You are on page 1of 3

NATIONAL TRANSMISSION AND DESPATCH COMPANY LMTD

ANNUAL TESTING RESULTS


IN RESPECT OF 500 KV GRID STATION NTDC NEW LAHORE (SOUTH)

ISOLATOR APPLIED MEASURED VALUE in µΩ


PTW NO / DATE
NAME CURRENT Rφ Yφ Bφ
B1Q12 100Amp 91 µΩ 95 µΩ 93 µΩ 1952 / 06-10-2021
B1Q31 100Amp 95 µΩ 93 µΩ 101 µΩ 1955 / 07-10-2021
B1Q32 100Amp 90 µΩ 95 µΩ 92 µΩ 1965 / 12-10-2021
B1Q21 100Amp 95 µΩ 91 µΩ 91 µΩ 1965 / 12-10-2021
B1Q20 100Amp 88 µΩ 91 µΩ 92 µΩ 1965 / 12-10-2021
B1Q22 100Amp 90 µΩ 85 µΩ 92 µΩ 993 / 30-03-2022
B1Q10 100Amp 93 µΩ 93 µΩ 91 µΩ 1952 / 06-10-2021
B1Q11 100Amp 89 µΩ 92 µΩ 90 µΩ 984 / 02-03-2022

B2Q12 100Amp 97 µΩ 90 µΩ 93 µΩ 1959 / 09-10-2021


B2Q31 100Amp 92 µΩ 88 µΩ 91 µΩ 1963 / 11-10-2021
B2Q32 100Amp 94 µΩ 93 µΩ 94 µΩ 987 / 15-03-2022
B2Q10 100Amp 91 µΩ 88 µΩ 90 µΩ 1959 / 09-10-2021
B2Q11 100Amp 92 µΩ 89 µΩ 91 µΩ 984 / 02-03-2022
B2Q21 100Amp 95 µΩ 92 µΩ 90 µΩ 987 / 15-03-2022
B2Q22 100Amp 94 µΩ 95 µΩ 95 µΩ 993 / 30-03-2022
B2Q20 100Amp 88 µΩ 93 µΩ 94 µΩ 987 / 15-03-2022

B4Q10 100Amp 85 µΩ 92 µΩ 91 µΩ 1979 / 01-11-2021


B4Q11 100Amp 90 µΩ 83 µΩ 88 µΩ 984 / 02-03-2022
B4Q12 100Amp 95 µΩ 91 µΩ 96 µΩ 1979 / 01-11-2021
B4Q31 100Amp 90 µΩ 88 µΩ 84 µΩ 1982 / 02-11-2021
B4Q21 100Amp 88 µΩ 85 µΩ 90 µΩ 937 / 05-12-2021
B4Q22 100Amp 82 µΩ 86 µΩ 81 µΩ 993 / 30-03-2022
B4Q32 100Amp 98µΩ 90 µΩ 92 µΩ 937 / 05-12-2021
B4Q20 100Amp 99 µΩ 98µΩ 98µΩ 937 / 05-12-2021

B3Q10 100Amp 91 µΩ 94 µΩ 94 µΩ 905 / 11-11-2021


B3Q11 100Amp 88 µΩ 88 µΩ 88 µΩ 984 / 02-03-2022
B3Q12 100Amp 88 µΩ 92 µΩ 84 µΩ 905 / 11-11-2021
B3Q31 100Amp 90 µΩ 93 µΩ 91 µΩ 905 / 11-11-2021
B3Q32 100Amp 94 µΩ 92 µΩ 95 µΩ 989 / 16-03-2022
B3Q21 100Amp 91 µΩ 90 µΩ 91 µΩ 989 / 16-03-2022
B3Q20 100Amp 89 µΩ 93 µΩ 95 µΩ 927 / 28-11-2021
B3Q22 100Amp 89 µΩ 89 µΩ 89 µΩ 993 / 30-03-2022

B5Q10 100Amp 85 µΩ 86 µΩ 86 µΩ 1996 / 08-11-2021


B5Q11 100Amp 84 µΩ 85 µΩ 81 µΩ 984 / 02-03-2022
B5Q12 100Amp 80 µΩ 88 µΩ 90 µΩ 1996 / 08-11-2021
B5Q32 100Amp 80 µΩ 80 µΩ 80 µΩ 993 / 30-03-2022
B5Q31 100Amp 91 µΩ 94 µΩ 94 µΩ 1996 / 08-11-2021
REMARKS:

Deputy Manager
Signature: FM Signature: AM (M)
500KV G/S New Lahore (South)
NATIONAL TRANSMISSION AND DESPATCH COMPANY LMTD
ANNUAL TESTING RESULTS
IN RESPECT OF 500 KV GRID STATION NTDC NEW LAHORE (SOUTH)

EQUIPMENT NAME : 500 Kv


BusBar1--CVT-1
PTW # 984 DATE: 02-03-2022

CAPACITANCE AND DESSIPATION FACTOR TEST

PHASE APPLY VOLTYAGES MODE LEACKAGE CURRENT (mA) Cp (F) D.F (%)

YELLOW 10 KV GST 4.5 mA 1642 pF 0.31%

INSULATION RESISTANCE TEST

APPLIED
PHASE CONNECTION VOLTAGES 15 SEC 60 SEC FORM FACTOR
PRIMARY TO
YELLOW 2 KV 80 GΩ 95 GΩ 1.18
GROUND

REMARKS:

Deputy Manager
Signature: FM Signature: AM (M) 500KV G/S New Lahore (South)