You are on page 1of 8

TUV 

INDIA PRIVATE LIMITED
INSPECTION VISIT REPORT
IVR­050102050120/45­1­Rev.0

General:

TUV India Control Number: 050102050120/45 Branch: Mumbai


(SAP Number) (8115689137)

Notification Number: E­mail dtd. 5.05.2022 Date(s) of Inspection: 06/05/2022

Project Name & Location: VENDOR INSPECTION FOR NEO Inspection Location: Plot no 1828 Kalmboli MUMBAI


STRUCTO AT VARIOUS
LOCATIONS

TUV India Client Name: NEO STRUCTO End User Name: NEO STRUCTO


CONSTRUCTION PVT. LTD. CONSTRUCTION PVT. LTD.
(7837)

DEC / PMC / EPC Name: ­ DEC / PMC / EPC Assignment ­
(If applicable)
Number:
(If applicable)

Vendor Name & Location: NANDINI STEEL P.O. Number: PO NO: 001117 Dated


(Client PO on Vendor)
04/05/2022

Sub Vendor Name & Location: ­ P.O. Number:
(If applicable) (If applicable – Vendor PO on Sub Vendor)

Stages Of Inspection:

Kick Off / Pre Inspection Meeting  Material Identification  Interim Stages

 Document Review  Final Inspection  Re­Inspection

Item Description:

Item Item Item Description UOM P.O. Offered Acceptable


No. Code Quantity Quantity Quantity

1 2700291 REQUIREMENT AS PER PO ­ PIPE SEMLESS 2’’ (60.3 meter 5512 4742.14 REFER


MM) X SCH.STD (3.91 MM THK.), ASTM A106 GR.B, APPROXIMATE CONCLUSION
LENGTH : 6 MTR (224 NOS), 6.1 MTR (224 NOS), 6.2 (744 NOS
MTR (224 NOS), 6.3 MTR (224 NOS),  APPROXIMATE)

OFFERED MATERIAL ­ PIPE SEMLESS 2’’ (60.3 MM) X
3.91 MM THK, ASTM A106 GR.B

MAKE ­ ISMT,
HEAT NO.3119234/B NO.BTI­357, QTY OFFER – 3
BUNDLES (APPROXIMATE 181 NOS OF PIPES), 
HEAT NO.6628/B.NO.BUD­655, QTY OFFER – 5­6
BUNDLE (APPROXIMATE 294 PIPES)
TOTAL APPROX. MTR ­ 3040 MTR

MAKE ­ MSL/JSL,
HEAT NO.AA2640, BUNDLE NO.V4617, QTY OFFER – 1
BUNDLE (69 NOS, 436.77 MTR), 1 bundle (100 NOS,
632.27 MTR)
HEAT NO.AA2638, BUNDLE NO.V4618, QTY OFFER ­ 1
BUNDLE (100 NOS, 633,10 MTR)

Reference Documents:

Sr.
Document Name Client Document Number Vendor Document Number Approval Status
No.

1 PR/MR/ARM ­ ­ ­

2 QAP/ITP/QCP AS PER DISCUSSED WITH CLIENT ­ AS PER DISCUSSED WITH


­ VISUAL, DIMENSION & CLIENT ­ VISUAL, DIMENSION
MARKING/STENCILING & MARKING/STENCILING
VERIFICATION ON ACCESSIBLE VERIFICATION ON
PIPES
Disclaimer: This IVR shall not be considered as final acceptance of inspected item(s).The final acceptance will be given through Inspection Release Note.
ACCESSIBLE PIPES
The inspection by TUV India Pvt. Ltd., review of Test Certificates / Reports and issue of Inspection Visit Report does not relieve the Client / Supplier / Manufacturer / Stockiest from their responsibility towards the Client
3 Drawing(s) ­ ­ ­
/ End User to supply the genuine material / item(s) and document(s) in full compliance with applicable Order, Specification, Technical, Quality, Quantity, Warranty, Guarantee requirements. Supplier / Manufacturer /
stockiest is wholly legally responsible for genuineness of the material / item(s) supplied and document(s) submitted. TÜV India’s responsibility is only limited to correctness of inspection results including review of the
documents, within its agreed scope against written requirements and neither TUV India nor any of its group companies, associates or employees are in any way/ legally responsible for genuineness of the material /
4 Datasheet(s) ­ ­ ­
item(s) and document(s). If the calibration certificate(s) for the measuring instrument(s) / equipment(s) used during inspection do not have traceability to NABL / Other certifying bodies, then the scope of review is limited
only to technical content in the calibration certificate.
Copyright:
5 This document is the property of TUV India Pvt. Ltd. and should not be reproduced, except in full without the consent of TUV India Pvt. Ltd.
Procedure(s) ­ ­ ­
TUV India Pvt. Ltd. (TÜV NORD GROUP) : (REGD. & HEAD OFFICE), 801, Raheja Plaza ­ I, LBS Marg, Ghatkopar (West), Mumbai – 400086, Maharashtra, India.
Tel: + 91 22 66477000, Email: inspection@tuv­nord.com;  Website: www.tuv­nord.com/in.
6 Others(Specify) ­
Form No. : F / INSP / VR / 11 – R12; Revision Date: 14.03.2020 / TIIMES ­ ­ Page 1 of 8
Inspection Activities Carried Out:
Document Name Client Document Number Vendor Document Number Approval Status
No.

