You are on page 1of 39

High-efficiency

High Efficiency Room Air Conditioners 1

Room Air
Conditioners
Uniflair and EcoBreeze
Air conditioners designed for precision environmental
control of mission-critical applications

^
High Efficiency Room Air Conditioners 2 High Efficiency Room Air Conditioners 3

Room Air
Conditioners Table of Contents

Combining cutting-edge technology with energy efficiency Data Centre Needs Page 7
and environmental sustainability is the basis of Schneider Room Air Conditioners Page 8
ElectricTM Room Air Conditioners, designed to offer a complete
cooling solution for any IT environment. High energy efficiency, Uniflair Page 10
complete reliability, and total flexibility guarantee TCO reduction Uniflair Benefits Page 12
and the integration in Tier III and IV data centres and mission-
critical installations. Uniflair AM-LE Configurations Page 18

EcoBreeze Page 20
All the units are all-in-one for easy design and installation,
EcoBreeze Features and Benefits Page 22
and completely configurable to guarantee use in multiple
applications and environmental conditions for a continuous and Uniflair Mobile Telecom Air Conditioners Page 24
quiet operation.
Room Air Conditioners Portfolio Page 26

Uniflair AM Technical Data Sheets Page 28

Uniflair LE Technical Data Sheets Page 40

Uniflair WM Technical Data Sheets Page 66

Uniflair MB Technical Data Sheets Page 68

Uniflair SP Technical Data Sheets Page 70

Active Floor Technical Data Sheets Page 71

Uniflair CAP Technical Data Sheets Page 72

EcoBreeze Technical Data Sheets Page 73

StruxureWare for Data Centres Page 74

Schneider Electric policy is one of continuous technological innovation and the Company therefore reserves the right to amend any data herein without prior notice. The
images shown in this catalogue are for descriptive purposes only. They may therefore differ from specific models which are selected. Some of the features described
may be available only for some models or configurations. Please refer to the specific technical literature for further details.
High Efficiency Room Air Conditioners 4 High Efficiency Room Air Conditioners 5

Flexibility
Modular and tailored solutions for any application

Availability
Continuous operation to safeguard the customer’s business

Energy Saving
Technological excellence for efficient performance

Make the most of your energySM


High Efficiency Room Air Conditioners 6 Data Centre Needs

Efficiency and Sustainability Infrastructure Management


Data centres represent one of the highest energy- Data centres are complex environments; providing
consuming elements within the electrical chain. complete systems composed of integrated elements
The objective is — therefore —to optimize the operation of guarantees compatibility, a single source of responsibility,
this infrastructure, reduce energy consumption, maximize and strategic integration of a regulated system.
efficiency, and minimize CO2 emissions. This is a departure from the traditional logic of single
For the cooling system to provide increased flexibility and elements and a move towards a situation where all of Keeping up with
significant improvement in energy consumption metrics the operating parameters can be optimized (both energy
growing heat
(e.g. PUE), it is important that the structure presents a and operational) through integrated logics (internal units,
densities
7 while
significant level of efficiency not only at nominal loads, but distribution systems, and external units). The cooling
system must then be able to communicate with the
reducing operating
also at partial loads.
various building management systems. costs is today’s
Indirect free cooling solutions should be proposed
challenge.
whenever possible, as well as optimization systems
according to the heat load in the room. Reliability Schneider Electric Room
Air Conditioners rise to this
A fundamental requirement for each data centre is to challenge because energy
Modularity and Flexibility guarantee continuous operation and total reliability. This efficiency, availability, and
flexibility are the priorities.
New server technology has introduced an increased level is achieved thanks to the design and implementation
of cooling systems which are intrinsically reliable and Our wide range of products
of modularity in infrastructure growth, adapting to the allows to meet the ooling
needs of the client and facilitating upgrades which are incorporate an appropriate level of redundancy. requirements of every size
difficult to predict long term. System reliability is based on several basic considerations data centre, from small
(below 200 kW) to large
Cooling solutions must therefore allow for modular such as a dual source of cooling and electrical power.
(1MW+), and to apply the
planning and integration and adapt automatically to the right technology according
new load conditions of the room. Cost of Ownership to the IT equipments and
environmenal infrastructure.
A simple infrastructure creates significant advantage in Reduced management and operating costs is a
terms of management costs. This can be achieved by competitive advantage in the data centre market.
using cooling systems which can be implemented over The cooling system accounts for about 40% of the total
time. Another important element that influences operating on-site energy consumption. In addition to reducing
costs and system reliability is system maintenance. A energy consumption, it is also important to reduce the
structure which allows simple maintenance is based costs of maintenance and reconfiguration due to inevitable
on consolidated, tested, and reliable systems and changes in the IT system.
represents an indisputable advantage of simplified system
To improve data centre efficiency in terms of cost, it is
management.
necessary to reduce the initial investment in the system
with an infrastructure that grows in line with real needs
over time.
An increase in the effectiveness of a cooling system allows
auxiliary systems to be precisely “sized” without extra
cost due to the excess power installed. Such CapEx
optimization can be achieved by using a cooling system
that is simply implemented and adapted to changing site
requirements.

