Professional Documents
Culture Documents
16/08/2020
Interactive Awareness
Center
MECHINCAL
DESIGN CRITERIA
Saudi Food TECHNICAL
and Drug Authority
REPORT
TABLE OF CONTENTS
Date:
23/12/2020
2
Date:
23/12/2020
The aim of this report is to outline the design Criteria for Mechanical Works systems, as
described hereinafter.
4.2.1.1 INTRODUCTION:
The purpose of this section is to define the plumbing systems that will serve the project.
The main systems that will be described in follows items:
A. Domestic water supply system.
B. Drainage and vent system.
The Plumbing system shall include cold & hot water supply, sanitary drainage system and
other special plumbing system applicable for the project
The design, installation and testing for Plumbing system shall be in accordance with the
following codes and standards:
a. Water piping shall be sized based on the fixture unit demand with minimum residual
pressure of 20 PSI (to be verified with selected fixtures actual requirements), at most
remote fixture. Maximum velocity in the pipes shall be limited to 1.5 m/s. The water
hammer arrester shall be provided on Hot & Cold-water piping for each group of
fixtures to prevent noise & water surge noise.
- Domestic Cold-Water supply will be obtained from the main water network through
an individual water meter in every floors.
- The existing booster pump set distribute domestic water to all the plumbing fixtures.
3
Date:
23/12/2020
- The sizing of the domestic water supply system will be based on fixture unit method
as per IPC-2018 table -604.3, Table-604.5, Table E103.3(2) and Table E 103.3(3)
Domestic hot water system that shall be applied for the project shall be consisting of
individual Electrical water heater in the ceiling of Private toilets & kitchenette to provide the
hot water to the fixture requiring hot water supply.
- Grey Water supply will be obtained from the main water network in every floor to
flush tanks of Water closets.
- The sizing of the Grey water supply system will be based on fixture unit method same
table of IPC-2018 of Cold-Water Supply.
4
Date:
23/12/2020
g. All floor drains in stores and Mechanical Rooms shall have deep seal
trap with priming line.
4.2.2.1 INTRODUCTION:
To provide an efficient and controlled air-conditioning system utilizing the design criteria
between minimum and maximum limits, to meet the required air volumes and external
resistances.
5
Date:
23/12/2020
Air-conditioning shall mean and include all the processes necessary to bring space to the
required conditions, including cooling, dehumidifying, heating, space ventilation and dust
control.
We will use existing design load as per provided capacity and Air Flow Rate. Cooling Load
and air will be distributed as per assigned zone with terminal VAV unit.
6
Date:
23/12/2020
Our Project will use Existing Air handling units (AHU) and Add Variable Air
Volume (VAV) units System as per space utilization.
4.2.2.5 VENTILATION SYSTEM:
Private toilet Exhaust System will be designated to provide 10 air changes per hour or
25 L/S per water closet whichever is greater or as Per ASHRAE STANDARD-62.1.
Private Toilet, Kitchenette, Copier, Janitor shall be ventilated by connecting of
Existing exhaust ducts and outlets connected to exhaust fans of the exhausting
outside.
All enclosed spaces are ventilated to maintain an acceptable Indoor Air Quality
(IAQ).
The ductwork sizing will be done in accordance with SMACNA standard based on
existing duct size by Equal Friction method.
Duct work will be provided with the required volume dampers for proper balancing of
air system.
Fabrication and installation of duct work shall be carried out as per SMACNA latest
edition.
The type of diffusers or grilles selected for supply, return or extract applications
coordinated with Reflecting ceiling, arrangement of lighting, fittings, and general
aesthetic requirements are well defined.
Air distribution and ductworks, air terminals, sound attenuation and air filtration shall
be strictly in accordance with applicable codes of ASHRAE and SMACNA to achieve
proper air distribution and specified noise criteria in the space. Ducts shall be sized
using equal friction method and air velocities in supply, return and exhaust ducts shall
be from 900 – 1500 FPM. The Air handling units (AHU) shall have a smoke
detection system as per NFPA codes and shall stop in case of fire.
7
Date:
23/12/2020
4.2.3.1 INTRODUCTION:
The purpose of this section is to describe the outline of the firefighting systems that will be
adopted in the project.
Water based Firefighting System, including a Supervised and Automatic Sprinkler System
throughout the Project.
Where Water based fire protection is not applicable, then a Clean Agent Automatic Fire
Protection System shall be provided.
All buildings shall be provided with portable Fire Extinguishers in accordance with-
NFPA-10.
The fire protection systems shall be designed in accordance to the regulations of Local
Civil Defense requirements and NFPA regulations.
The design, installation and testing for Firefighting system shall be in accordance with the
following codes and standards:
8
Date:
23/12/2020
Portable dry chemical extinguishers shall be distributed throughout the building; having a
capacity adequate for occupant use, distributed at distances not exceeding 20m housed
inside dedicated cabinets or inside fire hose cabinets. Extinguisher cabinets to be recessed.
Kitchenette shall be provided with dry powder portable fire extinguisher(s) as per NFPA-
10 requirements.
Portable CO2 fire extinguishers will be provided inside Electrical & Data rooms, and
rooms with electronic equipment.
Must be put post signs to show the locations of fire extinguishers, particularly in large
floor areas where they could be easily blocked from view.
Based on the function of the protected area; sprinklers will be distributed as ordinary
hazard.
Special Hazard Occupancies such as Server Rooms, Control Rooms, Data Center, IT
Rooms, Main Electrical Rooms, shall be protected by a Clean Agent (FM-200) Fire
Suppression System or other approved clean agent, in accordance with NFPA-2001
requirements.