Room Air
Conditioners
Uniflair and EcoBreeze
Air conditioners designed for precision environmental
control of mission-critical applications
^
High Efficiency Room Air Conditioners 2 High Efficiency Room Air Conditioners 3
Room Air
Conditioners Table of Contents
Combining cutting-edge technology with energy efficiency Data Centre Needs Page 7
and environmental sustainability is the basis of Schneider Room Air Conditioners Page 8
ElectricTM Room Air Conditioners, designed to offer a complete
cooling solution for any IT environment. High energy efficiency, Uniflair Page 10
complete reliability, and total flexibility guarantee TCO reduction Uniflair Benefits Page 12
and the integration in Tier III and IV data centres and mission-
critical installations. Uniflair AM-LE Configurations Page 18
EcoBreeze Page 20
All the units are all-in-one for easy design and installation,
EcoBreeze Features and Benefits Page 22
and completely configurable to guarantee use in multiple
applications and environmental conditions for a continuous and Uniflair Mobile Telecom Air Conditioners Page 24
quiet operation.
Room Air Conditioners Portfolio Page 26
Schneider Electric policy is one of continuous technological innovation and the Company therefore reserves the right to amend any data herein without prior notice. The
images shown in this catalogue are for descriptive purposes only. They may therefore differ from specific models which are selected. Some of the features described
may be available only for some models or configurations. Please refer to the specific technical literature for further details.
High Efficiency Room Air Conditioners 4 High Efficiency Room Air Conditioners 5
Flexibility
Modular and tailored solutions for any application
Availability
Continuous operation to safeguard the customer’s business
Energy Saving
Technological excellence for efficient performance
total availability
thanks to innovative according to Uptime
components like Institute certification
* average value in a medium RadiCal EC fans, tandem standards.
data centre in Europe
compressors, EEV valves, *Uniflair CRACs are Tier III and
R-410A refrigerant, and Tier IV ready design.
Room Air
Conditioners
Schneider Electric offers a comprehensive portfolio
of solutions for virtually any cooling need in critical IT
environments, from network closets and server rooms to
data centres of all sizes.
EcoBreezeTM solution
Perfect for racked and non-racked IT loads, these products meet the
diverse requirements of any data centre environment. These intelligent
units monitor the status of components and environmental parameters
to ensure correct functionality during all modes of operation. When
combined with hot-or-cold-aisle containment solutions, Uniflair products
can further improve efficiency and achieve higher densities.
High Energy Efficiency SHR (Sensible Heat Ratio) Close to 1 Compact Dimensions and Simple Reliability
Minimizing operating costs in high-tech installations is The primary objective of precision air conditioning must be Handling/Installation Units ensure reliability through:
becoming more essential than ever in the competitive to dissipate the real heat load in the space. Uniflair LE units are designed with special attention to • Monitoring of all components
marketplace and emphasis on environmental Electronic equipment produces only sensible heat. Any equipment dimensions and to the logistics of handling, • Precise and clear display of any malfunctions or
sustainability is increasing. This means that high energy unwanted latent cooling (dehumidification) provides no installation, and accessibility. Given the very high cost abnormal operating conditions, including a record of the
efficiency is now a key factor in precision air conditioning useful service to the equipment being cooled and is a of space in high-tech environments, it is vital not only last 100 events
and Schneider Electric units have been designed with a considerable waste of energy in itself and in the extra that precision air conditioning has the smallest possible • Management of emergency conditions with ability to
major focus on this objective. energy that may need to be expended to put humidity footprint, but also that there is full frontal component deactivate the operation of heaters and humidifiers in
Low energy consumption is the result of an exhaustive back into the space. access to enable units to be installed next to each other predetermined emergency situations while still maintaining
analysis — from the choice of components to the For this reason Schneider Electric units have been or next to other equipment. Uniflair units represent the basic cooling needs
constant refinement of design solutions. designed to provide a very high ratio of sensible to total industry benchmark — particularly compact, low weight,
cooling (Sensible Heat Ratio). quick and simple to install, and easy to maneuver, even in Flexibility
confined spaces.
Net Sensible Cooling Capacity The control software enables the operation of the unit to
Versatile Configurations
A wide range of configurations has been developed to
give building services engineers maximum design freedom
without the need for expensive solutions.
Versatility is at the heart of the Schneider Electric units,
including:
• Different fan configurations to cover a wide range of
requirements
• A range of filter types and grades
• Different acoustic linings for the panels of the unit casing
• Adaptability to a variety of plant configurations
• Versions available with one or two independent
refrigerant circuits
• Minimal footprint with frontal access for all maintenance
• Minimal service clearance
• Adaptability to a wide range of supervision and network
languages and protocols
• Simple on-site implementation of a variety of
configurations
Tcondensing
conditioning units that are highly energy efficient at outdoor temperature, the greater the energy saving.
part-load. Uniflair LE models (with suffix **21, **42) are Free-cooling is provided without the need to operate compressors and does not depend upon pulling outside air into the
specifically designed with part-load environments in 70°C space (indirect free-cooling). This guarantees stable humidity and air quality in the space.
mind; fitted with two compressors operating in parallel Evaporator Evaporator
on the same circuit, these models offer two stages 60°C 3
COP
4
of cooling on a single circuit of refrigeration. As the A 5
50°C
B 6
evaporator coil surface area (designed for the capacity
Tcondensing Tcondensing
of two compressors) is fixed, one single compressor in 16000
operation (fig. B) benefits from the availability of a “double
5°C 10°C 15°C
Tevaporating
Pressure
Pressure
35
33
31
29
27
25
23
21
19
17
15
13
11
9
7
5
3
1
-1
-3
-5
-7
-9
-11
-13
A B
Tcondensing
External Temperature [°C] Standard unit LEONARDO Energy-saving Unit
(W100%x COP100%) + (W75%x COP75%) + (W50%x COP50%) + (W25%x COP25%)
70°C
100 Evaporator Evaporator
60°C 3
COP
A
4 Comparison of annual power consumption between a standard unit and a unit without a free-cooling system (Space conditions
50°C
B
5
6
24°C, 50% RH at costant load, TDER1822A + 2 x RAL3600 - Frankfurt).
Tcondensing Tcondensing
Tcondensing
Pressure
Uniflair AM-LE units are equipped with sophisticated controls and management software conceived, developed,
implemented, and tested by Schneider Electric. In addition to guaranteeing maximum flexibility in application to any specific
70°C
Tevaporating Tevaporating
project, every control solution is designed to maximize the performance and reliability of the type of unit to which it is fitted.
rator Every component of the unit is monitored in real time, its performance optimized and kept within design parameters. As
Enthalpy Enthalpy
60°C 3 sophisticated as the control algorithms may be, the interface is user friendly and intuitive with an easy-to-read backlit display.
