Device Maintenance Reports

Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.


Panel Version : 26 Active Project : XLS3000PYM

DeviceMaintenance:Detectors

Active Sensitivity

Active Sensitivity
TypeCode Label

Pre-Alarm Level
Device Address

ExtendedLabel
Custom Label

Pre-Alarm %

Alarm Level
Battery Life
SLC Loop

Alarm %
Peak %
Drift %
1 1 Smoke(Photo) SHF1 CC Piso 7 35 8 0 0 N/A 9 9

1 2 Smoke(Photo) SHF2 CC Piso 7 36 8 0 0 N/A 9 9

1 3 Smoke(Photo) SHF CTO Piso 7 35 13 1 2 N/A 9 9


MAS

1 4 Smoke(Photo) SHF FOSO Piso 7 35 9 0 0 N/A 9 9


ASC SER

1 5 Smoke(Photo) SHF CTO Piso 7 35 8 1 2 N/A 9 9


MAP

1 6 Smoke(Photo) SHF FOSO Piso 7 35 8 0 0 N/A 9 9


ASC CAM

1 7 Smoke(Photo) SHF FOSO Piso 7 35 8 0 0 N/A 9 9


ASC US

1 8 Smoke(Photo) SHF CTO Piso 7 35 9 0 0 N/A 9 9


COMP

1 9 Smoke(Photo) SHF CTO Piso 7 35 13 0 0 N/A 9 9


SIS

1 10 Smoke(Photo) SHF1 COM Piso 7 35 13 0 0 N/A 9 9


COL

1 11 Smoke(Photo) SHF ES Piso 7 36 13 0 0 N/A 9 9


EMER

1 12 Smoke(Photo) SHF2 COM Piso 7 36 13 0 0 N/A 9 9


COL

1 13 Smoke(Photo) SHF3 COM Piso 7 35 8 0 0 N/A 9 9


COL

1 14 Smoke(Photo) SHF CON Piso 5 35 13 0 0 N/A 9 9


510

1 15 Smoke(Photo) SHF CON Piso 5 35 9 0 0 N/A 9 9


511

1 16 Smoke(Photo) SHF CON Piso 5 35 18 0 0 N/A 9 9


512

1 17 Smoke(Photo) SHF CON Piso 5 36 13 0 0 N/A 9 9


513

1 18 Smoke(Photo) SHF CON Piso 5 35 6 0 0 N/A 9 8


509

1 19 Smoke(Photo) SHF CON Piso 5 35 13 0 0 N/A 9 9


508

1 20 Smoke(Photo) SHF CON Piso 5 35 13 0 0 N/A 9 9


507

1 21 Smoke(Photo) SHF CON Piso 5 35 17 0 0 N/A 9 9


506

1 22 Smoke(Photo) SHF CON Piso 5 35 13 0 0 N/A 9 9


505

1 23 Smoke(Photo) SHF CON Piso 5 35 13 0 0 N/A 9 9


504

1 24 Smoke(Photo) SHF CPN Piso 5 35 13 0 0 N/A 9 9


503

1 25 Smoke(Photo) SHF CON Piso 5 35 13 0 0 N/A 9 9


502

1 26 Smoke(Photo) SHF CON Piso 5 35 9 1 2 N/A 9 9


501

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 1 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Active Sensitivity

