Professional Documents
Culture Documents
Preface............................................................................................................................................... 3
Features of Hitachi Centrifugal Chillers ........................................................................................... 3
1. Scope of supply ........................................................................................................................... 7
2. Standard specification ................................................................................................................. 9
2.1 HC-F-GSG-S Series Chillers Specifications ............................................................................... 9
2.2 HC-F-GXG-S Series Chillers Specifications ............................................................................ 12
2.3 HC-F-GFG-S Series Chillers Specifications ............................................................................. 15
2.4 Electrical data .................................................................................................................................. 18
3. Structure of Standard Type of Chillers ..................................................................................... 20
4. Characteristics Data .................................................................................................................. 20
4.1 Control Characteristic .................................................................................................................... 20
4.1.1 Capacity control characteristic ..................................................................................... 20
4.1.2 Temperature Control Characteristic............................................................................. 21
4.2 Motor characteristic........................................................................................................................ 23
4.2.1 Starting current characteristic ....................................................................................... 23
4.3 Vibration ........................................................................................................................................... 24
4.3.1 Vibration value ................................................................................................................. 25
4.3.2 Measured vibration value (take HC-F500GSG-S for example) ............................ 25
5. Operation Control ..................................................................................................................... 26
5.1 Operating control mode ................................................................................................................. 26
5.2 Safety and protection control device .......................................................................................... 30
5.3 Interlocked Operation with Auxiliary Equipment
(pump, cooling tower fan) (see wiring diagram for wiring method). .................................. 32
5.4 Electric Cabinet Wiring Diagram of Centrifugal Chillers ...................................................... 33
5.5 Electric cabinet showing ............................................................................................................... 33
6. Starting box ............................................................................................................................... 37
7. Main Components & Main Optional Function ......................................................................... 38
7.1 System Loop Diagram ................................................................................................................... 38
7.2 Compressor and Motor .................................................................................................................. 38
7.3 Heat exchanger ................................................................................................................................ 39
7.4 Main Optional Function ................................................................................................................ 39
7.4.1 Cooling Capacity Lower Limit 10% (Optional) ....................................................... 39
7.4.2 High Temperature Differential Technology (Optional) ........................................... 40
7.4.3 Variable Flow Rate Control of Chilled Water/Cooling Water (Optional) ............ 40
7.4.4 Heat Recovery System (Expanded Function) ............................................................ 40
1 Z0031524-2016-A
7.4.5 Hot Pump Application (Expanded Function) ............................................................ 41
7.4.6 Cool Storage System (Expanded Function) ............................................................... 42
7.4.7 VFD System (Expanded Function) .............................................................................. 42
8. Main Inspection Items and Instructions of Centrifugal Chillers ............................................... 43
9. Precautions for Equipment Design ........................................................................................... 44
9.1 Machine Room and Safety Devices ............................................................................................ 44
9.2 Precautions for Chillers Operation .............................................................................................. 44
9.2.1 Winter Operations ........................................................................................................... 44
9.2.2 Standard Operating Range of Chillers ........................................................................ 44
9.2.3 Other precautions ............................................................................................................ 45
9.3 Low Load Operation ...................................................................................................................... 45
9.3.1 Hot Gas Bypass Control................................................................................................. 45
9.4 Vibration-Proof, Earthquake Resistance .................................................................................... 45
9.4.1 Vibration-Proof Efficiency ............................................................................................ 45
9.4.2 Earthquake Resistance .................................................................................................... 46
9.5 Variable Flow Rate Control (Optional) ...................................................................................... 46
9.5.1 Variable Flow Rate Control of Cooling Water .......................................................... 46
9.5.2 Variable Flow Rate Control of Chilled Water............................................................ 47
9.6 Group Control (Optional).............................................................................................................. 47
10. Safety Precautions on Construction Work ................................................................................ 47
10.1 Carrying-In Work ............................................................................................................................ 47
10.2 Installation project .......................................................................................................................... 48
10.3 Water Piping Work.......................................................................................................................... 48
10.4 Electrical Wiring Work .................................................................................................................. 49
11. Information ............................................................................................................................... 49
11.1 Refrigerant Properties .................................................................................................................... 49
11.2. Lubricant ........................................................................................................................................... 51
11.3 Maintenance & Inspection Checklist .......................................................................................... 51
11.4 Water Quality Control .................................................................................................................... 52
2 Z0031524-2016-A
Preface
Since its founding in 1910, Hitachi has been providing people with colorful life, and enterprises and public
institutions with reliable, safe, high valued-added products and services through development of superior, original
technology and products.
In 1932, Hitachi started making its first centrifugal chillers, achieving remarkable performance and rich experiences
of more than 80 years. Early in 1993, Hitachi introduced the centrifugal chillers featuring environmentally friendly
HFC-134a refrigerant having an ozone depletion potential of zero in order to protect our earth and achieve social
sustainability. Since its launching, Hitachi centrifuges have been winning trusts from customers around the world,
providing now more than 6,000 units for our clients in total.
In 2006, Air-Conditioning & Refrigerating Products (Guangzhou) Co., Ltd introduced the whole series of products
drawings and production technology of Japanese Hitachi centrifugal chillers and launched three series of products
HC-F-GSG-S, HC-F-GXG-S and HC-F-GXG-S using environmentally friendly HFC-134a refrigerant, indicating a
start for producing Hitachi centrifugal chillers in China.
The technical specification summarizes various data of two series of products for your reference during product
design and type selection.
3 Z0031524-2016-A
☆ 2 Our rich experiences in design and R&D and quality-oriented concept make Hitachi centrifugal chillers
become a leader in the industry!
1st stage impeller 2nd stage impeller
(1) Hitachi High-Efficiency Centrifugal Compressor
Leaflet
Vaned diffuser
For the diffuser, which is used to convert the
velocity of refrigerant gas accelerated by the
impeller into static pressure, vanes of small
chord-pitch ratio and a high pressure recovery ratio
were developed by computer design to realize high
efficiency. The ideal diffuser shape, which is
implemented by NC machines, realizes stable
operation in a wide range from high to low load
conditions.
Low specific speed compressor enables the use of low-loss bearing structure
Due to the employed 2-stage compression system, the speed of the compressor can be lowered, which results in
reducing bearing loss.
4 Z0031524-2016-A
☆3 Stability
(1) Adopting strict criteria specified in JIS on partial load and 3D 2-stage impeller enable stable operation even at
low cooling load or high cooling water temperature which prevents occurrence of surge, ensuring high
reliability of chillers.
(2) Chillers are equipped with surge protection device to ensure chillers will not be damaged under abnormal
situations.
(3) More than 80 years of rich experiences and continuous improvement of powerful control systems ensure
reliable operation of chillers.
☆5 10.4 inch color touch panel, displayed in Chinese (English and Japanese are available), is easy to
operate.
Control center is fully composed of 10.4 inch color LCD
touch panel screens with a tidy and clear look.
Colorful touch panel screen increases convenience of
identification; and makes operations easy and fast.
Display simple process and various operating data of chillers
Control various settings and conditions of chillers.
Set up 3 level access control based on different requirements
of manufacturer’s settings, maintenance provided by customer
service center and use of customers.
5 Z0031524-2016-A
(1) Display information
Control center conducts continuous monitoring on operation of system, display and record chillers’ operation
situation, warning and failure information. Buzzer on control cabinet will also sound when failure or alarming
occurs.
Find out possible causes and solutions on touch panel screen when chillers are stopped due to failure. Customers
may identify the causes of troubles in a shorter time in accordance with possible causes and corresponding solutions
we provided and solve problems rapidly, providing convenience to customers and maintenance persons.
