You are on page 1of 1

CLIENT: CELEC EP – TRANSELECTRIC

BATTERY TYPE: VRLA NUMBER OF CELLS: 24 x BANCO

CAPACITY : 200 Ah Equipment type : FP40R30 100 48V

BATTERY 1 BATTERY 2
Cell Cell Cell Cell Cell Cell Cell Cell
N° Vot N° Volt N° Volt N° Volt

1 2,264 21 2,251 1 2,255 21 2,258


2 2,247 22 2,249 2 2,242 22 2,250
3 2,262 23 2,259 3 2,251 23 2,255
4 2,249 24 2,267 4 2,251 24 2,265
5 2,254 25 -- 5 2,251 25 --
6 2,239 26 -- 6 2,254 26 --
7 2,246 27 -- 7 2,243 27 --
8 2,247 28 -- 8 2,255 28 --
9 2,255 29 9 2,254 29
10 2,243 30 10 2,245 30
11 2,261 31 11 2,247 31
12 2,243 32 12 2,255 32
13 2,265 33 13 2,246 33
14 2,242 34 14 2,252 34
15 2,238 35 15 2,256 35
16 2,246 36 16 2,257 36
17 2,250 37 17 2,258 37
18 2,262 38 18 2,254 38
19 2,262 39 19 2,256 39
20 2,253 40 20 2,247 40

OVERALLVOLTAGE B1: 54,05V OVERALLVOLTAGE B2 : 54,06V ROOM TEMPERATURE : 22°C


BATT1: CURRENT : 0,0 A TIME OF THE READING: First cell : 2,264 Last cell : 2,267
BATT2: CURRENT : 0,0 A TIME OF THE READING: First cell : 2,255 Last cell : 2,265
COMMENTS : ……………………………………………………………………………………………………………………
……………………………………………………………………………………………………………………………………..

COMPANY INSPECTION EMERSON / PROTECOMPU INSPECTION CUSTOMER


NETWORK POWER IS
NAME Rodrigo Torres B. Alvaro Cevallos
DATE 07/junio/2016 07/junio/2016

SIGNATURE

Date : Origin : Checked by : Approval by :


PCT 5.10
Page 1/1
Reference :
BATTERY COMMISSIONING
INS-E 09 EN Ind. 7
CHARGE
Revision Date : 01/08/2014
Model Reference : IMP00-006 EN

You might also like