You are on page 1of 2

ISMAIL KHONJI ASSOCIATES Convention Centre

BASE PLATE DETAIL - SB46


Location: Along Grid Line 2 - at Grids 2/J, 2/K, 2/L, 2/M, & 2/N
Reference Drawing: EB_STR_TD_SC_GA_25 - SECTION CC-2A
Reference Drawing: NECC-MAB-CR-CEB-STR-CC-A02 & A03

ANCHORAGE TO CONCRETE DESIGN REVIEW PARAMETERS

GEOMETRY FACTORED LOAD


Profile Section As Shown below Vertical Load in (Tension) -360.0 KN
Width Length Moment, Mx = 0.0 Mz = 0.0 KNm
Base Plate 400 400 mm Shear, Vx = 220.0 Vz = 220.0 KN
Concrete Wp1 375 Lp1 375.0 mm Eccentricity, ex = 0.0 ez = 0.0 mm
Support Wp2 375 Lp2 375.0 mm Note: All washers are welded to base plate
Rod Edge 125 125 mm ANCHOR ROD
Rod Spacing 150 150 mm Rod Diameter M36 mm
Thickness of Grout 40 mm Embedment, hef 750 mm
Support Depth/Thickness 1,500 mm Number of Rods, 4 pcs
MATERIALS Participation of Actual Load in Anchor Rods in 50%
Plate Steel Strength, fy, pl 355 Mpa Resisting the Total Shear.
Plate Steel Strength, fu, pl 480 Mpa SHEAR LUG
Concrete Strength, fck 40 MPa Shear Lug Width, Wlug 300 mm
Rebar Strength, fy, re 460 MPa Shear Lug Height, Hlug 90 mm
Rod Yield Strength, fyk 660 MPa Shear Lug Thickness, tlug 30 mm
Rod Tensile Strength, fuk 830 MPa Shear Lug Weld Size, Z 10 mm

NECC - Anchorage to Concrete Design Review Page|1


ISMAIL KHONJI ASSOCIATES Convention Centre

BASE PLATE DETAIL - SB46


Location: Along Grid Line 2 - at Grids 2/J, 2/K, 2/L, 2/M, & 2/N
Reference Drawing: EB_STR_TD_SC_GA_25 - SECTION CC-2A
Reference Drawing: NECC-MAB-CR-CEB-STR-CC-A02 & A03

ANCHORAGE TO CONCRETE DESIGN REVIEW SUMMARY


No. of Rods, 4.0 fyk= 660 MPa, fuk= 830 MPa Anchor Rods, M36 diameter x 750 mm Embedment
TENSION ANALYSIS SHEAR ANALYSIS
Concrete is cracked at service load level Shear Resisted by Shear Lug and Anchors
g g
Total Tension Force, NEd = 360.00 KN Total Shear Force, VEd = 311.13 KN
Tension Force per Rod, NEd = 90.0 KN Shear Force in Lug, Vx = 175.0 KN Vz = 175.04 KN
All Anchor Bolts are Effective
Anchor Reinforcement: 4 - T20 bars per anchor rod Anchor Reinf't: 8 - T16 bars for lug in the form of ties
- -
FAILURE MODE NRd Ratio FAILURE MODE VRd (ΦVn) Ratio
Steel Failure of Rod, NRd,s = 404.42 0.22 Steel Failure of Rod, VRd,s,M = 40.77 0.39
Concrete Cone Failure, NRd,c = NA NA Steel Flexure Failure of Lug = 247.55 0.72
Concrete Pull-out Failure, NRd,cp = 2216.40 0.04 Steel Shear Failure of Lug = 1844.63 0.13
Concrete Blowout Failure, NRd,cb = 838.50 0.21 Weld Strength Failure = 1044.96 0.94
Anchor Reinf. Failure, NRd,re = 502.65 0.18 Conc. Bearing Failure from Lug = 336.00 0.74
Anchorage Failure, NRd,a = 471.24 0.19 Conc. Breakout Failure from Lug = NA NA
Anchor Reinf. Failure, NRd,re = 321.70 0.77
Anchorage Failure, NRd,a = 271.43 0.91
Tension Design Ratio OK 0.22 Shear Design Ratio OK 0.94

DESIGN CODES TENSION AND SHEAR INTERACTION


Steel Design EN 1993-1-1, 2005 EN 1992-4, Equation 7.54 Not Required
Anchorage Design EN 1992-4, 2018 EN 1992-4, Equation 7.55 0.97 ≤ 1.0 OK
Concrete Check due to Shear Lug ACI-318-2019 EN 1992-4, Equation 7.56 1.13 ≤ 1.2 OK
Load Combinations (Pre-Combined) EN 1990 Note: Shear lug is not part of the the interaction verifications

NECC - Anchorage to Concrete Design Review Page|2

You might also like