6 Z0031524-2016-A
1. Scope of supply
Item Scope Specifications
Closed centrifugal 2-stage compressor, capacity control device, step-up gear and
Compressor ○
built-in oil supply device
Semi-closed squirrel cage asynchronous motor cooled by refrigerant Insulation grade:
Main motor ○
Grade F
Oil supply device ○ Trochoid rotor oil pump, oil cooler cooled by refrigerant, oil strain.
Heat exchanger ○ Horizontal shell and tube, copper tube (high-efficiency tube), flanged water pipe
Low oil Main motor
Chilled water
supply coil high Control sensor abnormality
suspended
pressure temperature
High oil Main motor
Chilled water Low oil tank CPU
supply restart
overcooled temperature abnormal
temperature restriction
Protective device ○
Capacity
Low evaporating Oil pump Starter panel Surge
control valve
pressure overloaded abnormal protection
fully closed
Abnormality
High condensing Motor Starting time
connection of Safety valve
pressure overloaded is too long
pump
External control Remote start & stop: water pump interlock control; set up remotely chilled water outlet
○
junction temperature; set up remotely load limit value; water pump interlock control
1. external monitoring Operation and failure status; valve opening degree display; main motor current
○
Machine portal display; chilled water outlet temperature
Electric cabinet ○ Installed on chillers, indoor, non-Ex type.
Starting box ○ Installed separately, indoor, non-Ex type.
○ Lubricant and refrigerant (initial charge amount)
Accessories Vibration-proof rubber (wave-shaped rubber with vibration transmission rate of
○
approx. 25%).
○ Oil strainer and sealing gasket.
Prepared Parts
○ Desaturator.
△ Power source: AC380V/3kV/6kV/10kV, 50Hz, 3Φ. (380V:1400RT or lower)
△ Starter panel breaker.
Evaporator/condenser water side pressure: standard pressure of 1.0MPa, 1.6MPa and
△
2.0MP are available.
Optional items and △ Cooling water suspension relay.
special
△ Cooling capacity can be controlled as low as 10%. (Standard control value: 20%)
correspondence
△ Heat recovery system.
△ Hot pump application.
△ Cool storage system.
△ VFD System.
All chillers are subject to test for commercial use. Performance test is done for samples
Plant delivery test ○
2. from batches.
Test Plant acceptance
☆ One of the chillers is chosen for test.
functional test
Main body ○ Grey.
Electric cabinet
3. ○ Munsell color code 5Y 8/1 high gloss.
(inside/outside)
Painting
Starter panel
○ Munsell color code 5Y 7/1 semi gloss.
(inside/outside)
7 Z0031524-2016-A
Item Scope Specifications
Transport and
○ Transport the unit from our factory to site (Free On Truck) as a whole.
handling
Carrying-in × Unload the main body of chillers and starter panel and pull transversely
Installation × Assemble the main body of chillers and find out center point.
Foundation
× Conduct foundation mortar construction for the main body of chillers and starter panel.
construction
Assembly ☆ Reassemble chillers when carrying in knockdown form excluding lifting.
Cold insulation ○ Cold insulation work on main body of chillers.
External pipework of chillers, companion flange connection and wiring for chilled
Piping engineering ×
water, cooling water and safety valve.
× Starter panel ~ main motor and electric cabinet.
4.
Secondary electrical × Monitoring electric cabinet ~ electric cabinet.
Project
wiring work × Interlock wiring with other machines.
× Grounding work
Primary electrical
× Electrical wiring and grounding work from starter panel to electric cabinet.
wiring work
Temperature control × Cooling water temperature control
Site commissioning ○ Commissioning and adjustment (power and water shall be supplied free of charge).
Operation instructions ○ Once.
Overall
commissioning for ×
acceptance
Free service ○ Warranty period
※ Note: (○) scope of supply (×) out of supply scope (△ ) standard scope of supply (☆ ) special optional items
8 Z0031524-2016-A
2. Standard specification
2.1 HC-F-GSG-S Series Chillers Specifications
USRT 300 350 400 450 500 550 600 650 700 750
Refrigerating capacity
kW 1055 1231 1407 1582 1758 1934 2110 2286 2461 2637
Flow m3/h 182 212 242 273 303 333 363 394 424 454
number of passes - 2 2 2 2 2 2 2 2 2 2
Flow m3/h 224 261 298 335 372 410 447 476 513 549
Number of passes - 2 2 2 2 2 2 2 2 2 2
Electrical machine 380V kW 208 242 270 301 320 351 382 410 443 473
input power 10kV kW — — — — — — — — — —
380V mm 2750 2800 2800 3250 3250 3250 3250 3500 3500 3500
Length
10kV mm — — — — — — — — — —
Outline Width mm 1900 2000 2000 2100 2100 2100 2100 2350 2350 2350
Dimension
Height mm 2350 2350 2350 2500 2500 2500 2500 2700 2700 2700
Size of pulling
mm 2000 2000 2000 2500 2500 2500 2500 2800 2800 2800
tubes
Shipping 380V 5.5 6.8 6.9 8.4 8.5 8.6 8.8 10.2 10.3 10.4
t
Wt. 10kV — — — — — — — — — —
Weight
Operating 380V 6.7 7.5 7.6 9.3 9.4 9.5 9.8 11.6 11.7 11.8
t
wt. 10kV — — — — — — — — — —
380V - 5.06 5.09 5.22 5.25 5.50 5.51 5.52 5.57 5.56 5.57
COP
10kV - — — — — — — — — — —
Insulating area m2 19 20 20 22 22 22 24 24 24 26
1. For type selections, chilled water inlet/outlet temperature is 7/12℃, cooling water inlet/outlet temperature is
32/37℃.
2. We provide you with specific type selection based on your cooling capacities and operational conditions.
3. The table is applicable to chillers manufactured for normal water. If seawater and brine are necessary, please
contact us.
4. Capacity control range is 100% to approx. 20%
5. Operating voltage: AC 380V/50Hz/3φ/4W
Capacity: 3.0kVA 300~400RT / 5.0kVA 450~2000RT
6. Working pressure is 1.0MPa for both chilled and cooling water; If higher maximum working pressure is
required, please specify during inquiry (It is possible to produce up to 2.0MPa).
7. For water piping connections, see the dimensional outline drawing.
9 Z0031524-2016-A
(Continued)
USRT 800 850 900 950 1000 1050 1100 1150 1200 1250
Refrigerating capacity
kW 2813 2989 3165 3340 3516 3692 3868 4044 4220 4395
Flow m3/h 484 515 545 575 605 636 666 696 726 756
Chilled Pressure loss kPa 99 100 100 108 108 107 108 108 108 108
water Interface dimension DN 250 250 300 300 300 300 300 300 300 300
Number of passes - 2 2 2 2 2 2 2 2 2 2
Flow m3/h 581 617 654 696 732 769 805 842 879 915
Cooling Pressure loss kPa 90 90 90 110 110 110 110 110 110 110
water Interface dimension DN 300 300 300 300 350 350 350 350 350 350
Number of passes - 2 2 2 2 2 2 2 2 2 2
Electrical machine input 380V kW 484 511 540 582 613 667 692 719 745 667
power 10kV kW 487 514 544 586 615 670 697 723 750 670
380V mm 3500 3500 3500 3750 3750 3750 3750 3750 3750 3750
Length
10kV mm 3700 3700 3700 3950 3950 3950 3950 3950 3950 3950
Outline
Width mm 2450 2450 2450 2450 2450 2450 2650 2650 2650 2650
Dimension
Height mm 2800 2800 2800 2800 2800 2800 2950 2950 2950 2950
Size of pulling tubes mm 2800 2800 2800 3000 3000 3000 3000 3000 3000 3000
Shipping 380V 11.5 11.6 11.7 12.2 12.3 12.4 13.2 13.3 13.4 13.5
t
Wt. 10kV 11.8 11.9 12 12.5 12.6 12.7 13.5 13.6 13.7 13.8
Weight
Operating 380V 13 13.2 13.3 14.2 14.3 14.5 15.3 15.4 15.5 15.6
t
wt. 10kV 13.3 13.5 13.6 14.5 14.6 14.8 15.6 15.7 15.8 15.9
380V - 5.81 5.85 5.86 5.74 5.74 5.80 5.84 5.87 5.90 5.80
COP
10kV - 5.78 5.81 5.82 5.70 5.72 5.77 5.80 5.84 5.86 5.77
Insulating area m2 26 26 28 28 28 28 30 30 30 30
1. For type selections, chilled water inlet/outlet temperature is 7/12℃, cooling water inlet/outlet temperature is
32/37℃.