Active Sensitivity
TypeCode Label

Pre-Alarm Level
Device Address

ExtendedLabel
Custom Label

Pre-Alarm %

Alarm Level
Battery Life
SLC Loop

Alarm %
Peak %
Drift %
1 27 Smoke(Photo) SHF REV Piso 5 35 15 0 0 N/A 9 9
RX

1 28 Smoke(Photo) SHF RX Piso 5 35 9 0 0 N/A 9 9

1 29 Smoke(Photo) SHF HALL Piso 5 35 12 0 0 N/A 9 9


AS

1 30 Heat(Fixed) SHD 0 59 50 0 N/A Fixed N/A


ENTREGA
EST P5

1 31 Heat(Fixed) SHD ALISTA 0 56 54 0 N/A Fixed N/A


MIENTO P5

1 32 Smoke(Photo) SHF HALL Piso 5 35 8 0 0 N/A 9 9


AP

1 33 Smoke(Photo) SHF COOR Piso 5 35 9 0 0 N/A 9 9


SOR

1 34 Smoke(Photo) SHF1 SAL Piso 5 35 13 0 0 N/A 9 9


ESP PC

1 35 Smoke(Photo) SHF2 SAL Piso 5 35 8 0 0 N/A 9 9


ESP

1 37 Smoke(Photo) SHF REC Piso 5 35 13 0 0 N/A 9 9


ORI

1 38 Smoke(Photo) SHF CON Piso 5 35 9 0 0 N/A 9 9


514

1 39 Smoke(Photo) SHF CON Piso 5 35 13 1 2 N/A 9 9


515

1 40 Smoke(Photo) SHF CON Piso 5 35 26 0 0 N/A 9 9


516

1 41 Smoke(Photo) SHF CON Piso 5 36 26 0 0 N/A 9 9


517

1 42 Smoke(Photo) SHF CON Piso 5 36 12 0 0 N/A 9 9


518

1 43 Smoke(Photo) SHF CON Piso 5 35 13 1 2 N/A 9 9


519

1 44 Smoke(Photo) SHF CON Piso 5 35 17 1 2 N/A 9 9


520

1 45 Smoke(Photo) SHF CON Piso 5 35 9 0 0 N/A 9 9


521

1 46 Smoke(Photo) SHF CON Piso 5 35 13 1 2 N/A 9 9


522

1 47 Smoke(Photo) SHF CON Piso 5 35 13 0 0 N/A 9 9


523

1 48 Smoke(Photo) SHF CON Piso 5 35 13 0 0 N/A 9 9


524

1 49 Smoke(Photo) SHF CON Piso 5 35 9 0 0 N/A 9 9


525

1 50 Smoke(Photo) SHF2 SAL Piso 5 35 9 0 0 N/A 9 9


ESP

1 51 Smoke(Photo) SHF3 SAL Piso 5 35 8 0 0 N/A 9 9


ESP

1 52 Smoke(Photo) SHF ESTERI Piso 5 35 0 0 0 N/A 8 8


LZACION

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 2 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Active Sensitivity

Active Sensitivity
TypeCode Label

Pre-Alarm Level
Device Address

ExtendedLabel
Custom Label

Pre-Alarm %

Alarm Level
Battery Life
SLC Loop

Alarm %
Peak %
Drift %
1 53 Smoke(Photo) SHF CTO Piso 5 35 9 0 0 N/A 9 9
SIS

1 54 Smoke(Photo) SHF1 SAL Piso 3 36 17 0 0 N/A 9 9


EDA

1 55 Smoke(Photo) SHF PROC Piso 3 35 13 0 0 N/A 9 9


MEN

1 56 Smoke(Photo) SHF ORT Piso 3 36 8 1 2 N/A 9 9

1 57 Smoke(Photo) SHF2 SAL Piso 3 35 13 0 0 N/A 9 9


EDA

1 58 Smoke(Photo) SHF3 SAL Piso 3 35 18 0 0 N/A 9 9


EDA

1 59 Smoke(Photo) SHF CON Piso 3 36 12 0 0 N/A 9 9


304

1 60 Smoke(Photo) SHF CON Piso 3 35 13 0 0 N/A 9 9


303

1 61 Smoke(Photo) SHF CON Piso 3 37 7 1 2 N/A 9 9


302

1 62 Smoke(Photo) SHF CON Piso 3 35 17 0 0 N/A 9 9


301

1 63 Smoke(Photo) SHFCON Piso 3 35 8 0 0 N/A 9 9


PRE DIAG

1 65 Smoke(Photo) SHF REC Piso 3 36 13 1 2 N/A 9 9


OCC

1 66 Smoke(Photo) SHF1 HALL Piso 3 36 12 1 2 N/A 9 9


AP

1 67 Smoke(Photo) SHF1 SAL Piso 3 35 13 0 0 N/A 9 9


ESP

1 68 Smoke(Photo) SHF2 SAL Piso 3 46 10 0 0 N/A 9 9


ESP

1 69 Smoke(Photo) SHF REC Piso 3 34 9 0 1 N/A 9 9


ORI

1 70 Smoke(Photo) SHF CON Piso 3 36 12 0 0 N/A 9 9


305

1 71 Smoke(Photo) SHF CON Piso 3 36 12 0 0 N/A 9 9


306

1 72 Smoke(Photo) SHF CON Piso 3 35 13 0 0 N/A 9 9


307

1 73 Smoke(Photo) SHF CON Piso 3 35 8 0 0 N/A 9 9


308

1 74 Smoke(Photo) SHF CON Piso 3 36 13 1 2 N/A 9 9


309

1 75 Smoke(Photo) SHF CON Piso 3 36 26 0 0 N/A 9 9


310

1 76 Smoke(Photo) SHF CON Piso 3 38 9 0 0 N/A 9 9


311

1 77 Smoke(Photo) SHF CON Piso 3 35 9 0 0 N/A 9 9


312

1 78 Smoke(Photo) SHF CON Piso 3 36 17 1 2 N/A 9 9


313

1 79 Smoke(Photo) SHF CON Piso 3 35 13 0 0 N/A 9 9


314

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 3 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Active Sensitivity

