WORK METHOD STATEMENT SUBMISSION

Document
Title
WMS for Level 19 Water Tank Leakages

Work
WMS Ref. No: CBSB/CAPRI/WMS/C&S/046
Package

Date of Revision Date Received By Client /


Submission
15/02/20
No. 0 Consultant
(Chop & Sign)

SUBMITTED BY REVIEWED BY CLIENT / CONSULTANT’S REPLY


Sub-Contractor or NSC Main Contractor

Marcus

___________________ ___________________ ____________________


Name : Name: Marcus Hui Name :
Date : Date : 15/02/2020 Date :
Designation : Designation : P. Engineer Designation :
APPROVAL STATUS

APPROVAL A B C
DATE
APPROVED FOR APPROVED REJECTED
CONSTRUCTION
WITH COMMENT

COMMENTS :

C. C To :
Architect Site -RE / RA / COW –
C & S Eng Site – SPM / PM --
M & E Eng HQ – Project --
QS HQ – Contract –
Others HQ – QAQC –
MAIN BUILDING WORKS FOR CADANGAN PEMBANGUNAN 1 BLOK HOTEL 44 TINGKAT (317
BILIK) DENGAN 2 TINGKAT BESMEN YANG MENGANDUNGI: i. 2 TINGKAT LOBI DAN SERVIS
(ARAS TANAH & ARAS 40) ii. 4 TINGKAT RUANG MEKANIKAL DAN RUANG PEKERJA (ARAS 1 -
ARAS 4) iii. 34 TINGKAT HOTEL PENGINAPAN (ARAS 5 - ARAS 38) iv. 6 TINGKAT KEMUDAHAN
REKREASI / KOLAM RENANG (ARAS 39 - ARAS 43, TERMASUK ARAS 40 MEZANIN) v. 1 TINGKAT
RUANG MEKANIKAL LIF (ARAS 44) vi. TEMPAT LETAK KERETA MEKANIKAL BERTINGKAT
Crest Builder (ARAS TANAH - ARAS 18) DI ATAS LOT 790, 791, 792 & 793, JALAN IMBI, SEKSYEN 67, KUALA
S/B LUMPUR, WILAYAH PERSEKUTUAN UNTUK MEGA CAPITAL DEVELOPMENT SDN BHD
Ref. No: CBSB/CAPRI/WMS/C&S/046 Rev: 0 Date: 15/02/2020
WORK METHOD STATEMENT FOR LEVEL 19 WATER TANK LEAKAGES
RECTIFICATION WORKS

1. OBJECTIVE

The main purpose of this method statement is to outline the rectification procedure for Level 19
water tank leakages.

2. Purpose

This method statement describes the procedure to be followed for the rectification works for
Level 19 water tank leakages. This is to ensure that all activities are in full compliance with
requirements as per manufacturer’s standard.

3. Materials

High Pressure Injection Pump


PENTENS PU-300

4. Preparatory Works & Work Methodology

i. To ascertained water tank leakages area and details along with client / consultant’s
representative
ii. Drill the holes for the injector/packer with 150mm spacing c/c along the leakage area in
order to receive the application.
iii. To inject PENTENS PU300 into leakage area by using high pressure (refer to product data
sheet)
iv. Allow 1 hour for initial cure and remove the mechanical packer
v. To patch back the hole by using cementitious grout
7. Safety & Environment

• All HSSE procedure and regulation must be complied


• To provide proper and safe access for inspection and working
• Site personnel must be in proper safety attire e.g. Safety boots and helmets must be worn at
all times
• Proper and adequate lighting to be provided when working at night
• Water ponding must be constantly pumped out and mosquito infestation checked and
controlled
Doc. Ref: QP-15 Form 03
Crest Builder Sdn Bhd
Effective. Date : 30 /05/14
SITE MEMO Rev : 0

Photo No. 1: Water leakages found at Level 19 water tank wall (interior)

Photo No. 2: Water leakages found at Level 19 water tank wall (interior)
Doc. Ref: QP-15 Form 03
Crest Builder Sdn Bhd
Effective. Date : 30 /05/14
SITE MEMO Rev : 0
PENTENS PU-300 Product Data Sheet
One Part Polyurethane