2. We provide you with specific type selection based on your cooling capacities and operational conditions.
3. The table is applicable to chillers manufactured for normal water. If seawater and brine are necessary, please
contact us.
4. Capacity control range is 100% to approx. 20%
5. Operating voltage: AC 380V/50Hz/3φ/4W
Capacity: 3.0kVA 300~400RT / 5.0kVA 450~2000RT
6. Working pressure is 1.0MPa for both chilled and cooling water; If higher maximum working pressure is
required, please specify during inquiry (It is possible to produce up to 2.0MPa).
7. For water piping connections, see the dimensional outline drawing.
10 Z0031524-2016-A
(Continued)
USRT 1300 1350 1400 1450 1500 1600 1700 1800 1900 2000
Refrigerating capacity
kW 4571 4747 4923 5099 5274 5626 5978 6329 6681 7033
Flow m3/h 817 847 877 908 968 1029 1089 1150 1210 817
Pressure loss kPa 124 124 124 124 128 128 129 128 129 124
Chilled
water Interface
DN 350 350 350 350 400 400 400 400 400 350
dimension
Number of passes - 2 2 2 2 2 2 2 2 2 2
Flow m3/h 988 1025 1062 1098 1171 1245 1318 1391 1464 988
Pressure loss kPa 111 111 111 112 109 109 110 110 110 111
Cooling
water Interface
DN 400 400 400 400 400 400 450 450 450 400
dimension
Number of passes - 2 2 2 2 2 2 2 2 2 2
380V mm — — — — — — — — — —
Length
10kV mm 4700 4700 4700 4700 4700 5000 5000 5000 5000 5000
Outline Width mm 3300 3300 3300 3300 3300 3500 3500 3500 3500 3500
Dimension
Height mm 3400 3400 3400 3400 3400 3700 3700 3700 3700 3700
Size of pulling
mm 3500 3500 3500 3500 3500 4000 4000 4000 4000 4000
tubes
Shipping 380V — — — — — — — — — —
t
Wt. 10kV 18.6 18.7 18.8 18.9 19 21 21.2 21.5 21.7 22
Weight
Operating 380V — — — — — — — — — —
t
wt. 10kV 21.6 21.7 21.8 22 22.1 24.7 25 25.4 25.7 26
380V - — — — — — — — — — —
COP
10kV - 6.02 6.02 6.03 6.03 6.03 6.03 6.04 6.04 6.05 6.05
Insulating area m2 38 38 38 38 38 45 45 45 45 45
1. For type selections, chilled water inlet/outlet temperature is 7/12℃, cooling water inlet/outlet temperature is
32/37℃.
2. We provide you with specific type selection based on your cooling capacities and operational conditions.
3. The table is applicable to chillers manufactured for normal water. If seawater and brine are necessary, please
contact us.
4. Capacity control range is 100% to approx. 20%
5. Operating voltage: AC 380V/50Hz/3φ/4W
Capacity: 3.0kVA 300~400RT / 5.0kVA 450~2000RT
6. Working pressure is 1.0MPa for both chilled and cooling water; If higher maximum working pressure is
required, please specify during inquiry (It is possible to produce up to 2.0MPa).
7. For water piping connections, see the dimensional outline drawing.
11 Z0031524-2016-A
2.2 HC-F-GXG-S Series Chillers Specifications
USRT 300 350 400 450 500 550 600 650 700 750
Refrigerating capacity
kW 1055 1231 1407 1582 1758 1934 2110 2286 2461 2637
Power Source AC380V/50Hz 3 phrase ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Power Source AC10kV/50Hz 3 phrase — — — — — — — — — —
Flow m3/h 182 212 242 273 303 333 363 394 424 454
Flow m3/h 215 251 286 322 354 389 424 460 496 530
Electrical machine 380V kW 185 215 240 270 292 320 348 377 407 434
input power 10kV kW — — — — — — — — — —
380V mm 3550 3550 3550 3550 4050 4050 4050 4050 4050 4050
Length
10kV mm — — — — — — — — — —
Outline Width mm 1650 1650 1900 1900 1900 2000 2000 2000 2250 2250
Dimension
Height mm 2200 2200 2400 2400 2450 2500 2500 2500 2650 2650
size of pulling
mm 2400 2400 3500 3500 3500 3500 3500 3500 3500 3500
tubes
Shipping 380V 5.8 5.8 7.0 7.0 8.4 8.7 8.9 9.1 10.7 10.7
t
Wt. 10kV — — — — — — — — — —
Weight
Operating 380V 7.0 7.1 8.5 8.6 9.9 10.4 10.5 10.9 12.6 12.7
t
wt. 10kV — — — — — — — — — —
380V - 5.70 5.72 5.86 5.87 6.03 6.05 6.06 6.07 6.05 6.07
COP
10kV - — — — — — — — — — —
Insulating area m2 18 18 20 20 22 24 24 24 27 27
1. For type selections, chilled water inlet/outlet temperature is 7/12℃, cooling water inlet/outlet temperature is
32/37℃.
2. We provide you with specific type selection based on your cooling capacities and operational conditions.
3. The table is applicable to chillers manufactured for normal water. If seawater and brine are necessary, please
contact us.
4. Capacity control range is 100% to approx. 20%
5. Operating voltage: AC 380V/50Hz/3φ/4W
Capacity: 3.0kVA 300~400RT / 5.0kVA 450~2000RT
6. Working pressure is 1.0MPa for both chilled and cooling water; If higher maximum working pressure is
required, please specify during inquiry (It is possible to produce up to 2.0MPa).
7. For water piping connections, see the dimensional outline drawing.
12 Z0031524-2016-A
(Continued)
USRT 800 850 900 950 1000 1050 1100 1150 1200 1250
Refrigerating capacity
kW 2813 2989 3165 3340 3516 3692 3868 4044 4220 4395
Power Source AC380V/50Hz 3 phrase ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Power Source AC10kV/50Hz 3 phrase — ○ ○ ○ ○ ○ ○ ○ ○ ○
Flow m3/h 484 515 545 575 605 636 666 696 726 756
Pressure loss kPa 103 114 105 114 120 131 122 131 108 116
Chilled
water Interface
DN 250 250 300 300 300 300 300 300 300 300
dimension
Number of passes - 2 2 2 2 2 2 2 2 2 2
Flow m3/h 564 602 636 672 704 741 776 811 845 880
Electrical machine 380V kW 463 494 523 550 579 608 639 667 696 725
input power 10kV kW — 523 550 579 523 608 639 667 696 725
380V mm 4050 4050 4050 4050 4550 4550 4550 4550 4550 4550
Length
10kV mm — 4150 4150 4150 4750 4750 4750 4750 4750 4750
Outline Width mm 2250 2400 2400 2400 2400 2600 2600 2600 2600 2600
Dimension
Height mm 2650 2800 2800 2800 2800 2900 2900 2900 2900 2900
Size of pulling
mm 3500 3500 3500 3500 4000 4000 4000 4000 4000 4000
tubes
Shipping 380V 11.1 12.2 12.4 12.4 13.9 14.6 14.8 14.8 15.8 15.8
t
Wt. 10kV — 12.5 12.7 12.7 14.2 14.9 15.1 15.1 16.1 16.1
Weight
Operating 380V 13.3 14.5 14.8 14.9 16.9 17.7 18.0 18.1 19.1 19.2
t
wt. 10kV — 14.8 15.1 15.2 17.2 18.0 18.3 18.4 19.4 19.5
380V - 6.07 6.05 6.05 6.07 6.07 6.07 6.05 6.06 6.06 6.06
COP
10kV - — 6.05 6.07 6.07 6.05 6.07 6.05 6.06 6.06 6.06
Insulating area m2 27 28 28 28 31 33 33 33 33 33
1. For type selections, chilled water inlet/outlet temperature is 7/12℃, cooling water inlet/outlet temperature is
32/37℃.