Active Sensitivity
TypeCode Label

Pre-Alarm Level
Device Address

ExtendedLabel
Custom Label

Pre-Alarm %

Alarm Level
Battery Life
SLC Loop

Alarm %
Peak %
Drift %
1 80 Smoke(Photo) SHF CON Piso 3 36 17 0 0 N/A 9 9
315

1 81 Smoke(Photo) SHF CON Piso 3 36 12 0 0 N/A 9 9


316

1 82 Smoke(Photo) SHF1 Piso 3 35 13 0 0 N/A 9 9


ADMON

1 83 Smoke(Photo) SHF 2 Piso 3 35 13 0 0 N/A 9 9


ADMON

1 84 Smoke(Photo) SHF3 Piso 3 36 12 1 2 N/A 9 9


ADMON

1 85 Smoke(Photo) SHF3 SAL Piso 3 35 4 0 0 N/A 9 9


ESP

1 87 Heat(Fixed) SHT Piso 3 0 42 33 0 N/A Fixed N/A


CAFETE

1 88 Smoke(Photo) SALA Piso 1 35 21 0 0 N/A 9 9


ESPERA

1 91 Smoke(Photo) SHF TOMA Piso 1 35 20 0 0 N/A 9 9


MUESTRAS

1 92 Smoke(Photo) SHF COOR Piso 1 35 17 0 0 N/A 9 9


LAB

1 93 Smoke(Photo) SHF1 TOMA Piso 1 35 17 0 0 N/A 9 9


MU

1 94 Smoke(Photo) SHF2 TOMA Piso 1 35 13 0 0 N/A 9 9


MU

1 95 Smoke(Photo) SHF3 TOMA Piso 1 35 13 0 0 N/A 9 9


MU

1 96 Smoke(Photo) SHF TOMA Piso 1 35 30 0 0 N/A 9 9


MU E

1 97 Smoke(Photo) SHF REC Piso 1 35 17 0 0 N/A 9 9


VIG

1 98 Smoke(Photo) SHF4 TOMA Piso 1 35 17 0 0 N/A 9 9


MU

1 100 Smoke(Photo) SHF HALL Piso 1 40 26 1 1 N/A 9 9


AP

1 101 Smoke(Photo) SHF1 SAL Piso 1 35 13 0 0 N/A 9 9


ESP PAI

1 102 Smoke(Photo) SHF2 SAL Piso 1 35 13 0 0 N/A 9 9


ESP PAI

1 103 Smoke(Photo) SHF3 SAL Piso 1 35 13 0 0 N/A 9 9


ESP PAI

1 104 Smoke(Photo) SHF4 SAL Piso 1 35 17 0 0 N/A 9 9


ESP PAI

1 105 Smoke(Photo) SHF1 AREA Piso 1 44 15 0 0 N/A 9 9


RECAUDO

1 107 Smoke(Photo) SHF Piso 1 35 13 0 0 N/A 9 9


RECAUDO

1 108 Smoke(Photo) SHF 2 AREA Piso 1 35 9 0 0 N/A 9 9


RECAUDO

1 109 Smoke(Photo) SHF A PAG Piso 1 35 13 0 0 N/A 9 9


MOD11

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 4 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Active Sensitivity

Active Sensitivity
TypeCode Label

Pre-Alarm Level
Device Address

ExtendedLabel
Custom Label

Pre-Alarm %

Alarm Level
Battery Life
SLC Loop

Alarm %
Peak %
Drift %
1 110 Smoke(Photo) SHF A PAG Piso 1 35 24 0 0 N/A 9 9
MOD8

