided.
3.4.1.2. General
i. Grit chambers shall be provided for all STPs. If grit chambers are not provided, a Specification
waiver shall be sought from and provided by the Client.
ii. If a treatment facility is designed without grit removal devices, the design shall include provision
for future installation. This condition shall be evaluated on a case-by-case basis with the Client.
iii. Grit removal devices shall be located after screens, but ahead of pumps and other treatment
units.
iv. Mechanical grit removal devices shall be provided where substantial amounts of grit passing
through the plant processes or equipment will interfere with the operation and maintenance; will
cause deterioration and subsequent replacement of equipment; or will substantially increase the
need for additional storage capacity in other treatment units where grit is likely to accumulate.
v. The Designer shall determine the grit quantity and loading rates to design the grit collector and
grit handling plant accordingly.
vi. System inlet and outlet turbulence shall be minimised by design considerations for transition
sections, such as approach channels, and inlet and outlet devices. The inlet and outlet shall be
designed to avoid short circuiting. In some cases, the installation of longitudinal and traverse
baffles shall be considered to improve grit removal.
vii. All grit removal plants shall be designed to remove grit particles down to 0.2 mm.
viii. Grit removal: plants shall remove 95 percent of grit/sand particles of diameter 0.1 mm and above
and with a specific gravity equal to or greater than 2,650 kg/m 3.
ix. Grit/sand removal efficiency shall be maintained under all flow conditions to the maximum design
flow specified.
x. Any grit separators shall be sized to operate over the full range of flows;
xi. All grit removal facilities shall be provided with adequate automatic control devices to regulate
detention time, agitation, and air supply. The units shall have manual override capability.
xii. Grit classifiers shall be of proprietary design. The unit shall facilitate removal of organic matter
from the removed grit. All extraneous solids and water shall be returned to the wastewater flow
for treatment.
xiii. Grit chambers and all grit conveying, washing, and handling facilities shall be located outdoors in
the plants with flows up to 4 MLD. In larger plants, all equipment shall be located in a building that
has adequate ventilation, which if continuous, shall provide at least 12 complete air changes per
hour, or if intermittent, at least 30 complete air changes per hour.
xiv. Design of grit disposal facilities, including bins and skips, shall be capable of working with
standard bins, skips, and similar components. A suitable system to prevent rainwater ingress and
odour nuisance shall be provided.
xv. Drainage of the skip loading area shall be connected to the foul drainage system.
xvi. All electrical Works in enclosed grit removal areas where hazardous gases may accumulate shall
meet the requirements of the National Electrical Code for Class I, Division 1, Group D, locations.
Explosion-proof gas detectors shall be provided.
3.4.1.3. Capacity
i. Since grit storage capacity is essential but cannot be easily determined due to the extreme
variations in grit quantities of different collection systems, the typical design values of 0.02 to
0.1 m3/1,000 m3 shall be used where no specific data is available
3.4.1.4. Odour Control
i. To minimise odours and nuisance, the unit shall be subjected to air extraction to an odour control
unit.
3.4.2. Selection Criteria
i. The suitability of grit/sand removal equipment shall be selected from the types provided in Table
12, and shall be appropriate to the size of Works and conditions.
Table 12: Grit Removal Selection Table
Grit/Sand Trap
vii. Air diffusers shall be removable without taking the basin out of service. Swing type diffusers are
most desirable.
viii. Safe access shall be provided to the grit chambers and, where mechanical equipment is involved,
all moving parts shall be enclosed.
ix. Typical design parameters are provided in Table 13.
Table 13: Typical Design Parameters for Aerated Grit Tanks
ii. Grit/sand shall be separated, washed, and dewatered prior to transfer to a skip for disposal.
iii. The grit handling plant shall be designed to deliver a product containing no more than 30 percent
volatile solids and not less than 50 percent dry solids to a skip.
3.4.3.4.iii.a...1. Transfer and Classification
i. Transfer mechanisms shall be designed to remove grit from the tank floor or hoppers. The grit
shall be classified by separating out organic material and sewage. Transfer and classification
shall be combined using a reciprocating rake classifier or screw classifier.
ii. Where an airlift/air wash assembly is required to facilitate grit removal, transfer or washing it shall
consist of an airlift and discharge pipe delivering grit to the grit classifier and shall be complete
with separate air wash, airlift headers, and actuated three-way ball valve. The air wash header
shall discharge an adequate quantity of air to effect the transfer and washing of the collected grit.
The airlift shall operate on an operator adjustable time clock control.
iii. The air lift shall be designed for static heads in the range of 3.5 to 5.0 m. The air supply shall be
piped to the point of entry to the uptake pipe. The rate of air flow shall be determined to provide a
flow of water into the uptake pipe sufficient to suspend the grit and transport it to a high level
classifier.
3.4.3.4.iii.a...1. Grit Pumps
i. Where transfer by airlift alone is not possible (for example, due to static head requirements), grit
pumps shall generally be used for the transfer of grit from the collection sump/hopper to the
classifier. Where necessary, carrier water shall be provided to re-suspend the grit and facilitate
grit removal, with the return liquor discharge back to treatment.
ii. The grit pumps shall operate in conjunction with the classifier unit (where appropriate) on an
operator adjustable time clock control.
iii. Grit pumps shall incorporate abrasion resistant materials and recessed torque flow impellers.
Suction and discharge isolation valves and a discharge non-return valve shall be provided.
3.4.3.4.i.a...1. Materials
i. Due consideration shall be given to the selection of materials because of corrosive conditions
present.
ii. Consideration shall be given to locating drain valves, weir plates, and stop gates for ease of
operation and safety.
3.4.4. Fats, Oil, and Grease
3.4.4.1. General
i. Fats, oil, and grease (FOG) removal shall either be a separate system or combined with the grit
and screenings removal system. It shall protect downstream equipment and reduce operational
attendance on a best WLC basis.
ii. FOG separation by diffused air is the preferred solution, but other methods shall be considered if
appropriate process guarantees can be obtained and the method is agreed upon with the Client.
iii. Variations in effluent quality and ambient temperatures (typically 0 to 55C) shall be taken into
consideration when designing FOG removal facilities.
iv. FOG shall be transferred from the separation tank for appropriate further treatment or disposal, or
both.
v. Unless otherwise specified, FOG in the raw sewage shall be considered as a minimum of 31 g
per capita per day as shown in standard references for wastewater produced from domestic
sources.
vi. The provision of standby plant shall be site-specific and depend upon the risk of plant failure on
the downstream processes.
vii. Where a single FOG separation unit is used, a bypass facility shall be provided, complete with
isolation penstocks or valves for maintenance purposes.
viii. Provisions shall be made for isolating and dewatering each unit for maintenance purposes.
ix. Turbulence shall be minimised by design considerations for transition sections such as approach
channels and inlet and outlet devices.
x. The inlet and outlet devices shall be designed to avoid short-circuiting. In some cases, the
installation of longitudinal and traverse baffles shall be considered to improve grit removal.
4.1. Pre-Aeration
i. Pre-aeration periods shall be 10 to 15 minutes if odour control and prevention of septicity are the
prime objectives.
4.2. Flocculation
4.2.1. Detention Periods
i. At plants where there are two or more flocculation basins utilising chemicals, provision shall be
made for a rapid mix of the sewage with the chemical so that the sewage passing to the
flocculation basins shall be of uniform composition.
ii. The detention period provided in the rapid mixing chamber shall be very short (that is, 0.5 to
1.0 minutes).
iii. When air or mechanical mixing is employed in conjunction with chemicals to coagulate and
flocculate the waste effluent, a detention time of approximately 30 minutes shall be employed.
This detention period may be reduced if the use of a polymer is employed.
4.2.2. Stirring Devices
4.2.2.1. Paddles
i. Paddles shall have a peripheral speed of 0.5 to 0.75 m/s to prevent deposition of solids.
4.2.2.2. Aerators
i. Any of the types of equipment used for aerating activated sludge may be utilised.
ii. It shall be possible to control agitation, to obtain good mixing and maintain self-cleaning velocities
across the tank floor.
5. Flow Equalisation
5.1. Objectives
i. The primary objective of flow equalisation basins is to dampen the diurnal flow variation, as well
as variations caused by inflow/infiltration, and thus achieve a nearly constant flow rate through
the downstream treatment processes.
ii. The secondary objective is to dampen the strength of wastewater constituents by blending the
wastewater in the equalisation basin to maintain a degree of reliability and operational control.
5.2. General
i. Flow equalisation shall be provided in mechanical plants where large diurnal variations are
expected to cause mechanical, hydraulic, or biological process upsets.
ii. For treatment plants with capacities of less than 2 MLD, employment of this process is particularly
recommended.
5.3. Location
i. Equalisation basins shall be located downstream of storm overflows and pre-treatment facilities
such as bar screens, grit chambers and, where possible, primary clarifiers.
5.4. Type
i. Equalisation basins shall be designed as either in-line or side-line units.
ii. Separate basins or unused on-line treatment units, such as primary clarifiers or aeration tanks,
may be utilised for flow equalisation during the early period of the plant’s design life.
iii. If no other unit is available and a single basin is used for flow equalisation, then a bypass pipe
with an isolation valve shall be provided around the basin to the downstream portion of the
treatment facility.
5.6. Operation
5.6.1. Mixing
i. Aeration or mixing equipment shall be supplied to maintain adequate mixing within equalisation
basins. Requirements for normal domestic wastewater shall range from 0.4 to 0.8 kW/100 m 3 of
storage.
ii. Hopper bottoms with draw-offs shall be provided to remove periodical accumulation of sludge and
grit.
5.6.2. Aeration
i. Multiple aeration or mixing units (or both) shall be provided to maintain adequate mixing and for
continuous operation.
ii. To maintain aerobic conditions, air shall be supplied at a rate of 0.01 to 0.015 m3/m3-min.
iii. Aeration shall be sufficient to maintain aerobic conditions and prevent septic conditions from
developing.
iv. All compressors, blowers, and aeration equipment shall comply with the details in the Technical
Standard Specification – Mechanical Section 03 – Pumps, Compressors, Blowers, and Cutters
(AM-ENG-SS-03-03).
5.6.3. Controls
i. All inlets and outlets of each basin compartment shall be provided with accessible flow control
devices.
ii. Facilities shall be provided downstream of the basins to monitor liquid levels and equalised flow
rates.
iii. Flow division control facilities shall be provided, as necessary, to ensure organic and hydraulic
loading control to plant process units, and shall be designed for easy operator access, change,
observation, and maintenance. Appropriate flow measurement shall be incorporated in the flow
division control design.
6. Sedimentation
i. The Clients upcoming new STPs have adopted technologies which do not require primary
sedimentation except for the existing assets which are planned for demobilisation once the new
STPs are commissioned.
ii. The following section is retained based on the previous version as a reference, and for any future
reference, if the need arises.
ii. The length-to-width ratio for rectangular clarifiers shall be equal to or greater than 4 to 1. The
maximum horizontal velocity in a rectangular clarifier shall not exceed 0.6 m/min in a final clarifier.
6.2.3. Channels
i. Inlet channels shall be designed to maintain a velocity of at least 0.3 m/s at 50 % design flow.
Where minimum velocities are less, provisions shall be made for the re-suspending of the solids.
Corner fillets or channelling shall be provided to eliminate corner pockets and dead ends.
ii. Width of effluent channels shall be at least 300 mm. Bottom of the channels at the outlet
structures shall be at least equal to or above the water levels of the downstream treatment units.
The effluent channel shall be sized to prevent weir submergence at the peak hourly flow. The
bottom of effluent channels shall be at least 1 foot below water levels maintained in the clarifiers,
except for small package plants.
6.2.4. Freeboard
i. The outer walls of clarifiers shall extend at least 150 mm above the surrounding terrain or
100-year flood plain and shall provide at least 300 mm of freeboard to the water surface. Where
clarifier walls do not extend 1 m above the surrounding terrain, a cover, fence, wind screen, or
suitable barrier shall be provided to prevent high wind currents and debris from entering the
clarifier.
6.2.5. Baffling and Scum Removal
i. Scum baffles shall be provided around and prior to all effluent weirs. The baffles shall be located
at the water surface to intercept all floating materials and scum. Baffles shall extend at least
75 mm above the weir plate elevation and 300 mm below the water surface.
ii. Circular clarifiers shall be provided with symmetrical baffling, a minimum of 150 mm inside the
weir plate, to distribute the flow uniformly in all radial directions. In a circular centre-feed clarifier,
the inlet baffle shall have a diameter of 15 to 20 percent of the clarifier diameter and shall not
extend more than 3 feet below the water surface. With 100 percent recirculation, circular centre-
feed clarifier inlet baffles shall not be less than 20 percent of the clarifier diameter and have a
depth of 55 to 65 percent of the side wall depth. The maximum inlet velocity to a centre inlet well
shall not exceed 1.0 m/s. The outflow velocity shall not exceed 5 m/min. In a circular peripheral-
feed clarifier, the inlet baffles shall extend at least 300 mm below the flow line of the inlet and
shall be located above the sludge blanket zone at a distance where the critical horizontal velocity
will just begin to produce scour.
iii. Rectangular clarifiers shall be provided with inlet ports or pipes and baffles for uniform distribution
of flow across the clarifier and effluent weirs. The baffles shall extend across the width of the
clarifier and upstream to the effluent weirs. Effective scum collection and removal facilities,
including baffling, shall be provided ahead of the effluent weirs on all clarifiers. Provisions shall be
made for disposal of scum with the sludge; however, other special provisions for disposal of scum
and floating materials may be necessary. A scum pit shall be located outside of the clarifier but
adjacent to the scum collection point, on the side of the clarifier opposite the prevailing wind
direction. Provisions shall be made for mixing the contents of the scum pit with such equipment
as a mechanical mixer or air diffuser.
