2018 21st International Conference on Electrical Machines and Systems (ICEMS) October 7-10, 2018┃Jeju, Korea

Development of ±400Mvar World Largest MMC


STATCOM
Jungsoo Park Sangmin Yeo Jongyun Choi
Power Systems Perofmance Unit Power Systems Perofmance Unit Power Systems Perofmance Unit
Hyosung Heavy Industries Corporation Hyosung Heavy Industries Corporation Hyosung Heavy Industries Corporation
Gyeonggi-do, Korea Gyeonggi-do, Korea Gyeonggi-do, Korea
jspark98@hyosung.com harc@hyosung.com choris007@hyosung.com

Abstract — This documents deals with 400MVA world metropolitan area is constrained and KEPCO system can be
largest MMC STATCOM projects in Korea. The STATCOM in danger of voltage collapse because power system voltage
has many technical advantages superiors to SVC. Those are is dropped too much.
very fast response time, excellent output capability under low
voltage condition and very weak system having extremely low
short circuit level, smaller foot print, extremely low harmonic
generation, and so on. This paper introduces the design, testing,
and commissioning of the MMC STATCOM.

Keywords—Modular Multilevel Converter, MMC,


STATCOM

I. INTRODUCTION
Static synchronous compensator(STATCOM) is a
voltage source converter based reactive power compensator.
Comparing to Static Var Compensator(SVC) which is
composed of thyristor switched capacitors(TSC) and
thyristor controlled reactors(TCR), it has advantages which
are very fast response time, excellent output capability under
low voltage condition and very weak system having
extremely low short circuit level, smaller foot print, and so
on. In addition, it does not need harmonic filter or sometimes
require small size high frequency filter. [1]
Especially, the superior capacitive reactive power output
capability under low voltage condition is the representative
advantage of STATCOM. Under low voltage condition
where output is reached to capacitive limit, the capacitive
reactive power output of SVC is decreased in proportional to
the square of power system voltage. However the output of
STATCOM is decreased in proportional to the power system
voltage.
In early 2000s, adopting Modular Multilevel
Converter(MMC) technology, STATCOM becomes to have
additional advantages such as scalability, low conversion
losses, lower harmonic generation, and redundant design. [2] Fig. 1. Location of ±400Mvar STATCOMs

Because of the advantages mentioned above, the In order to maximize the transmission line capacities of
demands of STATCOM are being increased. Moreover, the neighbor 345kV transmission lines and prevent voltage
since it becomes possible to make large scale MMC, the collapse, KEPCO is installing 3 x ±400Mvar MMC
STATCOMs whose rated reactive power is more than STATCOM at Shinchungju, Shinyoungju, and Donghae
300MVA is being discussed. 345kV substations. Currently, they are the world largest
MMC STATCOMs. Among them, the 2 x ±400Mvar
In 2017, Korea Electric Power Corporation(KEPCO) STATCOM at Shinyoungju and Shinchungju 345kV
system recorded the peak load around 80GW and about 40% substation is commissioned and under operation.
of load is concentrated in Seoul and near Seoul. In order to
support the huge load, 2 x 765kV double circuits and 4 x The ±400Mvar STATCOM is composed 3 x ±134Mvar
345kV double circuits are transmitting electric power from MMCs and a 400MVA coupling transformer. It is very huge
other areas to Seoul metropolitan area. However if one of the size. Nevertheless, it responds very fast and harmonic
765kV double circuits is tripped, the massive electric power generation is too low without any harmonic filters at both
transmitted on the line has to be bypassed through neighbor primary and secondary side of coupling transformer. It is
345kV lines. At that time, since power system voltage is designed to work with reactive power control mode within a
dropped too much, the transmission capacity to Seoul