1 PR/MR/ARM ­ ­ ­
TUV INDIA PRIVATE LIMITED
2 QAP/ITP/QCP AS PER DISCUSSED WITH CLIENT ­
INSPECTION VISIT REPORT AS PER DISCUSSED WITH
­ VISUAL, DIMENSION & CLIENT ­ VISUAL, DIMENSION
MARKING/STENCILING IVR­050102050120/45­1­Rev.0 & MARKING/STENCILING
VERIFICATION ON ACCESSIBLE VERIFICATION ON
PIPES ACCESSIBLE PIPES

3 Drawing(s) ­ ­ ­

4 Datasheet(s) ­ ­ ­

5 Procedure(s) ­ ­ ­

6 Others(Specify) ­ ­ ­

Inspection Activities Carried Out:

Stages Witnessed:

1 Vendor offered Pipes for inspection is in stack condition as well as sub vendor not ready to offered all Pipes bundle for inspection.
Same is discussed with Client. As per discussion scope of inspection is Visual, Dimension and Marking/Stenciling verification carried
out on accessible Pipes. Please note that vendor offered single bundle per make.

2 Visual Inspection ­ Visual inspection carried out on accessible pipes for any surface defects. No any kind of injurious defects were
observed at the time of inspection except observation mentioned in area of concern section.

3 Dimension Inspection ­ Dimension inspection carried out on accessible pipes i.e. O/D, Thickness, Length checked. Thickness checked
at edge of Pipes as D­meter not available with Vendor. Dimension found as per requirements.

4 Marking Verification ­ Marking verification carried out on accessible pipes. Observed Mill stenciling on pipes and noted as no hard
copies of MTC's available with Vendor for verification.

Documents Reviewed:

1 No original MTC's and hard copies of MTC's available with vendor. Reviewed of MTCs balance.

2 No calibration certificate provided by Vendor.

Details of Equipment(s) / Instrument(s) used for measuring / testing During Inspection:(Refer Notes)
NABL / OTHER NON­NABL
Sr.Detail of Range ID Validity till Calibration Certificate CERT. BODIES /
Equipment(s)/ Date Number NABL Traceability
No. Instrument(s) Please tick or Write Yes (whichever is applicable)

See Note 1 & 2 See Note 3
Notes: 
1) Other Certifying bodies are: NPL­India, CIPM (International Committee for Weights & Measures), ILAC & APLAC MRA Signatories.
2) Visiting inspector to ensure continued suitability for intended use, periodic maintenance, proper identification and valid calibration records and traceability to known National / International standards of the measuring Instrument(s) / testing equipment(s).
3) Non NABL: If the calibration certificate(s) for the measuring instrument(s) / equipment(s) used during inspection do not have traceability to NABL / Other certifying bodies, then the scope of review is limited only to technical content in the calibration certificate.
4) In lieu of table above inspectors may collect master list from manufacturer / vendor/ sub vendor with all above details clearly highlighting the details of instrument(s) / equipment(s) used during inspection.