1 111 Smoke(Photo) SHF A PAG Piso 1 35 17 0 0 N/A 9 9


MOD3

1 112 Smoke(Photo) SHF SAL Piso 1 35 13 0 0 N/A 9 9


ESP TM

1 114 Smoke(Photo) SHF SALIDA Piso 1 35 13 0 0 N/A 9 9


EMER RESI

1 116 Heat(Fixed) SHT PQ 31 Sotano 2 0 33 29 0 N/A Fixed N/A

1 117 Smoke(Photo) SHF CTO Sotano 2 35 13 0 0 N/A 9 9


BOM

1 118 Smoke(Photo) SHF Sotano 2 35 13 0 0 N/A 9 9


BODEGA
ASEO

1 119 Smoke(Photo) SHT Sotano 2 36 12 0 0 N/A 9 9


LOCKER
ASEO

1 120 Smoke(Photo) SHT VEST Sotano 2 35 13 0 0 N/A 9 9


M

1 121 Heat(Fixed) SHT PQ 1 Sotano 2 0 36 28 0 N/A Fixed N/A

1 122 Heat(Fixed) SHT PQ 5 Sotano 2 0 36 29 0 N/A Fixed N/A

1 123 Heat(Fixed) SHT PQ 8 Sotano 2 0 36 28 0 N/A Fixed N/A

1 124 Heat(Fixed) SHT PQ 6 Sotano 2 0 36 28 0 N/A Fixed N/A

1 125 Heat(Fixed) SHT PQ 10 Sotano 2 0 33 28 0 N/A Fixed N/A


1 126 Smoke(Photo) SHF T ELEC Sotano 2 35 9 0 0 N/A 9 9

1 127 Heat(Fixed) SHT PQ 14 Sotano 2 0 33 26 0 N/A Fixed N/A

1 128 Heat(Fixed) SHT PQ 17 Sotano 2 0 36 29 0 N/A Fixed N/A

1 129 Heat(Fixed) SHT PQ 20 Sotano 2 0 42 29 0 N/A Fixed N/A

1 130 Smoke(Photo) SHF Sotano 2 35 17 0 0 N/A 9 9


TALLER PIE

1 132 Heat(Fixed) SHT PQ27 Sotano 2 0 36 29 0 N/A Fixed N/A

1 133 Heat(Fixed) SHT PQ27 Sotano 2 0 36 29 0 N/A Fixed N/A

2 1 Smoke(Photo) SHF HALL Piso 6 35 4 0 0 N/A 9 1


AP

2 2 Smoke(Photo) SHF1 SAL Piso 6 36 6 0 0 N/A 9 1


ESP

2 3 Smoke(Photo) SHF2 SAL Piso 6 35 6 0 0 N/A 9 1


ESP

2 4 Smoke(Photo) SHF OF FISICA P6 35 4 0 0 N/A 9 1


TERAPIA

2 5 Smoke(Photo) SHF1 SAL Piso 6 36 6 0 0 N/A 9 1


TER

2 6 Smoke(Photo) SHF2 SAL Piso 6 35 4 0 0 N/A 9 1


TER

2 7 Smoke(Photo) SHF CON Piso 6 36 7 0 0 N/A 9 1


601

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 5 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Active Sensitivity