COP
4 B. Part-load Operation The result is a control system that is reliable, flexible, and high performing.
A 5
50°C
B 6
0 0%
35 42 60 70 85 89 110 125 160
Cooling capacity [kW]
Radical Fans EC fan Traditional fan % Energy-saving
Uniflair LE Chilled Water units are equipped with the latest
generation Radical EC Fans for maximum efficiency. Comparison of power consumption between a unit fitted with EC
Impellers are made of high-tech compound material with fans and one with traditional fans (space conditions 24°C, 50%
optimized flow control and high-efficiency GreenTech EC RH at constant load, series TDCR and TDCV).
motors.
7 Radical
EEVs can be integrated with the microprocessor range in all Uniflair models. This innovation provides highly-efficient electronic control of
6 the flow of refrigerant that is unmatched by any traditional mechanical expansion valve. Under the control of the Schneider Electric Control
System, the EEV provides accurate control of the refrigerant superheat to ensure an increase in the COP at low external temperatures;
5 it enables the unit to operate at much lower condensing pressures than would be possible with a traditional mechanical valve. The
4 dehumidification function is also controlled through the operation of the EEV. In this way dehumidification is achieved without a reduction
in the airflow rate, ensuring continuous and uniform air distribution in the space and avoiding any sudden variations in discharge air
3 temperature.
2
Percentage annual reduction in energy consumption of
1 -9,0%
a unit fitted with EEV compared to a traditional version
0 (cooling capacity: 60 kW, Space conditions: 24°C, 50%
RH at constant load, TDAV1822A + 2 x CAL0801).
4500
5000
2700A
1000A
1200A
1700A
2000A
2500A
3400A
4000A
4300A
-5,6%
-6,4% -4,1%
The cooling water may be fed from the mains supply (where
permitted), a cooling tower or a well (i.e. open circuit), or
circulated in a closed loop cooled by external dry-coolers.
In the latter case, an anti-freeze mixture of water and
ethylene glycol is normally used. Water-cooled units have the
advantage that the refrigerant circuits are pre-charged and
sealed in the factory.
This makes system installation extremely simple, eliminating
the need for any site-installed refrigerant pipework.
6000 Hours
5500 Hours
5000 Hours
4500 Hours
4000 Hours
3500 Hours
Modern telephone technology uses equipment that is Intelligent Free-cooling Continuous Operation During
usually housed in shelters or in small- to medium-sized
rooms. These sites form effective technological rooms, The microprocessor control continuously monitors Emergencies
with common needs from which a series of particular the room temperature and the outside environmental Telephone shelters are constructed to guarantee
requirements arise. conditions: if these conditions allow the dissipation of the continuous operation even during power failures.
thermal load, free-cooling is then activated. The free-cooling damper, microprocessor control and
Round the clock operation every day of the year Unlike traditional systems, the free-cooling start-up evaporator fan can also be powered by the UPS in the
temperature varies as the thermal load in the conditioned shelter. During power failures the room is cooled by the
• Highly-reliable equipment
room varies. outside air through the free-cooling damper. Without air
• Reduced running costs
conditioning, the temperature in the racks rises from 45°C
High breakdown costs
to 70°C in less than 15 minutes.
• Rapid intervention Cooling Mechanical Free-cooling Mixed
• Avoidance of critical conditions Compressor ON OFF OFF
Evaporator fan
Expensive equipment Evaporator fan ON ON ON
• Autonomous control of emergencies Minimal discharge air temperature with modulating Condenser fan
damper Rack
• Elimination only of the sensible heat
Compressor
Reduced space
Rack
• High density of thermal loads
Electric heaters
• Protection of the space dedicated to the instruments Rack
Applications in various environments
• Easy installation
• Adaptable for any site
Uniflair Mobile telecom air conditioners provide the features • Automatic power turns on if there is an exceptional
of the most advanced cooling units. thermal load
• Control of the combined operating phases with excellent
energy savings
Connection to Supervision Systems
All the units can be connected to a RS485 serial line by
using an additional card, ensuring complete monitoring of
system. This allows for:
• Control through the Uniflair Netvisor supervision system or
• Connection to a centralised supervision system.
Furthermore, all the units are fitted with digital alarm outputs
(between three and six depending on the model), which
makes it easier to control the status of the cooling unit and
the connection to the external control PLC.
Stand-by operation
Upflow Downflow Upflow Downflow Upflow Downflow Upflow Downflow Upflow Downflow Upflow Downflow Upflow Downflow Ceiling Mounted Wall Mounted
Small
Uniflair AM Uniflair AM Uniflair AM Uniflair AM Uniflair AM Uniflair AM Uniflair WM Uniflair WM Uniflair MB Uniflair MB Uniflair SP Uniflair SP
SUC(C-V) SDC(C-V) SUA(C-V) SDA(C-V) SUW(C-V) SDW(C-V)Page WMA-WDF WDA-WDF- XMA-XMF XDA-XDF UCA-UCF UWA-UWF
Page 28, 30 Page 28, 30 Page 20, 22 Page 20, 22 Page 32, 34 24, 26 Page 59 Page 58 Page 60 Page … Page 62 Page 62
Medium
Uniflair LE Uniflair
LE
Uniflair LE Uniflair LE Uniflair LE Uniflair LE TUT(R-V) TDT(R-V) Uniflair LE Uniflair LE
TUA(R-V) TDA(R-V) TUW(R-V)Page TDW(R-V) [Air-cooled] [air-cooled] TUE(R-V) TDE(R-V)
Page 32, 34 Page 32, 34 36, 38 Page 36, 38 TUD(R-V) TDD(R-V) Page 44, 46 Page 44, 46
Water-cooled] [Water-cooled]
Page 50, 48, Page 50, 48,
52, 54 52, 54
Uniflair LE Uniflair LE
TUC(R-V) TDC(R-V)
Page 40, 42 Page 40, 42
Large
Extra-large
Uniflair LE
HDCV
Page 56 EcoBreeze
Page 65
Uniflair AM
SDAC – SUAC
Uniflair AM
SDAV – SUAV
Uniflair AM
SDWC – SUWC
Uniflair AM
SDWV – SUWV
Uniflair AM
SDCC – SUCC
Uniflair AM
SDCV – SUCV
Uniflair LE
TDAR – TUAR
• The electrical panel is situated in a compartment BMS Height mm 1960 2150 2150 2150 2150 2150 2150
separated from the air flow and complies with the • LON FTT10 serial adaptor to communicate with external Length mm 2170 2580 2580 2580 2580 2580 2580
2006/95/EC directive and related standards. BMS managed with LON protocol Depth mm 865 865 865 865 865 865 865
• Microprocessor control system includes: • TCP/IP serial adaptor to communicate with external TUAR MODEL 2222A 2242A 2522A 2542A 2842A 3342A
- Regulation logic of cooling capacity and airlow BMS managed with SNMP protocol Fans Nr. 3 3 3 3 3 3
integration • AFPS (Automatic Floor Pressurization System) that Airflow m3/h 22154 22154 23467 23467 23068 23068
- Local user terminal with external accessibility permits to adapt its availability as a kit with installation N° of compressors 2 4 2 4 4 4