Description Technical & Physical Data


Concrete often cracks. It is inevitably recognized Foam Single part Liquid
and experienced. Concrete construction requires Colour Dark Brown
construction joints and cold joints. All of these Solubility in Water Hydrophobic
unwanted openings in concrete structures may Max. Expansion, % 3000
cause very serious problems of water leakage. Induction Time, 30 Sec
Most of these problems can be economically 20°C/68°F
solved by utilizing the PENTENS Pressure Elongation at break (%) >20
Injection Systems. Its have been proven to (ASTM D 412-98)
accomplish two major purposes: one, is to stop Gel. Time, 40 Sec
water leakage permanently, and the other is to 20°C/68°F
maintain or even restore design strength. Slabs Unconfined Compressive Strength 2000 Psi
(Sand Filled)
on grade, construction or control joints, parking
Corrosiveness Non-Corrosive
garages, manholes, tanks, dams, and many other
Chemical Resistance Resistant to
structures can now be fixed permanently. more organic
Solvent, Mild
Uses Acids, Alkali
and olther.
Areas of application include: Shelf Life 1 year when
- Floor slabs unopened and
- Suspended floors undamaged
- Terraces and balconies Storage Condition Store in a dry
- Patios cool place
- Bathrooms Packaging 20kg pail
- RC gutters and planter boxes
- Swimming pools
- Water tanks Important Notes
- Basements and fountains
- Retaining walls 1. Minimum ambient and substrate temperature
is 5oC.
Advantages 2. Material Shall be store in a dry cool place.

Negative side application possible


Deep penetration into very small cracks
Foam increases in volume to fill cavities and voids
Adjustable gel times
Excellent bond to wet surfaces
Underwater injection approved
Good elastic strength, tolerant of movement
Inert after curing, constant volume, no shrinkage
Does not create new cracks
Non-toxic.

Disclaimer. All representations and recommendations set forth are given in good faith and to the best of our knowledge. However due to
varying conditions and applications, the buyer shall conduct its own tests of this product before use. Under no circumstances will the
manufacturer be liable for any loss or damages caused by incorrect usages. The sale of this product shall be on terms and conditions set
forth on Pentens order acknowledgement.
Product Data Sheet

Instruction for Use Step 6 : Clean Up


Once the injection work is completed, a good
and thorough clean up is essential. The packers
Step 1 : Clean Surface
can be removed within 1 hour and the holes
Sometimes the concrete surface is hidden under a
should be use PENTENS T-800 to patched.
surface of mineral deposits left from long-term
water leakage. For more details, please refer to our Technical
Department.
Step 2 : Drilling Injection Holes
In order to inject the resin into the crack, it is Cleaning
necessary to install injection ports, also called Tools and equipment just can be clean with
mechanical packers. Thinner immediately after use.
The depth of the drill hole intersecting the crack
should be somewhere close to the center of
structure, if possible. Safety
Step 3 : Insert Injection Packers Impervious gloves and barrier cream should be
Place packers in the previously drilled hole, so used when handling these products. Eye
that the top of the rubber sleeve is below the protection should be worn. In case of contact
concrete surface. If the packer can't be pushed with eyes, wash thoroughly with plenty of water
into the hole, tap it in. Tighten the packer with a and seek medical advice if symptoms persist. If
wrench as tight as necessary. contact with skin occurs, it must be removed
before curing takes place. Wash off with an
Step 4 : Flush Crack If Necessary industrial skin clearer followed by plenty of
In some circumstances, it can be very useful to soap and water. Do not use solvent. Ensure
flush the crack with water to improve the adequate ventilation when using these products.
subsequent penetration of the PENTENS
injection resin into thicker walls.

Step 5 : Crack Injection


Choose the proper resin for the correct
application. The nature of the crack / joint and
the conditions at the job site determine the choice
of material. Active water flow at a high rate is
best stopped by using PENTENS PU-300.
Moving cracks and expansion joints should be
injected with PENTENS PU-101. Hairline
cracks and dry cracks should be sealed using
PENTENS T-800. Some problems are solved by
using a combination of products.

UFON NANO-CHEMICAL LTD. DONG JI (M) SDN. BHD.


PENTENS No.38, Lane 229, Sec.3, Chang Shing Road,
Luju Shiang, Taoyuan, Taiwan, R.O.C.
No. 8, Jalan TPP 5/7, Taman Perindustrian Puchong,
47100 Puchong Selangor, Malaysia.
Tel: +886 3 324 0722 Fax: +886 3 324 0942 Tel: +603 8060 4396 Fax: +603 8060 4394
URL: www.pentens.com URL: www.pentens.com
E-mail: pentens@ms35.hinet.net E-mail: dongji@tm.net.my