2. We provide you with specific type selection based on your cooling capacities and operational conditions.
3. The table is applicable to chillers manufactured for normal water. If seawater and brine are necessary, please
contact us.
4. Capacity control range is 100% to approx. 20%
5. Operating voltage: AC 380V/50Hz/3φ/4W
Capacity: 3.0kVA 300~400RT / 5.0kVA 450~2000RT
6. Working pressure is 1.0MPa for both chilled and cooling water; If higher maximum working pressure is
required, please specify during inquiry (It is possible to produce up to 2.0MPa).
7. For water piping connections, see the dimensional outline drawing.
13 Z0031524-2016-A
(Continued)
USRT 1300 1350 1400 1500 1600 1700 1800 1900 2000
Refrigerating capacity
kW 4571 4747 4923 5274 5626 5978 6329 6681 7033
Power Source AC380V/50Hz 3 phrase ○ ○ ○ — — — — — —
Power Source AC10kV/50Hz 3 phrase ○ ○ ○ ○ ○ ○ ○ ○ ○
Flow m3/h 787 817 847 908 968 1029 1089 1150 1210
Chilled Pressure loss kPa 124 132 140 127 127 132 131 133 134
water Interface dimension DN 350 350 350 400 400 400 400 400 400
Number of passes - 2 2 2 2 2 2 2 2 2
Flow m3/h 915 950 984 1058 1128 1200 1269 1339 1407
Cooling Pressure loss kPa 103 110 117 105 107 109 109 108 110
water Interface dimension DN 400 400 400 400 400 400 450 450 450
Number of passes - 2 2 2 2 2 2 2 2 2
Insulating area m2 33 35 35 40 40 47 47 48 48
1. For type selections, chilled water inlet/outlet temperature is 7/12℃, cooling water inlet/outlet temperature is
32/37℃.
2. We provide you with specific type selection based on your cooling capacities and operational conditions.
3. The table is applicable to chillers manufactured for normal water. If seawater and brine are necessary, please
contact us.
4. Capacity control range is 100% to approx. 20%
5. Operating voltage: AC 380V/50Hz/3φ/4W
Capacity: 3.0kVA 300~400RT / 5.0kVA 450~2000RT
6. Working pressure is 1.0MPa for both chilled and cooling water; If higher maximum working pressure is
required, please specify during inquiry (It is possible to produce up to 2.0MPa).
7. For water piping connections, see the dimensional outline drawing.
14 Z0031524-2016-A
2.3 HC-F-GFG-S Series Chillers Specifications
USRT 300 350 400 450 500 550 600 650 700 750
Refrigerating capacity
kW 1055 1231 1407 1582 1758 1934 2110 2286 2461 2637
Flow m3/h 182 212 242 273 303 333 363 394 424 454
Chilled Pressure loss kPa 87 113 103 127 93 109 97 112 101 113
water Interface dimension DN 150 200 200 200 200 200 250 250 250 250
Number of passes - 2 2 2 2 2 2 2 2 2 2
Flow m3/h 213 248 283 318 353 388 423 458 494 529
Number of passes - 2 2 2 2 2 2 2 2 2 2
Electrical machine 380V kW 174 202 230 258 283 310 336 363 394 421
input power 10kV kW — — — — — — — — — —
380V mm 4050 4050 4550 4550 4550 4550 4550 4550 4550 4550
Length
10kV mm — — — — — — — — — —
Outline Width mm 1650 1650 1900 1900 2000 2000 2000 2000 2250 2250
Dimension
Height mm 2200 2200 2400 2400 2500 2500 2500 2500 2650 2650
Size of pulling
mm 3500 3500 4000 4000 4000 4000 4000 4000 4000 4000
tubes
Shipping 380V 6 6 7.6 7.6 9.1 9.1 9.3 9.3 11.2 11.2
t
Wt. 10kV — — — — — — — — — —
Weight
Operating 380V 7.4 7.5 9.4 9.5 10.9 11 11.2 11.4 13.3 13.4
t
wt. 10kV — — — — — — — — — —
380V - 6.06 6.10 6.11 6.13 6.21 6.23 6.28 6.30 6.25 6.26
COP
10kV - — — — — — — — — — —
Insulating area m2 19 19 23 23 25 25 25 25 28 28
8. For type selections, chilled water inlet/outlet temperature is 7/12℃, cooling water inlet/outlet temperature is
32/37℃.
9. We provide you with specific type selection based on your cooling capacities and operational conditions.
10. The table is applicable to chillers manufactured for normal water. If seawater and brine are necessary, please
contact us.
11. Capacity control range is 100% to approx. 20%
12. Operating voltage: AC 380V/50Hz/3φ/4W
Capacity: 3.0kVA 300~400RT / 5.0kVA 450~1400RT
13. Working pressure is 1.0MPa for both chilled and cooling water; If higher maximum working pressure is
required, please specify during inquiry (It is possible to produce up to 2.0MPa).
14. For water piping connections, see the dimensional outline drawing.
15 Z0031524-2016-A
(Continued)
USRT 800 850 900 950 1000 1050 1100 1150 1200 1250
Refrigerating capacity
kW 2813 2989 3165 3340 3516 3692 3868 4044 4220 4395
Flow m3/h 484 515 545 575 605 636 666 696 726 756
Pressure loss kPa 104 116 106 116 120 131 126 132 108 116
Chilled
water Interface
DN 250 250 300 300 300 300 300 300 300 300
dimension
Number of passes - 2 2 2 2 2 2 2 2 2 2
Flow m3/h 564 599 634 669 704 739 774 809 843 878
Electrical machine 380V kW 448 474 502 528 555 583 609 635 659 682
input power 10kV kW — — 505 533 561 595 623 650 674 698
380V mm 4550 4550 4550 4550 5050 5050 5050 5050 5050 5050
Length
10kV mm — — 4650 4650 5150 5150 5150 5150 5150 5150
Outline Width mm 2250 2250 2400 2400 2400 2400 2400 2600 2600 2600
Dimension
Height mm 2650 2650 2800 2800 2800 2800 2800 2900 2900 2900
Size of pulling
mm 4000 4000 4000 4000 4500 4500 4500 4500 4500 4500
tubes
Shipping 380V 11.6 11.6 13 13 14.5 14.5 14.7 15.5 16.5 16.5
t
Wt. 10kV — — 13.3 13.3 14.8 14.8 15 15.8 16.8 16.8
Weight
Operating 380V 14.1 14.2 15.7 15.8 17.8 17.9 18.2 19.1 20.2 20.3
t
wt. 10kV — — 16 16.1 18.1 18.2 18.5 19.4 20.5 20.6
380V - 6.28 6.30 6.31 6.32 6.33 6.33 6.35 6.37 6.40 6.44
COP
10kV - — — 6.27 6.27 6.27 6.20 6.21 6.22 6.26 6.30
Insulating area m2 28 28 30 30 33 33 33 35 35 35
8. For type selections, chilled water inlet/outlet temperature is 7/12℃, cooling water inlet/outlet temperature is
32/37℃.
