Split Case Fire Pump Selection Criteria NFPA Limits


Pump Mo de l: 8x6 x18F Rat e d Flo w 1500 US gpm 140% He ad o f Rat e d He ad 196 psi
No m. Spe e d: 2 100 rpm Rat e d He ad 140 psi 6 5% He ad at 150% Flo w 91.6 psi
Marke t : List e d Fire Pump Imp. Dia 15.891 in Flo w at 150% 2 2 50 US gpm
Appro val/List ing: FM/UL Po we r Re quire d at Dut y 16 5 hp He ad at 150% 107 psi
Rat e d Efficie ncy 7 4.3 % Po we r Re q at 150% 17 9 hp
Fluid Wat e r Efficie ncy at 150% 7 8.3 %
T e mpe rat ure 85 ºF Max BHP 189 hp
Sp. Gravit y 1.000 Clo se d Valve He ad 158 psi

140% He ad o f Rat e d He ad 196PSI

Typical Performance Curve is shown. Fire Pumps are tested to ANSI/HI 14.6 acceptance grade 1U.
Rated Duty Point is guaranteed within the following tolerances: Flow 0% to + 10%, Head 0% to + 6%.
NO OTHER POINTS ARE GUARANTEED. PLEASE CONSULT FACTORY IF NEEDED.

Pe rfo rmance Curve Dat a


Flo w (US gpm) He ad (psi) Efficie ncy (%) Po we r Re quire d (hp) NPSHr (ft )
0 158 0 0 8
37 5 156 43.2 102 8
7 50 154 55 12 5 8
112 5 149 6 6 .4 147 8
1500 140 7 4.3 16 5 8
2 2 50 107 7 8.3 17 9 14.1
2 501 90.6 7 3.6 17 9 19