6.2.6. Submerged Surfaces
i. The topside of beams, troughs, or similar construction components shall have a minimum slope
of 1.4 vertical to 1 horizontal; the underside of such components shall have a slope of 1 to 1 to
prevent the accumulation of scum and solids.
6.2.7. Weirs
i. Weir plates shall be adjustable for levelling and sealed against the effluent channel. Weirs shall
be located to optimise actual hydraulic detention time and minimise short-circuiting. Circular
clarifiers, with peripheral-feed or centre-feed inlets, shall be provided with a full weir. Effluent
launders may be placed at points other than at the periphery. The minimum water depth below
effluent weirs located near the centre shall be 3.0 to 3.5 m if weirs are located at the periphery.
These minimum water depths need not be provided for small clarifiers having low weir and
surface-loading rates.
ii. Double weirs to increase the length are permissible if installed sufficiently in-board for good
separation of flow to minimise velocity problems at the periphery. Experimentally, circular weir
troughs placed at two-thirds to three-fourths of the radial distance from the centre are at the
optimum position to intercept well-clarified effluent.
iii. The weir length of double weirs shall be computed as double the length of the centreline of the
launder. Weirs shall be of the saw-tooth or serpentine type to allow for better weir overflow and
flow distribution.
iv. To determine the spacing of multiple weirs in rectangular clarifiers, the up-flow velocity near the
weir shall be limited to approximately 3.5 to 7.0 m/h. If weirs are located at end walls in
rectangular clarifiers, the minimum water depth below the effluent weir shall be 3.5 m.
6.2.7.2. Weir Loadings
i. Weir loadings shall not exceed 5 m 3/h per lineal meter for primary, intermediate, or final clarifiers
at peak hourly flows unless select design parameters are considered (for example, depth, surface
area, detention time, horizontal or vertical velocities [or both], and solids density), then the higher
weir loadings may be considered. Hydraulic loading criteria in clarifier design shall be based on
the sum of plant inflow and recycle rates.
ii. Weir loadings at peak hourly flows shall not exceed 5 m 3/h per lineal meter for final clarifiers in
plants with average design flows of 4.0 MLD or less. Weir loadings at peak hourly flows in plants
with average design flows larger than 4.0 MLD shall not exceed 7.5 m 3/h per lineal meter for final
clarifiers.
iii. Final rectangular clarifiers with launder and weir at the outer wall shall not exceed a weir loading
of 10 m3/h per lineal meter at peak hourly flow. If pumping is required, weir loadings shall
correspond to the pumping rates to prevent short-circuiting.
6.2.8. Detention Time
i. Nominal detention periods shall be in the 2 to 3 hour range at the average design flow rate
including consideration for recirculation.
ii. If no recirculation is employed, then the minimum detention time shall be >2 hours.
iii. Detention periods in clarifiers vary with surface-loading rates and side water depths.
iv. The detention periods for final clarifiers following various activated sludge processes shall be
adjusted between 2 and 4 hours, dependent upon the type of process, design flow, recirculation
rate, and surface-loading rate.
6.2.9. Surface-Loading Rates
6.2.9.1. Final Clarifiers
i. Surface-loading rates for final clarifiers following fixed film reactors shall not exceed 1.4 m/h at
average design flow and shall not exceed 2.0 m/h at peak hourly flow.
ii. Surface-loading rates for final clarifiers following activated sludge processes, such as:
conventional, step aeration, contact stabilisation, or the carbonaceous stage of separate-stage
nitrification, shall not exceed 2.0 m/h at peak hourly flow. Surface-loading rates for final clarifiers
following an extended aeration process shall not exceed 1.7 m/h at peak hourly flow. Surface-
loading rates for final clarifiers following separate-stage nitrification shall not exceed 1.4 m/h at
peak hourly flow.
iii. Surface-loading rates recommended for various floc suspensions at peak hourly flow are
provided in Table15.
Table 15: Recommended Surface Loading Rates
iv. Tests shall be conducted whenever a pilot plant study is warranted because of unusual waste
characteristics, treatment requirements, or where design loadings exceed those limits set forth in
this section.
6.2.10. Solids Loading Rate
i. The solids loading rate, excluding chemical additives applied to final clarifiers, shall not exceed
5 kg/m2/h at peak flow rate with 100 % recirculation. Clarifiers following an extended aeration
process or an oxidation ditch shall not exceed this loading rate.
ii. The solids loading rate for final clarifiers following most activated sludge processes shall not
exceed 10 kg/m2/h at peak hourly flow. The Designer shall assure that the clarifier area is equal
to or greater than that required by surface-loading or solids loading rates based on the maximum
sludge volume index (SVI) anticipated and mixed-liquor suspended solids (MLSS).
iii. The solids loading rate is to be evaluated for both peak hourly and design average flow conditions
to determine which values shall govern in a 24-hour period. Due consideration must be given to
the duration of peak hourly flows.
6.3. Sludge
6.3.1. Sludge Collection
i. The floors of circular clarifiers shall be sloped at 1 inch per foot (1:12) to form an inverted cone to
a central sludge hopper. Floors of sludge thickeners shall be sloped at 2:12 or greater. Simple
mechanical scrapers are recommended over the suction or siphon type since rapid recirculation
of solids is not required.
ii. The floor of a rectangular clarifier shall be sloped at approximately 1 percent (1:100) toward the
cross collectors or sludge hoppers located at the influent end. If a header type suction sludge
removal mechanism is used, then the slope shall be sufficient only to provide for drainage.
iii. The sludge or settled solids in clarifiers shall be scraped or drawn to a hopper or sump
appropriately located for removal. Where cross collectors or screw conveyors are not provided,
multiple hoppers shall be installed for rectangular clarifiers or multiple clarifiers. The minimum
slope of the side walls of sludge hoppers shall be 1.7 vertical to 1.0 horizontal. Hopper bottoms
shall have a maximum dimension of 600 mm. Hopper walls shall be smooth with rounded
corners. Extra depth sludge hoppers for sludge thickening are not permissible. Vertical sludge
draw-off systems shall be considered on a case-by-case basis.
iv. Sludge draw-off pipes located on the side or bottom shall be flush with the hopper bottom. Each
sludge hopper shall have an individually valved sludge draw-off line of at least 150 mm in
diameter if gravity flow, and if pumped, of 100 mm in diameter. The static head available for
withdrawal of sludge shall be at least 0.75 m to maintain a 1 m/s velocity when removal is
dependent upon gravity flow.
6.3.2. Sludge Handling and Withdrawal
6.3.2.1. Clarifier Desludging System
i. All pumps shall comply with details in the Technical Standard Specification – Mechanical
Section 03 – Pumps, Compressors, Blowers, and Cutters (AM-ENG-SS-03-03).
ii. All piping shall comply with details in the Technical Standard Specification – Mechanical
Section 06 – Piping and Accessories (AM-ENG-SS-03-06).
iii. Mechanical sludge collection and withdrawal equipment is required and shall provide complete
and continuous removal of settled sludge for final clarifiers. The sludge collection equipment and
the drive assembly shall be designed to withstand the maximum anticipated loads of transporting
sludge to a hopper.
iv. The peripheral speed for circular flight mechanisms shall be in the range of 0.02 to 0.05 rpm but
shall not exceed 2.4 m/min in final clarifiers.
v. The straight line flight speed shall be in the range of 0.6 to 1.2 m/min but shall not exceed 0.3
m/min in final clarifiers.
vi. Air lift systems for sludge removal shall not be used for removal of sludge.
vii. Desludging systems shall be of the pumped type with a manual bypass capable of removing
8 percent dry solids sludge on a routine basis.
viii. The Designer shall determine the sludge thicknesses and the sludge flow rates depending on the
systems and mode of operation which is proposed. Due allowance shall be made for bends,
valves, and similar components, and an appropriate pipe wall roughness co-efficient (ks) when
determining the friction losses of the delivery pipe.
ix. The Designer shall be responsible for determining the most suitable size, number, and
combination of pumps to cope with the range of flows expected. The pumps shall be uniformly
sized.
x. Positive displacement pumps shall be provided for pumping primary sludge intermittently and
continuously. A positive head shall be provided on pump suctions. If motor driven return sludge
pumps are used, the maximum return sludge capacity shall be obtained with the largest pump out
of service. Pumps shall have at least 75 mm suction and discharge openings. Automatic controls
shall be provided to separately activate sludge pumps and sludge collection mechanisms. Sludge
pumping in large plants shall be controlled by timers and valve activators to provide continuous
"on-off" operation. A means of measuring the sludge withdrawal rate shall be provided for each
unit. It is recommended that sludge pumping stations have a standby pump and serve two or
more units.
xi. Pumps shall be capable of handling all sludge up to 8 percent DS.
xii. Pumps shall be designed to run 16 hours per day at 1 percent DS in normal operation. This shall
also allow for 4 hours per day at 4 percent DS.
xiii. All Designers shall consider that pumps may need to be designed to account for increased
volume incurred when receiving emergency return of waste-activated sludge (WAS) from aeration
plants.
xiv. All pumps shall be configured in a duty/standby basis. (The standby pump can be common to
other duties or a boxed spare.)
xv. Rapid sludge withdrawal pipes shall return sludge to a well at the water surface that enables
visual observation of the flow. The return sludge withdrawal pipes shall be at least 100 mm in
diameter with a hydraulic differential between the clarifier water level and the return sludge well
level sufficient to maintain a velocity of 1 m/s. The discharge piping shall be designed to maintain
a velocity of at least 0.6 m/s when return sludge facilities are operating at normal return sludge
rates. Each sludge withdrawal pipe shall be accessible for rodding or back-flushing when the
clarifier is in operation. Cleanouts and couplings shall be provided in sludge piping to facilitate
pipe cleaning and removal of pumping equipment. High points in piping shall be provided with air
releases.
xvi. Each tank shall be fitted with a drain valve that can serve as an emergency desludging option.
xvii. Sludge wells/scum pits shall be provided adjacent to the basin and equipped with suitable
devices for viewing, sampling, and controlling the rate of sludge withdrawn. Metering devices
shall be installed and located to indicate flow rates of all influent and effluent points, return
sludge, and waste sludge lines. Meters shall be accurate to within +5 percent of the actual flow
rates.
xviii. All clarifiers shall be equipped with appropriate safety features for the protection of operators.
Such features shall include drive mechanism enclosures, life lines, lighting, stairways, walkways,
handrails, deck gratings, and slip-resistant surfaces. Effluent pipes larger than 300 mm in
diameter shall be provided with bars to prevent entry of an operator if a fall shall occur.
xix. If side walls are extended some distance above the water level to provide flood protection or for
other purposes, convenient and safe walkways must be provided to facilitate housekeeping and
maintenance. For plants having an average design capacity greater than 0.4 MLD, meters shall
totalise and record.
xx. Clarifier facilities shall include a convenient and safe means of access to routine maintenance
items such as baffles, weirs, channels, scum equipment, gear boxes, and pumping facilities.
Hoisting or other means of equipment removal shall be provided. As a safety precaution, it is
recommended that telescoping valves with tees and blow-off valves at the base be provided in
sludge wells to unplug draw-off lines.
xxi. Pressurised wash water facilities shall be provided for washing scum boxes, tanks, and other
equipment. Potable wash water facilities may be used but shall have backflow preventers. If wash
water is non-potable, all outlets shall be permanently posted to indicate water is not safe.
xxii. Electrical equipment, fixtures, lighting, and controls shall be located to provide convenient and
safe access for operation and maintenance. A positive means of locking out each mechanical
device shall be provided.
xxiii. Due consideration shall be given to the selection of materials because of corrosive conditions
present.
6.3.2.2. Sludge Holding Tanks
i. Sludge treatment and conditioning centres shall have 4 days of sludge storage for indigenous
sludge (to avoid duplication of storage at satellite Works and allow for plant maintenance).
ii. Sludge storage facilities shall be designed so that the following is achieved:
7. Biological Treatment
i. The form of biological treatment to be used shall be generally based on the activated sludge
process. The actual process configuration to be used at a particular site shall be the subject of a
specific process evaluation to be undertaken in close liaison with the Client.
ii. Biological treatment shall comprise a biological oxidation process for the reduction of
carbonaceous and nitrogenous pollutants.
iii. Whilst all feasible treatment schemes shall be considered for biological treatment, the main types
of biological treatment considered most appropriate are as follows:
a) Activated Sludge Process – Extended Aeration, Conventional Systems
vi. The aeration system shall be controlled by measurement of DO within the aeration tanks.
vii. Overall average DO value from all in-service aeration lanes shall be used for blower control.
viii. Centrifugal type blowers are preferred.
ix. Membrane or ceramic disc type diffusers shall be used for new installations, with membrane disc
diffusers being preferred.
x. Diffused air fine-bubble aerators shall be laid out to give plug flow tapered aeration.
xi. Where surface aerators or hyperbolic aerators are used, it shall be possible to take one aerator
per lane out of service for maintenance whilst maintaining the required DO level.
xii. Sizing of aeration systems shall allow for increased airflow in the remaining tanks/lanes during
maintenance periods.