9. We provide you with specific type selection based on your cooling capacities and operational conditions.
10. The table is applicable to chillers manufactured for normal water. If seawater and brine are necessary, please
contact us.
11. Capacity control range is 100% to approx. 20%
12. Operating voltage: AC 380V/50Hz/3φ/4W
Capacity: 3.0kVA 300~400RT / 5.0kVA 450~1400RT
13. Working pressure is 1.0MPa for both chilled and cooling water; If higher maximum working pressure is
required, please specify during inquiry (It is possible to produce up to 2.0MPa).
14. For water piping connections, see the dimensional outline drawing.
16 Z0031524-2016-A
(Continued)
USRT 1300 1350 1400
Refrigerating capacity
kW 4571 4747 4923
Number of passes - 2 2 2
Number of passes - 2 2 2
Insulating area m2 35 35 35
8. For type selections, chilled water inlet/outlet temperature is 7/12℃, cooling water inlet/outlet temperature is
32/37℃.
9. We provide you with specific type selection based on your cooling capacities and operational conditions.
10. The table is applicable to chillers manufactured for normal water. If seawater and brine are necessary, please
contact us.
11. Capacity control range is 100% to approx. 20%
12. Operating voltage: AC 380V/50Hz/3φ/4W
Capacity: 3.0kVA 300~400RT / 5.0kVA 450~1400RT
13. Working pressure is 1.0MPa for both chilled and cooling water; If higher maximum working pressure is
required, please specify during inquiry (It is possible to produce up to 2.0MPa).
14. For water piping connections, see the dimensional outline drawing.
17 Z0031524-2016-A
2.4 Electrical data
19 Z00301524-2016-A
3. Structure of Standard Type of Chillers
Model code of standard type of Model code of special
chillers type of chillers
Dual operating
conditioning
Centrifugal water chiller chillers
CFC'S Substitute adapted type (HCF-134a used) Heat pump unit
4. Characteristics Data
4.1 Control Characteristic
4.1.1 Capacity control characteristic
(a) Partial load characteristic
Centrifugal chillers’ capacity control is achieved by adjusting the opening degree of inlet vane which is built
in the inlet of compressor to control refrigerant cycling volume, ensuring that chilled water outlet
temperature is within the scope of settings.
With the temperature sensor sit at chilled water outlet and high performance micro control panel, continuous
and stable capacity control can be achieved by inlet vane at the range of 100%-approx. 20% even when the
unit operates with low temperature cooling water in winter. (①area)
In winter where external air temperature is low, the maximum cooling capacity is increased due to the low
temperature of cooling water, thus ensuring smooth operation. (②area)
In hot summer, stable operation continues even when condenser pressure rises due to high temperature of
cooling water and heat transfer tube fouling by simply adjusting air suction valve in an adequate manner.
(③area)
The relationship between capacity control range and required power is shown as below:
Temperature at
the inlet of
cooling water
Motor input (%)
Temperature at
Load change start point
the inlet of
chilled water
21 Z00301524-2016-A
(b) Accompanying Characteristic When Starting
See Figure 4.4 for accompanying characteristic of cooling water when centrifugal chillers start. The time for
chilled water outlet and inlet temperatures becoming stable depends on overall heat capacity of cooling water
system and capacity of chillers.
Chilled water temperature (℃)
22 Z0031524-2016-A
4.2 Motor characteristic
4.2.1 Starting current characteristic
The main motor of closed centrifugal chillers is squirrel cage asynchronous type. Generally, it is started with
reduced voltage. See Figure 4.1 for various starting methods and their characteristics.
Starting methods are classified by power voltage and capacity. See Figure 4.5~4.7 for starting currents of common
starting methods
Starting current depends on chilled water temperature before start. The higher the temperature of cooling water,
the greater the transient current when start. Error from unit itself should be considered when determining power
capacity, taking over 130% of values shown in Figure 4.5~4.7.
Open-transition type
Starting mode Direct starter (DOL) Reactor starter
star-delta starter
S1S1 S1
Circuit S2S2 S2
S3S3 S3
23 Z00301524-2016-A
Starting current is ranging from 700% to 900%
depending on different chillers.
Time (s)
Figure 4.6 Reactor Starting Characteristic (65% tap) Figure 4.7 Open-transition type star-delta
starting characteristic
※Since transformer’s residual voltage may ※ Since peak current reaches its maximum
generate peak current when starting, care value at 380V during switch-over from star
should be exercised to select primary to delta position, equal to 15 times of rated
overload relay. value, care should be exercised to select
24 primary overload relay. Z0031524-2016-A
4.3 Vibration
4.3.1 Vibration value
25 Z00301524-2016-A
5. Operation Control
5.1 Operating control mode
Generally, the operation of Hitachi centrifugal chillers is controlled via electric cabinet to achieve fully
automatic operation.
(a) Start
Press START button on electric cabinet to activate interlocked operation of oil pump and chilled water
pump. At the same time, check for proper temperature of chilled water and for restart restriction. Then
cooling water pump is activated for interlocked operation. After 20 seconds when oil pressure is stable,
all interlocks have been established. Main contactor starts working. Main motor is started with reduced
voltage through starter panel. After a period of time, the reduced voltage will be switched to full voltage
automatically, getting the main motor to run up to full speed. At this point, with temperature regulating
and load limit loops, capacity control valve (hereinafter referred to as valve) will be opened/closed
automatically to achieve proper operation and make chilled water temperature constant.
(b) Stop
Press STOP button on electric cabinet and close the valve to the minimum degree of opening to stop
chillers and cooling water pump. At the same time, the valve and the electric secondary suction butterfly
valve are closed automatically. Approx. 1 minute later (delay operation), chilled water pump stops.
Approx. 4 minutes (delay operation) later, oil pump stops automatically.
(c) Automatic temperature regulating device (featuring load limit)
Automatic temperature regulating device, containing load limit loop, enables temperature and load limit
control by adopting loop equipped with integral and derivative control developed by Hitachi. Load limit
refers to limitation of valve opening (only for opening restriction) and secondary mandatory control of
valve closing. Thanks to this function, stable operation continues even when condenser pressure rises
due to high temperature of cooling water and heat transfer tube fouling in summer. Operation can be
secure since shutdown due to failure is minimized. (Equipped with alarm reminding)
(d) Automatic Start/Stop
Automatic start/stop is activated after detection signal of chilled water outlet temperature is processed
by electric cabinet. Under low load operation beyond the minimum limit of capacity control, automatic
start/stop will be activated, resulting in temporary shutdown of chillers. Chillers will be restarted
automatically after 15 minutes when load recovers.
(e) Shutdown due to failure
The action of protection switch triggers warning. Meanwhile, failure causes will be displayed on electric
cabinet screen. Chillers stop running.
(f) Oil heater
Oil heater is activated automatically when chillers stop to keep proper oil temperature so that oil mist
will not occur when restarting. (Therefore, control circuit should not be de-energized even when chillers
stop).
(g) Emergency stop
Chillers are switched off instantly when the emergency stop button is pressed. Then the valve is closed
automatically. Approx. 4 minutes later, oil pump stops automatically.