Active Sensitivity
TypeCode Label

Pre-Alarm Level
Device Address

ExtendedLabel
Custom Label

Pre-Alarm %

Alarm Level
Battery Life
SLC Loop

Alarm %
Peak %
Drift %
2 8 Smoke(Photo) SHF CON Piso 6 35 4 0 0 N/A 9 1
602

2 9 Smoke(Photo) SHF CON Piso 6 35 4 0 0 N/A 9 1


603

2 10 Smoke(Photo) SHF CON Piso 6 35 4 0 0 N/A 9 1


604

2 11 Smoke(Photo) SHF1 TER Piso 6 36 4 0 0 N/A 9 1


FIS

2 12 Smoke(Photo) SHF2 TER Piso 6 35 4 0 0 N/A 9 1


FIS

2 13 Smoke(Photo) SHF2 TER Piso 6 36 4 0 0 N/A 9 1


FIS

2 14 Smoke(Photo) SHF TOMA PLAN COMP P6 36 4 0 0 N/A 9 1


MUEST

2 15 Smoke(Photo) SHF3 SALA ESPERA P6 35 6 0 0 N/A 9 1


DE

2 16 Smoke(Photo) SHF CC Piso 6 35 4 0 0 N/A 9 1

2 17 Smoke(Photo) SHF CON Piso 4 35 4 0 0 N/A 9 1


408

2 18 Smoke(Photo) SHF CON Piso 4 39 3 1 17 N/A 9 1


409

2 19 Smoke(Photo) SHF CON Piso 4 35 4 0 0 N/A 9 1


410

2 20 Smoke(Photo) SHF CON Piso 4 35 7 0 0 N/A 9 1


411

2 21 Smoke(Photo) SHF CON Piso 4 35 4 0 0 N/A 9 1


407

2 22 Smoke(Photo) SHF CON Piso 4 35 3 0 0 N/A 9 1


406

2 23 Smoke(Photo) SHF CON Piso 4 36 4 0 0 N/A 9 1


405

2 24 Smoke(Photo) SHF CON Piso 4 35 4 0 0 N/A 9 1


404

2 25 Smoke(Photo) SHF CON Piso 4 35 4 0 0 N/A 9 1


403

2 26 Smoke(Photo) SHF CON Piso 4 36 4 0 0 N/A 9 1


402

2 27 Smoke(Photo) SHF CON Piso 4 35 4 0 0 N/A 9 1


401

2 29 Smoke(Photo) SHF HALL Piso 4 35 3 0 0 N/A 9 1


AS

2 30 Smoke(Photo) SHF2 Piso 4 36 4 0 0 N/A 9 1


CAPACITA

2 31 Smoke(Photo) SHF HALL Piso 4 35 6 0 0 N/A 9 1


AP

2 32 Smoke(Photo) SHF1 SAL Piso 4 36 4 0 0 N/A 9 1


ESP

2 33 Smoke(Photo) SHF2 SAL Piso 4 36 7 0 0 N/A 9 1


ESP

2 34 Smoke(Photo) SHF REC Piso 4 35 6 0 0 N/A 9 1


ORI

2 35 Smoke(Photo) SHF CON Piso 4 36 4 0 0 N/A 9 1


412

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 6 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Active Sensitivity

Active Sensitivity
TypeCode Label

Pre-Alarm Level
Device Address

ExtendedLabel
Custom Label

Pre-Alarm %

Alarm Level
Battery Life
SLC Loop

Alarm %
Peak %
Drift %
2 36 Smoke(Photo) SHF CON Piso 4 35 3 0 0 N/A 9 1
413

2 37 Smoke(Photo) SHF CON Piso 4 35 4 1 17 N/A 9 1


414

2 38 Smoke(Photo) SHF CON Piso 4 36 4 1 16 N/A 9 1


415

2 39 Smoke(Photo) SHF CON Piso 4 35 4 0 0 N/A 9 1


416

2 40 Smoke(Photo) SHF CON Piso 4 35 3 0 0 N/A 9 1


417

2 41 Smoke(Photo) SHF CON Piso 4 36 7 0 0 N/A 9 1


418

2 42 Smoke(Photo) SHF CON Piso 4 35 7 0 0 N/A 9 1


419

2 43 Smoke(Photo) SHF CON Piso 4 36 4 0 0 N/A 9 1


420

2 44 Smoke(Photo) SHF CON Piso 4 36 4 0 0 N/A 9 1


421

2 45 Smoke(Photo) SHF CON Piso 4 35 4 0 0 N/A 9 1


422

2 46 Smoke(Photo) SHF CON Piso 4 35 3 0 0 N/A 9 1


423

2 47 Smoke(Photo) SHF CON Piso 4 35 3 0 0 N/A 9 1


424

2 49 Smoke(Photo) SHF3 SAL Piso 4 35 3 0 0 N/A 9 1


ESP

2 50 Smoke(Photo) SHF4 SAL Piso 4 36 4 0 0 N/A 9 1


ESP

2 51 Smoke(Photo) SHF REC Piso 4 36 4 0 0 N/A 9 1


OCC

2 52 Smoke(Photo) SHF CC Piso 4 36 4 0 0 N/A 9 1

2 53 Smoke(Photo) SHF HALL Piso 2 36 4 0 0 N/A 9 1


AS

2 54 Smoke(Photo) SHF2 SALA Piso 2 30 3 0 5 N/A 9 1


RX

2 55 Smoke(Photo) SHF1 SALA Piso 2 35 4 0 0 N/A 9 1


RX

2 56 Smoke(Photo) SHF HALL Piso 2 35 7 0 0 N/A 9 1


RX

2 57 Smoke(Photo) SHF Piso 2 35 6 1 17 N/A 9 1


ELECTRO

2 58 Smoke(Photo) SHF2 ECO Piso 2 36 4 0 0 N/A 9 1

2 59 Smoke(Photo) SHF1 ECO Piso 2 36 7 0 0 N/A 9 1

2 60 Smoke(Photo) SHF Piso 2 35 4 0 0 N/A 9 1


COORD
IDIME

2 61 Smoke(Photo) SHF Piso 2 35 4 0 0 N/A 9 1


LOCKER
IDIME

2 62 Smoke(Photo) SHF REC Piso 2 36 4 1 16 N/A 9 1


OCC

2 63 Smoke(Photo) SHF HALL Piso 2 35 7 0 0 N/A 9 1


AP

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 7 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Active Sensitivity