- Integrated LAN card for local network connection of a instructions Refrigerating Circuits 2 2 2 2 2 2
group of CRACs • Motorized damper Gross Total Cooling
• Suction from the top or front discharge plenums kW 75,4 82,7 86,5 87,5 97,9 108,2
Capacity(1) (2)
• Adjustable floor stands Gross Sensible Cooling
kW 75,4 81,8 85,5 86,4 93,8 95,6
Capacity(1) (2)
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960
Length mm 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865
Uniflair LE
TDAV – TUAV
pressure switch and low airflow differential pressure • RS485 serial adaptor to communicate with external Height mm 1960 2175 2175 2175 2175 2175 2175
switch. BMS Length mm 2170 2580 2580 2580 2580 2580 2580
• The Uniflair LE range offers the possibility to select • LON FTT10 serial adaptor to communicate with external Depth mm 865 865 865 865 865 865 865
units equipped with two compressors (tandem) for each BMS managed with LON protocol TUAV MODEL 2222A 2242A 2522A 2542A 2842A 3342A
circuit,, granting better efficiency and regulation capacity • TCP/IP serial adaptor to communicate with external Fans Nr. 3 3 3 3 3 3
at partial loads (models with the **21 or **42 suffix). BMS managed with SNMP protocol Airflow m3/h 22000 22000 22500 22500 23000 23000
• Total front access is available for unit maintenance. • AFPS (Automatic Floor Pressurization System) that N° of compressors 2 4 2 4 4 4
• The electrical panel is situated in a compartment permits to adapt its availability as a kit with installation Refrigerating Circuits 2 2 2 2 2 2
separated from the air flow and complies with the instructions Gross Total Cooling
• Motorized damper kW 75,3 82,6 86,8 88,3 95,6 105,6
2006/95/EC directive and related standards. Capacity(1) (2)
• Microprocessor control system includes: • Condensate drain pump Gross Sensible Cooling
• Suction from the top or front discharge plenums kW 75,3 81,7 85,8 85,7 91,8 93,6
- Integrated management of the EEV Capacity(1) (2)
and refrigerating circuit parameters • Adjustable floor stands DIMENSIONS
- Local user terminal with external accessibility Height mm 1960 1960 1960 1960 1960 1960
- Integrated LAN card for local network connection Length mm 2580 2580 2580 2580 2580 2580
of a group of CRACs Depth mm 865 865 865 865 865 865
Uniflair LE
TDWR – TUWR
Uniflair LE
TDWV – TUWV
TECHNICAL DATA 1. Gross Cooling capacities;
fans must be deduced to obtain
TDWV –TUWV MODEL 0611A 0921A 1321A 1622A 1822A
Range net cooling data.
Fan type EC Backward-curved centrifugal motor fan
Cooling capacity: 20 ÷ 100 kW Power supply V/ph/Hz 400/3/50Hz 2. Data refers to nominal
conditions : room at 24°C°
Fans Nr. 1 1 2 2 2
Refrigerant R-410A -50% RH, water temperatures
Airflow m3/h 5700 8600 12320 16000 16000
30-35°C, and ESP = 20Pa.
EC Fans N° of compressors 1 2 2 2 2
Available Versions: Refrigerating Circuits 1 1 1 2 2
Gross Total Cooling
- Downflow (TDWV) kW 24,0 32,5 45,6 56,7 62,3
Capacity(1) (2)
- Upflow (TUWV) Gross Sensible Cooling
kW 21,3 28,6 38,1 54,3 55,2
Capacity(1) (2)
DIMENSIONS
Height mm 1960 1960 1960 1960 1960
Length mm 1010 1310 1720 2170 2170
Depth mm 750 865 865 865 750
TDWV MODEL 2242A 2542A 2842A 3342A
Fans Nr. 3 3 3 3
Airflow m3/h 21500 21500 21500 21500
Standard Features equipped with two compressors (tandem) for each circuit,
N° of compressors 4 4 4 4
• Advanced microprocessor control system with a local or which grants better efficiency and regulation capacity at
Refrigerating Circuits 2 2 2 2
remote user terminal. partial loads (models with the **21 or **42 suffix).
Gross Total Cooling
• The units are equipped with EC fans for efficiency • Total front access is available for unit maintenance. kW 85,7 92,3 99,5 110,7
Capacity(1) (2)
maximization. • The electrical panel is situated in a compartment
Gross Sensible Cooling
• The structure of the unit is characterized by a self- separated from the air flow and complies with the kW 81,6 82,8 88,8 90,8
Capacity(1) (2)
supporting frame in galvanized steel with panels. The 2006/95/EC directive and related standards.
DIMENSIONS
external panels are coated with RAL9003 epoxy-polyester • Microprocessor control system includes:
paint* and internally lined with heat and sound-proofing - Integrated management of the EEV Height mm 1960 2150 2150 2150
insulation. and refrigerating circuit parameters Length mm 2580 2580 2580 2580
• Electronic expansion valve is controlled by the - Local user terminal with external accessibility Depth mm 865 865 865 865
microprocessor and a dedicated software that increases - Integrated LAN card for local network connection TUWV MODEL 2242A 2542A 2842A 3342A
the precision of the cooling and the energy efficiency of of a group of CRACs Fans Nr. 3 3 3 3
the cooling cycle. - Rotation and active stand-by management Airflow m3/h 22000 22500 23000 23000
• The cooling coil is designed for an elevated SHR and - Free contact for general and two for addressable N° of compressors 4 4 4 4
reduced pressure drops in the air section. The coil is alarms Refrigerating Circuits 2 2 2 2
made from copper tubes mechanically expanded on - Remote on/off switch Gross Total Cooling
kW 85,9 92,9 100,4 111,7
aluminum fins, complete with a hydrophilic treatment. - Ability to interface with Modbus protocol directly Capacity(1) (2)
• Internal water-cooled condenser braze is welded and on RS485 serial card Gross Sensible Cooling
kW 83,0 85,4 92,9 94,6
Capacity(1) (2)
made of AISI 304 stainless steel. - Ability to interface with main external communication
• Uniflair LE units meet the following directives: 2006/42/ protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP, DIMENSIONS
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC SNMP, and StruxureWareTM platform Height mm 1960 1960 1960 1960
F-GAS regulation. Length mm 2580 2580 2580 2580
• High-efficiency, EU4-pleated air filters are housed in a *RAL5013 may be used during transition period. Depth mm 865 865 865 865
metal frame and equipped with a dirty filter differential
pressure switch and low airflow differential pressure
switch. Construction Options Accessories
• The Uniflair LE range offers the possibility to select units • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Condensation control on refrigerant side with constant • LON FTT10 serial adaptor to communicate with external
water flow BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
46 | High-efficiency Room Air Conditioners 47 | High-efficiency Room Air-Conditioners
Chilled water units with backward-curved fans
Uniflair LE
TDCR – TUCR
Uniflair LE
TDCV – TUCV
CW MODE DX MODE
kW 19,2 23,8 27,0 28,5 30,4 32,1 34,6 RH,water temperature 7/12°C;
Range Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 19,2 21,1 27,0 28,5 28,5 27,9 30,3
Cooling capacity: 20 ÷ 100 kW Capacity(1) (2) 4. Data refers to Downflow unit.