26 Z0031524-2016-A
※Control flow chart for various conditions of chillers is shown below:
1. Start flow chart
油压上升正常
Oil pressure rises properly 自动开停
Auto
时间继电器动作
Time relay action 限时动作
Time limit
start/stop
(Oil pressure interlock)
(油压联锁) Starting for voltage 自动开停
Auto on/off trips 开关动作
switch trips
降压启动 Switch action
开关动作
reduction
Auto温度自动调节回路动作
temperature regulating loop trips
load limit loop trips
负荷限制回路动作
27 Z00301524-2016-A
2. Normal operation
运转开始
Operation starting
Local 供货范围外
Out of scope of
本地 supply
远程
Remote 远程/本地
Remote / Local
switch button 运转开关ON
Operating switch ON
AND回路
AND loop
切换按钮
远程运转
Remote
operating
信号
signal OR回路
OR loop
运转指示灯亮
Operating indicator light On
Chilled
冷水泵 water 冷水泵
Chilled water pump
pump in
运转
operation
运转信号
operation signal
Restart
Proper chilled
冷水温度正常 再启动限制
restriction: 15
water
temperature 15分钟
minutes
油罐温度
Proper oil tank
无故障
No-failure
正常
temperature
Chilled water
冷却水泵
pump in
运转
operation
Chilled water
恒温器
ThermostatON
ON 冷却水泵
pump operation
运转信号
signal Oil油泵启动
Capacity
冷却塔运转
Cooling water pump startup 容量控制阀
control valve
tower in fully closed
全闭
operation 20 seconds after油压确立后20秒
oil pressure is established
Economizer
经济器阀全闭
valve is fully
closed
断水继电器
Proper water
suspension
Interlock
联锁成立 正常relay
established
Main主电动机自动起动
motor starts automatically
运转表示
Operation Direct 保护回路成立
Protection loop 油加热器OFF
Oil heater OFF
indicator 直接启动 established
starting
冷水机组自动运转
Chillers run automatically
冷水温度低下
Low chilled water temperature
冷冻负荷低下
Low refrigeration load 冷却水泵
Cooling water 冷却水泵
Cooling water
停止信号
pump stop signal 停止
pump stopping
自动开停
Auto on/off 冷水机组自动停机
Chillers stop automatically
容量控制阀闭
Capacity control valve closed 经济器阀闭
Economizer valve is closed
延时运转
Delay 油加热器
Oil heater
operation for
4分
4 minutes
thermostat
恒温器
冷冻负荷增加
Refrigeration load increases
Chilled冷水温度上升
water temperature rising 油泵停止
Oil pump stop 油加热器ON
Oil heater ON
28 Z0031524-2016-A
3. Normal Shutdown
运转停止
Operation stopping
Cooling water
远程
Remote 远程/本地
Remote / Local 直接
Direct pump stopping
switch button
切换按钮
停止信号
Operation stopping 停止开关ON
Stop switch ON
Stop 停止表示灯亮
indicator light ON
阀关闭至最小开度
Valve is closed to the minimum opening degree
冷冻机停止
Refrigerator stops
冷却水泵
Cooling water 延时运转
Delay 延时运转Delay 油加热器
Oil heater
operation for 1 operation for 4
pump
停止信号stop signal 1分钟
minute 4分钟
minutes 恒温器
thermostat
容量控制阀全闭
Capacity control valve 经济器阀全闭
Economizer valve
fully closed is fully closed
冷却水泵
Cooling water 冷水泵 油泵停止
Oil pump stop 油加热器ON
Oil heater ON
Chilled water
停止
pump stopping 停止信号
stop signal
冷却塔停止
Cooling water 冷水泵停止
Chilled water
tower stops pump stops
Cooling water
冷却水断水(选配件)
Cooling water suspended (optional)
冷却水泵 主电动机线圈温度上升
Main motor coiler temperature rises
pump
异常
abnormality ※主电动机过负荷
※Main motor overloaded
※启动箱异常
※Starter panel failure
冷水过冷却
Chilled water overcooled
给油温度上升
Oil feed temperature rising
冷凝压力上升
Condensing
蒸发压力低下 pressure rising
※CPU
※CPU异常 failure
控制传感器异常
Control sensor abnormality
供货范围外
Out of scope of supply
AND
AND loop
回
路
Mode
模式表示器indicator
OR loop
回
路
OR
蜂鸣器
Buzzer 蜂鸣器停止
Buzzer silence
Buzzer STOP
蜂鸣器停止按钮 Failure cause
故障原因调查
Stop 停止表示灯亮
indicator light ON button warning investigation
警报停止
stops
Capacity control valve is
Note: If failure with ※ occurs, chillers will shut
at the minimum opening 注意:带※的故障不等到容量控制
容量控制阀最小开度degree
down instantly instead of adjusting capacity valve
阀开到最小开度,就停止机组。
to its minimum opening degree.
冷水机组停止
Chiller unit stopping Delay
冷却水泵
Chilled water
延时运转
Delay
operation for 延时运转
operation for 油加热器
Oil heater
stop signal 4 minutes thermostat
停止信号 1 minutes
1分钟 4分钟 恒温器
容量控制阀全闭 经济器阀全闭
Capacity control Economizer
valve fully closed valve is
冷却水泵
Cooling water 冷水泵
Chilled water 油泵停止
fully Oil pump stop 油加热器ON
Oil heater ON
pump
停止stopping stop signal
停止信号 closed
冷却塔停止
Cooling water 冷水泵停止
Chilled water
tower stops pump stops
29 Z00301524-2016-A
5.2 Safety and protection control device
① Electrical Safety and Protection Devices
Safety and protection devices are equipped with the following switches (protection relay). If any one of them
trips, main motor will stop automatically. Warning is triggered, and failure causes will be displayed.
Oil temperature switch .................................... When oil temperature rises abnormally
Oil pressure differential switch ....................... Oil pressure is too low
Chilled water suspension switch ..................... Chilled water amount is reduced abnormally
Cooling water suspension switch .................... Cooling water amount is reduced abnormally (optional)
Chilled water temperature switch ................... Chilled water temperature is too low
Overload relay ................................................ Main motor is overloaded
Coil temperature switch .................................. The temperature of main motor coil is too high
Oil tank temperature switch ............................ The temperature of oil tank is too low
Oil pump thermorelay ..................................... Oil pump is overloaded
30 Z0031524-2016-A
Protective Relay Table
For Protection For Operation
Name Mark
Failure Reset Failure Reset
Note (1) The above settings of switches is applicable to chilled water outlet temperature of 7℃ and cooling
water outlet temperature of 37℃.
(2) Chilled water temperature protection relay (26WLX), automatic start/stop protection relay (23ASX),
oil supply protection relay (26QBX) and oil heater temperature relay (26QHX) are built in micro
computer with fixed setting.
(3) Settings of motor coil temperature switch (49M) are also fixed.
(4) Cooling water suspension relay is optional.
31 Z00301524-2016-A
5.3 Interlocked Operation with Auxiliary Equipment (pump, cooling tower fan) (see wiring
diagram for wiring method).
We recommend interlocked operation with chilled water pump, cooling water pump, and cooling tower fan to
ensure chillers operate in a reliable and safe manner (start and stop in sequence). Instructions sent by electric
cabinet of centrifugal chillers should be followed completely. Actions operation and information handover of
connections are shown below.
(1) Operation Start Flow Chart
运转开始
Operation starting Chillers
冷水机组电控箱 electric cabinet
Operating switch ON
运转开关ON
冷却水泵
Cooling water Proper oil tank
油罐温度正常
temperature
No-failure
无故障
pump operating
运转
Cooling water
冷却塔运转
tower in operation
油泵启动
Oil pump startup
Capacity
20 seconds after oil pressure 容量控制阀
油压确立后20秒 control valve
fully closed
is established 全闭
Economizer
※※运转指令60秒内
If water suspension relay 经济器阀全闭
valve is fully
fails to be removed within 60 closed
断水继电器还没
seconds after giving operation
解除时,冷水机
instruction, chillers will trip
and stop. Proper water
组跳闸停机。 断水继电器
suspension
联锁成立
Interlock 正常
relay
established
Star delta
星三角启动
starting
油加热器OFF
Oil heater OFF 保护回路成立
Protection loop established
冷水机组全
Chiller unit full
Automatic operation
自动运转
阀关闭至最小开度
Valve is closed to the minimum opening degree
Delay
延时运转
operation for
冷却水泵
Cooling water Delay
延时运转 Oil heater
pump stopping 1分钟
1 minutes
冷水机组停止
Chiller unit stopping operation for 油加热器
停止 44分钟
minutes
thermostat
恒温器
冷却塔风
Cooling tower 冷水泵
Chilled water
机停止
fan stopping 停止
pump stops 控制阀全闭 经济器阀全闭
Control valve is Economizer valve is 油泵停止
Oil pump stop 油加油器ON
Oil heater ON
fully closed fully closed
32 Z0031524-2016-A
5.4 Electric Cabinet Wiring Diagram of Centrifugal Chillers
Electric cabinet wiring diagram of centrifugal chillers may different depending on various series of
products and project special requirements. Delivery Specifications shall prevail.