Active Sensitivity
TypeCode Label

Pre-Alarm Level
Device Address

ExtendedLabel
Custom Label

Pre-Alarm %

Alarm Level
Battery Life
SLC Loop

Alarm %
Peak %
Drift %
2 64 Smoke(Photo) SHF1 SAL Piso 2 35 4 0 0 N/A 9 1
ESP

2 65 Smoke(Photo) SHF2 SAL Piso 2 35 6 0 0 N/A 9 1


ESP

2 66 Smoke(Photo) SHF REC Piso 2 35 4 0 0 N/A 9 1


ORI

2 67 Smoke(Photo) SHF VAC Piso 2 35 6 0 0 N/A 9 1


2 68 Smoke(Photo) SHF CON Piso 2 35 6 0 0 N/A 9 1
201

2 69 Smoke(Photo) SHF CON Piso 2 35 3 0 0 N/A 9 1


202

2 70 Smoke(Photo) SHF CON Piso 2 35 4 0 0 N/A 9 1


203

2 71 Smoke(Photo) SHF CON Piso 2 35 4 0 0 N/A 9 1


204

2 72 Smoke(Photo) SHF CON Piso 4 36 6 0 0 N/A 9 1


205

2 73 Smoke(Photo) SHF CON Piso 2 35 4 0 0 N/A 9 1


206

2 74 Smoke(Photo) SHF CON Piso 2 35 6 0 0 N/A 9 1


207

2 75 Smoke(Photo) SHF CON Piso 2 35 6 0 0 N/A 9 1


208

2 76 Smoke(Photo) SHF CON Piso 2 35 4 0 0 N/A 9 1


209

2 77 Smoke(Photo) SHF DEP Piso 2 35 6 0 0 N/A 9 1


AUD

2 78 Smoke(Photo) SHF1 AUD Piso 2 35 4 0 0 N/A 9 1

2 79 Smoke(Photo) SHF2 AUD Piso 2 36 7 1 16 N/A 9 1

2 80 Smoke(Photo) SHF3 SAL Piso 2 36 9 0 0 N/A 9 1


ESP

2 81 Smoke(Photo) SHF DEP RL Piso 2 36 3 0 0 N/A 9 1

2 82 Smoke(Photo) SHF CC Piso 2 35 4 0 0 N/A 9 1

2 83 Smoke(Photo) SHF DEP Piso 2 35 4 0 0 N/A 9 1


INS LAB

2 84 Smoke(Photo) SHF1 PROC Piso 2 35 0 0 0 N/A 9 1


LAB

2 85 Smoke(Photo) SHF2 PROC Piso 2 35 4 0 0 N/A 9 1


LAB

2 86 Smoke(Photo) SHF MICRO Piso 2 36 4 0 0 N/A 9 1

2 87 Smoke(Photo) SHF3 PROC Piso 2 35 4 0 0 N/A 9 1


LAB

2 88 Heat(Fixed) SHT PQ 24 Sotano 1 0 36 29 0 N/A Fixed N/A

2 89 Heat(Fixed) SHT PQ 19 Sotano 1 0 33 29 0 N/A Fixed N/A

2 90 Heat(Fixed) SHT1 P Sotano 1 0 70 42 0 N/A Fixed N/A


ELEC

2 91 Smoke(Photo) SHF2 P Sotano 1 35 4 0 0 N/A 9 1


ELEC

2 92 Heat(Fixed) SHT PQ 16 Sotano 1 0 54 31 0 N/A Fixed N/A

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 8 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Active Sensitivity

Active Sensitivity
TypeCode Label

Pre-Alarm Level
Device Address

ExtendedLabel
Custom Label

Pre-Alarm %

Alarm Level
Battery Life
SLC Loop

Alarm %
Peak %
Drift %
2 93 Smoke(Photo) SHF TAQ Sotano 1 35 4 0 0 N/A 9 1
PQ

2 94 Smoke(Photo) SHF Sotano 1 35 3 0 0 N/A 9 1


BODEGA

2 95 Heat(Fixed) SHT PQ 13 Sotano 1 0 54 31 0 N/A Fixed N/A

2 96 Heat(Fixed) SHT PQ 11 Sotano 1 0 42 31 0 N/A Fixed N/A

2 97 Smoke(Photo) SHF DEP Sotano 1 35 3 0 0 N/A 9 1


2 98 Heat(Fixed) SHT PQ 8 Sotano 1 0 36 31 0 N/A Fixed N/A

2 99 Heat(Fixed) SHT PQ 6 Sotano 1 0 36 31 0 N/A Fixed N/A

2 100 Heat(Fixed) SHT PQ MIN Sotano 1 0 40 33 0 N/A Fixed N/A

2 101 Smoke(Photo) SHF CEN Sotano 1 35 3 0 0 N/A 9 1


GASES

2 102 Heat(Fixed) SHT1 T Sotano 1 0 35 31 0 N/A Fixed N/A


ELEC

2 103 Smoke(Photo) SHF2 T Sotano 1 35 3 0 0 N/A 9 1


ELEC

2 104 Smoke(Photo) SHF SUB Sotano 1 35 3 0 0 N/A 9 1


ELEC

2 105 Heat(Fixed) SHT SUB Sotano 1 0 42 40 0 N/A Fixed N/A


ELEC

2 106 Smoke(Photo) SHF CC Sotano 1 35 3 0 0 N/A 9 1

2 107 Heat(Fixed) SHT CC Sotano 1 0 35 31 0 N/A Fixed N/A

2 109 Smoke(Photo) SHF CONS ESPECIALE P6 35 4 0 0 N/A 9 1


TOMAS

DeviceMaintenance: Detectors-Part2
Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date