CW MODE DX MODE
kW 37,1 37,3 39,3 47,0 50,2 49,6 55,9
Standard Features • Microprocessor control system includes: Capacity(1) (2)
• Advanced microprocessor control system is available - Integrated management of the EEV and Gross Sensible Cooling
kW 30,3 37,3 39,3 42,3 41,5 49,6 55,9
with local or remote user terminal. refrigerating circuit parameters Capacity(1) (2)
• The units are equipped with backward-curved fans with - Local user terminal with external accessibility Gross Total Cooling
kW 28,3 41,9 41,9 41,9 41,9 54,0 54,0
Capacity(1) (3)
directly-coupled asynchronous motor. - Integrated LAN card for local network connection
Gross Sensible Cooling
• The structure of the unit is characterized by a self- of a group of CRACs kW 28,2 41,7 41,7 41,7 41,7 53,7 53,7
Capacity(1) (3)
supporting frame in galvanized steel with panels. The - Rotation and active stand-by management
DIMENSIONS
external panels are coated with RAL9003 epoxy-polyester - Free contact for general and two for addressable
Height mm 1960 1960 1960 1960 1960 1960 1960
paint* and internally lined with heat and sound-proofing alarms
Length mm 1010 1720 1720 1720 1720 2170 2170
insulation. - Remote on/off switch
Depth mm 750 750 865 865 865 865 865
• Electronic expansion valve is controlled by the - Ability to interface with Modbus protocol directly
TDER MODEL 1822A 2222A(4) 2242A(4) 2522A(4) 2542A(4) 2842A(4)
microprocessor and a dedicated software that increases on RS485 serial card
Fans Nr. 2 3 3 3 3 3
the precision of the cooling and the energy efficiency of - Ability to interface with main external communication
Airflow m3/h 15906 21809 21809 21809 21809 21809
the cooling cycle. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
N° of compressors 2 2 4 2 4 4
• The cooling coil is designed for an elevated SHR and SNMP, and StruxureWareTM platform
Refrigerating Circuits 2 2 2 2 2 2
reduced pressure drops in the air section. The coil is
Gross Total Cooling
CW MODE DX MODE
made from copper tubes mechanically expanded on *RAL5013 may be used during transition period. kW 60,5 78,4 83,6 86,2 87,9 96,0
Capacity(1) (2)
aluminum fins, complete with a hydrophilic treatment.
Gross Sensible Cooling
• The cooling coil is characterized by chilled water Construction Options Capacity(1) (2)
kW 55,8 72,0 78,3 75,0 75,5 77,7
and direct expansion circuits interlaced to increase the • Immersed electrode humidifier (D/U versions) Gross Total Cooling
• Low surface temperature electrical heaters with kW 54,0 97,6 97,6 97,6 97,6 97,6
efficiency of the unit in all running conditions. Capacity(1) (3)
• Unit is equipped with an indirect free cooling system extended fans, complete with double safety thermostat Gross Sensible Cooling
kW 53,7 96,7 96,7 96,7 96,7 96,7
that provides the required cooling capacity when the and manual resetting (T/H versions) Capacity(1) (3)
external temperature is lower than the internal ambient. • Hot gas and hot water reheating DIMENSIONS
Compressor power consumption is minimized while • Condensation control on refrigerant side with constant
Height mm 1960 2150 2150 2150 2150 2150
internal and external environments are kept separate. water flow
Length mm 2170 2580 2580 2580 2580 2580
• Internal water-cooled condenser braze is welded and Depth mm 750 750 865 865 865 865
made of AISI 304 stainless steel. Accessories
TUER MODEL 2222A 2242A 2522A 2542A 2842A
• Uniflair LE units meet the following directives: 2006/42/ The units can be supplied with the following external
Fans Nr. 3 3 3 3 3
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC accessories:
Airflow m3/h 22160 22160 23194 23194 23194
F-GAS regulation. • Remote, semi-graphic user terminal
N° of compressors 2 4 2 4 4
• High-efficiency, EU4-pleated air filters are housed in a • RS485 serial adaptor to communicate with external
Refrigerating Circuits 2 2 2 2 2
metal frame and equipped with a dirty filter differential BMS
Gross Total Cooling
CW MODE DX MODE
pressure switch and low airflow differential pressure • LON FTT10 serial adaptor to communicate with external kW 78,5 83,8 86,8 88,7 96,8
Capacity(1) (2)
switch. BMS managed with LON protocol
Gross Sensible Cooling
• TCP/IP serial adaptor to communicate with external kW 72,7 79,2 77,8 78,3 80,4
• The Uniflair LE range offers the possibility to select units Capacity(1) (2)
equipped with two compressors (tandem) for each circuit, BMS managed with SNMP protocol Gross Total Cooling
kW 98,8 98,8 102,3 102,3 102,3
• AFPS (Automatic Floor Pressurization System) that Capacity(1) (3)
which grants better efficiency and regulation capacity at
partial loads (models with the **21 or **42 suffix). permits to adapt its availability as a kit with installation Gross Sensible Cooling
kW 97,9 97,9 101,3 101,3 101,3
instructions Capacity(1) (3)
• Total front access is available for unit maintenance.
• Motorized damper DIMENSIONS
• The electrical panel is situated in a compartment
separated from the air flow and complies with the • Condensate drain pump Height mm 1960 1960 1960 1960 1960
2006/95/EC directive and related standards. • Suction from the top or front discharge plenums Length mm 2580 2580 2580 2580 2580
• Adjustable floor stands Depth mm 750 865 865 865 865
CW MODE DX MODE
kW 19,1 23,7 27,0 28,4 30,4 32,2 34,6 RH,water temperature 7/12°C;
Capacity(1) (2)
Range glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 19,1 20,8 27,0 28,4 28,7 28,0 30,5 4. Data refers to Downflow unit.