Conclusion (Acceptable / Not Acceptable / Acceptance subject to):

Acceptance of Pipes subjected to clearance of observation mentioned in area of concern section and completion of pending activities
mentioned in pending activities section.
IRN can not be issued for all PO items because activities balance as per QAP/ITP/QCP,concerns are open.
Pending activities:

1. MTC's review & endorsement
2. Clearance of observation mentioned in area of concern section
Identification of inspected Item(s):

All inspected pipes double low stress hard stamped as   near mill marking as well as Bluecolor/Red color marked at one end of Pipes for
identification ..
Areas of Concerns:

1. Vendor offered only accessible Pipes in Single bundle for inspection. Vendor need to check all pipes per Bundle for Visual, Dimension and
Marking verification.
2. Visual Inspection ­ Observed handling marks on outer surface of Pipes. Observed minor rusting inside accessible area of Pipes.Pipe
External areas varnish and Inside cleaning required, Client to be advise to vendor
3. Dimension Inspection ­ During inspection observed short length pipes means pipe length less than 6.0 mtr. Same is rejected. Vednor need to
reconfirmed /rechecked length of pipes as per PO requirements. Also Thickness of pipes checked at edge by using Vernier Caliper as
Thickness meter not available with Vendor.
4. Marking Verification ­ Marking/Stencilling on Pipes noted as hard copy of MTC’s not available with Vendor.
5. Points to be note ­ 1. As Vendor offered accessible Pipes from single Bundle, there is possibility that we get different heat number other than
mentioned in Item description. 2. Length required as PO 6.0 mtr, 6.1 mtr, 6.2 mtr & 6.3 mtr but Vendor offered length ranges from 6.060 mtr ­
6.750 mtr. Client to be note. 3. There is chances of change in Qty of Pipes as during inspection observed short length of pipes which was
Disclaimer: This IVR shall not be considered as final acceptance of inspected item(s).The final acceptance will be given through Inspection Release Note.
The inspection by TUV India Pvt. Ltd., review of Test Certificates / Reports and issue of Inspection Visit Report does not relieve the Client / Supplier / Manufacturer / Stockiest from their responsibility towards the Client
rejected. Vendor need to check Length of all pipes. Also Vendor need to ensure that quantities of Pipes as per PO requirement only.
/ End User to supply the genuine material / item(s) and document(s) in full compliance with applicable Order, Specification, Technical, Quality, Quantity, Warranty, Guarantee requirements. Supplier / Manufacturer /
6. Calibration certificate for Measuring Tape, Vernier Caliper not available with Vendor at the time of inspection.
stockiest is wholly legally responsible for genuineness of the material / item(s) supplied and document(s) submitted. TÜV India’s responsibility is only limited to correctness of inspection results including review of the
documents, within its agreed scope against written requirements and neither TUV India nor any of its group companies, associates or employees are in any way/ legally responsible for genuineness of the material /
7. Approximate 4742.14 mtr Pipes offered against 5512 mtr. Client to be note.
item(s) and document(s). If the calibration certificate(s) for the measuring instrument(s) / equipment(s) used during inspection do not have traceability to NABL / Other certifying bodies, then the scope of review is limited
only to technical content in the calibration certificate.
Non Conformities raised / Discrepancies observed during inspection
Copyright: This document is the property of TUV India Pvt. Ltd. and should not be reproduced, except in full without the consent of TUV India Pvt. Ltd.
(If Any, Mention TUV India NCR Number):
TUV India Pvt. Ltd. (TÜV NORD GROUP) : (REGD. & HEAD OFFICE), 801, Raheja Plaza ­ I, LBS Marg, Ghatkopar (West), Mumbai – 400086, Maharashtra, India.
Tel: + 91 22 66477000, Email: inspection@tuv­nord.com;  Website: www.tuv­nord.com/in.
NA
Form No. : F / INSP / VR / 11 – R12; Revision Date: 14.03.2020 / TIIMES Page 2 of 8
Attachments:
External areas varnish and Inside cleaning required, Client to be advise to vendor
3. Dimension Inspection ­ During inspection observed short length pipes means pipe length less than 6.0 mtr. Same is rejected. Vednor need to
TUV INDIA PRIVATE LIMITED
reconfirmed /rechecked length of pipes as per PO requirements. Also Thickness of pipes checked at edge by using Vernier Caliper as
Thickness meter not available with Vendor.
INSPECTION VISIT REPORT
4. Marking Verification ­ Marking/Stencilling on Pipes noted as hard copy of MTC’s not available with Vendor.
IVR­050102050120/45­1­Rev.0
5. Points to be note ­ 1. As Vendor offered accessible Pipes from single Bundle, there is possibility that we get different heat number other than
mentioned in Item description. 2. Length required as PO 6.0 mtr, 6.1 mtr, 6.2 mtr & 6.3 mtr but Vendor offered length ranges from 6.060 mtr ­
6.750 mtr. Client to be note. 3. There is chances of change in Qty of Pipes as during inspection observed short length of pipes which was
rejected. Vendor need to check Length of all pipes. Also Vendor need to ensure that quantities of Pipes as per PO requirement only.
6. Calibration certificate for Measuring Tape, Vernier Caliper not available with Vendor at the time of inspection.
7. Approximate 4742.14 mtr Pipes offered against 5512 mtr. Client to be note.
Non Conformities raised / Discrepancies observed during inspection (If Any, Mention TUV India NCR Number):

