Issued To : M/S.Machine Tool Aids (India)


Address : C/o:GHMC- Ambedkar Nagar, Hyderabad Report No : STL/210715001514
Telangana Date of Receipt : 15/07/2021
Contact Person :Mr.Pavan Kumar
Phone : 9550074291 Date of Start : 15/07/2021
E-Mail : pavan.mtaindia@gmail.com Date of Completion : 21/10/2021
Report Date : 21/10/2021

Ref. No : CRF No:1157,Dt:15/07/2021


Sample Details : Harden Concrete Cores ''M30 Grade''
Sample Description : Construction of 2BHK Diginity House at Ambedkar Nagar(Ramgopal pet) Sanath Nagar Constitnency
Sample Qty : 09 No's
Test Required : Compression Test

Test Result
Mechanical Testing :
Buliding Materials :
Average
Equivalent
Equivalent
Corrected Cube
Original Core Cube
Core Observed Core comp. Correction Cyl. Comp.
Sl. Heidht length** Dia (d) l/d Comp.
Core Identification Load Strength # factor for Comp. Strength +
No (H) Ratio Strength +
(l) (mm) (mm) (kN) (N/sq.mm) (l/d) ratio+ Strength +
(mm) +
(N/sq.mm) (N/sq.mm)
(N/sq.mm)
Individual
Individual
Block – E (Nala
1 178 168 119 296 26.61 1.41 0.9.5 24.9 31.1
Side)
In Between Block
2 152 141 119 298 26.89 1.18 0.910 24.4 30.5
– C&D (Nala Side)
Block –C (Nala
3 190 166 119 319 28.68 1.39 0.933 26.8 33.5
Side)
Block- B (Nala
4 164 148 119 293 26.34 1.24 0.917 24.2 30.2
Side)
Block – A (Nala
5 150 132 119 317 28.50 1.11 0.902 25.7 32.1 32.7
Side)
Before Block- A
6 170 142 119 306 27.51 1.19 0.911 25.1 31.3
(Nala Side)
Block- A (Fron-
7 193 176 119 389 34.98 1.48 0.943 33.0 41.2
Footpath)
Block-B (Front-
8 170 145 119 323 29.04 1.22 0.914 26.5 33.2
Road Side)
Block-C (Front
9 196 172 119 294 26.43 1.45 0.939 24.8 31.0
Road Side)
*Details as furnished by the customer
** Core length / weight after trimming and capping: Core length may increase or decrease when compared to extracted core length after
capping.
+For l/d ratio, correction factors are as per Figure – 1 of IS: 516 – 1959 (Reaffirmed 2013).
++ Equivalent cube compressive strength = 1.25 x corrected cylinder compressive strength as per IS: 516 – 1959 (Reaffirmed 2013).
#After correction factor applied for diameter of core which is less than 100mm (i.e., strength of core x 1.08) as per SP 24-1983,
Clause 16.3.2.
Acceptance Criteria as per IS: 456 – 2000 (RA : 2011): Concrete cores tested shall be considered acceptable if the average
equivalent cube strength of the cores is equal to at least 85 percent of the cube strength of the grade of concrete
specified for the corresponding age and no individual core has a strength less than 75 percent.
**END OF REPORT**
For SANRAY LABORATORIES PVT LTD
Authorized Signatory

REMARKS The sample is submitted by the customer. *IBR Approved Laboratory


The results printed on the report are limited only to the sample submitted.
The report cannot be used for any legal purpose.