Client Frankson group Date 12-01-2022

Building Elevator Structure Rev 0

Design Basis

Analysis and design of the structure is carried out in STAAD pro software. All the loads are
calculated as per IS 875 part1 to part 5. The code used for design of structural member is IS 800
in working stress method. As wind load will be very dominant compared to seismic loads,
therefore only wind load analysis is performed for the design of the structure.
All the tubular steel shall be of material specification as
as specified in TATA structura brochure YST 310.

Load Calculation

1. Self weight of structure given in STAAD COMMAND = 1.1

2. ACP weight @ 25Kg/m2 with all fixings

Span Load unit


0.95 0.2375 kN/m

3. Glass weight @ 25Kg/m2 with all fixings

Span Load unit


1.01 0.2525 kN/m

4. Lift car load running condition = 6 kN

7. Wind load calculation

Wind load calculation for rectangular clad building:


Basic wind speed (Vb) = 39 m/s
Terrain category= 2
k1 = 1.07
K3= 1
K4= 1

Design
Basic wind
Height k1 k2 k3 k4 wind Pz ka kd
speed
speed
39 0-10 1.07 1 1 1 41.73 1.04483574 0.9 0.9
39 10-15 1.07 1.05 1 1 43.8165 1.1519314 0.9 0.9
Client Frankson group Date 12-01-2022
Building Elevator Structure Rev 0

Effective
Wind Effective wind load wind load
kc col width Cf x Cfz
pressure col width Z +Z +X
X
0.9 0.761685 1.01 0.95 1.8 1.8 1.384744 1.30248179
0.9 0.839758 1.01 0.95 1.8 1.8 1.52668 1.43598617