AREA [m²] = (W [m] * H [m]) + {(DIA [m]/2)² * PI}, ASSUMING ZERO ENTRY FOR EITHER W & H <OR> DIA.

VELOCITY [m/s] = FLOW [m³/s] / AREA [m²]

VELOCITY HEAD [Pa] = DENSITY [kg/m³] * {VELOCITY [m/s]²} / 2

HYDRAULIC DIAMETER [m] = 2 * HEIGHT * WIDTH / (HEIGHT + WIDTH) <OR> DIA

SEGMENT LOSS [Pa] = (1 + CONTINGENCY) * { (QTY * VEL HEAD [Pa] * FITTING COEFF) + (VEL HEAD [Pa] * DUCT L [m] * FRICTION FACT / HYDRAULIC DIA [m] ) }

PROJECT: S07 STATION VENT. CAL. (CRITICAL CASE, EXCEPT FAN) BY:

SYSTEM: S07/TVF FANS CHECK:


CALCULATIONS PERFORMED FOR AIR DENSITY: 1.200 kg/m³ VALUES DISPLAYED ROUNDED TO DIGITS SHOWN
CONTINGENCY, INCLUDED IN EACH SEGMENT LOSS: 15% FAN CAPACITY 200.0 m³/s
SEGM. ITEM QTY DIMENSIONS AREA FLOW VELOCITY VELOCITY FITTING DUCT HYDRAULIC FRICTION SEGMENT
NO. TYPE W H DIA A Q V HEAD COEFF. LENGTH DIAMETER FACTOR LOSS
[m] [m] [m] [m²] [m³/s] [m/s] [Pa] z [m] Dh [m] l [Pa]
1 entrance 1 5.40 4.00 21.60 200.00 9.26 51.44 0.50 4.60 29.58
2 screen 1 5.40 4.00 21.60 200.00 9.26 51.44 0.91 4.60 53.83
3 concrete Duct 1 5.40 4.00 21.60 200.00 9.26 51.44 5.20 4.60 0.02 1.34
4 sudden expansion 1 8.00 5.60 44.80 200.00 4.46 11.96 0.38 6.59 5.23
5 90° return 1 8.00 5.60 44.80 200.00 4.46 11.96 1.70 6.59 23.38
6 concrete Duct 1 8.00 5.60 44.80 200.00 4.46 11.96 12.00 6.59 0.02 0.50
7 90° return 1 8.00 5.60 44.80 200.00 4.46 11.96 1.70 6.59 23.38
8 concrete Duct 1 8.00 5.60 44.80 200.00 4.46 11.96 28.00 6.59 0.02 1.17
9 90° return 1 7.60 5.60 42.56 200.00 4.70 13.25 1.70 6.45 25.90
10 sudden contraction 1 4.50 4.50 20.25 200.00 9.88 58.53 0.20 4.50 13.46
11 concrete Duct 1 4.50 4.50 20.25 200.00 9.88 58.53 0.50 4.50 0.02 0.15
12 sudden expansion 1 6.00 5.10 30.60 200.00 6.54 25.63 0.38 5.51 11.20
13 90° return 1 6.00 5.10 30.60 100.00 3.27 6.41 1.70 5.51 12.53
14 concrete Duct 1 6.00 5.10 30.60 100.00 3.27 6.41 15.00 5.51 0.02 0.40
15 90° return 1 6.00 5.10 30.60 100.00 3.27 6.41 1.70 5.51 12.53
16 fan damper 1 2.80 2.80 7.84 100.00 12.76 97.62 0.37 2.80 41.54
attenuator, splitter type 1 2.80 2.80 7.84 100.00 12.76 97.62 2.80 0.00
17 (from manufacturer data)
18 transition, square to round 2 2.00 3.14 100.00 31.83 607.92 0.11 2.00 153.80
attenuator, splitter type 1 2.80 2.80 7.84 100.00 12.76 97.62 2.80 0.00
19 (from manufacturer data)
20 fan damper 1 2.80 2.80 7.84 100.00 12.76 97.62 0.37 2.80 41.54
21 sudden expansion 1 7.60 5.00 38.00 200.00 5.26 16.62 0.38 6.03 7.26
22 concrete Duct 1 8.25 5.00 41.25 200.00 4.85 14.10 7.60 6.23 0.02 0.40
23 sudden contraction 1 5.60 3.60 20.16 200.00 9.92 59.05 0.20 4.38 13.58
24 exit 1 5.60 3.60 20.16 200.00 9.92 59.05 1.00 4.38 67.91
total 540.60