KMBR

GROUP J MUTIPLEX COMPLEX


FSI = TOTAL BUILT UP AREA / PLOT AREA
FOR GROUP J FSI IS PERMISSIBLE
WITHOUT FEE = 3
WITH FEE = 4
COVERAGE = 65%
FRONT YARD MIN 10 UPTO 10M HEIGHT
REAR YARD MIN 5 M AND SIDES MIN 5 M
INCREASE AT THE RATE 0.5 PER EVERY ADDITIONAL
3 METRES.
KMBR
IF THE HEIGHT IS 16M - FRONT YARD = 11M
REAR YARD = 6 M
TWO SIDES = 6 M
IF THE HEIGHT IS 14M, 14.5,15, 15.5 M -
FRONT YARD = 11M
REAR YARD = 6 M
TWO SIDES = 6 M
KMBR
SITE AREA 1 ACRE = 100 CENTS = 100X40.47= 4047 M2
COVERAGE 65% = 4047 X 65/100 = 2630 MAX.
KMBR
FSI = 4
MAX BUILT UP AREA IN 4047 M2 = 4 X 4047 M2
= 16,188 M2
OUR MAX COVERAGE ARE =2630
NO OF FLOOR MAXIMUM = 16188 / 2630 = 6.15
ie MAX 6 FLOORS WITH 65% COVERAGE.
KMBR
PARKING CALCULATIONS
CAR PARKING SIZE = 15 M2 LENGTH NOT LESS THAN 5.5 M
2.7 X 5.60
COMMERCIAL - 90 sq. metres of built-up area for buildings
having total built-up area upto1260 sq. metres and 60 sq
metres of built-up area for the total built up area in excess of
1260sq. metres.
For eg:- 7890 commercial area
No of parking = 1260 / 90 = 14 cars
Balance area = 7890 – 1260 = 6630
No of car parking = 6630 / 60 = 110.5= 111 cars
TOTAL CARS FOR COMMERCIAL AREA = 111 + 14 = 125 CARS
KMBR
MULIPLEX AREA car parking 60m2 of built up area
For eg:- multplex area = 1500 m2
No of car parking = 1500 / 60 = 25 nos.
TOTAL CAR PARKING AREA OF WHOLE BUILDING
IS 125 + 25 = 150 CARS
Differentially abled parking width 3.6 m
3% of the total parking = 150 x 3/100 = 4.5 = 5 cars provide
near entrance
TWO WHEELER PARKING
25% of area for car parking
Here , car parking area = 150 x 15 = 2250 m2
So two wheeler parking area = 2250 x 25/100 = 562.5 m2 = 563
m2 this is not necessary to provide in single area we can split
and provide
KMBR
Drive way leading to off-street parking space shall
have width not less than 3 metres.
Width of ramp for driveway for one-way direction
shall not be less than 3.5metres, 5.5 metres
for two-way direction and at curves it shall not be less
than 4 metres and 6m. Respectively and slope of such
ramps shall not be steeper than 1: 7.
The headroom for the drive way, ramps, passage etc.
for motor car movement shall not be less
than 2.2metres at any point.
Minimum turning radius of 9 metres to be provided
for fire tenders.
KMBR
Not exceeding fifty percent of each mandatory
open yard shall be taken into account for parking

Of the mandatory off-street car parking


requirement as per these Rules, fifty per cent at the
maximum may be provided for by mechanised
parking.
KMBR
SANITATION CALCULATIONS
The area of bathroom shall not be less than 1.50 sq.
metres with either side not less than1.1m
area of a latrine shall not be less than 1.10 sq.
metres with one side not less than 1.0 metre:
Differentially abled toilet = Minimum size of toilet
shall be 1.50 m x 1.75 m.
These shall be provided at the ground floor for J
occupancy and at every floor in multiples of three
for J occupancy.
KMBR
NO OF OCCUPANTS IN F OCCUPANCY = 1person/5.9 m2 built up
area
For eg:- here in three floor 2630 m2 each
GF= 2630/5.9 = 446 , FF = 446, SF= 446
No males in GF = 446 X 2/3 = 297
No of females in GF = 446 X 1/3 = 149
No WC for males GF = 1 per 25 males = 12Nos
Urinals= 1 per 25 persons = 12 Nos
No WC for females GF = 1 per 15 females = 10Nos
No WC for males FF = 1 per 25 males = 12Nos
Urinals= 1 per 25 persons = 12 Nos
No WC for females FF = 1 per 15 females = 10Nos
No WC for males SF = 1 per 25 males = 12Nos
Urinals= 1 per 25 persons = 12 Nos
No WC for females SF = 1 per 15 females = 10Nos
KMBR
NO OF OCCUPANTS IN J OCCUPANCY = 1person/1.8 m2
built up area
For eg:- here in multiplex floor 1500 m2
1500/1.8 = 833 persons
No males = 833 X 2/3 = 555
No of females = 833 X 1/3 = 278
No WC for males = 1 per 200 males = 3 Nos
Urinals = 1 per 50 persons = 11
Wash basins = 1 per 200 males = 3 nos
No WC for females = 1 per 100 females = 3Nos
Wash basin = 1 per 200 females = 2 Nos.
KMBR
FIRE ESCAPE STAIRCASE
Non-residential occupancies exceeding two storeys
above ground level.
Fire escape stairs shall have straight flight for building
exceeding 10 metres height. The use of spiral staircase
shall be limited to buildings up to 10 metres in height.
At least one side abutting external wall, this side being
provided with openable glass or break open glass
or fully open and has landing areas accessible from the
external side to facilitate rescue operations during an
emergency.
Emergency exits shall be located in such a way that the
travel distance on each floor shall not exceed 30 metres
for every occupant.