NA
Attachments:

Inspection records –  Master List of calibrated
Total Page Nos. Instruments / equipment :

Inspection Photos –
4 to 8 Others (Specify) :
Refer Page Nos.

Authorised Signature:

TUV India representative: Vendor / Sub Vendor Representative (If Applicable):

Name: Abhay Karande Date:07/05/2022 Name:

Distribution List:  TUVI Client / End User  TUVI Executing Branch / TUV Originating Branch  Vendor / Sub Vendor


Revision Number (If Applicable) [0] : ­
This Document Supersedes IVR No. :­

Disclaimer: This IVR shall not be considered as final acceptance of inspected item(s).The final acceptance will be given through Inspection Release Note.
The inspection by TUV India Pvt. Ltd., review of Test Certificates / Reports and issue of Inspection Visit Report does not relieve the Client / Supplier / Manufacturer / Stockiest from their responsibility towards the Client
/ End User to supply the genuine material / item(s) and document(s) in full compliance with applicable Order, Specification, Technical, Quality, Quantity, Warranty, Guarantee requirements. Supplier / Manufacturer /
stockiest is wholly legally responsible for genuineness of the material / item(s) supplied and document(s) submitted. TÜV India’s responsibility is only limited to correctness of inspection results including review of the
documents, within its agreed scope against written requirements and neither TUV India nor any of its group companies, associates or employees are in any way/ legally responsible for genuineness of the material /
item(s) and document(s). If the calibration certificate(s) for the measuring instrument(s) / equipment(s) used during inspection do not have traceability to NABL / Other certifying bodies, then the scope of review is limited
only to technical content in the calibration certificate.
Copyright: This document is the property of TUV India Pvt. Ltd. and should not be reproduced, except in full without the consent of TUV India Pvt. Ltd.
TUV India Pvt. Ltd. (TÜV NORD GROUP) : (REGD. & HEAD OFFICE), 801, Raheja Plaza ­ I, LBS Marg, Ghatkopar (West), Mumbai – 400086, Maharashtra, India.
Tel: + 91 22 66477000, Email: inspection@tuv­nord.com;  Website: www.tuv­nord.com/in.
Form No. : F / INSP / VR / 11 – R12; Revision Date: 14.03.2020 / TIIMES Page 3 of 8
TUV INDIA PRIVATE LIMITED
INSPECTION VISIT REPORT
IVR­050102050120/45­1­Rev.0

Inspection Pictures :

OBSERVED OFFERED PIPES IN STACK CONDITION MILL MARKING VERIFIED

MILL MARKING VERIFIED MILL MARKING VERIFIED

ACCESSIBLE PIPES FOR INSPECTION MILL MARKING VERIFIED

Disclaimer: This IVR shall not be considered as final acceptance of inspected item(s).The final acceptance will be given through Inspection Release Note.
The inspection by TUV India Pvt. Ltd., review of Test Certificates / Reports and issue of Inspection Visit Report does not relieve the Client / Supplier / Manufacturer / Stockiest from their responsibility towards the Client
/ End User to supply the genuine material / item(s) and document(s) in full compliance with applicable Order, Specification, Technical, Quality, Quantity, Warranty, Guarantee requirements. Supplier / Manufacturer /
stockiest is wholly legally responsible for genuineness of the material / item(s) supplied and document(s) submitted. TÜV India’s responsibility is only limited to correctness of inspection results including review of the
documents, within its agreed scope against written requirements and neither TUV India nor any of its group companies, associates or employees are in any way/ legally responsible for genuineness of the material /
item(s) and document(s). If the calibration certificate(s) for the measuring instrument(s) / equipment(s) used during inspection do not have traceability to NABL / Other certifying bodies, then the scope of review is limited
only to technical content in the calibration certificate.
Copyright: This document is the property of TUV India Pvt. Ltd. and should not be reproduced, except in full without the consent of TUV India Pvt. Ltd.
TUV India Pvt. Ltd. (TÜV NORD GROUP) : (REGD. & HEAD OFFICE), 801, Raheja Plaza ­ I, LBS Marg, Ghatkopar (West), Mumbai – 400086, Maharashtra, India.
Tel: + 91 22 66477000, Email: inspection@tuv­nord.com;  Website: www.tuv­nord.com/in.
Form No. : F / INSP / VR / 11 – R12; Revision Date: 14.03.2020 / TIIMES Page 4 of 8
TUV INDIA PRIVATE LIMITED
INSPECTION VISIT REPORT
IVR­050102050120/45­1­Rev.0