1
2
33 Z00301524-2016-A
5.5.3 Screen and Operation Summary
It provides main screen, setup screen, data screen, failure screen and warning screen. Operator may switch
over these screens at will via pressing buttons.
34 Z0031524-2016-A
Trend graph shows curves of chilled water outlet temperature, cooling water inlet temperature, oil supply
temperature, condenser pressure, capacity valve opening degree and main motor current.
On main screen, all user screen operations can be achieved.
Local Failure Local Failure
chiller suspended Local
Remote l Alarm
chiller suspended Local
Remote l Alarm
Chilled water pump Standard settings Time setting
Main motor Main motor
Inlet of chilled water stopping Setting of temperature at the setup items stopping
outlet of chilled water
Evaporator Limit value of current _(mm) __(dd), 20
oil pump stop oil pump stop
Buzzer On Hour minute second
Outlet of chilled water Oil heater Maintenance switch OFF On Off Oil heater
stopping Real time stopping
Energy saving mode In revision Off
Main motor Oil supply _(mm) __(dd), 20 start chilled
chilled water outlet setting start chilled capacity valve operation switchover
water machine Hour minute second water machine
Auto On Off
stop chilled Setting Confirm Startup stop chilled
Outlet of cooling water water machine capacity valve opening position water machine
Temperature at the outlet of chilled Corrected value Correct
Condensator water
Home page modify current value Confirm Home page
Internal SP
Control output History menu
Cooling water inlet Setting Setting
operation history
record every hour
Cooling water pump Data Transducermotor-operated Data
operation history
Oil pump valveoperation switchover record every minute
Failure/Alarm Failure/Alarm
Oil tank Interlock shutdown due to
failure
warning history
Oil heater Trend graph record
Local Failure
chiller suspended Local
Remote l Alarm
fetch data: 1 hour Data extraction suspended
D
start chilled
S water machine
capacity valve operation switchover
Startup stop chilled
Auto On Off water machine
Correct
capacity valve opening position
Confirm Home page
Temperature at the outlet of chilled water
Internal SP Setting
Control output operation history
record every hour Data
operation history
record every minute
Failure/Alarm
shutdown due to failure
Home page
Main motor overloaded, main motor high temperature Main motor Main motor
stopping buzzer Failure stopping
[Causes] →[ Countermeasures ] silence resetting
oil pump stop oil pump stop
36 Z0031524-2016-A
6. Starting box
Starter panel is equipped with signal light and has in-built breaker (optional) and magnetic contactor, —△
starting contractor, 2E motor protection relay and current transformer. These reasonable configurations
ensure easy inspection and maintenance of chillers.
Starter panel can be placed any proper places since operation is achieved via electric cabinet installed on
chillers.
Standard control voltage is 380V and 10000V.
380V........... —△ low voltage starter
10000V......... reactor starter
※Direct-on-line starter panel may also be used if power supply capacity is high enough.
Starter panel dimensions table
Size
Type
—△ starter (for 380V, 50Hz) Reactor starter (for 10000V,50Hz)
(HC-F)
L(mm) H(mm) W(mm) L(mm) H(mm) W(mm)
300~600GXG-S
800 2000 750 - - -
300~500GSG-S
650~800GXG-S
1000 1800 800 - - -
550~800GSG-S
850~1000GXG-S
1000 2100 800 - - -
850~900GSG-S
1050~1200GXG-S
1500 2000 1000 - - -
950~1250GSG-S
850~2000GXG-S
- - - 1880 2300 1680
800~2000GSG-S
L
Star-delta starting (taking HC-F500GSG-S for example, Reactor starter
see delivery specifications for details)
※ If an incoming line vacuum breaker is installed, surge may occur when breaker trips. Surge absorber should
be installed at incoming line side.
37 Z00301524-2016-A
7. Main Components & Main Optional Function
7.1 System Loop Diagram
Mark Name
Oil filter
Automatic start/stop
protection relay
Chilled water temperature
Low fuel supply pressure protection relay
Oil heater temperature
protection relay
Oil tank temperature
protection relay
Oil supply temperature
protection relay
Oil supply voltage
Compressor
Main differential relay
Cold water cutoff relay
motor
Mark Name
Manually operated
Oil cooler
valve
Condensing Evaporating Electrically operated
pressure pressure valve
Angle valve
Venturi tube
Filter
Safety valve
Electric cabinet
Sight glass
Fuel Orifice
tank
Note: The motor-driven valve is Desaturator
available to VFD centrifuge Temperature detection
and is not provided for other wiring
Economizer
Capillary tube
Refrigerant liquid
Outlet of flow direction
Outlet of Refrigerant gas flow
Condensator
Note
Refers to direct connection
(without piping).
Fully closed manually operated valve
and angle valve are shown by
38 Z0031524-2016-A
7.3 Heat exchanger
Evaporator is horizontal shell and tube type, employing high-efficiency heat transfer tube exclusively
owned by Hitachi. Condenser is also shell and tube type.
Compressor
Condensator
Evaporator
39 Z00301524-2016-A
7.4.2 High Temperature Differential Technology (Optional)
High temperature differential is employed to reduce pump power (chilled water inlet /outlet temperature is
15℃/7℃; the minimum cooling water inlet temperature can be 12℃). Since flow rate of water pump is
reduced, the pump power is lowered. Thus, size of piping can be and cost is saved.
40 Z0031524-2016-A
The flow rate of water circulates Air conditioner for
Cooling heating
tower in cooling tower is controlled by
a three-way valve.
Scope of supply of
Hitachi Steam
Throttling
Compressor device
Evaporator
Condensate
water
Maximum temperature of
heat recovery is 49℃.
Air conditioner for
cooling
Cooling Cooling
load load
Condensator Condensator
Evaporator Evaporator
Open valve
Water supply inlet Water supply outlet Water supply inlet Water supply outlet Close valve
41 Z00301524-2016-A
7.4.6 Cool Storage System (Expanded Function)
Taking advantage of difference between on-peak and off-peak power prices, night cool storage and
daytime cooling are achieved by means of switchover of cool storage condition and air conditioning
condition. As a result, on-peak power consumption is reduced while cooling requirement is met ensuring
cost-effective operating.
(1) This system applies to the area where difference between on-peak and off-peak power prices is
great.
(2) “Night cool storage and daytime cooling” not only can meet cooling requirement but also can
balance on-peak and off-peak power consumptions in buildings, enabling users to reduce installed
capacity of air conditioners.
42 Z0031524-2016-A
8. Main Inspection Items and Instructions of Centrifugal Chillers
(1) Pressure Test and Air Tightness Test of Pressure Vessel
Design pressure
Equipment name Pressure Test MPaG Air tight test MPaG
MPaG
Compressor 0.92 1.7 1.15
Evaporator 0.92 1.25 1.15
Condensator 1.3 1.5 1.3
(2) Impeller overspeed test
Impeller, the single part, shall be subject to over-speed test at 1.2 times of rated rpm to check for abnormal
deformation and internal defect.
