fo"k;% Return of Civil Drawing for correction of Central Inpit Conveying System Kusmunda OC
Expansion (15-50 MTY) project on turnkey.
Ekgksn;]
mi;qZDr ds lanHkZ esa fuEufyf[kr flfoy M~zkbax dks xzkgd ds vuqeksnu ds fy, izLrqr fd;k x;k Fkk A
The above drawings were checked and it was observed that active earth pressure has been taken instead of earth pressure at rest,
Moreover the above drawings are not matching with system drawings. It is recommended to instruct the contractor to resubmit
the said drawings with correction.