7.1.6. Aeration Tanks
7.1.6.1. General
i. The size of the aeration tank for any particular adaptation of the process shall be determined by
full scale experience, pilot plant studies, or rational calculations based mainly on solids retention
time, food to microorganism ratio, and MLSS levels. Other factors, such as size of treatment
plant, diurnal load variations, and degree of treatment required, shall also be considered. In
addition, temperature, alkalinity, pH, and reactor DO shall be considered when designing for
nitrification.
ii. Calculations shall be submitted to justify the basis for design of aeration tank capacity.
iii. The tanks shall be outdoors and uncovered.
iv. Each tank shall be provided with penstocks to allow isolation of each tank in the event of an
equipment failure, routine maintenance, and cleaning of the tank.
7.1.6.2. Dimensions
i. The dimensions of each independent mixed liquor aeration tank or return sludge re-aeration tank
shall be such as to maintain effective mixing and utilisation of air.
ii. Depth: Ordinarily, liquid depths shall not be less than 5.0 m for diffused aeration systems to
maximise the oxygen utilisation. Unless specified otherwise, the water depth of the tank shall be
limited to 8.0 m. Where the water depth is > 6 m, provision for degassing shall be made prior to
final settlement.
iii. Typically, tanks are designed with a length : width ratio of 4:1 to provide near plug flow conditions.
7.1.6.3. Short-Circuiting
i. For very small tanks or tanks with special configurations, the shape of the tank, the location of the
influent and sludge return, and the installation of aeration equipment shall provide for positive
control to prevent short-circuiting through the tank.
7.1.6.4. Configuration
i. Total aeration tank volume shall be divided among two or more units, capable of independent
operation, when required for maintenance and to meet applicable effluent limitations and
reliability guidelines.
ii. The hydraulic properties of the system shall permit the design peak instantaneous flow to be
carried with any single aeration tank unit out of service.
iii. Non-nitrifying aeration tanks shall be preceded by a selector zone. Hydraulic retention time (HRT)
in the selector zone shall be between 10 and 30 minutes at average flow.
iv. Nitrifying aeration tanks shall be preceded by an anoxic zone. Hydraulic retention time in the
anoxic zone shall be between 20 and 60 minutes at average flow. Dual zones are recommended.
v. Measures shall be provided to maintain the biomass in the selectors in suspension at all times.
Mechanical mixers shall be low-speed and low-shear, and shall not cause air entrainment or
shearing of the floc.
vi. Equal flow splitting and distribution to the aeration tanks shall be provided by equal length non-
submerged weirs for all tank configurations.
vii. The tank floors shall have a nominal slope not less than 1 in 100 to assist tank emptying and
cleaning. Each tank shall also have a drainage sump normally sized to be at least 400 mm
square by 400 mm deep to receive a submersible pump to assist tank emptying. The tank shall
also be fitted with guiderails and a davit socket above the drainage sump.
7.1.6.5. Inlets and Outlets
i. Return-activated sludge (RAS) shall be fully mixed with incoming sewage. Each flow shall enter
the selector box at right angles within a small baffle zone, and then flow into the selector in a fully
mixed state.
ii. Inlets and outlets for each aeration tank unit shall be suitably equipped with valves, gates, stop
plates, weirs, or other devices to permit controlling the flow to any unit and to maintain reasonably
constant liquid level.
iii. The effluent weir for a horizontally mixed aeration tank system must be easily adjustable by
mechanical means and shall be sized based on the design peak instantaneous flow plus the
maximum return sludge flow.
7.1.6.6. Freeboard
i. All aeration tanks shall have a freeboard of not less than 500 mm. However, if a mechanical
surface aerator is used, the freeboard shall be not less than 0.9 m to protect against windblown
spray on walkways, or similar occurrences.
7.1.6.7. Froth Control Units
i. It is essential to include some means of controlling froth formation in all aeration tanks. A series of
spray nozzles shall be fixed on top of the aeration tank. Screened effluent or tap water shall be
sprayed through these nozzles (either continuously or on a time clock on-off cycle) to physically
break up the foam.
ii. Provision shall be made to use antifoaming chemical agents injected at the inlet of the aeration
tank, or preferably, used in the spray water.
7.1.6.8. Conduits
i. Channels and pipes carrying liquids with solids in suspension shall be designed to maintain self-
cleansing velocities or shall be agitated to keep such solids in suspension at all rates of flow
within the design limits.
ii. Adequate provisions shall be made to drain segments of channels which are not being used due
to alternate flow patterns.
7.1.6.9. Anoxic Zones
i. Anoxic zones are to be constructed at the head of each aeration channel or as a common tank.
ii. Each anoxic zone shall have submersible mixers or hyperbolic mixers (non-aeration type)
capable of keeping the whole volume mixed but not aerated.
7.1.6.10. Anaerobic Zones
i. Anaerobic zones shall be used to aid phosphorus removal in biological nutrient removal systems.
ii. Anaerobic zones shall be constructed at the head of each aeration channel in conjunction with
pre- or post-anoxic zones, with typical retention times at full treatment flow of 20 to 30 minutes
(including average RAS flow rate).
iii. Each anaerobic zone shall have submersible mixers or hyperbolic mixers (non-aeration type)
capable of keeping the whole volume mixed but not aerated.
7.1.7. Return and Waste Activated Sludge
7.1.7.1. Return Sludge Rate (Return Activated Sludge)
i. The minimum permissible return sludge rate of withdrawal from the final settling tank is a function
of the concentration of suspended solids in the mixed liquor entering it, the sludge volume index
of these solids, and the length of time these solids are retained in the settling tank. Since undue
retention of solids in the final settling tanks may be deleterious to both the aeration and
sedimentation phases of the activated sludge process, the rate of sludge return expressed as a
percentage of the average design flow of wastewater shall generally be variable between the
limits provided in Table 17.
Table 17: Typical Sludge Return as a Percentage of Plant Average Design Flow
ii. The Designer shall determine the most suitable size, number, and combination of pumps to cope
with the range of flows calculated. The pumps shall be uniformly sized.
iii. At least one standby RAS pump shall be provided.
iv. All pumps shall comply with details in the Technical Standard Specification – Mechanical
Section 03 – Pumps, Compressors, Blowers, and Cutters.
v. Pumps shall be configured on a duty/assist/standby arrangement.
vi. Settled sludge shall be withdrawn continuously from the base of the final settlement tanks and
returned to the selector as RAS at a constant rate that can be varied by the operator. Return-
activated sludge flow shall be increased based on the sludge blanket level rising to within 1.2 m
of the clarifier top water level.
vii. On large plants, RAS shall also have the facility to be returned at a rate proportional to the
incoming flow.
viii. The rate of sludge return shall be varied by means of variable speed motors, drives, or timers
(small plants) to pump sludge.
ix. All RAS and WAS pumps shall be capable of pumping sludge with a dry solids concentration in
the range 0.1 to 1.5 percent.
x. Return-activated sludge and settled sewage shall be properly mixed before distribution to
aeration lanes.
xi. Discharge piping shall be at least 100 mm in diameter and shall be designed to maintain a
velocity of not less than 0.6 m/s when return sludge facilities are operating at normal return
sludge rates. Suitable devices for observing, sampling, and controlling RAS flow from each
settling tank hopper shall be provided.
xii. The minimum permissible return sludge rate of withdrawal from the final clarifier is a function of
the concentration of MLSS entering it, the SVI of these solids, and the detention time that these
solids are retained in the clarifier.
xiii. The design of the nominal sludge return rate shall be made according to the maximum sludge
concentration, which shall be calculated with the hypothesis of an SVI of 150 mL/g.
7.1.7.2. Waste-Activated Sludge
i. Waste-activated sludge shall be transferred to a WAS handling system.
ii. Waste-activated sludge shall be withdrawn by either dedicated pumps or bled from the RAS
return line via an automated valve.
iii. Sludge wasting shall be variable to enable zero wasting to 50 percent of the total system solids
daily.
iv. The rate of waste sludge return shall be varied by means of variable speed motors, drives, or
timers to pump sludge as set forth in this section.
v. Waste sludge control facilities shall have a maximum capacity of not less than 25 percent of the
average rate of wastewater flow and function satisfactorily at rates of 0.5 percent of average
wastewater flow or a minimum of 2 m 3/h, whichever is greater. Means for observing, measuring,
sampling, and controlling WAS flow shall be provided.
vi. The Designer shall determine the most suitable size, number, and combination of pumps to cope
with the range of flows calculated. The pumps shall be uniformly sized.
vii. At least one standby WAS pump shall be provided.
viii. All pumps shall comply with details in the Technical Standard Specification – Mechanical
Section 03 - Pumps, Compressors, Blowers, and Cutters (AM-ENG-SS-03-03).
ix. Pumps shall be configured on a duty/assist/standby arrangement.
x. Waste-activated sludge shall be wasted to maintain the MLSS concentration or sludge age (or
both) in the aeration tanks within process limits.
xi. Co-settlement of WAS in the primary settlement tank shall be avoided except on small sites
where it is not economical to provide separate systems.
7.1.8. Measurement
i. Devices shall be installed in all plants for indicating flow rates of raw wastewater or primary
effluent, return sludge, and air to each tank unit. For plants designed for wastewater flows of 450
m3/day or more, these devices shall totalise and record, as well as indicate flows.
ii. Where the design provides for all return sludge to be mixed with the raw wastewater (or primary
effluent) at one location, then the mixed liquor flow rate to each aeration unit shall be measured.
iii. Sampling points after the WAS pumps on the common manifold shall be provided.
iv. Total RAS and WAS flows shall be measured on each main aeration stream on the Site by inline
magnetic flow meter.
v. At least one DO probe in each aeration tank shall be provided, unless aeration tanks with a high
degree of plug-flow are used. If the latter is the case, a multiple point DO control system shall be
considered.
vi. In all methods using DO control, the DO value for an individual instrument shall be continuously
read and validated, and a rolling average produced (for example, 20 samples over a 2-minute
period).
vii. The rolling average DO value from individual instruments shall be averaged together to obtain an
overall DO value for blower control.
viii. On nitrifying plants, high level control using effluent ammoniacal nitrogen concentration may be
considered to work in conjunction with the DO system.
b) A sufficient quantity of air is provided to satisfy the average and peak hourly oxygen
demand and maintain the required DO level.
c) Good solids separation occurs during the settle phase.
d) Reliable automatic process control with easy access to adjust all necessary operational
control set points.
e) All automatic default operational control conditions shall be alarmed (for example, high
flow, process control, or instrument failure).
ii. The design MLSS concentration at the bottom water level shall not normally be higher than
5,000 mg/L.
iii. As class “A” waters must achieve a total ammoniacal-nitrogen discharge consent of <5 mg/L, the
Designer shall consider the additional design requirements for appropriateness:
a) The maximum design food to Microorganism (F:M) ratio of the aerated time shall be 0.15
kg BOD per kg MLSS per day.
b) The minimum design sludge age of the aerated time shall be 10 days.
c) The design DO set point shall be 2.0 mg/L, but should be operator adjustable between
1.0 and 3.0 mg/L.
d) The design sludge yield shall be a minimum of 0.9 kg SS per kg BOD applied for systems
treating crude sewage.
e) The aeration system capacity shall be designed to allow for the lower demand resulting
from denitrification where an adequate anoxic period is provided.
iv. The design sludge age and F:M ratios shall be based upon the aerated biomass and not the total
biomass:
Where; Aerated biomass = Total Biomass x Aerated Fraction of SBR Cycle
v. The reactor mixed liquor volatile suspended solids and MLSS concentrations and aeration tank
volumetric loading shall be calculated at the low water level and at least more than two tanks
shall be provided.
vi. The volume required for settled biomass (Vs) shall be calculated by an SVI of not less than
180 mL/g to the total biomass in the reactor.
vii. The volume required per reactor for filling (Vf) shall be the maximum flow rate (m 3/day) to
secondary treatment divided by the minimum number of SBR cycles per day (d).
viii. A minimum clear water zone of 1.0 m depth shall be allowed between the bottom decant depth
and the top of the settled sludge blanket (clear water reactor volume = Vc).
ix. The design MLSS shall be determined at the design stage to provide the optimum balance
between having a high concentration to minimise the react time and a low concentration to
minimise the required settling time. The optimum concentration depends on the degree of
treatment required. The SBR filling strategy shall be designed to encourage conditions that
promote a substrate gradient and selection of floc forming bacteria. Completely mixed fills that do
not generate sufficient substrate gradient are to be avoided.
7.2.4. Aeration System
i. All compressors, blowers, and aeration equipment shall comply with details in the Technical
Standard Specification – Mechanical Section 03 – Pumps, Compressors, Blowers, and Cutters
(AM-ENG-SS-03-03).
ii. The blowers shall be provided in multiple units, arranged and in such capacities as to meet the
maximum air demand in the oxic portions of the fill/react and react phases of the cycle with the
single largest unit out of service.
iii. The actual oxygen requirement (AOR) shall be calculated from the peak weekly rolling average
BOD and ammonia loads to the plant. A factor allowing for the proportion of aeration time must be
considered with appropriate peaking factors applied.
iv. The aeration system shall incorporate membrane diffusers with variable speed blowers,
hyperbolic aeration system or floating variable speed surface aerators. The system design shall
have sufficient turndown so that over-aeration shall not occur during the diurnal low load condition
at the end of the aeration cycle.
v. Membrane diffuser systems shall be designed with an alpha factor of 0.7 and a beta factor of
0.95. Surface aerators shall have an alpha factor of 0.9 and a beta factor of 0.95.
vi. A standby blower shall be provided where diffused air or jet blowers are used.
vii. A dissolved oxygen monitor shall be provided per reactor, and a minimum control set point shall
be 2.0 mg/L during the aeration cycle.
