You are on page 1of 1

CLIENT: CELEC EP - TRANSELECTRIC

BATTERY TYPE: VRLA NUMBER OF CELLS: 24 x BANCO

CAPACITY : 200 Ah Equipment type : FP40R30 100 48 V

BATTERY 1 BATTERY 2
Cell Cell Cell Cell Cell Cell Cell Cell
N° Vot N° Volt N° Volt N° Volt

1 2,071 21 2,071 1 2,068 21 2,069


2 2,072 22 2,070 2 2,071 22 2,072
3 2,070 23 2,073 3 2,070 23 2,069
4 2,071 24 2,070 4 2,072 24 2,069
5 2,070 25 -- 5 2,072 25 --
6 2,071 26 -- 6 2,074 26 --
7 2,073 27 -- 7 2,070 27 --
8 2,073 28 -- 8 2,070 28 --
9 2,069 29 9 2,069 29
10 2,073 30 10 2,072 30
11 2,073 31 11 2,072 31
12 2,075 32 12 2,070 32
13 2,072 33 13 2,069 33
14 2,072 34 14 2,069 34
15 2,073 35 15 2,069 35
16 2,072 36 16 2,067 36
17 2,070 37 17 2,068 37
18 2,069 38 18 2,070 38
19 2,070 39 19 2,069 39
20 2,070 40 20 2,071 40

OVERALLVOLTAGE B1: 49,67V OVERALLVOLTAGE B2 : 49,64V ROOM TEMPERATURE : 22°C


BATT1: CURRENT : 31 A TIME OF THE READING: First cell : 2,071 Last cell : 2,070
BATT2: CURRENT : 29 A TIME OF THE READING: First cell : 2,068 Last cell : 2,069
COMMENTS : La prueba de descarga se realizó por el lapso de 30 minutos con una carga de 60 Amp.
……………………………………………………………………………………………………………………………………..

COMPANY INSPECTION EMERSON / PROTECOMPU INSPECTION CUSTOMER


NETWORK POWER IS
NAME Rodrigo Torres B. Alvaro Cevallos
DATE 07/junio/2016 07/junio/2016

SIGNATURE

Date : Origin : Checked by : Approval by :


PCT 6.30
Page 1/1
Reference :
BATTERY COMMISSIONING
INS-E 09 EN Ind. 7
DISCHARGE TEST
Revision Date : 01/08/2014
Model Reference : IMP00-006 EN