(3) Dynamic Balance Inspection of Impeller
Dynamically balance the impeller to ensure that the residual deviation of rotating body meets the standard,
that is, above G1.0 specified in JIS B0905 1992 (Rotating Machines-Balance Quality Requirements of
Rigid Rotors).
(4) Water Chamber Pressure Test
Water chamber of condenser and evaporator should be subject to pressure test at 1.15 times of design
pressure.
(5) Air tight inspection
(a) Pressure Leak Test When the unit is assembled, conduct tightness test via compressed air at
1.15MPaG.
(b) Vacuum Leak Test If refrigerant side is proved tight after test, vacuum the unit to 0.3kPa and hold
for 30 minutes at minimum. Pressure increase should not exceed 0.15kPa.
(6) Specifications Confirmation
Keep chilled water amount, cooling water amount and temperature at rated value in accordance with GB/T
18430.1-2007, check if cooling capacity can be met within the rated output range of motor.
(7) Capacity Control Test
The lower capacity limit that units can continuously control should be tested according to method specified
in item 6.
(8) Vibration Test
Check and make sure vibration value of main parts (total amplitude) is blow 15μm when operating at load.
(9) Noise Test
Test noise in accordance with rectangular hexahedron method specified in JB/T 4330.
(10) Frictional Head Loss Measurement
Check and make sure water pressure loss is not greater than 115% of nominal value at rated water supply
condition.
(11) Safety Protection Control Switch Actuation Inspection
All single parts of safety protection control switch should be subject to tripping inspection before they are
installed on the main body of the unit.
(12) Appearance inspection
Check for damage and uneven painting of the unit in accordance with delivery specifications.
(13) And other tests specified in national standard GBT18430.1-2007 “Water chilling (heat pump) packages
using the vapor compression cycle—Part 1: Water chilling (heat pump) packages for industrial &
commercial and similar application.
43 Z00301524-2016-A
9. Precautions for Equipment Design
9.1 Machine Room and Safety Devices
(1) Avoid places that are near fumes or fire or inflammable substances (for example, extreme care shall be
exercised regarding radiation heat when installed together with a heating element such as boiler)
(2) Please select a well ventilated place where room temperature is less 40℃.
(Extreme care shall be exercised that high temperatures may cause electrical fault and early corrosion of
equipment. Allowable ambient humidity: max 95% RH at 40℃)
(3) Select a low-dust area (Dust also may cause electrical fault).
(4) Select a place where is convenient for inspection and maintenance, paying attention to lighting.
(5) Keep sufficient space for pulling tubes, disassembling the water chamber, and inspection & maintenance.
(6) To facilitate the lifting up/down of equipment, provide lifting hooks on the ceiling or keep a sufficient room
height for setting a lifting pole.
(7) Provide sufficient drainage.
(8) Pay attention to avoid direct sunbathing of sunray.
(8) Make sure water source and receptacles for maintenance work are in place.
(10) Keep sufficient maintenance space at the entrance for carrying equipment out.
45 Z00301524-2016-A
60 kg
0 : inherent vibration value, 0 =
2 w
: mechanical vibration value g: acceleration of gravity (9.8m/s2)
ε: mechanical loss coefficient of vibration-proof materials (metal spring=0, vibration-proof rubber
=0.1~0.3)
w: weight (kg)
K: Spring coefficient
47 Z00301524-2016-A
Adjust center of
gravity by pulley
Center of Center of
gravity of the gravity of the
unit unit
Lifting hook
Side B Side A
Wiring from starter panel to motor power, and wiring from starter
panel to electric cabinet operation should be performed by user.
Frontage
Starter panel
Figure 10.4 Centrifugal Chillers Electrical Wiring Diagram
11. Information
11.1 Refrigerant Properties
The refrigerant, HFC134a, used for centrifugal chillers has the following properties.
① Gas under ambient temperature and pressure.
② No odour
③ Non-flammable; Explosion absolutely will not occur when mixing it with air in any way.
④ The liquefied refrigerant is clear colorless. It is heavier than water and will not solute with water. Water flows
on the surface of the refrigerant.
⑤ Metals do not corrode when they are exposed to purified liquid or vapor of refrigerant. However, metals,
especially ordinary steels may be corroded when they are exposed to refrigerant containing air, since air
contains water.
49 Z00301524-2016-A
⑥ Regardless of any ratio between the refrigerant and the mineral lubricant, the solubility will be reduced.
Therefore, synthetic oil (polyester oil) which is compatible with HFC 134a is recommended.
⑦ It is harmless to human being and animals. (however, ventilation system should be efficient)
⑧ Vapor refrigerant is 5.1 times heavier than air. Thus, when disassembling chillers, the gas emitted will be
attached onto the ground.
(MPaG)
1.6
1.5
1.4
1.3
1.2
1.1
1.0
飽
Saturation pressure
0.9
和
圧 0.8
力 0.7
0.6
0.5
0.4
0.3
0.2
0.1
0 10 20 30 40 50 60
(℃)
温 度
Temperature
50 Z0031524-2016-A
11.2. Lubricant
The lubricant selected to be used for chillers must meet very strict criteria. Along with its heat stability and
high lubrication efficiency, such lubricant should be insulated and compatible. The lubricant should be
synthetic oil which is compatible with HFC134a. Please contact us for recharge of lubricant.
Synthetic oil (grease oil) is featured with high moisture absorption. Air must not be mixed up during
recharge or storage of lubricant. Used lubricant should be discarded.
Oil filter
Compressor ○
replacement
Insulation
○
measurement
Evaporator tube
○
cleanup
Water quality
○
Evaporator analysis
Condensator
Refrigerant analysis ○
51 Z00301524-2016-A
Minimum Inspection Interval Every 1 every Every Every 6
Remarks
Item month one year 3 years years
2 times every quarter
Check protection
○
relay for tripping
Other Replacement of
○
strainer and dryer
Supervise regulations
Safety valve
○ according to Safety Technique
calibration
of Pressure Vessels
Note)
1. The interval listed in this table is a general recommendation. User may shorten or prolong this time based on
your operation conditions or inspection results.
52 Z0031524-2016-A
Cooling Water Quality
Tendency
Item Reference value Scale
Corrosion
formation
pH (25℃) 6.5~8.0 ○ ○
Conductivity (25℃) S / cm <800 ○ ○
Reference
value Sulphate ion SO 2 mg( SO 2 ) / L <200 ○
Acid consumption
mg(CaCO3 ) / L <100 ○
(pH=4.8)
Sulphur S 2 mg ( S 2 ) / L Undetectable ○
Reference
Ammonia ion NH mg( NH ) / L <1.0 ○
Note: items with ○ refer to relevant factors generating corrosion and fouling.
Note) (1) For specific name and unit for each item, please refer to GB/T 18430.1-2007.
(2) Units and values listed in bracket were used before. Here is just for your information.
(3) Generally, more serious corrosion will be occurred under high temperature (greater than 40℃),
especially for steel and metal materials without any protection film and contacting with water directly.
Corrosion prevention measures should be taken properly such as adding preservative or degassing.
(4) Water supply and supplementary water access should be sourced from tap water (feed water), industrial
water, underground water, purified water, neutralized water and softened water.
53 Z00301524-2016-A
Eddy current inspection Please contact with professional
5
test maintenance company.
Please contact with professional
6 Water treatment
maintenance company.
Note (1) Supplementary water and circulating water should be subject to water quality analysis. Decision should
be made for the necessity of replacement of water or change of water supply frequency depending on
analysis result.
(2) Water quality analysis should be conducted on a quarterly basis (in spring, summer, autumn and
winter), and judgment basis should be documented.
54 Z0031524-2016-A
All contents specified in the manual are subject to change for technical improvements without prior notice.
Hitachi reserves the rights to explain, and modify contents of the manual.
55 Z00301524-2016-A