7.2.5. Tanks
i. A minimum of two SBR reactors shall be provided.
ii. The aeration tank volumetric loading shall not exceed 0.24 kg BOD5 per m 3/day.
iii. The decantable volume and decanter capacity of the sequencing batch reactor system with the
largest basin out of service shall be sized to pass at least 75 percent of the design maximum day
flow without changing cycle times.
iv. A decantable volume of at least 4 hours with the largest basin out of service based on 100
percent of the design maximum day flow is permissible.
v. The agreed-upon process configuration shall allow for one bioreactor to be taken out of service
for maintenance with no overall deterioration in performance with respect to TE quality.
vi. System reliability with any single aeration tank unit out of service and the instantaneous delivery
of flow shall be evaluated in the design of decanter weirs and approach velocities.
vii. Where the instantaneous discharge rate from SBRs exceeds the consented instantaneous
discharge flow rate, a balancing tank shall be provided to attenuate the flow to the watercourse.
viii. A balancing tank shall also be considered where any further treatment process situated
downstream of the SBRs requires a continuous feed. The balancing tank shall be designed so
that a risk of algae growth is minimised.
ix. The flow balancing tank may be used as the process wash water storage tank.
x. The TE from each reactor shall be free of scum and have a suspended solids concentration no
greater than 20 mg/L at any time.
xi. Solids management to accommodate basin dewatering shall be considered.
xii. Mechanical mixing independent of aeration shall be provided for all systems where biological
phosphorus removal or denitrification is required. The mixing equipment shall be sized to
thoroughly mix the entire basin from a settled condition within 5 minutes without aeration.
7.2.6. Control
i. The control systems shall ensure that the plant does not switch to storm cycle during peak dry
weather flows and, therefore, shall not be lower than 1.5 times the average dry weather flow.
ii. A hard-wired backup for manual override shall be provided in addition to automatic process
control. Both automatic and manual controls shall allow independent operation of each tank. In
addition, a fail-safe control shall be provided which cannot be adjusted by the operator, allowing
at least 20 minutes of settling between the react and decant phases.
b) A sufficient quantity of air is provided to satisfy the average and peak hourly oxygen
demand and maintain the required DO level.
c) Good solids separation occurs during the settle phase.
ii. The design MLSS concentration at the bottom water level shall not normally be in range of 3,000-
7,000 mg/L.
iii. As class “A” waters must achieve a total ammoniacal nitrogen discharge consent of < 5 mg/L, the
Designer shall consider the additional design requirements for appropriateness:
a) The maximum design food to Microorganism (F: M) ratio of the aerated time shall be
0.05-0.3 kg BOD per kg MLSS per day.
b) The design Solid Retention Time shall be 15-20 days.
c) The design DO set point shall be 2.0 mg/L, but should be operator adjustable between
1.0 and 3.0 mg/L.
d) The design sludge yield shall be 0.5-1.0 kg SS per kg BOD applied for systems.
e) The aeration system capacity shall be designed to allow for the lower demand resulting
from denitrification where an adequate anoxic period is provided.
f) Organic Loading rate in MBBR reactor: 1.5-3.5 kg BOD/m3 reactor volume/day.
vi. The nitrogenous oxygen demand (NOD) shall be taken as 4.6 times the diurnal peak hourly Total
Kjehldahl Nitrogen content of the influent. In addition, the oxygen demands due to recycle flows
must be considered due to the high concentrations of BOD5 and Total Kjehldahl Nitrogen
associated with such flows.
vii. Careful consideration shall be given to maximising oxygen utilisation per unit of power input.
Unless flow equalisation is provided, the aeration system shall be designed to match the diurnal
organic load variation whilst economising on power input.
viii. The specified capacity of blowers or air compressors, particularly centrifugal blowers, shall take
into account that the air intake temperature may reach 50°C or higher, and the pressure may be
less than normal. The specified capacity of the motor drive shall also take into account that the
intake air may require over-sizing of the motor or a means of reducing the rate of air delivery to
prevent overheating or damage to the motor.
ix. The blowers shall be provided in multiple units, arranged and in such capacities as to meet the
maximum air demand with the single largest unit out of service. The design shall also provide for
varying the volume of air delivered in proportion to the load demand of the plant.
x. Aeration equipment shall be easily adjustable in increments and shall maintain solids suspension
within these limits.
xi. The average DO signal from all in-service aeration lanes shall be used for blower control.
xii. Diffuser systems shall be capable of providing for 200 percent of the designed average day
oxygen demand. The air diffusion piping and diffuser system shall be capable of delivering normal
air requirements with minimal friction losses.
xiii. Air piping systems shall be designed such that total head loss from blower outlet (or silencer
outlet where used) to the diffuser inlet does not exceed 0.5 psi (3.4 kPa) at average operating
conditions.
xiv. Pipework shall be securely fixed to the concrete floors and walls. On all sections of feeder
pipework which are not immersed, the provision of manually valved drains at all low points shall
be considered to monitor and allow for the removal of condensate.
xv. The spacing of diffusers shall be in accordance with the oxygen requirements through the length
of the channel or tank, and shall be designed to facilitate adjustment of their spacing without
major revisions to air header piping.
xvi. All plants employing less than four independent aeration tanks shall be designed to incorporate
removable diffusers that can be serviced or replaced (or both) without dewatering the tank.
xvii. Individual assembly units of diffusers shall be equipped with control valves, preferably with
indicator markings, for throttling or for complete shut-off. Diffusers in any single assembly shall
have substantially uniform pressure loss. Air filters shall be provided in numbers, arrangements,
and capacities to furnish at all times an air supply sufficiently free from dust to prevent damage to
blowers and clogging of the diffuser system used.
xviii. Centrifugal type blowers are preferred, but root types may be used with justification.
xix. All blowers shall generally be configured on a duty/assist/standby basis. The duty/assist
combinations shall be capable of providing sufficient process air to satisfy the peak demand and
to cater for low load periods.
xx. Membrane or ceramic disc type diffusers shall be used for new installations, with membrane disc
diffusers being preferred.
xxi. The air diffusion system shall be of the fine-bubble type (2 to 3 mm) provided by flexible
membrane diffusers which shall enable airflow to be varied to match the demand and improve
energy efficiency. The diffusers shall also be able to resist the ingress of the tank contents when
the air supply is reduced or failed.
7.4.2. Hyperbolic Mixer/Aerator System
i. Due to the high demand for nitrogen removal correlating with high demands for nitrification and
denitrification and good sludge settling only combined mixing and aeration systems are allowed.
ii. For good mixing and uniform conditions within the whole tank during the denitrification mode and
also during aeration mode (anoxic or oxic or anaerobic) only high efficient, combined mixing and
aeration systems are allowed.
iii. Typical submersed aerators with small diameter and high speed are not allowed due to high
shear forces and destruction of sludge. Submerged motors and surface aerators will not be
allowed.
iv. Type: Each mixer shall be a Hyperboloid impeller type Mixer / Aerator with a dry installed gear
drive and a separate ring sparger to provide supplemental air.
v. The Mixer / Aerators shall be designed to provide complete suspension of solids in the tank. The
shear ribs in the mixer body shall be capable of dispersing the air into fine bubbles while handling
solids, fibrous materials, heavy sludge, and other matter found in sanitary sewage applications.
vi. Materials: Mixer components in contact with the liquid shall be of Type 316 stainless steel with
smooth surfaces devoid of blow holes and other irregularities or high quality composite. All
exposed nuts, bolts, fasteners, and hardware shall be of Type 316 stainless steel with “Never
Seize” coating. Transport fins at the mixer body shall be integrated and designed I a way to avoid
any clogging with fibrous material. In case mixer body is made from stainless steel only both-
sided seamless welding is allowed. Deformations at the rim of the mixer body shall not exceed a
tolerance of +/- 0.5 mm to achieve a uniform aeration pattern. Spot-welding of fins to the mixer
body is not allowed. Spot welding is not allowed at any part of the mixer body is not allowed. Any
welding which may cause an unbalance of the mixer body is not allowed.
vii. Each mixer assembly shall consist of a heavy duty speed reducer with hollow shaft, electric
motor, baseplate, fiberglass reinforced plastic / high-grade stainless steel agitator shaft, and
hyperbolic mixing body. Mechanical details of each component shall be as follows:
a) Gear Drive: The gear drive for the Mixer / Aerator shall be a parallel shaft helical geared
motor. The drive shall have a high-quality corrosion protection coating, robust weather
protective hood, and humidity and acid protection of the winding (tropical protection).
The motor shall be a vertical, heavy-duty, high efficiency, TEFC, hollow shaft electric
motor suitable for 400-volt, 3-phase, 50 Hz power supply capable of accepting the total,
unbalanced thrust imposed by the Mixer / Aerator. The gear drive shall be rated for a long
bearing service life under adverse operating conditions. (Lh10 > 100,000 h under
operational load conditions) The motor shaft shall be mounted in a hollow shaft motor
and secured by means of a hex screw to the gear drive. The torque shall be transmitted
by a feather key connection. The hollow shaft shall be covered and sealed with a special
hollow shaft cap. Service factor of the gear box at 100 % load shall be 2.0 at minimum
and gear box must be designed for a calculated lifetime of > 100,000 hours of operation
at actual loading.
b) Mounting base: The mounting base of the mixer consists of a gear base plate mounted in
rubber buffers connected permanently to the bridge by bolted connection. The gear plate
is designed as a distortion-proof steel structure with an impact-proof powder-coated
surface. The plate can be leveled out using the threaded bolts which can be adjusted in
height. The rubber buffers must be centre bonded mounts with steel inserts and two
washers in order to absorb starting-up jolts, prevent any transfer of vibrations to the
bridge and constitute the galvanic separation of the mixer from its surroundings.
c) Shaft: The drive shaft of the mixer is made from high quality fiberglass reinforced
plastic/high-grade stainless steel (304/316Ti). At the top end there is a steel tappet for the
connection to the gear hollow shaft. At the lower end there are stainless steel inserts
(316Ti) for the connection to the mixer body without using a flange to provide non-
clogging operation.
d) Hyperboloid Mixer Body: The Hyperboloid Mixer Body is a streamlined non-clogging body
segmented in 8 parts. The motion fins which accelerate the flow are integrated in the
mixer body. The shape of the motion fins has to be according to the latest fluid-
mechanical state of the art. The height of the motion fins at half of the radius of the mixer
body must be in excess of the height of the motion fins at the circumference of the mixer
body. The mixer body must have non-clogging ventilation holes close to the shaft
connection. It is made of top quality, high-strength impact resistant polymer material with
smooth surface. Depending on the design, the Hyperboloid Mixer has a laminated
stainless steel insert nut (316Ti).
8. Tertiary Filtration
i. The filtration system applied shall able meet the TE compliance used on sewage treatment
plants, particularly with respect to Helminths Ova. The actual process configuration to be used at
a particular site shall be subject of a specific process evaluation to be undertaken in close liaison
with the Client.
ii. The following section is retained based on previous the version for reference and to address
existing assets.
i. The media selection, depth of media, effective size, and uniformity co-efficient is based on the
type of filter selected, such as depth filters with single medium or dual media filters.
8.1.3. Under Drains
i. Porous-plate bottoms or perforated pipe under-drains shall not be used. False bottoms with
orifices (nozzles) shall be used, consisting of a several plates supporting several vertical nozzles.
Under-drain systems allowable in water plants are acceptable. The orifice loss in backwashing
must exceed the sum of the minor hydraulic losses in the under-drain system to secure good
distribution of flow over the entire area of the filter bottom.
ii. Under-drains shall be made of corrosion- and scale-resistant materials, or properly protected
against corrosion. The glazed tile filter block used in some filter bottoms and the stainless steel
modules used in other filter bottom designs are recommended to provide even and uniform
distribution of backwash water. Hydraulic distribution data on each standard filter size shall be
submitted.
8.1.4. Backwash
i. Provisions shall be made for washing filters as follows:
a) Automatic washing with air and water (two successive sequences)
b) Water loss during filter backwash shall be limited to 3 percent
c) Each filter shall be cleaned a maximum of once per day
d) Provision for a filtered water tank shall be made to provide three times the volume
pumped for one filter washing
ii. Release of backwash water shall be controlled by a timer and the head loss measurement.
iii. Washwater pumps shall be provided in duplicate.
iv. Rate of flow indicators on the main wash-water line shall be provided and shall be located so that
they it can be easily read by the operator during backwash.
v. Air release must be provided with blowers: one standby shall be planed; one pressure release on
the air pipe (to control the pressure during filter backwash) as well as anti-backflow system shall
be provided.
vi. The false-bottom of the filters (supporting the nozzles) shall be designed to resist the maximum
pressure applied during the backwash to avoid any moving of the plates.
vii. Backwash wastewater treatment and disposal must be accomplished within the rated design
capacities of the treatment system. Backwash wastewater cannot be discharged to a stream
without first receiving adequate treatment.
viii. If it is desired to recycle the backwash wastewater through a secondary system, then the
hydraulic design of the entire system (including the clarifier and filter) must be based on the
anticipated rate of raw influent flow plus the flow rate at which the backwash water enters the
system.
ix. A backwash water holding tank and controlled discharge system shall be required. This holding
system must be capable of storing the wastes from two backwashes and discharging the wastes
to the treatment system within 24 hours at a rate which, in combination with the raw influent, does
not exceed the hydraulic design of any system component when the loading period for the plant is
24 hours. For plants with loading periods less than 24 hours, additional backwash holding
capacity may be required.
