TCD 209 Point of ● Run CPU ● DI120-150

Group Management Operation Error Application


Detection ○ Speed CPU ● DI180-420

[Meaning] When an error occurs in communication with group management panel. [Actions to take]

1.Verify if GNET terminal resistance of DIP SW8-1 is


correctly set in DOC-200.
[Diagram]
<< S/W SKELETON >> 2.Verify if group management panel is normal.
(Refer to Group management Panel related Manual.)
Group_Main_Err
GIS_OP_MICOM_RUN INC
3.Referring to control panel, group management panel, and
0x50ED
relay communication line diagram(3X03743 CTLC. [2]), check
General_Spec.Group Receive_GNET_Buff(SIZE) = 0
circuit wiring for MIC contact error, etc.. Especially,
0x0015 focus on power connection and communication line connection
Group_Main_Err > 8 ERR_GROUP_MASTER S status.
TCD 209

<< H/W SKELETON >>


NO.1 C.P
COMM-01 40T1-37 JOB SITE WIRING
40T2-37
COMM-02 40T1-38 40T2-38

DOR-200 DOA-100 DOR-200 DOA-100


MA

MA

CN2 CN2 40T1


MC-01 MC-01 COMM-06 -39
TO SVP
NO.2 C.P
MC-02 COMM-07
40T1 40T2-37
MC-02 -40
ANN ANN 40T2-38
MA

MA

TRX1 TRX2 TRX1 TRX2


DOC-200 DOC-200
(MPU1) (MPU2)
TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2

MD-01
MD-01

ME-02
ME-01
MD-02

MD-02
ME-02

MD-01

MD-02

ME-01

TRX1 TRX2 NO.8 C.P


DOL-200

40T2-37
40T2-38

TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2

Diagram No. : 3X03743 CTL C.[2]

* When the communication packet data cannot be received from the group management
panel or communication packet where GIS_OP_MICOM_RUN (ADDR:0x50ED) is not set
for 8 consecutive times is received.
Point of ● Run CPU ● DI120-150
TCD 215 RELAY MASTER FAULT Application
Detection ○ Speed CPU ● DI180-420

[Meaning] When relay is failed. [Actions to take]

1.Verify that GNET terminal resistance of DIP SW8-1 is


correctly set in DOC-200.
[Diagram]
2.Verify that group control panel is normal.
<< S/W SKELETON >> (Refer to Group Control Panel related Manual.)

3.Referring to control panel, group control panel, and relay


GIS_COMMON_POWER S
TCD 215 communication line diagram(3X03743 CTLC. [2]), check circuit
0x50EF
wiring for MIC contact error, etc.. Especially, focus on
power connection and communication line connection status.

<< H/W SKELETON >>

NO.1 C.P
COMM-01 40T1-37 JOB SITE WIRING
40T2-37
COMM-02 40T1-38 40T2-38

DOR-200 DOA-100 DOR-200 DOA-100


MA

MA

CN2 CN2 40T1


MC-01 MC-01 COMM-06 -39
TO SVP
NO.2 C.P
MC-02 COMM-07
40T1 40T2-37
MC-02 -40
ANN ANN 40T2-38
MA

MA

TRX1 TRX2 TRX1 TRX2


DOC-200 DOC-200
(MPU1) (MPU2)
TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2

MD-01
MD-01

ME-02
ME-01
MD-02

MD-02
ME-02

MD-01

MD-02

ME-01

TRX1 TRX2 NO.8 C.P


DOL-200

40T2-37
40T2-38

TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2

Diagram No. : 3X03743 CTL C.[2]

* When the communication packet data cannot be received from the group management
panel or communication packet where GIS_COMMON_POWER(ADDR:0x50EE) is not set
for is received.