Submit t al

Jo b/Pro je ct : Re pre se nt at ive :


ESP-Syst e mwize : WIZE-FA95A8 Cre at e d O n: 03/06 /2 02 2 Pho ne :
Lo cat io n/Tag: Email:
Engine e r: Submit t e d By: Dat e :
Co nt ract o r: Appro ve d By: Dat e :

Split Case Fire Pump Selection Criteria NFPA Limits


Pump Mo de l: 8x8x17 F Rat e d Flo w 1500 US gpm 140% He ad o f Rat e d He ad 154 psi
No m. Spe e d: 17 50 rpm Rat e d He ad 110 psi 6 5% He ad at 150% Flo w 7 1.5 psi
Marke t : List e d Fire Pump Imp. Dia 16 .7 51 in Flo w at 150% 2 2 50 US gpm
Appro val/List ing: FM/UL Po we r Re quire d at Dut y 12 5 hp He ad at 150% 89 psi
Rat e d Efficie ncy 77 % Po we r Re q at 150% 144 hp
Fluid Wat e r Efficie ncy at 150% 80.7 %
T e mpe rat ure 85 ºF Max BHP 158 hp
Sp. Gravit y 1.000 Clo se d Valve He ad 12 7 psi

140% He ad o f Rat e d He ad 154PSI

Typical Performance Curve is shown. Fire Pumps are tested to ANSI/HI 14.6 acceptance grade 1U.
Rated Duty Point is guaranteed within the following tolerances: Flow 0% to + 10%, Head 0% to + 6%.
NO OTHER POINTS ARE GUARANTEED. PLEASE CONSULT FACTORY IF NEEDED.

Pe rfo rmance Curve Dat a


Flo w (US gpm) He ad (psi) Efficie ncy (%) Po we r Re quire d (hp) NPSHr (ft )
0 12 7 0 0 14
37 5 12 4 45.2 7 7 .6 14
7 50 12 1 57 .4 93.7 14
112 5 116 6 9.6 110 14
1500 110 77 12 5 14.3
2 2 50 89 80.7 144 17 .2
2 945 56 7 4.4 12 9 2 0.1