8.1.5. Surface Wash
i. Surface wash facilities are required. Disinfected filtered wastewater effluent shall be used for
surface wash. Revolving-type surface washers shall be provided; however, other types may be
considered. All rotary surface wash devices shall be designed with provision for the following:
a) Minimum wash-water pressures of 2.5 bar (g)
b) Surface wash-water rate of 1.25 to 2.5 m 3/h per square metre of filter area
iii. Filters shall be located after final settlement tanks, but ahead of disinfection facilities.
iv. Filters devices shall be provided as an alternative to mixed media sand filter or pressure filters,
where appropriate. A review of the most appropriate filtration system shall be determined on a
case-by-case basis and with consultation from the Client.
v. Pleated media filters are preferred over flat sheet media systems. Pleated media systems provide
greater filtration surface area per m 2 and are mechanically more robust.
vi. All filter systems shall be designed and equipped to provide a normal backwash and a high
pressure spray wash cycle. The water used for the normal backwash and high pressure
backwash spray shall be filtered water.
vii. All backwash water shall be collected and rerouted to the plant inlet Works or primary
sedimentation tank (if applicable).
viii. Rotation speed under normal backwash conditions shall be limited to 1 rpm.
ix. Pre-engineered units may be designed with different rotation speeds. If these are used a
Specification waiver shall be sought from and provided by the Client.
x. All disc media filtration units shall be provided with adequate automatic control devices to
regulate head loss through the screen, rotation speed, and backwash frequency. The units shall
have manual override capability.
xi. Backwash of units shall be automatically initiated when a predetermined (operator settable) head
loss through the system is reached. The system shall also have a built in timer that shall initiate
backwashing after a set time has elapsed if head loss has not triggered a backwash.
xii. Manual override control facilities shall be provided.
xiii. A minimum of two units shall be supplied to provide full duty/standby capacity. If one unit is taken
out of service, the operational unit shall have sufficient capacity to treat the full Works flow without
requiring excessive cleaning or causing backup of flow.
xiv. Each filter unit shall be provided in its own dedicated housing. Each unit shall be capable of
upstream and downstream isolation.
xv. Provisions shall be made for isolating and dewatering each unit.
xvi. Each unit shall be provided with a bypass facility to prevent flooding. In the event of full blockage
of the filters, bypass facilities capable of taking the full flow to unit shall be provided.
xvii. Filter tanks shall be designed to take account of floating and settling solids. All settled solids shall
be returned to the head Works (or solids processing plant).
iii. For tertiary treatment applications, carbon contact times of 15 to 20 minutes shall be used where
the desired effluent quality is a COD of 10 to 20 mg/L, and 30 to 35 minutes when the desired
effluent COD is 5 to 15 mg/L.
iv. For chemical-physical treatment plants, carbon contact times of 20 to 35 minutes shall be used,
with a contact time of 30 minutes being typical.
8.3.4. Hydraulic Loading Rate
i. Hydraulic loading rates of 2.5 to 7.0 L/m 2s of cross section of the bed shall be used for up-flow
carbon columns.
ii. For down-flow carbon columns, hydraulic loading rates of 2.0 to 3.3 L/m 2s are used.
iii. Actual operating pressure seldom rises above 7 kN/m 2 for each 0.3 m of bed depth.
8.3.5. Depth of Bed
i. The depth of bed may vary considerably, depending primarily on carbon contact time, and may
be from 3 to 12 m.
ii. A minimum carbon depth of 3 m is recommended.
iii. Typical total carbon depths range from 4.5 to 6 m.
iv. The Designer shall take account of sufficient freeboard to be added to the carbon depth to allow
an expansion of 10 to 50 percent for the carbon bed during backwash or for expanded bed
operation.
v. The Designer shall take into account carbon particle size and water temperature to determine the
required quantity of backwash water to attain the desired level of bed expansion.
8.3.6. Number of Units
i. A minimum of two parallel carbon contactor units shall be provided.
ii. A sufficient number of contactors shall be provided to insure an adequate carbon contact time to
maintain effluent quality whilst one column is off-line during removal of spent carbon for
regeneration or for maintenance.
8.3.7. Backwashing
i. The Designer shall determine the rate and frequency of backwash on hydraulic loading, the
nature and concentration of suspended solids in the wastewater, the carbon particle size, and the
method of contacting.
ii. Backwash frequency shall be prescribed arbitrarily (each day at a specified time), or by operating
criteria (head loss or turbidity).
iii. The duration of backwash is typically 10 to 15 minutes.
iv. The normal quantity of backwash water employed is less than 5 percent of the product water for a
0.8 m deep filter and 10 to 20 percent for a 4.5 m filter.
v. Recommended backwash flow rates for granular carbons of 8 by 12 or 12 by 30 mesh are 8 to
14 L/m2s.
8.3.8. Valving and Piping
i. All piping shall comply with details in the Technical Standard Specification – Mechanical Section
06 – Piping and Accessories (AM-ENG-SS-03-06).
ii. Up-flow units shall be piped to operate either as up-flow or down-flow units as well as being
capable of being backwashed.
9.1. Introduction
i. Membrane bioreactors consist of a suspended growth biological reactor (activated sludge system
variation) integrated with a microfiltration membrane system.
ii. The key to the technology is the membrane separator, which allows elevated levels of biomass to
degrade or remove the soluble form of the organic pollutants from the waste stream.
iii. These systems typically operate in the ultrafiltration or microfiltration range, which results in
removal of particles greater than 0.01 and 0.1 μm, respectively. In its simplest form, an MBR can
combine the functions of an activated sludge aeration system, secondary clarifiers, and tertiary
filtration in a single tank. In most cases, however, the membrane units are immersed in a
separate tank.
iv. The ability of MBRs to combine process operations allows the following major benefits to be
realised over conventional treatment:
a) Significantly reduce footprint (usually one-third to one-fourth the size of conventional
treatment)
b) Operation at much higher MLSS than conventional activated sludge processes (typically
up to 12,000 MLSS)
c) Higher volumetric loading rates and shorter reactor hydraulic retention times
d) Longer SRT, resulting in less sludge production
e) Operation at lower DO concentrations with potential for simultaneous nitrification-
denitrification in long SRT designs
f) Consistent, high quality effluent with very low turbidity, bacteria, total suspended solids
(TSS), and BOD (reducing disinfection requirements)
v. There are generally two types of immersed MBRs used for municipal water treatment:
a) Flat sheet pressure (gravity) driven systems
b) Hollow fibre, vacuum pumped systems
vi. Both systems are suitable for use in municipal wastewater treatment, but have significant design
differences, both in operational and constructional design. Depending on the
system/manufacturer, membranes will differ in pore size, construction, system configuration,
operating procedure, maintenance requirements, and TE quality. This Manual has been prepared
on the basis that hollow fibre systems are preferred by the Client. However, flat sheet systems
may offer significant benefits over hollow fibre systems depending on the specifics of each site.
vii. The membrane bioreactor/ultrafiltration system shall be supplied by a single source with total
package including membrane modules and the control system for easy integration during the
project execution.
viii. Membrane bioreactor systems shall consist of the following major items and unit processes:
9.6. Membranes
i. The Contractor shall use suitable hollow fibre or flat sheet membranes having a nominal pore size
of 0.5 micron or less.
ii. Effluent flow through the membranes shall be from the outside to the inside of the fibre or sheet.
iii. Membranes shall be constructed of chemically resistant materials and shall be capable of being
washed in high chlorine solutions (minimum 1,000 mg/L) for 10 hours, and low pH (range 2 to 3)
and high pH (range 10 to 11) wash solutions for 10 hours, respectively.
iv. Membranes shall be physically strong enough to withstand the operating conditions associated
with continuous operation in an aerated tank of mixed liquor at concentrations of up to 15,000
mg/L.
v. For systems which use back pulsing, membranes shall be able to withstand backwash flow (from
inside to outside) as proposed by the equipment manufacturer, without any indication of damage.
vi. The Contractor shall provide a warranty for the replacement of membranes, for a 5-year period
commencing following issuing of the Take-Over Certificate.
all design conditions with one tank out of service during annual average daily flow and maximum
monthly conditions.
ii. The Designer shall determine the optimum number of tanks in association with the Client so as
not to cause undue operational restrictions or over-design, and spare capacity is to be included.
iii. Typically, the MBR membranes shall be situated in a separate section of the tank from the main
biological aeration compartment; however, this does not have to be the case and is dependent on
the system chosen.
iv. The process units for membrane bioreactors shall be completely covered to prevent sand
accumulation in the reactors and possible clogging of membrane pores.
9.13. Aeration
9.13.1. Biological Aeration
i. All compressors, blowers, and aeration equipment shall comply with details in the Technical
Standard Specification – Mechanical Section 03 – Pumps, Compressors, Blowers, and Cutters
(AM-ENG-SS-03-03).
ii. Biological process aeration including fine-bubble aeration, coarse-bubble aeration, and jet
diffusion shall be as defined in the previous section 8.1.4 “Biological Treatment - Aeration” .
iii. Aeration shall be sufficient to maintain aerobic conditions in the biomass at all times, maintaining
residual a DO concentration of 2 mg/L under all design load conditions.
iv. The Designer shall provide separate aeration systems, inclusive of all pipework, valves, and
headers for the process aeration requirement and the membrane agitation, allowing for
optimisation of both processes.
v. The Contractor shall provide details of the aeration system and shall be required to guarantee
percent standard oxygen transfer efficiency into clean water.
vi. Tubular or disc type-membrane fine-bubble diffusers are preferred for biological aeration.
vii. Duty plus standby blower units shall be provided to supply air to all biological process strains.
9.13.2. Coarse-Bubble Aeration
i. All compressors, blowers, and aeration equipment shall comply with details in the Technical
Standard Specification – Mechanical Section 3 – Pumps, Compressors, Blowers, and Cutters
(AM-ENG-SS-03-03).
ii. Coarse-bubble aeration shall be provided to each membrane unit.
iii. The Contractor shall provide details of air blowers, design alpha factors, diffuser configuration,
blower on/off times, and all blower operating conditions to the Client for review.
iv. Blowers, which provide airflow to scour the membranes for control of fouling and to assist in
keeping the mixed liquor in a membrane tank in suspension, shall be provided.
v. Air distribution headers for each membrane train shall be provided within the limits of each
membrane tank.
vi. There shall be duty and standby blowers to provide scour air to the membrane basins. Space
shall be provided for a future blower.
vii. Air scour blowers shall be sized to provide air quantities, pressures, and turn-down capabilities
specified by the membrane system manufacturer.
9.14. Mixing
i. All un-aerated zones in the bioreactor shall be equipped with dedicated mixers to keep solids in
suspension.
ii. All mixers shall ensure proper contact between biomass, substrate, oxygen source, and complete
volume without short-circuiting across any zone.
iii. Mixed-liquor recycle shall be returned to the head of the anoxic zone either under gravity from the
membrane zone or via pumping arrangements. This is to be a continuous flow, flow rate to be
selected by the Designer to offer optimum membrane and aeration performance and to meet the
final effluent quality limits.
viii. All back-flush and Clean in Place chemical cleaning shall be fully automated with dedicated
chemical tanks.
ix. Permeate water and air scour shall be used for the backwash, which shall then be released to
drain. All chemicals used for chemical cleaning to be compatible with the membrane material.
x. Membrane cassettes and housings shall be resistant to chemicals used in the membrane
chemical cleaning process.
xi. A warm water tank shall be provided to supply water for the membrane cleaning solutions,
shortening cleaning time.
9.15.2. Membrane Cleaning
i. Systems shall be provided with a fully automatic mechanism for back-pulsing the membranes for
regular maintenance and cleaning.
ii. Membrane backwashing shall be initiated once the trans-membrane pressure reaches design
limitations, and defaulted to a set minimum time interval.
iii. The system shall also allow an operator to initiate a backwash manually.
iv. The backwash water source shall be the permeate produced from the system.
v. Chemical cleaning shall be initiated once the interval between backwashes is reduced to below a
predetermined time interval or once the trans-membrane pressure after backwash is double that
of a clean membrane or as specified by the Contractor to meet his guaranteed performance.
vi. Maintenance cleaning for each membrane train shall not be performed more frequently than once
every 4 days.
vii. Recovery cleaning for each membrane train shall not be performed more frequently than once
every 90 days.