Cooling capacity: 20 ÷ 100 kW Capacity(1) (2)
Gross Total Cooling
Refrigerant R-410A kW 20,2 20,2 28,5 28,5 28,5 28,5 28,5
Capacity(1) (3)
EC Fans Gross Sensible Cooling
kW 20,1 20,1 28,3 28,3 28,3 28,3 28,3
Capacity(1) (3)
Available Versions:
DIMENSIONS
- Downflow (TDEV) Height mm 1960 1960 1960 1960 1960 1960 1960
- Upflow (TUEV) Length mm 1010 1010 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865
TDEV –TUEV MODEL 1022A 1121A 1122A 1321A 1322A 1422A 1622A
Fans Nr. 1 1 2 2 2 2 2
Airflow m3/h 8600 12320 12320 12320 12320 16000 16000
N° of compressors 2 2 2 2 2 2 2
Refrigerating Circuits 2 1 2 1 2 2 2
Gross Total Cooling
CW MODE DX MODE
kW 37,1 36,9 39,2 46,6 49,7 49,7 55,9
Standard Features • Microprocessor control system includes: Capacity(1) (2)
• Evoluted microprocessor control system is available with - Integrated management of the cooling modes Gross Sensible Cooling
kW 30,4 36,9 37,4 40,3 39,9 49,7 55,9
Capacity(1) (2)
local or remote user terminal. monitoring room temperature, external temperature
Gross Total Cooling
• The units are equipped with EC fans for efficiency and glycol circuit temperature; kW 28,5 40,1 40,1 40,1 40,1 54,1 54,1
Capacity(1) (3)
maximization. - Integrated management of the EEV and
Gross Sensible Cooling
• The structure of the unit is characterized by a self- refrigerating circuit parameters kW 28,3 39,9 39,9 39,9 39,9 53,9 53,9
Capacity(1) (3)
supporting frame in galvanized steel with panels. The - Local user terminal with external accessibility DIMENSIONS
external panels are coated with RAL9003 epoxy-polyester - Integrated LAN card for local network connection
Height mm 1960 1960 1960 1960 1960 1960 1960
paint* and internally lined with heat and sound-proofing of a group of CRACs
Length mm 1010 1720 1720 1720 1720 2170 2170
insulation. - Rotation and active stand-by management
Depth mm 750 750 865 865 865 865 865
• Electronic expansion valve is controlled by the - Free contact for general and two for addressable
TDEV MODEL 1822A 2222A(4) 2242A(4) 2522A(4) 2542A(4) 2842A(4)
microprocessor and a dedicated software that increases alarms
Fans Nr. 2 3 3 3 3 3
the precision of the cooling and the energy efficiency of - Remote on/off switch
Airflow m3/h 16000 21500 21500 21500 21500 21500
the cooling cycle. - Ability to interface with Modbus protocol directly
N° of compressors 2 2 4 2 4 4
• Unit is equipped with an indirect free cooling system on RS485 serial card
Refrigerating Circuits 2 2 2 2 2 2
that provides the required cooling capacity when the - Ability to interface with main external communication
Gross Total Cooling
CW MODE DX MODE
external temperature is lower than the internal ambient. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP, kW 60,5 78,2 83,5 86,1 87,7 95,8
Capacity(1) (2)
Compressor power consumption is minimized while SNMP, and StruxureWareTM platform Gross Sensible Cooling
kW 56,0 71,3 77,6 74,4 74,9 77,1
internal and external environments are kept separate. Capacity(1) (2)
• The cooling coil is designed for an elevated SHR and *RAL5013 may be used during transition period. Gross Total Cooling
kW 54,1 96,6 96,6 96,6 96,6 96,6
reduced pressure drops in the air section. The coil is Capacity(1) (3)
made from copper tubes mechanically expanded on Construction Options Gross Sensible Cooling
kW 53,9 95,7 95,7 95,7 95,7 95,7
• Immersed electrode humidifier (D/U versions) Capacity(1) (3)
aluminum fins, complete with a hydrophilic treatment.
• The cooling coil is characterized by chilled water • Low surface temperature electrical heaters with DIMENSIONS
and direct expansion circuits interlaced to increase the extended fans, complete with double safety thermostat Height mm 1960 2150 2150 2150 2150 2150
efficiency of the unit in all running conditions. and manual resetting (T/H versions) Length mm 2170 2580 2580 2580 2580 2580
• Internal water-cooled condenser braze is welded and • Hot gas and hot water reheating Depth mm 750 750 865 865 865 865
made of AISI 304 stainless steel TUEV MODEL 2222A 2242A 2522A 2542A 2842A
• Uniflair LE units meet the following directives: 2006/42/ Accessories
Fans Nr. 3 3 3 3 3
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC The units can be supplied with the following external
Airflow m3/h 22000 22000 22000 22500 22500
F-GAS regulation accessories:
N° of compressors 2 4 2 4 4
• High-efficiency, EU4-pleated air filters are housed in a • Remote, semi-graphic user terminal
Refrigerating Circuits 2 2 2 2 2
metal frame and equipped with a dirty filter differential • RS485 serial adaptor to communicate with external
Gross Total Cooling
CW MODE DX MODE
equipped with two compressors (tandem) for each circuit, • TCP/IP serial adaptor to communicate with external Gross Total Cooling
kW 98,3 98,3 98,3 100,0 100,0
BMS managed with SNMP protocol Capacity(1) (3)
which grants better efficiency and regulation capacity at
• AFPS (Automatic Floor Pressurization System) that Gross Sensible Cooling
partial loads (models with the **21 or **42 suffix) kW 97,4 97,4 97,4 99,0 99,0
Capacity(1) (3)
• Total front access is available for unit maintenance permits to adapt its availability as a kit with installation
instructions DIMENSIONS
• The electrical panel is situated in a compartment
• Motorized damper Height mm 1960 1960 1960 1960 1960
separated from the air flow and complies with the
• Condensate drain pump Length mm 2580 2580 2580 2580 2580
2006/95/EC directive and related standards
• Suction from the top or front discharge plenums Depth mm 750 865 865 865 865
• Adjustable floor stands
54 | High-efficiency Room Air Conditioners 55 | High-efficiency Room Air-Conditioners
Twin cool air-cooled units with backward-curved fans
Uniflair LE
TDTR – TUTR
DX MODE
kW 23,6 30,3 46,1 58,5 63,4 82,5 81,7 91,2 RH,water temperature 7/12°C;
Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 20,9 28,5 38,3 55,3 55,3 78,1 73,8 76,3 4. Data refers to Downflow unit.