Copyright ⓒ KIEE Electrical Machinery and Energy Conversion Systems 2060


certain voltage band, and with automatic voltage control The full-bridge submodule is composed of 4 IGBT &
mode outside of the band. free-wheeling diode modules and DC capacitor. Besides, it
has a mechanical bypass switch connected between its 2
This document will deals with the development of the terminals. If any fault is detected inside of full-bridge
±400Mvar World Largest MMC STATCOM. It will submodule, the mechanical bypass switch is switched in and
introduce the design, testing, and commissioning of the the faulted submodule is eliminated from the MMC
MMC STATCOM. operation and the MMC phase circuit can continue its normal
operation with other normal submodules.
II. DESIGN OF ±400MVAR STATCOM
As mentioned above, since the ±134Mvar MMC has 4
A. Single line diagram redundancy submodules per phase, it can continue its normal
operation with 4 faulted submodules per phase. If the 5th
Fig. 2 shows the single line diagram of the ±400Mvar submodule is bypassed within a MMC phase circuit, the
STATCOMs. The ±400Mvar STATCOM mainly comprises HV(high voltage circuit breaker) will be immediately opened.
of coupling transformers, MV bus, 3 x ±134Mvar MMCs, After opening the disconnector switch at the faulted MMC,
control & protection systems, auxiliary equipment, and so on. the STATCOM in Fig. 1 can be restarted and operated with
The MV bus voltage level is chosen to optimize the proposed only 2 or 1 x ±134Mvar MMCs.
solution which meets the requirements specified by KEPCO.

Fig. 4. Example layout of ±400Mvar STATCOM in Shinyoungju 345kV


substation.
Fig. 2. Single line diagram of ±400Mvar STATCOM

Fig. 3. Single line diagram of ±134Mvar MMC(Modular Multilevel


Converter)

In the STATCOM, 3 x ±134Mvar MMCs are connected


to 353kV(345kV) 3-phase bus through Y-Δ connected 3
single phase coupling transformer. As shown in Fig. 3, the
±134Mvar MMC consists of Δ-connected 3-phase MMC Fig. 5. Bird-eye view of ±400Mvar STATCOM in Shinyoungju 345kV
circuits, and each MMC phase circuit has a MMC valve substation.
being composed of series-connected 42 full-bridge
submodules, including 4 redundancies, whose rated DC B. Layout design
voltage is 2.5kVdc, and a phase reactor.
Fig. 4 shows the layout of ±400Mvar STATCOM in
Due to low THD characteristics of MMC, any harmonic Shinyoungju 345kV substation. Its footprint is just 100.8m x
or HF(High Frequency) filter is not required to the MV side 44.55m. Comparing to the layout of SVC having similar
of coupling transformers. capacity, it must be proved that the footprint of STATCOM
is much smaller than SVC.

2061
Each ±134Mvar MMC value room and its cooling room III. TEST RESULTS
are designed in independently from other MMCs. In addition, Fig. 7 shows the actual TFR(Transient Fault Recorder)
the AC yard component of each ±134Mvar MMC are also data measured for SAT(Site Acceptance Test) of
designed to be capable of being managed separated from Shinyoungju ±400Mvar STATCOM. It shows the step
other MMCs. Therefore, each MMC can be repaired and response of STATCOM output under automatic voltage
overhauled when other MMCs are being operated. control mode.
Fig. 5 shows the actual bird-eye shot of ±400Mvar At steady-condition, the voltage reference of STATCOM
STATCOM in Shinyoungju 345kV substation. Comparing to is set to Vref=0.99pu in order to make 0Mvar output. And
the similar picture of SVC, it must be also proved that the then, the voltage reference is changed to 1.1pu in
configuration of STATCOM is much more simple and step(Vref=0.99puÆ1.1pu). At that time, the current output of
compact than SVC. STATCOM is increased up to 1.0pu from 0.0pu within
11.7msec. It is just around 70% of 1 cycle(=1/60
C. Control fuctions sec=16.7msec).
The ±400Mvar STATCOM has control functions as
follows, The step response test from inductive to capacitive limit
could not be done because the 800Mvar reactive power could
x Mandatory functions give significant shock to power system.
- Automatic voltage control
- Reactive power control
x Auxiliary functions
- Power oscillation damping
- External device control
- Adaptive gain control
It is specified that the response time of STATCOM
output under automatic voltage control mode to the step
input of voltage change has to be equal to or less than 1 cycle
from inductive to capacitive limits or vice versa.
The ±400Mvar STATCOM has very excellent fault ride
though capability. It is designed to be capable of supplying
rated capacitive current output down to 0.3pu power system
voltage. In addition, it can supply symmetric rated capacitive
current output under single-line-to-ground fault condition.

