Project: TENDIDO LINEA DE MT 24,9 KV ETAP Page: 1

Location: YOTALA 19.0.1C Date: 06-06-2022

Contract: ESDESUR S.A. SN:

Engineer: Revision: Base


Study Case: LF
Filename: LINEA_MT_YOTALA Config.: Normal

Bus Loading Summary Report

Directly Connected Load Total Bus Load

Bus Constant kVA Constant Z Constant I Generic


Percent
ID kV Rated Amp MW Mvar MW Mvar MW Mvar MW Mvar MVA % PF Amp Loading

B1 0.380 0.019 0.009 0.004 0.002 0.026 90.0 42.2


B2 0.380 0.009 0.004 0.002 0.001 0.012 90.0 19.6
B3 0.380 0.009 0.004 0.002 0.001 0.012 90.0 19.6
B4 0.380 0.019 0.009 0.004 0.002 0.026 90.0 41.8
B5 0.380 0.020 0.009 0.004 0.002 0.027 90.0 42.8
B6 0.380 0.016 0.008 0.003 0.002 0.021 90.0 33.8
BT1 0.380 0.182 0.077 0.198 92.0 323.6
NODO 1 24.900 0.322 95.4 7.6
NODO 2 24.900 0.323 94.9 7.7
NODO 3 24.900 0.298 94.4 7.1
NODO 4 24.900 0.287 94.1 6.8
NODO 5 24.900 0.277 93.2 6.6
NODO 6 24.900 0.225 92.8 5.4
NODO 7 24.900 0.027 89.9 0.7
NODO 8 24.900 0.207 91.8 4.9
NODO 9 24.900 0.022 89.9 0.5

* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit (95.0% of the Continuous Ampere rating).
Project: TENDIDO LINEA DE MT 24,9 KV ETAP Page: 2

Location: YOTALA 19.0.1C Date: 06-06-2022

Contract: ESDESUR S.A. SN:

Engineer: Revision: Base


Study Case: LF
Filename: LINEA_MT_YOTALA Config.: Normal

Branch Loading Summary Report

Transformer
CKT / Branch Busway / Cable & Reactor
Loading (input) Loading (output)
Ampacity Loading Capability
ID Type (Amp) Amp % (MVA) MVA % MVA %

TRAF 1 Transformer 0.028 0.027 97.5 0.026 94.9

TRAF. 2 Transformer 0.028 0.013 45.1 0.012 44.5

TRAF. 3 Transformer 0.028 0.013 45.0 0.012 44.5

TRAF. 4 Transformer 0.028 0.027 95.9 0.026 93.3

TRAF. 5 Transformer 0.028 0.027 98.0 0.027 95.4

TRAF. 6 Transformer 0.028 0.022 77.3 0.021 75.7

TRAF. B Transformer 0.279 0.207 74.0 0.198 70.8

* Indicates a branch with operating load exceeding the branch capability.


Project: TENDIDO LINEA DE MT 24,9 KV ETAP Page: 3

Location: YOTALA 19.0.1C Date: 06-06-2022

Contract: ESDESUR S.A. SN:

