TEST REPORT FOR POWER

TRANSFORMER
Location: POWER TRANSFORMER ROOM

LARSEN & TOUBRO LTD. DATE : 12/10/2019

CLIENT: M/s. INDIAN OIL CORPORATION LIMITED - IOCL.


PROJECT : LPG BOTTLING PLANT AT GORKHPUR, UP Sheet No 1 of 4

Location: POWER TRANSFORMER

i. GENERAL DETAILS

NAME PLATE DETAILS


Serial No. : - DT6272/ 01 Make : - CG Power & Industrial Solution
Ltd.
Manufacturing : - 10/2018 Total Mass : - 5800 Kg
Year
Rated Power : - 1600 KVA Location : Power Transformer
:
Rated Voltage : - 11000 V (HV) Rated : - 83.98 A (HV)
Current
: - 433 V (LV) : - 2133.4 A (LV)

No. of Phase :-3 Frequency : - 50 Hz


Winding : - Copper Type of : - ONAN
Material cooling
Temperature : - 40°C (OIL) & 45°C (WDG) Impedance : - 6.48 % (HV-LV)
rise
Type of tap : - OFF load tap charger Vector group : - Dyn11
charger

ii. INSULATION RESISTANCE TEST

Reference IR value in G ohms Polarization Index


Applied Voltage
Winding 60 secs 600 secs PI = 600s/60s
HV – EARTH 5000 V DC 2.98 4.44 1.48
HV – LV 5000 V DC 3.14 6.27 2.0

LV – EARTH 500 V DC >1GΩ - -

iii. WINDING RESISTANCE TEST


LV side OTI: 42 oC WTI: 40 oC
Resistance (mΩ)
Winding
Site value @ 40 °C
2u – 2n 63 mΩ

2v – 2n 62 mΩ

2w – 2n 62 mΩ

Tested By L&T Witnessed by L&T Client by IOCL


Name: SARAVANAN.A Name: Mr. SATYENDRA KUMAR Name:
SIGN : SIGN : SIGN :
TEST REPORT FOR POWER
TRANSFORMER
Location: POWER TRANSFORMER ROOM

LARSEN & TOUBRO LTD. DATE : 12/10/2019

CLIENT: M/s. INDIAN OIL CORPORATION LIMITED - IOCL.


PROJECT : LPG BOTTLING PLANT AT GORKHPUR, UP Sheet No 2 of 4

HV side OTI: 42 oC WTI: 40 oC


Resistance (mΩ)
Tap Site value @ 40 °C
Position
U-V V-W W-U

1(MAX) 176 mΩ 178 mΩ 172 mΩ

2 189 mΩ 189 mΩ 192 mΩ

3(N) 204 mΩ 202 mΩ 206 mΩ

4 214 mΩ 216 mΩ 215 mΩ

5(MIN) 239 mΩ 227 mΩ 228 mΩ

iv. MAGNETISING CURRENT TEST

Tap Applied voltage on HV side (V) Measured current in mA


Position IU – IV 1V – IW 1W – 1U 1U 1V 1W
1(MAX) 409 412 411 11.1 8.3 9.5

3(N) 409 412 411 11.9 8.9 9.9

5(MIN) 409 412 411 12.7 9.3 10.6

v. MAGNETIC BALANCE TEST

Voltage Voltage measured at Voltage measured at


applied HV (V) LV (V)
at 1U-1V 1V-1W 1W-1U 2u-2v 2v-2w 2w-2u
Roff 226 410 184 14.23 13.50 0.908
Yoff 136 270 409 2.94 15.43 12.53

Boff 410 286 123 15.77 3.65 12.12

Tested By L&T Witnessed by L&T Client by IOCL


Name: SARAVANAN.A Name: Mr. SATYENDRA KUMAR Name:
SIGN : SIGN : SIGN :
TEST REPORT FOR POWER
TRANSFORMER
Location: POWER TRANSFORMER ROOM

LARSEN & TOUBRO LTD. DATE : 12/10/2019

CLIENT: M/s. INDIAN OIL CORPORATION LIMITED - IOCL.


PROJECT : LPG BOTTLING PLANT AT GORKHPUR, UP Sheet No 3 of 4

vi. VECTOR GROUP TEST

Short the terminal 1U & 2U & apply 3 phase 415 volts across the HV terminals.

Vector Group: Dyn11

Measured Measured values


Measured values (V) Condition Measured between
between (V)
1U-1V 412 Input 1V-1W 412
1W-1U 411 Input - 0

W1W2 392 < V2W1 410

U12N+ 2NV1 9.22+398 = U1V1 406.8

U1V1 405 = U1W1 406


Vector group Dyn11 is confirmed: YES

vii. VOLTAGE RATIO TEST


Applied Voltage in side Measured voltage in LV side (V) Measured voltage in LV side
Tap
HV (V) AC AC (V) AC
position
1U-1V 1V-1W 1W-1U 2U-2V 2V-2W 2W-2U 2U-2N 2V-2N 2W-2N
1(MAX) 409 412 411 15.6 15.4 15.5 8.7 8.9 8.9
2 410 411 411 16.0 15.9 15.89 9.04 9.01 8.9
3(NOR) 409 412 409 16.35 16.26 16.20 9.31 9.27 9.31
4 409 412 411 16.72 16.72 16.71 9.53 9.57 9.60
5(MIN) 409 412 411 17.2 17.16 17.04 9.72 9.84 9.75

viii. TRANSFORMER AUXILIARY PROTECTION CHECK


Tested By L&T Witnessed by L&T Client by IOCL
Name: SARAVANAN.A Name: Mr. SATYENDRA KUMAR Name:
SIGN : SIGN : SIGN :
TEST REPORT FOR POWER
TRANSFORMER
Location: POWER TRANSFORMER ROOM

LARSEN & TOUBRO LTD. DATE : 12/10/2019

CLIENT: M/s. INDIAN OIL CORPORATION LIMITED - IOCL.


PROJECT : LPG BOTTLING PLANT AT GORKHPUR, UP Sheet No 4 of 4

Protection elements Operation check up to HT PANEL


1. Buchholz Alarm Ok
2. Winding Temperature High Alarm (WTI) Ok
3. Oil Temperature High Alarm Ok
4. MOG Alarm Ok
5. Buchholz Trip Ok
6. Oil Temperature High Trip Ok

ix. GENERAL CHECK

Description Operation check


1. Check for any leakage of oil No
2. Check for any mechanical damage No
3. Check for tightness of terminal & connections Okay
4. Check for condition of silica gel Blue / try

SETTINGS
1. Setting of OTI alarm 85oC
2. Setting of OTI trip 90oC
3. Setting of WTI alarm 95oC
4. Setting of WTI trip 100oC

x. TRANSFORMER IS FIT FOR COMMISSIONING YES

Tested By L&T Witnessed by L&T Client by IOCL


Name: SARAVANAN.A Name: Mr. SATYENDRA KUMAR Name:
SIGN : SIGN : SIGN :