* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit (95.0% of the Continuous Ampere rating).
Project: TENDIDO LINEA DE MT 24,9 KV ETAP Page: 2
Transformer
CKT / Branch Busway / Cable & Reactor
Loading (input) Loading (output)
Ampacity Loading Capability
ID Type (Amp) Amp % (MVA) MVA % MVA %
Vd
From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
LINE 2 0.025 0.009 -0.025 -0.012 0.0 -2.7 97.2 97.2 0.01
LINE 3 0.270 0.093 -0.270 -0.097 0.4 -4.1 97.6 97.4 0.13
LINE 4 0.259 0.091 -0.258 -0.100 0.7 -9.1 97.4 97.2 0.27
LINE 5 0.190 0.080 -0.190 -0.082 0.1 -1.9 97.0 97.0 0.04
LINE 6 0.019 0.004 -0.019 -0.009 0.0 -5.4 97.0 97.0 0.01
LINE 7 0.209 0.079 -0.209 -0.084 0.3 -4.8 97.2 97.0 0.12
LINEA 1 0.307 0.097 -0.307 -0.102 0.6 -5.4 98.0 97.8 0.19
LINEA 2 0.282 0.090 -0.282 -0.098 0.7 -7.9 97.8 97.6 0.25
TRAF 1 -0.024 -0.012 0.024 0.012 0.6 0.4 95.2 97.8 2.58
TRAF. 2 -0.011 -0.005 0.011 0.005 0.1 0.1 96.4 97.6 1.20
TRAF. 3 -0.011 -0.005 0.011 0.005 0.1 0.1 96.2 97.4 1.20
TRAF. 4 -0.023 -0.011 0.024 0.012 0.6 0.4 94.6 97.2 2.56
TRAF. 5 -0.024 -0.012 0.025 0.012 0.6 0.4 94.5 97.2 2.62
TRAF. 6 -0.019 -0.009 0.019 0.009 0.4 0.2 95.0 97.0 2.07
TRAF. B -0.182 -0.077 0.190 0.082 7.8 4.7 92.8 97.0 4.22
13.0 -35.0
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Bus Voltage
OverVoltage 105.0 102.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
Critical Report
Marginal Report
Marginal Report
MW Mvar MVA % PF
Number of Iterations: 3