D. Harmonic performance
As mentioned above, the ±134Mvar MMC is composed
of 42 full-bridge submodules including 4 redundancies per
phase. Fig. 7. The response of STATCOM under automatic voltage control mode
(353kV PCC voltage, the current output to 353kV PCC, the RMS
value of current output, and reference voltage.)

Fig. 8 shows the RTDS test results for FAT(Factory


Acceptance Test) of control system of Shinyoungju
±400Mvar STATCOM. It shows the response of STATCOM
to single-line-to-ground fault condition at primary side of
coupling transformer.
At steady-state, the voltage reference of STATCOM is
set to Vref=1.0pu in order to make 0Mvar output. And then,
single-phase-ground fault is applied at phase A of 353kV
PCC(Point of Common Coupling). At that time, the voltage
Fig. 6. Schematic representation of AC output voltage of MMC valve at phase A becomes close to zero. It means that the positive
sequence voltage of 353kV PCC becomes around 0.667pu.
Since each full-bridge submodules can make positive, In order to support the positive sequence voltage component,
zero, and negative DC capacitor voltage between its 2 the STATCOM generates symmetric capacitive current
terminals and the MMC valve generates AC sinusoidal output.
voltage by connecting individual submodule voltage outputs.
Therefore, its output voltage can have 77-levels in maximum Fig. 9 shows the measured harmonic voltage for 8 hours at
from positive to negative peaks. Although it generates rated 353kV PCC for SAT(Site Acceptance Test) of Shinyoungju
inductive output at 0.9pu power system voltage, it is ±400Mvar STATCOM. For 8 hours, the ±400Mvar
expected that the output voltage have 39-levels. STATCOM was operated with rated inductive output.
Unfortunately, the background harmonic could not be
As shown in Fig. 6, the output voltage is very close to measured. It means that the harmonic voltage in Fig. 9 shows
AC sinusoidal voltage. Therefore, the harmonic
performance of ±400Mvar STATCOM is also very excellent.

2062
the sum of background harmonic and the harmonic be less than 0.5%, assuming the background harmonic is
contributions by ±400Mvar STATCOM. zero.
The v-THD=0.7% and V5=0.5% meet the harmonic
requirement in IEEE Std. 519 [3] specified by KEPCO,
without any harmonic filters.

Fig. 9. Meausred voltage harmnoic distortions (THD and individual)

IV. CONCLUSION
As noticed to public, the STATCOM has many technical
advantages superiors to SVC. Those are very fast response
time, excellent output capability under low voltage condition
and very weak system having extremely low short circuit
level, smaller foot print, extremely low harmonic generation,
and so on. As show in this paper, the large scale STATCOM
up to ±400Mvar rating becomes applicable in power system.
The test results also prove that STATCOM has better
configuration, dynamic performance, and harmonic
Fig. 8. The response of STATCOM to single-line-to-ground fault (353kV
characteristics
PCC voltage, the current measured at 353kV PCC, the MV bus
voltage, the current output to MV bus, and the current output to
MMC#1) REFERENCES
[1] CIGRE WG 14.19, "Static Synchronous Compensator," Brochure 144,
The upper graph in Fig. 9, the voltage THD(total harmonic Aug. 1999.
distortion) up to 50th was measured between 0.4% and 0.7%. [2] M. Pereira, D. Retzmann, J. Lottes, M. Wiesinger, G. Wong, "SVC
It means that the harmonic contribution by ±400Mvar PLUS: AN MMC STATCOM for Network and Grid Access
STATCOM must be less than 0.7%, assuming the Applications", Proc. IEEE Trondheim PowerTech, pp. 1-5, 2011.
background harmonic is zero. The lower graph in Fig. 9 [3] IEEE Std 519-1992, “IEEE Recommended Practices and
shows the maximum(Orange), average(Grey), and Requirements for Harmonic Control in Electrical Power Systems,”
minimum(Blue) individual harmonic voltages measured for 8 Institute of Electrical and Electronics Engineers, Inc. 1993
hours. The maximum component is 5th harmonic voltage
and it is less than 5%. It means that the maximum harmonic
voltage component induced by ±400Mvar STATCOM must

2063