TAURY GROUP

TG0001 - Retaining Wall Analysis


Being Limitless

Jl. Rungkut Harapan Blok G No.7, Rungkut, Surabaya, Indonesia.


TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

Table of Contents

TABLE OF CONTENTS....................................................................................................................2

A. CURRENT RETAINING WALL CONDITION......................................................................3


A.1 GUIDANCE FOR THE ABREVIATIONS.........................................................................................3
A.2 DIMENSIONS..............................................................................................................................4
A.3 MATERIAL PROPERTIES.............................................................................................................4

B. ENVIRONMENTAL CONDITION...........................................................................................5
B.1 SOIL PROPERTIES.......................................................................................................................5
B.2 OBJECT ABOVE SOIL.................................................................................................................5

C. WORK FORCES.........................................................................................................................6
C.1 ACTIVE FORCE...........................................................................................................................6
C.2 PASSIVE FORCE..........................................................................................................................6

D. RETAINING WALL ANALYSIS..............................................................................................7


D.1 WL - 0.0 M................................................................................................................................7
D.2 WL - 0.5 M................................................................................................................................8
D.3 WL - 1.0 M................................................................................................................................8
D.4 WL - 1.5 M................................................................................................................................8
D.5 WL - 2.0 M................................................................................................................................8
D.6 WL - 2.5 M................................................................................................................................9
D.7 WL - 3.0 M................................................................................................................................9
D.8 WL - 3.5 M................................................................................................................................9
D.9 WL - 4.0 M................................................................................................................................9
D.10 WL - 4.5 M............................................................................................................................10
D.11 WL - 5.0 M............................................................................................................................10
D.12 WL - 5.5 M............................................................................................................................10
D.13 ANALYSIS SUMMARY............................................................................................................10

E. RETAINING WALL MODIFICATION.................................................................................11


E.1 M - 1 M....................................................................................................................................11
E.2 M - 2 M....................................................................................................................................12
E.3 M - 3 M....................................................................................................................................12

TAURY GROUP 2
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

TAURY GROUP 3
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

A. Current Retaining Wall Condition

A.1 Guidance For The Abreviations

TAURY GROUP 4
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

A.2 Dimensions

Properties Value Units


D : 0.800 m
Z : 5.000 m
X1 : 0.700 m
Upper Side : 0.600 m
X2 : 0.700 m
Foot : 0.000 m
H : 5.800 m
B : 2.000 m

A.3 Material Properties

Properties Value Units


Agregat Kasar : Batu Belah
Agregat Halus : Pasir and Semen
Specific Gravity : 1.500 Ton/m^3
Pressure Maximum : - MPa (Ton/m^2)
Elastic Modulus : - MPa (Ton/m^2)

TAURY GROUP 5
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

B. Environmental Condition

B.1 Soil Properties

Properties Value Units


Soil Location : Manado
Soil Type : Lempung (Clay) - Normal Consolidated (NC)
Specific Gravity : 1.865 Ton/m^3
Kohesi : 1.223 Ton/m^3
Sudut Geser Dalam : 24.2 Degrees

B.2 Object Above Soil

In this analysis, we consider the object above soil as a general ton per meter area, which is
0,5 Ton/m^2. In other words, we do not offer the detailed list of the object above the soil.

TAURY GROUP 6
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

C. Work Forces

C.1 Active Force

Active force is an external force that affects the retaining wall to overturn or slide. It is
located at the backside of the retaining wall. Other than that, It contains some variety of
forces such as:
 The force of the surround soil
 The force of the water level involved
 The force of the object above soil

C.2 Passive Force

Passive force is an external force that tends to reduce the effect of the active forces. It works
in opposite with the active forces, either the location.

TAURY GROUP 7
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

D. Retaining Wall Analysis

The analysis will contain some different cases to know the reaction of the retaining wall due
to additional forces such as rain and weight above soil. At the end of the analysis, the reader
will know the condition of the retaining wall when it considers to overturn or slide.
Hopefully, through this analysis, the reader could avoid the overturning or sliding
circumtances later on. The analysis will put into considerations below these conditions:

Condition Object Above Soil Water Level


WL - 0.0 m 0.5 Ton/m^2 0.0 m
WL - 0.5 m 0.5 Ton/m^2 0.5 m
WL - 1.0 m 0.5 Ton/m^2 1.0 m
WL - 1.5 m 0.5 Ton/m^2 1.5 m
WL - 2.0 m 0.5 Ton/m^2 2.0 m
WL - 2.5 m 0.5 Ton/m^2 2.5 m
WL - 3.0 m 0.5 Ton/m^2 3.0 m
WL - 3.5 m 0.5 Ton/m^2 3.5 m
WL - 4.0 m 0.5 Ton/m^2 4.0 m
WL - 4.5 m 0.5 Ton/m^2 4.5 m
WL - 5.0 m 0.5 Ton/m^2 5.0 m
WL - 5.5 m 0.5 Ton/m^2 5.5 m

D.1 WL - 0.0 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 0.718 5.406 5.129 5.532 1.532
Information : Sliding Warning

TAURY GROUP 8
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

D.2 WL - 0.5 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 0.736 5.533 5.255 24.482 1.519
Information : Sliding Warning

D.3 WL - 1.0 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 0.787 5.726 5.624 188.522 1.451
Information : Sliding Failure

D.4 WL - 1.5 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 0.874 5.726 6.243 13.951 1.304
Information : Sliding Failure

D.5 WL - 2.0 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 0.995 5.726 7.110 4.394 1.142
Information : Sliding Failure

TAURY GROUP 9
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

D.6 WL - 2.5 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 1.151 5.726 8.223 2.145 0.983
Information : Overturning Warning

D.7 WL - 3.0 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 1.342 5.726 9.586 1.270 0.839
Information : Overturning Failure

D.8 WL - 3.5 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 1.567 5.726 11.196 0.842 0.714
Information : Overturning Failure

D.9 WL - 4.0 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 1.827 5.726 13.049 0.599 0.608
Information : Overturning Failure

TAURY GROUP 10
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

D.10 WL - 4.5 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 2.122 5.726 15.157 0.446 0.520
Information : Overturning Failure

D.11 WL - 5.0 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 2.451 5.726 17.509 0.343 0.446
Information : Overturning Failure

D.12 WL - 5.5 m

Resistance Forces Accused Force Stability Value


Weight of RW A. Force (Z) P. Force (X) A. Force (X)
Overturning Sliding
(Ton/m) (Ton/m) (Ton/m) (Ton/m)
12.150 2.815 5.726 20.107 0.270 0.384
Information : Overturning Failure

D.13 Analysis Summary

According to the calculation, the present retaining wall is vulnerable to sliding occurance. It
would begin to slide when the soil is flooded by the rain water that would give water level
about 1 meter, measured from the baseline. Afterward, when the precipitation remains stable,
the retaining wall would fail in terms of overturning. The retaining wall would overturn when
the rain water level arrives at about 3 meter measured from the base line.

Point :
 Water level @ 1 meter = Start to Sliding
 Water Level @ 3 meter = Start to Overturning

TAURY GROUP 11
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

E. Retaining Wall Modification

In order to ensure the safetyness of the retaining wall, we all agree that the design of the
retaining wall should be modified. This statement is proven by the calculation above, which
says that the retaining wall would slide and afterward overturn. Hence, the modification is
expected to cover all the possibilities of the environmental occurance.

Speaking of which, I would offer three different modifications. All changes emerge an
additional foot at the bottom of the retaining wall.

Modification Condition Length of Foot


M-1m 1m
M-2m 2m
M-3m 3m

E.1 M - 1 m

Before Modification
Weight of the
Object Above Water Level
Retaining Wall Overturning Sliding
Soil (Ton/m^2) (m)
(Ton/m)
12.150 0.500 2.000 m 4.394 1.142
After Modification
13.350 0.500 2.000 m 15.935 1.558

TAURY GROUP 12
TAURY GROUP
TG0001 - RETAINING WALL ANALYSIS

E.2 M - 2 m

Before Modification
Weight of the
Object Above Water Level
Retaining Wall Overturning Sliding
Soil (Ton/m^2) (m)
(Ton/m)
12.150 0.500 2.700 m 1.708 0.923
After Modification
14.550 0.500 2.700 m 11.717 1.520

E.3 M - 3 m

Before Modification
Weight of the
Object Above Water Level
Retaining Wall Overturning Sliding
Soil (Ton/m^2) (m)
(Ton/m)
12.150 1.100 3.000 m 1.037 0.829
After Modification Version 1
15.750 1.100 3.000 m 11.455 1.507

TAURY GROUP 13