1 1 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 2 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 3 2,35 1,5 Occupied No N/A N/A N/A Pass 28/03/2019


%Obs/Ft %Obs/Ft

1 4 2,35 1,5 Occupied No N/A N/A N/A Pass Untested


%Obs/Ft %Obs/Ft

1 5 2,35 1,5 Occupied No N/A N/A N/A Pass 28/03/2019


%Obs/Ft %Obs/Ft

1 6 2,35 1,5 Occupied No N/A N/A N/A Pass Untested


%Obs/Ft %Obs/Ft

1 7 2,35 1,5 Occupied No N/A N/A N/A Pass Untested


%Obs/Ft %Obs/Ft

1 8 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 9 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date
1 9 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022
%Obs/Ft %Obs/Ft

1 10 2,35 1,5 Occupied No N/A N/A N/A Pass 28/02/2022


%Obs/Ft %Obs/Ft

1 11 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 12 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 13 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 14 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 15 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 16 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 17 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 18 2,35 1,33 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 19 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 20 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 21 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 22 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 23 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 24 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 25 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 26 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 27 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 28 2,35 1,5 Occupied No N/A N/A N/A Fail: No Response 5/04/2022


%Obs/Ft %Obs/Ft

1 29 2,35 1,5 Occupied No N/A N/A N/A Fail: No Response 5/04/2022


%Obs/Ft %Obs/Ft

1 30 135 °F N/A Occupied No N/A N/A N/A Fail: No Response Untested

1 31 135 °F N/A Occupied No N/A N/A N/A Fail: No Response Untested

1 32 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 33 2,35 1,5 Occupied No N/A N/A N/A Fail: No Response 5/04/2022


%Obs/Ft %Obs/Ft

1 34 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 10 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date
1 35 2,35 1,5 Occupied No N/A N/A N/A Fail: No Response 4/04/2022
%Obs/Ft %Obs/Ft

1 37 2,35 1,5 Occupied No N/A N/A N/A Fail: No Response 4/04/2022


%Obs/Ft %Obs/Ft

1 38 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 39 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 40 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 41 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 42 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 43 2,35 1,5 Occupied No N/A N/A N/A Pass 20/03/2019


%Obs/Ft %Obs/Ft

1 44 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 45 2,35 1,5 Occupied No N/A N/A N/A Pass 20/03/2019


%Obs/Ft %Obs/Ft

1 46 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 47 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 48 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 49 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 50 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 51 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 52 2,12 1,33 Occupied No N/A N/A N/A Fail: No Response 5/04/2022


%Obs/Ft %Obs/Ft

1 53 2,35 1,5 Occupied No N/A N/A N/A Pass 21/03/2019


%Obs/Ft %Obs/Ft

1 54 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 55 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 56 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 57 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 58 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 59 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 60 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 11 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date
1 61 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022
%Obs/Ft %Obs/Ft

1 62 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 63 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 65 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 66 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 67 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 68 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 69 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 70 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 71 2,35 1,5 Occupied No N/A N/A N/A Pass 16/03/2020


%Obs/Ft %Obs/Ft

1 72 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 73 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 74 2,35 1,5 Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft %Obs/Ft

1 75 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 76 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 77 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 78 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 79 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 80 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 81 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 82 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 83 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 84 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 85 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 87 135 °F N/A Occupied No N/A N/A N/A Pass 21/03/2019

1 88 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 12 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date
1 91 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022
%Obs/Ft %Obs/Ft

1 92 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 93 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 94 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 95 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 96 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 97 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 98 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 100 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 101 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 102 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 103 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 104 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 105 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 107 2,35 1,5 Occupied No N/A N/A N/A Pass Untested


%Obs/Ft %Obs/Ft

1 108 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 109 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 110 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 111 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 112 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 114 2,35 1,5 Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft %Obs/Ft

1 116 135 °F N/A Occupied No N/A N/A N/A Pass 28/03/2019

1 117 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 118 2,35 1,5 Occupied No N/A N/A N/A Pass 28/03/2019


%Obs/Ft %Obs/Ft

1 119 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 120 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 13 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date
1 121 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

1 122 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

1 123 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

1 124 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019


1 125 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

1 126 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 127 135 °F N/A Occupied No N/A N/A N/A Pass 28/03/2019