Capacity(1) (2)
Gross Total Cooling
CW MODE
kW 20,5 28,3 38,6 53,9 53,9 97,6 97,3 97,6
Capacity(1) (3)
Gross Sensible Cooling
kW 20,4 28,2 38,4 53,7 53,7 96,7 96,4 96,7
Capacity(1) (3)
DIMENSIONS
Standard Features • The Uniflair LE range offers the possibility to select units Height mm 1960 1960 1960 1960 1960 2150 2150 2150
• Advanced microprocessor control system is available equipped with two compressors (tandem) for each circuit, Length mm 1010 1310 1720 2170 2170 2580 2580 2580
with local or remote user terminal. which grants better efficiency and regulation capacity at Depth mm 750 865 865 865 750 865 865 865
• The units are equipped with Backward-curved fans and partial loads (models with the **21 or **42 suffix). TUTR MODEL 2242A 2542A 2842A
directly-coupled asynchronuos motor. • Total front access is included for unit maintenance. Fans Nr. 3 3 3
• The structure of the unit is characterized by a self- • The electrical panel is situated in a compartment Airflow m3/h 22160 23194 23194
supporting frame in galvanized steel with panels. The separated from the air flow and complies with the N° of compressors 4 4 4
external panels are coated with RAL9003(*)epoxy- 2006/95/EC directive and related standards. Refrigerating Circuits 2 2 2
polyester paint* and internally lined with heat and sound- • Microprocessor control system includes: Gross Total Cooling
DX MODE
- Integrated management of the EEV and kW 82,7 82,5 91,9
proofing insulation. Capacity(1) (2)
• Unit is characterized by two independent cooling refrigerating circuit parameters Gross Sensible Cooling
kW 79,0 77,1 79,0
sources - one chilled water with related circuit and one - Local user terminal with external accessibility Capacity(1) (2)
direct expansion air cooled. - Integrated LAN card for local network connection Gross Total Cooling
CW MODE
kW 98,8 102,3 102,3
• Electronic expansion valve is controlled by the of a group of CRACs Capacity(1) (3)
microprocessor and a dedicated software that increases - Rotation and active stand-by management Gross Sensible Cooling
kW 97,9 101,3 101,3
the cooling precision and the energy efficiency of the - Free contact for general and two for addressable Capacity(1) (3)
cooling cycle. alarms DIMENSIONS
• The cooling coil is designed for an elevated SHR and - Remote on/off switch Height mm 1960 1960 1960
reduced pressure drops in the air section. The coil is - Ability to interface with Modbus protocol directly Length mm 2580 2580 2580
made from copper tubes mechanically expanded on on RS485 serial card Depth mm 865 865 865
aluminum fins, complete with a hydrophilic treatment. - Ability to interface with main external communication
• Uniflair LE units meet the following directives: 2006/42/ protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC SNMP, and StruxureWareTM platform
F-GAS regulation.
• High-efficiency, EU4-pleated air filters are housed in a *RAL5013 may be used during transition period.
metal frame and equipped with a dirty filter differential
pressure switch and low airflow differential pressure Construction Options Accessories
switch. • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• LON FTT10 serial adaptor to communicate with external
BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
56 | High-efficiency Room Air Conditioners 57 | High-efficiency Room Air-Conditioners
Twin cool air-cooled units with Backward-curved fans equipped with EC motor
Uniflair LE
TDTV – TUTV
DX MODE
kW 23,5 30,3 46,5 58,5 63,4 82,4 81,6 91,0 RH,water temperature 7/12°C;
Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 20,6 28,7 39,8 55,6 55,5 77,4 73,4 75,7
Capacity(1) (2)
Gross Total Cooling
CW MODE
kW 20,2 28,5 40,1 54,1 54,1 96,6 96,6 96,6
Capacity(1) (3)
Gross Sensible Cooling
kW 20,1 28,3 39,9 53,9 53,9 95,7 95,7 95,7
Capacity(1) (3)
DIMENSIONS
Standard Features pressure switch and low airflow differential pressure Height mm 1960 1960 1960 1960 1960 2150 2150 2150
• Advanced microprocessor control system is available switch. Length mm 1010 1310 1720 2170 2170 2580 2580 2580
with local or remote user terminal. • The Uniflair LE range offers the possibility to select units Depth mm 750 865 865 865 750 865 865 865
• The units are equipped with EC fans for efficiency equipped with two compressors (tandem) for each circuit, TUTV MODEL 2242A 2542A 2842A
maximization. which grants better efficiency and regulation capacity at Fans Nr. 3 3 3
• The structure of the unit is characterized by a self- partial loads (models with the **21 or **42 suffix). Airflow m3/h 22000 22500 22500
supporting frame in galvanized steel with panels. The • Total front access is included for unit maintenance. N° of compressors 4 4 4
external panels are coated with RAL9003(*)epoxy- • The electrical panel is situated in a compartment Refrigerating Circuits 2 2 2
polyester paint* and internally lined with heat and sound- separated from the air flow and complies with the Gross Total Cooling
DX MODE
2006/95/EC directive and related standards. kW 82,6 82,1 91,5
proofing insulation. Capacity(1) (2)
• Electronic expansion valve is controlled by the • Microprocessor control system includes: Gross Sensible Cooling
kW 78,6 75,5 77,6
microprocessor and a dedicated software that increases - Integrated management of the EEV and Capacity(1) (2)
the cooling precision and the energy efficiency of the refrigerating circuit parameters Gross Total Cooling
CW MODE
kW 98,3 100,0 100,0
cooling cycle. - Local user terminal with external accessibility Capacity(1) (3)
• Unit is characterized by two independent cooling - Integrated LAN card for local network connection Gross Sensible Cooling
kW 97,4 99,0 99,0
sources-one chilled water with related circuit and one of a group of CRACs Capacity(1) (3)
direct expansion air cooled. - Rotation and active stand-by management DIMENSIONS
• The cooling coil is designed for an elevated SHR and - Free contact for general and two for addressable Height mm 1960 1960 1960
reduced pressure drops in the air section. The coil is alarms Length mm 2580 2580 2580
made from copper tubes mechanically expanded on - Remote on/off switch Depth mm 865 865 865
aluminum fins, complete with a hydrophilic treatment. - Ability to interface with Modbus protocol directly
• The cooling coil is characterized by chilled water on RS485 serial card
and direct expansion circuits interlaced to increase the - Ability to interface with main external communication
efficiency of the unit in all running conditions. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
• The chilled water circuit is equipped with a three-way SNMP, and StruxureWareTM platform
valve and an actuator integrated with the microprocessor
• Uniflair LE units meet the following directives: 2006/42/ *RAL5013 may be used during transition period.
Construction Options Accessories
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
F-GAS regulation. • Low surface temperature electrical heaters with accessories:
• High-efficiency, EU4-pleated air filters are housed in a extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
metal frame and equipped with a dirty filter differential and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• LON FTT10 serial adaptor to communicate with external
BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
58 | High-efficiency Room Air Conditioners 59 | High-efficiency Room Air-Conditioners
Twin cool water-cooled units with backward-curved fans
Uniflair LE
TDDR – TUDR
DX MODE
kW 23,8 30,4 46,2 55,9 60,5 90,5 87,8 96,0 RH,water temperature 7/12°C;
Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 21,1 28,5 38,8 55,9 55,8 79,7 75,3 77,7 4. Data refers to Downflow unit.