Inspection Pictures :

MILL MARKING VERIFIED DIMENSION CHECKED

DIMENSION CHECKED DIMENSION CHECKED

DIMENSION CHECKED DIMENSION CHECKED

Disclaimer: This IVR shall not be considered as final acceptance of inspected item(s).The final acceptance will be given through Inspection Release Note.
The inspection by TUV India Pvt. Ltd., review of Test Certificates / Reports and issue of Inspection Visit Report does not relieve the Client / Supplier / Manufacturer / Stockiest from their responsibility towards the Client
/ End User to supply the genuine material / item(s) and document(s) in full compliance with applicable Order, Specification, Technical, Quality, Quantity, Warranty, Guarantee requirements. Supplier / Manufacturer /
stockiest is wholly legally responsible for genuineness of the material / item(s) supplied and document(s) submitted. TÜV India’s responsibility is only limited to correctness of inspection results including review of the
documents, within its agreed scope against written requirements and neither TUV India nor any of its group companies, associates or employees are in any way/ legally responsible for genuineness of the material /
item(s) and document(s). If the calibration certificate(s) for the measuring instrument(s) / equipment(s) used during inspection do not have traceability to NABL / Other certifying bodies, then the scope of review is limited
only to technical content in the calibration certificate.
Copyright: This document is the property of TUV India Pvt. Ltd. and should not be reproduced, except in full without the consent of TUV India Pvt. Ltd.
TUV India Pvt. Ltd. (TÜV NORD GROUP) : (REGD. & HEAD OFFICE), 801, Raheja Plaza ­ I, LBS Marg, Ghatkopar (West), Mumbai – 400086, Maharashtra, India.
Tel: + 91 22 66477000, Email: inspection@tuv­nord.com;  Website: www.tuv­nord.com/in.
Form No. : F / INSP / VR / 11 – R12; Revision Date: 14.03.2020 / TIIMES Page 5 of 8
TUV INDIA PRIVATE LIMITED
INSPECTION VISIT REPORT
IVR­050102050120/45­1­Rev.0

Inspection Pictures :

DIMENSION CHECKED VISUAL INSPECTION ­ INSIDE CLEANING REQUIRED

INSPECTED PIPES COLOR CODED PIPES IN STACK CONDITION

MILL MARKING VERIFIED PIPES IN STACK CONDITION

Disclaimer: This IVR shall not be considered as final acceptance of inspected item(s).The final acceptance will be given through Inspection Release Note.
The inspection by TUV India Pvt. Ltd., review of Test Certificates / Reports and issue of Inspection Visit Report does not relieve the Client / Supplier / Manufacturer / Stockiest from their responsibility towards the Client
/ End User to supply the genuine material / item(s) and document(s) in full compliance with applicable Order, Specification, Technical, Quality, Quantity, Warranty, Guarantee requirements. Supplier / Manufacturer /
stockiest is wholly legally responsible for genuineness of the material / item(s) supplied and document(s) submitted. TÜV India’s responsibility is only limited to correctness of inspection results including review of the
documents, within its agreed scope against written requirements and neither TUV India nor any of its group companies, associates or employees are in any way/ legally responsible for genuineness of the material /
item(s) and document(s). If the calibration certificate(s) for the measuring instrument(s) / equipment(s) used during inspection do not have traceability to NABL / Other certifying bodies, then the scope of review is limited
only to technical content in the calibration certificate.
Copyright: This document is the property of TUV India Pvt. Ltd. and should not be reproduced, except in full without the consent of TUV India Pvt. Ltd.
TUV India Pvt. Ltd. (TÜV NORD GROUP) : (REGD. & HEAD OFFICE), 801, Raheja Plaza ­ I, LBS Marg, Ghatkopar (West), Mumbai – 400086, Maharashtra, India.
Tel: + 91 22 66477000, Email: inspection@tuv­nord.com;  Website: www.tuv­nord.com/in.
Form No. : F / INSP / VR / 11 – R12; Revision Date: 14.03.2020 / TIIMES Page 6 of 8
TUV INDIA PRIVATE LIMITED
INSPECTION VISIT REPORT
IVR­050102050120/45­1­Rev.0