1 128 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

1 129 135 °F N/A Occupied No N/A N/A N/A Pass Untested

1 130 2,35 1,5 Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft %Obs/Ft

1 132 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

1 133 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

2 1 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 2 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 3 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 4 2,35 Auto Occupied No N/A N/A N/A Pass Untested


%Obs/Ft

2 5 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 6 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 7 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 8 2,35 Auto Occupied No N/A N/A N/A Pass 21/03/2019


%Obs/Ft

2 9 2,35 Auto Occupied No N/A N/A N/A Pass 22/03/2019


%Obs/Ft

2 10 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 11 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 12 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 13 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 14 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 15 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 16 2,35 Auto Occupied No N/A N/A N/A Pass 22/03/2019


%Obs/Ft

2 17 2,35 Auto Occupied No N/A N/A N/A Pass 22/03/2019


%Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 14 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date
2 18 2,35 Auto Occupied No N/A N/A N/A Pass 22/03/2019
%Obs/Ft

2 19 2,35 Auto Occupied No N/A N/A N/A Pass Untested


%Obs/Ft

2 20 2,35 Auto Occupied No N/A N/A N/A Pass 22/03/2019


%Obs/Ft

2 21 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 22 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 23 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 24 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 25 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 26 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 27 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 29 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 30 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 31 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 32 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 33 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 34 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 35 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 36 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 37 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 38 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 39 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 40 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 41 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 42 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 43 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 15 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date
2 44 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021
%Obs/Ft

2 45 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 46 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 47 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 49 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 50 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 51 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 52 2,35 Auto Occupied No N/A N/A N/A Pass 28/03/2019


%Obs/Ft

2 53 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 54 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 55 2,35 Auto Occupied No N/A N/A N/A Pass 22/03/2019


%Obs/Ft

2 56 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 57 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 58 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 59 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 60 2,35 Auto Occupied No N/A N/A N/A Pass 29/01/2022


%Obs/Ft

2 61 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 62 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 63 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 64 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 65 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 66 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 67 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 68 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 69 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 16 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date
2 70 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022
%Obs/Ft

2 71 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 72 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 73 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 74 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 75 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 76 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 77 2,35 Auto Occupied No N/A N/A N/A Pass 22/03/2019


%Obs/Ft

2 78 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 79 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 80 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 81 2,35 Auto Occupied No N/A N/A N/A Pass 22/03/2019


%Obs/Ft

2 82 2,35 Auto Occupied No N/A N/A N/A Pass 9/03/2021


%Obs/Ft

2 83 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 84 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 85 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 86 2,35 Auto Occupied No N/A N/A N/A Pass 22/03/2019


%Obs/Ft

2 87 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 88 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

2 89 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

2 90 135 °F N/A Occupied No N/A N/A N/A Pass 28/03/2019

2 91 2,35 Auto Occupied No N/A N/A N/A Pass 28/03/2019


%Obs/Ft

2 92 135 °F N/A Occupied No N/A N/A N/A Pass 28/03/2019

2 93 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 94 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 95 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

2 96 135 °F N/A Occupied No N/A N/A N/A Pass 28/03/2019

2 97 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.

Page 17 of 18
Device Maintenance Reports
Node Address : 2 : (XLS3000) sábado, 11 de junio de 2022 2:20:17 p. m.
Panel Version : 26 Active Project : XLS3000PYM

Functional Maintenance
Pre-Alarm Level Value
Alarm Level Value

CO-Concentration
Active Sensitivity
Active Sensitivity

Occupancy State

CO-Maintenance
Device Address

Trouble Status
Magnet Test
SLC Loop

CO-State

(ppm)
Date

Date
2 98 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

2 99 135 °F N/A Occupied No N/A N/A N/A Pass 23/03/2019

2 100 135 °F N/A Occupied No N/A N/A N/A Pass 28/03/2019

2 101 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

2 102 135 °F N/A Occupied No N/A N/A N/A Pass 28/03/2019

2 103 2,35 Auto Occupied No N/A N/A N/A Pass 28/03/2019


%Obs/Ft

2 104 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 105 135 °F N/A Occupied No N/A N/A N/A Pass Untested

2 106 2,35 Auto Occupied No N/A N/A N/A Pass 4/04/2022


%Obs/Ft

2 107 135 °F N/A Occupied No N/A N/A N/A Pass 28/03/2019

2 109 2,35 Auto Occupied No N/A N/A N/A Pass 5/04/2022


%Obs/Ft

Honeywell International Inc.https://honeywellprod.sharepoint.com/teams/hbsfire/SitePages/Home.aspx


This Report is compliant with NFPA-72 2007 Edition.