Capacity(1) (2)
Gross Total Cooling
CW MODE
kW 20,5 28,3 38,6 53,9 53,9 97,6 97,3 97,6
Capacity(1) (3)
Gross Sensible Cooling
kW 20,4 28,2 38,4 53,7 53,7 96,7 96,4 96,7
Capacity(1) (3)
DIMENSIONS
Standard Features equipped with two compressors (tandem) for each circuit, Height mm 1960 1960 1960 1960 1960 2150 2150 2150
• Advanced microprocessor control system is available which grants better efficiency and regulation capacity at Length mm 1010 1310 1720 2170 2170 2580 2580 2580
with local or remote user terminal. partial loads (models with the **21 or **42 suffix). Depth mm 750 865 865 865 750 865 865 865
• The units are equipped with Backward-curved fans and • Total front access is included for unit maintenance. TUDR MODELS 2242A 2542A 2842A
directly-coupled asynchronuos motor. • The electrical panel is situated in a compartment Fans Nr. 3 3 3
• The structure of the unit is characterized by a self- separated from the air flow and complies with the Airflow m3/h 22160 23194 23194
supporting frame in galvanized steel with panels. The 2006/95/EC directive and related standards. N° of compressors 4 4 4
external panels are coated with RAL9003(*)epoxy- • Microprocessor control system includes: Refrigerating Circuits 2 2 2
polyester paint* and internally lined with heat and sound- - Integrated management of the EEV and Gross Total Cooling
DX MODE
refrigerating circuit parameters kW 90,6 88,7 96,8
proofing insulation. Capacity(1) (2)
• Electronic expansion valve is controlled by the - Local user terminal with external accessibility Gross Sensible Cooling
kW 80,5 78,3 80,4
microprocessor and a dedicated software that increases - Integrated LAN card for local network connection Capacity(1) (2)
the precision of the cooling and the energy efficiency of of a group of CRACs Gross Total Cooling
CW MODE
kW 98,8 102,3 102,3
the cooling cycle. - Rotation and active stand-by management Capacity(1) (3)
• The cooling coil is designed for an elevated SHR and - Free contact for general and two for addressable Gross Sensible Cooling
kW 97,9 101,3 101,3
reduced pressure drops in the air section. The coil is alarms Capacity(1) (3)
made from copper tubes mechanically expanded on - Remote on/off switch DIMENSIONS
aluminum fins, complete with a hydrophilic treatment. - Ability to interface with Modbus protocol directly Height mm 1960 1960 1960
• Internal water-cooled condenser braze is welded and on RS485 serial card Length mm 2580 2580 2580
made of AISI 304 stainless steel. - Ability to interface with main external communication Depth mm 865 865 865
• Uniflair LE units meet the following directives: 2006/42/ protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC SNMP, and StruxureWareTM platform
F-GAS regulation.
• High-efficiency, EU4-pleated air filters are housed in a *RAL5013 may be used during transition period.
metal frame and equipped with a dirty filter differential
pressure switch and low airflow differential pressure
switch. Construction Options Accessories
• The Uniflair LE range offers the possibility to select units • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Condensation control on refrigerant side with constant • LON FTT10 serial adaptor to communicate with external
water flow BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
60 | High-efficiency Room Air Conditioners 61 | High-efficiency Room Air-Conditioners
Twin cool water-cooled units with backward-curved fans equipped with EC motor
Uniflair LE
TDDV – TUDV
DX MODE
kW 23,7 30,4 46,6 55,9 60,5 90,3 87,7 95,8 RH,water temperature 7/12°C;
Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 20,8 28,7 40,3 55,9 56,0 79,0 74,9 77,1 4. Data refers to Downflow unit.
Capacity(1) (2)
Gross Total Cooling
CW MODE
kW 20,2 28,5 40,1 54,1 54,1 96,6 96,6 96,6
Capacity(1) (3)
Gross Sensible Cooling
kW 20,1 28,3 39,9 53,9 53,9 95,7 95,7 95,7
Capacity(1) (3)
DIMENSIONS
Standard Features • High-efficiency, EU4-pleated air filters are housed in a Height mm 1960 1960 1960 1960 1960 2150 2150 2150
• Advanced microprocessor control system is available metal frame and equipped with a dirty filter differential Length mm 1010 1310 1720 2170 2170 2580 2580 2580
with local or remote user terminal. pressure switch and low airflow differential pressure Depth mm 750 865 865 865 750 865 865 865
• The units are equipped with EC fans for efficiency switch. TUDV MODEL 2242A 2542A 2842A
maximization. • The Uniflair LE range offers the possibility to select units Fans Nr. 3 3 3
• The structure of the unit is characterized by a self- equipped with two compressors (tandem) for each circuit, Airflow m3/h 22000 22500 22500
supporting frame in galvanized steel with panels. The which grants better efficiency and regulation capacity at N° of compressors 4 4 4
external panels are coated with RAL9003(*)epoxy- partial loads (models with the **21 or **42 suffix). Refrigerating Circuits 2 2 2
polyester paint* and internally lined with heat and sound- • Total front access is included for unit maintenance Gross Total Cooling
DX MODE
• The electrical panel is situated in a compartment kW 90,6 88,3 96,4
proofing insulation. Capacity(1) (2)
• Electronic expansion valve is controlled by the separated from the air flow and complies with the Gross Sensible Cooling
kW 80,1 76,9 79,0
microprocessor and a dedicated software that increases 2006/95/EC directive and related standards. Capacity(1) (2)
the precision of the cooling and the energy efficiency of • Microprocessor control system includes: Gross Total Cooling
CW MODE
kW 98,3 100,0 100,0
the cooling cycle. - Integrated management of the EEV and Capacity(1) (3)
• Unit is characterized by two independent cooling refrigerating circuit parameters Gross Sensible Cooling
kW 97,4 99,0 99,0
sources- one chilled water with related circuit and one - Local user terminal with external accessibility Capacity(1) (3)
direct expansion air cooled. - Integrated LAN card for local network connection DIMENSIONS
• The cooling coil is designed for an elevated SHR and of a group of CRACs Height mm 1960 1960 1960
reduced pressure drops in the air section. The coil is - Rotation and active stand-by management Length mm 2580 2580 2580
made from copper tubes mechanically expanded on - Free contact for general and two Depth mm 865 865 865
aluminum fins, complete with a hydrophilic treatment. for addressable alarms
• The cooling coil is characterized by chilled water - Remote on/off switch
and direct expansion circuits interlaced to increase the - Ability to interface with Modbus protocol directly
efficiency of the unit in all running conditions. on RS485 serial card
• Internal water-cooled condenser braze is welded and - Ability to interface with main external communication
made of AISI 304 stainless steel. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
• The chilled water circuit is equipped with a three-way SNMP, and StruxureWareTM platform
Construction Options Accessories
valve and an actuator integrated with the microprocessor • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Uniflair LE units meet the following directives: 2006/42/ *RAL5013 may be used during transition period.
• Low surface temperature electrical heaters with accessories:
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
F-GAS regulation. and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Condensation control on refrigerant side with constant • LON FTT10 serial adaptor to communicate with external
water flow BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
62 | High-efficiency Room Air Conditioners 63 | High-efficiency Room Air-Conditioners
Chilled water units with backward-curved fans equipped with EC motor; fan module can be installed under or above raised floor
Uniflair LE
HDCV
Uniflair WM Uniflair WM
WDA - WDF WMA – WMF
Range Range
Cooling capacity: 6 ÷ 15 kW Cooling capacity: 3.9 ÷ 16.9 kW
Refrigerant R407C Refrigerant R407C
Available Versions: Available Versions:
- Without direct free-cooling (WDA) - Without direct free-cooling (WMA)
- With direct free-cooling (WDF) - With direct free-cooling (WMF)
Standard Features • The external screws are stainless steel, anti-tamper and Standard Features can only be removed using special tools.