9.15.3. Air Scour System
i. Blowers, which provide airflow to scour the membranes for control of fouling and to assist in
keeping the mixed liquor in a membrane tank in suspension, shall be provided.
ii. The Contractor shall provide air distribution headers for each membrane train within limits of the
membrane tanks.
ii. One permeate pump per membrane sub-train is required. If no membrane sub-trains are
required, provide one permeate pump per membrane train.
iii. Rated Capacity: The Designer shall indicate the instantaneous rated capacity required based on
pumping maximum hour flow through all but one membrane train, taking into account any
permeate water used for membrane cleaning.
iv. All permeate pumps shall discharge into a downstream permeate collection header or tank.
v. There shall be duty and standby permeate pumps as mentioned in the Particular Specification, if
applicable to draw the TE through the membrane modules and transfer it to the TE storage tanks
Space shall be provided for a future pump.
vi. Each pump shall be inverter-controlled to maintain the correct system flow. The pumping head
required is the sum of the trans-membrane pressure plus the head and line losses to deliver TE
to the TE tanks. The system shall control the outlet flow to match the incoming flow by
maintaining a constant level in the aeration tanks. Each pump shall have a return line to
discharge back to the membrane system cell. This shall allow recirculation of cleaning solutions
to shorten cleaning times for the membrane system.
iv. The Designer shall allow for increase in sludge production due to the chemical addition and
increased solids capture at the primary treatment stage.
v. The Designer shall ensure that, as a result of chemical dosing, pH downstream of the dosing
point shall not decrease below 7.0 at any time.
vi. When primary precipitation takes place upstream of a biological process, the Designer shall
ensure the remaining load of phosphorus in the primary effluent shall be sufficient to sustain the
biological process.
ii. The design chemical dosage shall include the amount needed to react with the phosphorus in the
wastewater, the amount required to drive the chemical reaction to the desired state of completion,
and the amount required due to inefficiencies in mixing or dispersion.
iii. Excessive chemical dosage shall be avoided.
iv. For guidance, typical chemical dose rates are provided in Table 19. Actual dose rates specific to
each plant shall be determined by bench trials, jar tests, and pilot plant studies.
v. Each chemical must be mixed rapidly and uniformly with the flow stream. Where separate mixing
basins are provided, they shall be equipped with mechanical mixing devices. The detention
period shall be at least 30 seconds.
10.5.2. Flocculation
i. If separate flocculation or coagulation chambers are used (in case of tertiary precipitation), they
shall be equipped with mixers/stirrers.
ii. The particle size of the precipitate formed by chemical treatment may be very small.
Consideration shall be given in the process design to the addition of synthetic polyelectrolyte to
aid settling, if required.
iii. The flocculation equipment shall be adjustable to obtain optimum floc growth, control deposition
of solids, and prevent floc destruction.
x. Belowground pipework shall be double skinned or layered in a sealed duct, which shall drain back
to the bunded area or to a dedicated collection sump.
10.6.2. Dry Chemical Feed System
i. Each dry chemical feeder shall be equipped with a dissolver which is capable of providing
minimum 5-minute retention at the maximum feed rate.
ii. Polyelectrolyte feed installations shall be equipped with two solution vessels and transfer piping
for solution make-up and daily operation. Make-up tanks shall be provided with an educator
funnel or other appropriate arrangement for wetting the polymer during the preparation of the
stock feed solution. Adequate mixing shall be provided by a large-diameter, low-speed mixer.
10.6.3. Storage Facilities
i. Storage facilities shall be sufficient to ensure that an adequate supply of the chemical is available
at all times. Exact size required shall depend on size of shipment, length of delivery time, and
process requirements.
ii. Storage for a minimum supply of 30 days shall be provided.
iii. See Section 14 – Chemical Delivery, Storage and Dosing Systems for more details.
10.6.4. Location and Containment
i. All liquid chemical mixing and feed installations shall be installed on corrosion-resistant pedestals
and elevated above the highest liquid level anticipated during emergency conditions. The
chemical feed equipment shall be designed to meet the maximum dosage requirements for the
design conditions.
ii. Lime feed equipment shall be located so as to minimise the length of slurry conduits. All slurry
conduits shall be accessible for cleaning.
iii. The liquid chemical storage tank and tank fill connections shall be located within a containment
structure having a capacity exceeding the total volume of all storage vessels. Valves on
discharge lines shall be located adjacent to the storage tank and within the containment structure.
iv. Auxiliary facilities, including pumps and controls, within the containment area shall be located
above the highest anticipated liquid level. Containment areas shall be sloped to a sump area and
shall not contain floor drains.
v. Bag storage shall be located near the solution make-up point to avoid unnecessary transportation
and housekeeping problems.
10.6.5. Accessories
i. Platforms, stairs, and railings shall be provided, as necessary, to afford convenient and safe
access to all filling connections, storage tank entries, and measuring devices. Storage tanks shall
have reasonable access provided to facilitate cleaning.
10.6.6. Materials
i. All chemical feed equipment and storage facilities shall be constructed of materials resistant to
chemical attack by all chemicals normally used for phosphorus removal.
10.6.7. Temperature, Humidity, and Dust Control
i. Precautions shall be taken to prevent chemical storage tanks and feed lines from reaching high
temperatures likely to result in at the concentrations employed. Consideration shall be given to
temperature, humidity, and dust control in all chemical feed room areas.
10.6.8. Cleaning
11. Disinfection
ix. Any such system shall be capable of imparting a chlorine residual greater than 0.3 mg/L and less
than 1.0 mg/L at the consumer end. An allowable maximum concentration at the STP point of
discharge is 3.0 mg/L to allow for degradation in the distribution network.
11.2. Chlorination
i. The use of gaseous chlorine is not generally accepted for safety concerns.
ii. The use of bulk sodium hypochlorite for small plants and onsite chlorine generation (OSEC) for
larger plants shall be evaluated based on life-cycle costs.
iii. Chlorination equipment shall be designed as to be able to feed the desired level of chlorine into
the supply line on a flow proportional basis.
iv. The chlorination installation shall have a chlorine residual analyser with a recorder to accurately
record the chlorine residual continually in the TE. The recorder shall be accurate, reliable, and
approved by the Client.
v. Where flow varies, an automatic flow proportional system shall be installed. If chlorine demand
varies, then a residual analyser with recorder shall be installed. If both the flow and the chlorine
demand vary, then a compound loop system shall be installed.
11.2.1. Bulk Sodium Hypochlorite Dosing Plants
i. Any bulk sodium hypochlorite dosing systems shall comply with the design Specification for
chemical dosing systems as highlighted in Section 13 – Chemical Delivery, Storage and Dosing
Systems.
ii. Where bulk sodium hypochlorite (12 to 15 percent) solution is used, it shall be stored in a dark
cool area to minimise loss of strength of the solution. The rate of strength loss for sodium
hypochlorite doubles with every 5oC rise in temperature. In this regard, all storage tanks shall be
located away from any direct heat and light sources.
iii. Because of its shelf life, consideration must be given when purchasing sodium hypochlorite, as
too large quantities will be wasting money and possibly cause some impact on the adequacy of
the chlorination.
11.2.2. Onsite Chlorine Generation Plant
i. An OSEC plant shall be provided to automatically produce on demand sodium hypochlorite
solution.
ii. Any OSEC plant supplied shall comprise of the following main components:
a) Electrolyser working as duty/duty to produce the total daily requirement of sodium
hypochlorite over 12 hours
b) OSEC control panels
c) Transformers/rectifiers
d) Busbar set
e) Brine pump set (each set comprising duty/standby pumps and pump accessories [that is,
pressure reducing valves, pulsation dampers)
f) In-line water heater/chiller
g) Automatic, self-regenerating duplex water softener system
h) Salt saturator
viii. A baffle type chlorine chamber shall be provided. The chamber shall be constructed of reinforced
concrete or structural grade steel. Steel chambers shall be protected against corrosion through
the use of adequate covering material.
ix. Baffles shall be provided within the chamber to prevent short-circuiting and shall be designed to
keep floating material from leaving the chamber. A method for removing any floating material
shall be provided.
x. A sump shall be provided in the chamber as a method to remove any solids build-up.
iii. Equipment shall be provided at the plant to monitor free and total chlorine levels using accepted
test procedures.
iv. All chlorine products shall be stored in a dry location and in suitable containers. Safety equipment
shall be kept on hand in case of an emergency.
v. Chlorination of TE shall be by sodium hypochlorite solution. This may be by the use of bulk
sodium hypochlorite solution (12 to 15 percent) or sodium hypochlorite generated by OSEC.
11.2.5. Dechlorination
i. Decisions regarding the use of de-chlorination shall be made on a case-by-case basis.
ii. It is expected, particularly during the winter months, that surplus TE will need to be discharged to
the sea. As TE discharged to the marine environment requires free residual chlorine levels to be
<0.4 mg/L, (as highlighted in Section 3.2.3) the wastewater treatment Works shall be designed
with the ability to remove excess residual chlorine which may remain after the disinfection
process.
iii. The type of de-chlorination system shall be carefully selected considering criteria including the
following: type of chemical storage required, amount of chemical needed, ease of operation,
compatibility with existing equipment, and safety.
iv. The dosage of de-chlorination chemicals shall depend on the residual chlorine in the effluent, the
final residual chlorine limit, and the particular form of the dechlorinating chemical used.
v. Where necessary to meet the operating ranges, multiple units shall be provided for adequate
peak capacity and to provide a sufficient low feed rate on turn-down to avoid depletion of the DO
concentrations in the receiving waters.
vi. Mechanical mixers are required unless the mixing facility will provide the required hydraulic
turbulence to assure thorough and complete mixing. The high solubility of sulphur dioxide
prevents it from escaping during turbulence.
vii. A minimum of 30 seconds for mixing and contact time shall be provided at the design peak hourly
flow or maximum pumping rate.
viii. A suitable sampling point shall be provided downstream of the contact zone.
ix. Consideration shall be given to a means of reaeration to assure maintenance of an acceptable
DO concentration in the stream following sulphonation.
ii. Generally, low pressure units are preferable for installations with low flows, as they are easier to
operate and maintain. However, Works with higher flows may need the more concentrated effect
of medium pressure lamps to reduce the size of installation.
iii. The selection of a medium pressure or low pressure system shall be made at option study stage
in conjunction with the Client, by considering the size and location of the plant, capital, and
operating costs of the plant and associated structures, channels, and mechanical and electrical
components.
11.3.2. Ultraviolet Disinfection General Design Basis
i. Process area parameter (after UV disinfection):
a) Total coliforms: MPN/100 mL 30-day geometric mean
b) E. Coli : MPN/100 mL 30-day geometric mean
ii. The UV dose produced by the system shall be at a minimum of 80 mJ/cm 2 after 12,000 hours of
operation applied to an effluent with an UV transmittance of 65 to 70 percent. The dose
calculation shall be based on the UV intensity output at a wavelength of 253.7 nm, with the lamp
output at 80 percent of initial level (end of life), with clean, clear quartz sleeves.
iii. Ultraviolet systems shall be designed based on maximum effluent suspended solids levels.
iv. Iron can affect UV disinfection by absorbing UV light. Wastewater with iron levels greater than
0.3 mg/L may require pre-treatment to attain the desired disinfection level. This shall be
determined on a site-by-site basis.
v. Waters with elevated levels of hardness may cause scaling of UV lamps, reducing performance.
Any waters with hardness levels above 300 mg/L shall require pilot testing of systems. This is
especially important of low flows are expected.
vi. Dose calculation shall be in accordance with the point source summation method as described in
the EPA Design Manual (EPA/625/1-86-021), without exception.
vii. The UV lamp shall be a low or medium pressure mercury vapour lamp (where appropriate) that
shall produce short-wave (around 254 nm) UV energy. Justification of the dose provided by the
UV reactor shall be supplied at the delivery of the material (calculation notes or experimental
tests on microorganisms’ surrogates).
viii. All electronic and electrical components in the UV system shall be designed and installed in
accordance with the Oman Electrical Standards. The control box shall be housed outside the UV
disinfection chamber.
ix. Each UV plant, controls, and flow controls shall be provided with standby power provision.
x. Each UV disinfection unit shall be equipped with an automatic shut-off for electrical power when
the access panels to the disinfection chamber are opened. Protection shall be provided to avoid
any visual contact of operators with UV rays. An indicator of functioning of each lamp (type on/off)
shall be implemented to control the lamp operation.
xi. The system shall be designed for complete immersion of the UV lamps in the effluent at normal
operation. The design shall ensure that a constant head of effluent is maintained above the lamp
surfaces. If the UV lamps are housed in a concrete pit, then a drain shall be installed to collect
any wastewater.
xii. If a single channel is used, the minimum number of banks shall be determined by the requirement
to fully disinfect the flow, whilst one bank of lamps is out of service.
xiii. If two channels are provided, each channel shall have at least two banks of lamps (duty/standby
or duty/assist/standby).
xiv. Irrespective of the number of channels provided, each bank shall be able to shut down and be
taken out of the flow in a safe manner, whilst other banks continue to work without interruption.
xv. If two or more channels are used, provision shall be made for the isolation of each channel.