Inspection Pictures :

PIPES IN STACK CONDITION MILL MARKING VERIFIED

MILL MARKING VERIFIED MILL MARKING VERIFIED

MILL MARKING VERIFIED MILL MARKING VERIFIED

Disclaimer: This IVR shall not be considered as final acceptance of inspected item(s).The final acceptance will be given through Inspection Release Note.
The inspection by TUV India Pvt. Ltd., review of Test Certificates / Reports and issue of Inspection Visit Report does not relieve the Client / Supplier / Manufacturer / Stockiest from their responsibility towards the Client
/ End User to supply the genuine material / item(s) and document(s) in full compliance with applicable Order, Specification, Technical, Quality, Quantity, Warranty, Guarantee requirements. Supplier / Manufacturer /
stockiest is wholly legally responsible for genuineness of the material / item(s) supplied and document(s) submitted. TÜV India’s responsibility is only limited to correctness of inspection results including review of the
documents, within its agreed scope against written requirements and neither TUV India nor any of its group companies, associates or employees are in any way/ legally responsible for genuineness of the material /
item(s) and document(s). If the calibration certificate(s) for the measuring instrument(s) / equipment(s) used during inspection do not have traceability to NABL / Other certifying bodies, then the scope of review is limited
only to technical content in the calibration certificate.
Copyright: This document is the property of TUV India Pvt. Ltd. and should not be reproduced, except in full without the consent of TUV India Pvt. Ltd.
TUV India Pvt. Ltd. (TÜV NORD GROUP) : (REGD. & HEAD OFFICE), 801, Raheja Plaza ­ I, LBS Marg, Ghatkopar (West), Mumbai – 400086, Maharashtra, India.
Tel: + 91 22 66477000, Email: inspection@tuv­nord.com;  Website: www.tuv­nord.com/in.
Form No. : F / INSP / VR / 11 – R12; Revision Date: 14.03.2020 / TIIMES Page 7 of 8
TUV INDIA PRIVATE LIMITED
INSPECTION VISIT REPORT
IVR­050102050120/45­1­Rev.0

Inspection Pictures :

DIMENSION CHECKED DIMENSION CHECKED

DIMENSION CHECKED DIMENSION CHECKED

BUNDLE VERIFIED INSPECTED PIPES COLOR CODED

Disclaimer: This IVR shall not be considered as final acceptance of inspected item(s).The final acceptance will be given through Inspection Release Note.
The inspection by TUV India Pvt. Ltd., review of Test Certificates / Reports and issue of Inspection Visit Report does not relieve the Client / Supplier / Manufacturer / Stockiest from their responsibility towards the Client
/ End User to supply the genuine material / item(s) and document(s) in full compliance with applicable Order, Specification, Technical, Quality, Quantity, Warranty, Guarantee requirements. Supplier / Manufacturer /
stockiest is wholly legally responsible for genuineness of the material / item(s) supplied and document(s) submitted. TÜV India’s responsibility is only limited to correctness of inspection results including review of the
documents, within its agreed scope against written requirements and neither TUV India nor any of its group companies, associates or employees are in any way/ legally responsible for genuineness of the material /
item(s) and document(s). If the calibration certificate(s) for the measuring instrument(s) / equipment(s) used during inspection do not have traceability to NABL / Other certifying bodies, then the scope of review is limited
only to technical content in the calibration certificate.
Copyright: This document is the property of TUV India Pvt. Ltd. and should not be reproduced, except in full without the consent of TUV India Pvt. Ltd.
TUV India Pvt. Ltd. (TÜV NORD GROUP) : (REGD. & HEAD OFFICE), 801, Raheja Plaza ­ I, LBS Marg, Ghatkopar (West), Mumbai – 400086, Maharashtra, India.
Tel: + 91 22 66477000, Email: inspection@tuv­nord.com;  Website: www.tuv­nord.com/in.
Form No. : F / INSP / VR / 11 – R12; Revision Date: 14.03.2020 / TIIMES Page 8 of 8