• Monoblock conditioning units can be installed on the can only be removed using special tools. • Monoblock conditioning units are installed on the • The double external paneling is available in galvanized,
outside wall of the air conditioned room. • The double external paneling is available in galvanized, outside wall of the air conditioned room painted sheet steel and gives separate access to the fan
• Built-in air condenser is included. The units can be painted sheet steel and gives separate access to the fan • Air condenser is built in. The units can be supplied compartment and electric board compartments. This
supplied completely assembled and filled with refrigerant; compartment and electric board compartments. This completely assembled and filled with refrigerant enables maintenance and regulation to be carried out
all the components are set in the factory for normal enables maintenance and regulation to be carried out • All the components are set in the factory for normal without having to turn the unit off.
working conditions and the electrical and cooling without having to turn the unit off. working conditions. Electrical and cooling functions • Power Supply:
functions are tested. Installation only requires simple • Power Supply: are all tested. Installation only requires simple electrical - 230V/1/50Hz or 400V/3+N/50Hz (standard, according
electrical wiring and mechanical fixing to the shelter, even - 400V/3+N/50Hz standard wiring and mechanical fixing to the shelter, even by non- to the model)
by non-specialized personnel. on Request specialized personnel - Main power supply + UPS 230V
• The direct free-cooling units (WMF) are supplied with a - 230V/1/50Hz on 221 and 341 models • The direct free-cooling units (WMF) are supplied with a - Main power supply + UPS
motorized damper. During free-cooling the excess air is - Main power supply + UPS 48VDC (evaporator DC-fan/s) motorized damper. During free-cooling the excess of air - 48VDC (evaporator DC-fan/s)
expelled from the room through the condenser section • Microprocessor control is expelled from the room through the condenser section • Microprocessor control
without using any extra over-pressure dampers. • Scroll compressor without using extra over-pressure dampers • Scroll compressor (rotary for 0121 model) housed in
• Complete access to all the components allows servicing • EU4 filter (optional) • Complete access to all the components so that compartment isolated from the airflow
entirely from the outside, without having to enter the room • Modulating condenser fan/s speed control servicing can be entirely done from the outside, without • EU4 filter (optional)
which is normally protected by controlled access. • Free-cooling metal pre-filter having to enter the room which is normally protected by • Modulating condenser fan/s speed control
controlled access • Free-cooling metal pre-filter
• The external screws are stainless steel, anti-tamper and
Uniflair MB
XMA - XMF – XDA - XDF
Range Range
Refrigerant R407C
Available Versions:
- Ceiling mounted (UCA)
- Ceiling mounted with direct free-cooling (UCF)
- Wall-mounted (UWA)
- Wall-mounted with direct free-cooling (UWF)
Height mm 610 610 610 1230 1230 610 610 610 1230 1230
Width mm 850 850 850 1200 1200 850 850 850 1200 1200
Depth mm 345 345 345 80 80 345 345 345 480 480
Range
Cooling capacity: 7 ÷ 160 kW Range
• High-efficiency, EU4-pleated air filter housed in a metal Weight 1247 kg 7704 kg* 14261 kg*
frame and filter differential pressure switch. Length 2,8 m 6,1 m 12,2 m
• Welded refrigeration connections for rapid and safe Width 1m 2,4 m 2,4 m
connection. IT airflow 5,000 CFM (2360 l/s) 20,000 CFM (9439 l/s) 40,000 CFM (18878 l/s)
• Condensers are powered by the internal unit to grant Outside airflow 7,000 CFM (3304 l/s) 28,000 CFM (13215 l/s) 56,000 CFM (26429 l/s)
operation at 208V - 230V with a tolerance of +/-10%. Nominal cooling capacity 50 kW 200 kW 400 kW
Power supply V/ph/Hz 208-230/1/50Hz 2. Measured in free field Air econ w/heat wheel 1,1 503,999 48% 3. Bin weather data Saint Louis,
conditions at 5 meters from Water cooled chiller with econ 1,14 728,195 70% MO, USA
Performance capacity (1) kW 8,2 9,8 12,8 16,6 20,2 27,6 33,7 44,5
the unit
Air flow rate at 0.08in.w (20Pa) m3/h 3050 2750 3300 6100 9150 9150 8250 10980 Air cooled chiller with econ 1,16 846,039 81%
4. Does not reflect humidification
Number of circuits 1 1 1 1 1 1 1 1 Fresh air econ 1,14 718,159 69% losses
Noise level (2) dB(A) 51 50,5 51,5 53,2 52,6 54,6 54,1 54,6 DX fluid cooled CRAC w/econ 1,2 1,044,073 100%
5.Fan control proportional to IT
DIMENSIONS Nominal cooling capacity 50 kW 200 kW 400 kW load of design
Height mm 732 732 1067 1227 1227 1877 1877 2277
Width mm 350 350 350 350 350 350 350 350
Depth mm 700 700 700 700 700 700 700 700
CAP MODEL 1802 2002 3002 4002 5002 6002 7002
Fan type Axial
Power supply V/ph/Hz 208-230/1/50Hz
Performance capacity (1) kW 61,3 67 88,7 96,4 127,9 145,8 166,7
Air flow rate at 0.08in.w (20Pa) m3/h 17500 16900 27500 26250 35000 45000 42250
Number of circuits 2 2 2 2 2 2 2
Noise level (2) dB(A) 61 61 63 63 64 65 65
DIMENSIONS
Height mm 2217 2217 3217 3217 4217 5217 5217
Width mm 400 400 400 400 400 400 400
Depth mm 700 700 700 700 700 700 700
Good design and quality construction alone do not ensure a highly available and
efficient data center. Data centers require ongoing monitoring and management
to ensure the facility lives up to its design intent. StruxureWare™ for Data
Centers is a software management suite designed to collect and manage data
about a data center’s assets, resource use, and operational status throughout
the life cycle of the facility. This information is then distributed, integrated, and
applied in ways that help managers optimize the data center’s performance
and meet IT, business, and service-oriented goals. From IT assets to racks,
rows, rooms, and buildings, StruxureWare for Data Centers delivers the right
information to the right users at the right time.
Control level
Experts, on-site or remotely, can control process performance
and ensure business continuity in real time, while tracking energy
consumption in a highly critical and secure environment.
Operations level
Functional managers can optimize operations, energy, and assets
through smart analytical tools, often spanning multiple sites.
Enterprise level
C-level executives can drive their sustainability strategy efficiently,
choosing the best scenario that meets their business objective to
conserve enterprise-wide resources.