Upstream, this shall be by providing recesses for stop-logs. The (discharge) weir penstock shall
“double” as with an isolating penstock.
xvi. Flow fluctuations in the discharges of some systems, such as SBRs, may cause effluent levels to
vary such that the UV treatment is ineffective. This shall require measures, such as longer UV
inlet channels or flow balancing, to provide sufficient time for the lamps to react to the change in
flow rates.
xvii. If there is a high seasonal flow variation, consideration shall be given to configuring the plant so
that a complete bank or banks may be shut down in low season.
xviii. Channel/unit design shall prevent the formation of dead or excessively turbulent areas under all
flow conditions.
xix. Ultraviolet plant design shall ensure that units are located a sufficient distance downstream of
processes with varying discharges so as to provide sufficient flow smoothing. For SBRs, this shall
normally be more than 20 times the channel width.
xx. Systems shall be protected from excessive temperatures caused by very low flows (that is,
overnight by re-circulating or by variable power control linked to flow measurement).
xxi. Separate flow measurement, UV intensity, and transmissivity shall be provided for each channel.
xxii. Duty/standby transmissivity sensors shall be installed in each channel. Each sensor shall have its
own automatic wiper system.
xxiii. Sampling points shall be provided upstream and downstream of the UV plant.
xxiv. Each UV disinfection unit shall be equipped with a UV intensity meter (housed behind a quartz
window) that is fixed at the area of minimum expected intensity. An audio/visual alarm shall be
activated in the event that the UV intensity has dropped to 70 percent of the original lamp output
or when any of the individual lamps fail. All alarm functions shall be connected to the main control
panel housed in the control room.
xxv. All systems must incorporate an in situ automatic cleaning system. These systems shall use
chemical cleaning, a mechanical wiper regularly sweeping along the sleeves, or a combination of
both, to remove deposits on the quartz sleeves.
xxvi. The Designer shall submit hydraulic calculations determining head loss at minimum, average,
and maximum flow rates. Head loss shall be based on sewage effluent, not clean water.
xxvii. Hydraulic control of flows through the channels is critical to keep the lamps fully submerged and
to control lamp temperatures. It is also necessary to ensure laminar flow through the channels, so
approach channels need careful design.
xxviii. Final chlorination shall be added after UV to provide a disinfectant residual to meet the discharge
norms for residual chlorine.
xvi. After the maintenance of any element of the sludge plant, the process capacity must be sized to
remove any consequential build-up of sludge with a return to normal operation within 5 days. This
may be achieved through extended normal daily plant operating hours.
d) For tanks in excess of 10 m diameter, an access hatch at ground level shall be provided.
e) A high level overflow.
f) Pipework shall be designed to avoid potential blockages and provided with jetting or
rodding points, or both.
g) The tanks shall be sited with due consideration of minimising the lengths of any sludge
delivery mains.
h) Mixers shall be designed to be removed without the need for man-entry or tank emptying.
Where a compressed air mixing system is provided, an arrangement for containing
displaced odours shall be provided.
i) Access shall be provided for routine maintenance. Level probes, mixers, pumps, and any
other items of plant or instrumentation shall be accessible for maintenance without
requiring the use of portable ladders.
j) Routine maintenance access shall be designed on the basis of single-person
maintenance.
k) All sludge holding tanks shall be covered. At odour-sensitive sites, any odours generated
shall be contained and treated.
l) Where tanks may become liable to negative pressure due to the pumping system,
sufficient ventilation shall be provided.
ii. Specific additional requirements for holding tanks at sites prior to export, and requiring some
gravity thickening, shall be as follows:
a) Duplication of tanks and the decanting arrangements shall be based on WLC.
b) Supernatant shall be fed back to the Works at a controlled rate, with no adverse effect on
the wastewater treatment process.
c) The design must control odours discharged via the tanker vacuum pump.
d) Accessible and suitable connections for tankers shall be provided with a sludge outlet at
a height which provides a positive delivery head to the tankers wherever possible.
e) Where practical, tanker loading points shall be within 3 m of the holding tanks.
f) The tanker loading area shall incorporate localised lighting, spillage capture via grill
covered channels draining to the Works drainage system, and a pressurised wash-down
(potable water) hose point.
iii. Specific requirements for cake storage shall be in cake silos, skip marshalling areas, or covered
cake bays:
a) The facility shall provide sufficient and safe vehicular access for handling the sludge.
b) Access for taking material offsite shall allow vehicles to circulate the storage area.
c) There shall be hard standings and bounding to contain all spillage.
d) Wheel washing facilities shall be provided where there is an open cake storage area. The
area designated for vehicle washing shall be drained in such a way as to return the wash
back into the treatment Works.
12.3.5. Process Control and Operating Regime
i. Sludge holding tanks upstream of thickeners and dewaterers shall be operated to maintain
buffering of variations in sludge quality to minimise the need for operator adjustment to maintain
percent DS and solids capture, and optimise polymer usage.
ii. Each storage tank shall be provided with an ultrasonic level detector. Where an automatic
pumped feed system is used to fill the tanks, the ultrasonic level detector shall provide a high
level alarm to the control prior to tank overflow and inhibit further pumped discharge into the tank.
iii. Where tanks are provided with a pump suction discharge from the tank, low level pump protection
shall be provided. This shall also apply to mixing equipment where dry running would be
detrimental to the unit.
iii. Sufficient mixing shall be provided so as to disperse the conditioner throughout the sludge.
iv. The chemical feed rates shall allow for at least a 10:1 range of chemical flow to the dewatering
unit.
Centrifuge A A A -
xiii. Return liquors from the thickening process shall be returned to the front end of the wastewater
treatment Works.
xiv. A post-thickening storage tank shall be installed with a minimum usable volume equivalent to at
least 24 hours storage at 7 percent DS. This shall normally be operated near full and shall be
provided with a mechanical mixer. Plants with a cake import facility shall have additional post-
thickening storage with a minimum usable volume of at least 48 hours’ equivalent of the blended
cake stream at 5 percent DS.
12.5.2. Gravity Thickeners
12.5.2.1. General Design Criteria
i. Picket fence (gravity) thickeners shall only be used when 4 percent DS cannot be achieved by
normal gravity thickening decanting arrangements.
ii. Gravity thickeners shall be considered for the use of primary settled sludge alone.
iii. Primary sludge shall not be mixed with imported sludge or WAS and thickened by gravity picket
fence thickeners, to avoid adverse co-settlement of mixed sludge as a result.
iv. Sludge of average 5 percent DS shall be achievable.
v. Return supernatant liquors shall be returned to the STP, upstream of the inlet screens.
Submerged discharge to reduce the risk of hydrogen sulphide escape shall be considered.
12.5.2.1.v.a...1. Tank Design
i. Gravity thickeners shall be circular in shape.
ii. The diameter of the tank shall be selected to provide the appropriate specific plan area required
for effective thickening of the sludge load to the tank, and shall not be less than 9 m 2 of TDS per
day, unless specified otherwise within the Particular Specification.
iii. Typical maximum tank diameters shall range between 21 and 24 m. Side water depth shall be
between 3 and 3.7 m.
iv. A minimum of 6-hour detention of liquid is required. For maximum compaction of the sludge
blanket, 24 hours is the recommended time required. During peak conditions, the retention time
may have to be shortened to keep the sludge blanket depth below the overflow weirs, thus
preventing excessive solids carry-over.
v. The base of the tank shall be flat or shall slope to the centre, depending on whether the sludge
withdrawal point is peripheral or central.
vi. The acceptable range for gravity sludge thickener floor slopes is 2:12 to 3:12.
vii. A drain shall be provided so that the tank can be completely drained.
viii. Where the tank is sited outside, it shall be fitted with removable reinforced plastic covers.
Thickeners within odour-controlled sludge buildings may not require covers, but this shall be
reviewed on a site-by-site basis and where necessary.
12.5.2.1.viii.a...1. Sludge Feed and Withdrawal
i. Due consideration shall be given to provision for chemical conditioning of the sludge into the
sludge influent lines (see Section 13.4 – Sludge Conditioning).
ii. Gravity picket fence thickeners shall be operated on a continuous or near continuous basis. The
operation shall be completely automatic accept for occasional adjustments by the operator and
routine cleaning operations.
iii. Sludge shall be fed directly to the thickener on a timed or continuous basis, so that the sludge is
in a fresh condition. The maximum instantaneous upflow velocity shall not exceed 0.5 m/h.
iv. Sludge shall be fed into the central area of the tank either to a horizontally mounted disc or to a
diffusion chamber, which shall distribute the sludge uniformly in a horizontal direction so as not to
disrupt the sludge blanket.
v. Where a diffusion chamber is used, facilities shall be provided for removal of accumulated scum
or grease. This facility shall be easily accessible from the walkway.
vi. The tank shall have pumped discharge via positive displacement pumps.
vii. The sludge withdrawal pumps shall have a maximum instantaneous withdrawal rate sufficient to
draw down the sludge blanket, without causing rat-holing of the blanket. The withdrawal rate shall
typically be in the range two to four times the sludge production rate.
viii. Sludge shall be drawn-off either at the tank periphery or from a central sludge hopper, depending
on the tank diameter and sludge type. The draw-off shall be flush with or below the tank floor
level.
12.5.2.1.viii.a...1. Picket Fence
i. The picket fence thickener shall be supported by a fixed bridge and shall rotate with a peripheral
velocity on the order of 3 m/min.
ii. The picket fence shall have an auto-reverse function.
12.5.2.1.ii.a...1. Sludge Blanket
i. A sludge blanket level detector shall be fitted whose height shall be adjustable and shall be firmly
attached to the side of the tank.
12.5.3. Mechanical Thickeners
i. Typical mechanical thickener process include belt thickener and centrifuges plants.
ii. Mechanical thickeners shall be sized to treat the throughput within an 8-hour working day to allow
for start-up and cleaning/shut-down.
iii. The mechanical thickeners shall be designed so that the following is achieved:
a) Dry solids concentration shall be in the range 5 of 6 percent.
b) Solids recovery shall not be lower than 95 percent.
c) Operation of the thickener shall be automatic.
d) Odour control shall be provided.
iv. Mechanical thickeners shall typically operate in parallel where more than one unit exists.
v. Each thickener shall have its own dedicated polymer dosing system and shall not be fed from a
common manifold.
vi. The system shall be capable of accommodating interruptions due to maintenance or breakdown,
and shall be capable of recovery to normal operating conditions within a reasonable time (5
working days) at normal weekly average throughput.
vii. Starting of the thickener shall normally be a manual operation and, once energised, shall be fully
automated.
viii. The control system shall include the thickener assembly and associated equipment comprising
sludge feed, polyelectrolyte make-up and dosing system, flocculation tank, wash water system,
and thickened sludge transfer system.
ix. For belt thickeners, control for belt speed, sludge feed rate, and polymer dosing shall be manually
adjustable and locally available at belt.
i. Facilities shall be provided for effective separation or decanting of supernatant. Separate facilities
are recommended; however, supernatant separation shall be accomplished in the digestion tank
provided additional volume is provided.
ii. The supernatant draw-off unit shall be designed to prevent recycle of scum and grease back to
plant process units. Provision shall be made to withdraw supernatant from multiple levels of the
supernatant withdrawal zone.
iii. Facilities shall be provided for the effective collection of scum and grease from the aerobic
digester for final disposal, to prevent its recycle back to the plant process, and to prevent long-
term accumulation and potential discharge in the effluent.
12.6.2.5. High Level Emergency Overflow
i. An un-valved high level overflow and any necessary piping shall be provided to return digester
overflow back to the head of the plant or to the aeration process in case of accidental overfilling.
Design considerations related to the digester overflow shall include waste sludge rate and
duration during the period the plant is unattended, potential effects on plant process units,
discharge location of the emergency overflow, and potential discharge of suspended solids in the
plant effluent.
12.6.3. Air Requirements
i. All compressors, blowers, and aeration equipment shall comply with the details in the Technical
Standard Specification – Mechanical Section 03 – Pumps, Compressors, Blowers, and Cutters
(AM-ENG-SS-03-03).
ii. Sufficient air shall be provided to keep the solids in suspension and maintain DO between 1 and
2 mg/L.
iii. For minimum mixing and oxygen requirements, an air supply of 0.85 L/m 3s of tank volume shall
be provided with the largest blower out of service.
iv. If diffusers are used, the non-clog type is recommended, and they shall be designed to permit
continuity of service.
v. If mechanical turbine aerators are utilised, at least two turbine aerators per tank shall be provided
to permit continuity of service.
vi. For difficult sludges, the use of a centrifuge shall be considered more appropriate.
12.7.3. General Design Basis
i. Provision shall be made to maintain sufficient continuity of service so that sludge shall be
dewatered without accumulation beyond storage capacity.
ii. The number of centrifuges filters presses, belt filters, other mechanical dewatering facilities, or
combinations thereof shall be sufficient to dewater the sludge produced with the largest unit out of
service.
iii. Unless other standby wet sludge facilities are available, adequate storage facilities of at least
1-day production volume, in addition to any other sludge storage needs, shall be provided.
Documentation must be submitted justifying the basis of design of mechanical dewatering
facilities.
iv. The mechanical dewaters shall be designed so that the following is achieved:
a) Dry solids concentration exceeds 22 percent DS, except for surplus activated sludges
only, where the minimum DS content shall be 18 percent DS.
b) Solids recovery shall not be lower than 95 percent.
c) Operation of the dewaterer shall be automatic.
d) Odour control shall be provided.
e) Proven equipment for onward conveyance to appropriate storage shall be provided.
v. The dewatering plant shall include one or more identical dewaterers which shall have a total
capacity sufficient to treat peak weekly average feedstock flow and load rates whilst operating for
up to 16 hours per day, 5 days per week.
vi. An identical unit shall be installed for standby purposes, capable of operating in parallel if
required.
vii. “Starting” shall be carried out manually. Operation shall be continuous and fully automated.
viii. The dewatering plant shall be designed for a maximum operator attendance of 16 hours per day.
ix. Each dewaterer shall have its own dedicated polymer dosing system and shall not be fed from a
common manifold. On large sludge plants, the polymer pumps shall be linked to the dewatered
sludge feed pumps automatically with manual control of dilution/carrier water and dose-rate/m3
sludge treated.
x. A suitable, final effluent (where practicable), wash water system to wash the dewatering plant,
remove blinded material, and maintain optimum dewatering performance shall be provided.
xi. Special attention shall be given to dealing with sludges with a high FOG content.
xii. Drainage from dewatering units shall be returned to the wastewater treatment process at
appropriate points and rates.
xiii. One dedicated duty feed pump shall be provided per dewaterer.
xiv. A transfer system shall be provided to transfer dewatered sludge cake to the covered sludge cake
storage area.
xv. Sampling points shall be provided on each machine for sludge in, cake out, and filtrate.
xvi. Drainage and filtrate from dewatering units shall be returned to the sewage treatment process at
appropriate points.