Engineer: Revision: Base


Study Case: LF
Filename: LINEA_MT_YOTALA Config.: Normal

Branch Losses Summary Report

Vd
From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop

Branch ID MW Mvar MW Mvar kW kvar From To in Vmag

LINE 2 0.025 0.009 -0.025 -0.012 0.0 -2.7 97.2 97.2 0.01

LINE 3 0.270 0.093 -0.270 -0.097 0.4 -4.1 97.6 97.4 0.13

LINE 4 0.259 0.091 -0.258 -0.100 0.7 -9.1 97.4 97.2 0.27

LINE 5 0.190 0.080 -0.190 -0.082 0.1 -1.9 97.0 97.0 0.04

LINE 6 0.019 0.004 -0.019 -0.009 0.0 -5.4 97.0 97.0 0.01

LINE 7 0.209 0.079 -0.209 -0.084 0.3 -4.8 97.2 97.0 0.12

LINEA 1 0.307 0.097 -0.307 -0.102 0.6 -5.4 98.0 97.8 0.19

LINEA 2 0.282 0.090 -0.282 -0.098 0.7 -7.9 97.8 97.6 0.25

TRAF 1 -0.024 -0.012 0.024 0.012 0.6 0.4 95.2 97.8 2.58

TRAF. 2 -0.011 -0.005 0.011 0.005 0.1 0.1 96.4 97.6 1.20

TRAF. 3 -0.011 -0.005 0.011 0.005 0.1 0.1 96.2 97.4 1.20

TRAF. 4 -0.023 -0.011 0.024 0.012 0.6 0.4 94.6 97.2 2.56

TRAF. 5 -0.024 -0.012 0.025 0.012 0.6 0.4 94.5 97.2 2.62

TRAF. 6 -0.019 -0.009 0.019 0.009 0.4 0.2 95.0 97.0 2.07

TRAF. B -0.182 -0.077 0.190 0.082 7.8 4.7 92.8 97.0 4.22

13.0 -35.0

* This Transmission Line includes Series Capacitor.


Project: TENDIDO LINEA DE MT 24,9 KV ETAP Page: 4

Location: YOTALA 19.0.1C Date: 06-06-2022

Contract: ESDESUR S.A. SN:

Engineer: Revision: Base


Study Case: LF
Filename: LINEA_MT_YOTALA Config.: Normal

Alert Summary Report

% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0

Cable / Busway 100.0 95.0

Reactor 100.0 95.0

Line 100.0 95.0

Transformer 100.0 95.0

Panel 100.0 95.0

Protective Device 100.0 95.0

Generator 100.0 95.0

Inverter/Charger 100.0 95.0

Bus Voltage
OverVoltage 105.0 102.0

UnderVoltage 95.0 98.0

Generator Excitation
OverExcited (Q Max.) 100.0 95.0

UnderExcited (Q Min.) 100.0

Critical Report

Device ID Type Condition Rating/Limit Unit Operating % Operating Phase Type

B4 Bus Under Voltage 0.380 kV 0.359 94.6 3-Phase

B5 Bus Under Voltage 0.380 kV 0.359 94.5 3-Phase

B6 Bus Under Voltage 0.380 kV 0.361 95.0 3-Phase

BT1 Bus Under Voltage 0.380 kV 0.353 92.8 3-Phase

Marginal Report

Device ID Type Condition Rating/Limit Unit Operating % Operating Phase Type

B1 Bus Under Voltage 0.380 kV 0.362 95.2 3-Phase

B2 Bus Under Voltage 0.380 kV 0.366 96.4 3-Phase

B3 Bus Under Voltage 0.380 kV 0.366 96.2 3-Phase

NODO 1 Bus Under Voltage 24.900 kV 24.402 98.0 3-Phase

NODO 2 Bus Under Voltage 24.900 kV 24.355 97.8 3-Phase

NODO 3 Bus Under Voltage 24.900 kV 24.293 97.6 3-Phase

NODO 4 Bus Under Voltage 24.900 kV 24.261 97.4 3-Phase

NODO 5 Bus Under Voltage 24.900 kV 24.193 97.2 3-Phase


Project: TENDIDO LINEA DE MT 24,9 KV ETAP Page: 5

Location: YOTALA 19.0.1C Date: 06-06-2022

Contract: ESDESUR S.A. SN:

Engineer: Revision: Base


Study Case: LF
Filename: LINEA_MT_YOTALA Config.: Normal

Marginal Report

Device ID Type Condition Rating/Limit Unit Operating % Operating Phase Type

NODO 6 Bus Under Voltage 24.900 kV 24.164 97.0 3-Phase

NODO 7 Bus Under Voltage 24.900 kV 24.191 97.2 3-Phase

NODO 8 Bus Under Voltage 24.900 kV 24.153 97.0 3-Phase

NODO 9 Bus Under Voltage 24.900 kV 24.161 97.0 3-Phase

TRAF. 5 Transformer Overload 0.028 MVA 0.027 95.4 3-Phase

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW Mvar MVA % PF

Source (Swing Buses): 0.307 0.097 0.322 95.38 Lagging

Source (Non-Swing Buses): 0.000 0.000 0.000

Total Demand: 0.307 0.097 0.322 95.38 Lagging

Total Motor Load: 0.274 0.122 0.300 91.37 Lagging

Total Static Load: 0.021 0.010 0.023 90.00 Lagging

Total Constant I Load: 0.000 0.000 0.000

Total Generic Load: 0.000 0.000 0.000

Apparent Losses: 0.013 -0.035

System Mismatch: 0.000 0.000

Number of Iterations: 3