12.7.4. Belt Presses
i. The number of belt presses installed shall be sized so that peak weekly average sludge
production can be dewatered over 5 days per week, 16 hours per day with one belt out of service.
ii. All belts provided shall be capable of running together in automatic mode.
iii. The plant shall be designed with an inlet sludge of 3 to 6 percent DS.
iv. If pressing raw sludge, whether located in a box or a building, a ventilation system is required; it
shall be vented to an odour-control plant.
v. If pressing digested sludge in a building, ventilation shall be installed to assist in reducing the high
humidity in the building.
vi. The heating system shall be designed to cope with this rate of ventilation, to maintain a minimum
temperature of 6C in the building.
vii. Filtered pressurised effluent shall be used for belt washing.
viii. Control of belt speed, sludge feed rate, and poly-dosing rate shall be locally available at the belt.
ix. Belt drive speed and ramp angle shall be manually adjustable.
x. Feed and discharge pumps to be sized at 120 percent of design throughout.
xi. One pump per unit shall be employed.
xii. A dedicated pump to each crossover pipework facility for an external pump, with a Bauer
connection, shall be provided.
xiii. Progressive cavity feed pumps shall be used to enable defined control feed.
xiv. Shut-down shall be automatic on a timer with an automatic phased wash down.
12.7.5. Centrifuges
i. The decanter centrifuge (sometimes referred to as a solid bowl and scroll centrifuge) shall
comprise the following components:
a) Sludge feed system
b) Collecting vessel and support frame
c) Variable speed drive (where specified)
d) Differential scroll drive
e) Cake discharge system
f) Centrifuge washing
g) Concentrate collection
h) Control system
ii. Centrifuges and drum dewaterers can be sized for continuous operations but shall be capable of
catching up a backlog following an interruption to service of 4 days within the following 5 days to
return to stable.
iii. Since temperature affects the viscosity of sludges, the required centrifuge capacity shall be
determined for the lowest temperature expected.
iv. Centrifuge plants shall be sized to run continuously at 75 percent of capacity, with built-in
redundant capacity to allow for 25 days per annum downtime. This shall be in the form of
upstream and downstream capacity.
d) A sludge conveyor shall discharge to the area with a raised up wall of 2.5 m high to allow
a stacking machine to push against (the wall must be able to take this load).
e) A loading shovel shall be supplied under the scheme (if not already available).
f) Drainage shall be provided to take any run-off liquors away from the stacking area and
toward the traffic route. The design of this shall take the water and retain the sludge cake.
g) Preferably, drainage channels shall be open-topped; where covers are provided, they
shall be bolted down to prevent damage by loading shovel. Provision shall be made for
cleaning of drainage channels.
h) Drainage shall be led to a chamber utilising a weir to separate sludge from supernatant.
Separated sludge shall be returned to digested sludge storage.
12.10. Pipelines
i. All piping shall comply with the details in the Technical Standard Specification – Mechanical
Section 06 – Piping and Accessories (AM-ENG-SS-03-06).
ii. The flow velocity in liquid sludge and sludge liquor pipelines shall not be continuously less than
1 m/s unless measures for the prevention of sedimentation/encrustation are taken. If the rate of
gravity flow is too low, then pumping shall be considered.
iii. Systems shall be designed so that regular operations do not require pressure-tight isolation of
any section. This is to avoid the risk that high or damaging gas pressures could develop in a
sealed section.
iv. In sludge pipelines which are connected to permanently filled sludge tanks below the minimum
sludge level and which include a frequently operated isolation valve, a second manual valve shall
be installed between the reactor and the valve which is frequently operated.
v. Pipelines and other equipment which are installed in sludge tanks shall be corrosion-resistant.
g) Pump duty, including suction and delivery heads and flow rate
h) Local and operational conditions (for example, submersed or dry well, available space)
iii. All pumps shall comply with details in the Technical Standard Specification – Mechanical Section
03 – Pumps, Compressors, Blowers and Cutters (AM-ENG-SS-03-03).
13.1. General
i. All chemical delivery and storage facilities, dosing systems, ICA, control systems, and associated
equipment and materials shall be designed and constructed such that they are suitable for the
chemical being dosed. Reference shall be made to the chemical manufacturer’s data sheets and
guidelines as well as documented best practices for particular chemicals.
ii. Due consideration shall be given to the need for future internal inspection of the tanks. Safe
access to the inside shall be provided, with hatches that allow ventilation prior to inspection.
iii. The design shall incorporate the following features:
a) The storage tanks shall include an ultrasonic level instrument, a high level conductivity
probe, and a cat and mouse visual level indication.
b) The overflow from chemical storage tanks shall exit the side of the tank and be sized in
excess of the fill line diameter.
c) Where the chemical has a high freezing point, low density immersion type heaters
entering the tank from the top shall be used.
d) Isolation valves on the outlet of the tank shall be connected directly to the outlet flange of
the tank to ensure all pipework can be replaced without draining the tank.
e) Access to the top of storage tanks for maintenance of heaters, instruments, and other
equipment shall be provided.
13.2.1.3. Bunds
i. All tanks and containers (with the exception of reinforced concrete tanks) used for the storage of
liquid chemicals shall be contained within a bund.
ii. Where chemicals are to be stored in International Bulk Containers (IBCs), carboys, or drums, the
bunded area shall be sufficient for the maximum number of containers required both full and
empty, to be stored without stacking at ground level.
iii. Bund capacity shall be not less than 110 percent of the volume that could discharge from the
largest tank or container within the bund or, where there is more than one tank within the bund,
25 percent of the aggregate storage capacity, whichever is the greater.
iv. Construction shall be of reinforced concrete, in accordance with BS 8007, as a monolithic
structure without water bars, and water-tested accordingly.
v. Internal coating of bunds shall be with materials suitably resistant to the contained chemical.
vi. Where access is required within the bunded area, the local base area shall be “non-slip”.
vii. The area within the bund shall fall to a blind sump or other provision to facilitate the collection and
removal of any leakage or spillage. Spilled liquids shall normally be tankered offsite as a Special
Waste. No uncontrolled drainage from the bund shall be permitted.
viii. For removal of hazardous chemicals from the bund sump, fixed pipework shall be installed to
allow a mobile chemical resistant pump to be used to pump spills away to the chemical
interceptor tank.
ix. Detectors and alarms shall be fitted to indicate the presence of leakage and spillage.
x. Weatherproof rain “skirts” or roofs shall be fitted to external bunds wherever practicable.
xi. The bund base and walls shall not be penetrated by any valve, pipe, or other opening. Any valve,
filter, sight-gauge, vent-pipe, or other equipment ancillary to the container shall be situated within
the bund.
13.2.2. Apparatus for Chemical Transfer
13.2.2.1. Filling Points
i. The fill point shall be as close as practicable to the storage tanks and either within the catchment
of the hard-standing area or within the bund.
ii. It shall be possible to use a single length of delivery hose to connect the delivery tanker to the
filling point.
iii. The fill point hose connection shall be suitably supported to carry the weight of pipework, hose,
and chemicals, and to ensure the integrity of the fill line.
iv. A dedicated fill line shall be provided for each individual tank.
v. The filling point connection shall be locked off with a unique padlock, with the key held in a locked
key cabinet clearly marked to indicate which chemical it is for.
vi. External filling points shall be housed within a secure, lockable enclosure.
vii. A hose reel/wash-down point shall be provided local to the filling point.
viii. Where delivery volumes are variable, it shall be possible to ascertain the volume of the tank
contents from the filling point. This shall be via an indicator at the fill point or through the tank
contents gauge being visible from the filling point.
13.2.2.2. Fill Panel
i. A fill panel shall be provided adjacent to the filling point. The display shall show the following, at a
minimum:
a) High level indication in storage tanks
b) Position of valves to interceptor tank
c) High level in interceptor tank
ii. High level indication within the storage tank shall be linked to a flashing warning light and a
klaxon mounted on the fill panel.
iii. Where the delivery volumes are variable and the tank contents are not visible from the filling
point, the volume of the tank contents shall also be displayed.
13.2.3. Location
i. Chemical storage and dosing facilities shall be located as close as practicable to the dosing point.
13.2.4. Materials for Tanks and Dosing Systems
i. Pipe and fabrication materials shall be suitable for a 20-year design life in accordance with the
material data/safety sheets provided by the Contractor.
ii. Reference shall be made to international water industry best practices with respect to handling of
individual chemicals.
v. It shall be possible to interchange both the suction and the delivery lines at each dosing board
such that dosing can continue in the event of plant breakdown or maintenance to any section of
either duty or standby line.
vi. Flushing and drainage of dosing lines shall be provided and, where dosing lines are used
intermittently, flushing shall be initiated on cessation of use. A removable drain pot shall be
provided below the drain point.
vii. Calibration tubes shall be provided, and these shall be extended to the full height of the chemical
storage tank to prevent over-filling. This extension need not necessarily be at full bore.
13.3.3.2. Valves and Fittings
i. All valves shall comply with the details in the Technical Standard Specification – Mechanical
Section 04 – Valves, Penstocks, and Actuators (AM-ENG-SS-03-04).
ii. All isolation valves shall be accessible.
iii. Pressure relief valves shall be located immediately downstream of the dosing pumps, with a
catch-pot and alarm provided.
iv. A pressure gauge shall be located on the delivery side of each pump.
v. For coagulant dosing, a Y-strainer with local isolation valves shall be used on the suction side of
the dosing pump.
vi. Measures to prevent siphoning or back-feed shall include the following:
a) Positive displacement pump or peristaltic pump
b) Non-return valves (two if not included in dosing pump)
c) Loading valves and suction demand valves (or, where necessary, automatic isolation
valves)
13.3.3.3. Secondary Containment
i. Containment systems for leaks from dosing pipework shall be either spray-out protection or
secondary containment as determined through a Design Risk Assessment/Hazardous Operation
(HAZOP) process review. One system or another shall operate over the full length of each dosing
line.
ii. The system shall be designed to drain to a bund or drip-tray with liquid level detection.
iii. Detection of liquid in the bund or drip tray shall cause failure of the duty line and initiate start-up of
the standby line. An alarm shall be initiated on detection of liquid.
iv. Where dosing lines need to be exposed, proprietary spray-out protection systems shall be fitted
over pipe joints.
v. Joints between secondary containment and spray-out protection shall provide a permanent seal.
vi. Spray-out protection shall be provided for each dosing board.
vii. Where secondary containment cannot drain into a bund or drip-tray with level detection (all self-
draining), drain valves with catch-pot level switches shall be provided at the lowest point in the
secondary containment. Detection of liquid in the catch pot shall cause changeover of
duty/standby pumps and initiate an alarm.
13.3.4. Dosing Points
13.3.4.1. Dosing into Pipework
i. There shall be adequate means of mixing immediately downstream of the dosing point. In most
circumstances, dispersion via an in-line static mixer will be appropriate.
ii. Chemicals shall be mixed into the bulk process flow using a static mixer unless agreed upon with
Client at the design stage.
iii. Each dosing point shall be provided with a separate connection onto the mixer/main; this shall be
made via a withdrawable dosing lance with isolation valves to permit lance removal whilst the
process main is in operation and under pressure. It shall be possible to switch over pipework
between the duty and standby lances in an emergency.
iv. A short length of chemical-resistant, food-grade flexible hose of adequate pressure rating shall
run between fixed pipework and each dosing point on the main. (This allows easy withdrawal of
the injection fitting without dismantling the pipework.) Rigid pipework shall be well supported.
v. The dosing point shall include a bund or drip-tray with liquid level detection and alarm.
vi. Where a static mixer is used and there will be a need for cleaning of the mixer (due to lime scale
or other blockage), a bypass shall be provided. The diameter of the bypass (hence maximum flow
capacity) shall be agreed upon with the Client during detailed design.
13.3.4.2. Dosing into Open Channels
i. Fully independent duty/standby injection sparge systems shall be provided. It shall be possible to
switch over pipework between the duty and standby sparges in an emergency.
ii. The connection between dosing pipework and sparge pipe shall be fully protected against
accidental damage. It shall have adequate support and be firmly fixed. It shall also allow for easy
dismantling.
iii. There shall be adequate means of dispersion of the chemical immediately downstream of the
dosing point. When dispersion is via mixers, these shall be designed for a coefficient of variation
of 0.05 at the mixer outlet/sample point.
Chemical dosing into an open channel where the effluent weirs over a waterfall to provide
adequate mixing are acceptable for certain applications of chemical dosing.