Maximum efficiency, 30%*


of annual energy
consumption is reduced
99,99%
is the reliability of Tier III
and Tier IV Data Centres

total availability
thanks to innovative according to Uptime
components like Institute certification
* average value in a medium RadiCal EC fans, tandem standards.
data centre in Europe
compressors, EEV valves, *Uniflair CRACs are Tier III and
R-410A refrigerant, and Tier IV ready design.

Where no failure is allowed


AFPS systems.

7 | High-efficiency Room Air-Conditioners


UniflairTM solution

Room Air
Conditioners
Schneider Electric offers a comprehensive portfolio
of solutions for virtually any cooling need in critical IT
environments, from network closets and server rooms to
data centres of all sizes.

The room air conditioners portfolio includes solutions that


can be integrated a room or building level. A wide range of
options is available to enhance infrastructure efficiency in
any working conditions.

EcoBreezeTM solution

8 | High-efficiency Room Air Conditioners 9 | High-efficiency Room Air-Conditioners


Uniflair
Perimeter cooling for any data centre environments,
with a low cost of ownership
Uniflair AM and Uniflair LE are leading-edge precision cooling solutions
specifically designed to maintain temperature and humidity within
extremely tight tolerances.

Perfect for racked and non-racked IT loads, these products meet the
diverse requirements of any data centre environment. These intelligent
units monitor the status of components and environmental parameters
to ensure correct functionality during all modes of operation. When
combined with hot-or-cold-aisle containment solutions, Uniflair products
can further improve efficiency and achieve higher densities.

10 | High-efficiency Room Air Conditioners 11 | High-efficiency Room Air-Conditioners


Uniflair Benefits

High Energy Efficiency SHR (Sensible Heat Ratio) Close to 1 Compact Dimensions and Simple Reliability
Minimizing operating costs in high-tech installations is The primary objective of precision air conditioning must be Handling/Installation Units ensure reliability through:
becoming more essential than ever in the competitive to dissipate the real heat load in the space. Uniflair LE units are designed with special attention to • Monitoring of all components
marketplace and emphasis on environmental Electronic equipment produces only sensible heat. Any equipment dimensions and to the logistics of handling, • Precise and clear display of any malfunctions or
sustainability is increasing. This means that high energy unwanted latent cooling (dehumidification) provides no installation, and accessibility. Given the very high cost abnormal operating conditions, including a record of the
efficiency is now a key factor in precision air conditioning useful service to the equipment being cooled and is a of space in high-tech environments, it is vital not only last 100 events
and Schneider Electric units have been designed with a considerable waste of energy in itself and in the extra that precision air conditioning has the smallest possible • Management of emergency conditions with ability to
major focus on this objective. energy that may need to be expended to put humidity footprint, but also that there is full frontal component deactivate the operation of heaters and humidifiers in
Low energy consumption is the result of an exhaustive back into the space. access to enable units to be installed next to each other predetermined emergency situations while still maintaining
analysis — from the choice of components to the For this reason Schneider Electric units have been or next to other equipment. Uniflair units represent the basic cooling needs
constant refinement of design solutions. designed to provide a very high ratio of sensible to total industry benchmark — particularly compact, low weight,
cooling (Sensible Heat Ratio). quick and simple to install, and easy to maneuver, even in Flexibility
confined spaces.
Net Sensible Cooling Capacity The control software enables the operation of the unit to

Efficiency is a philosophy that is expressed through


Maintenance be adapted to every type of installation thanks to:
• The facility to input a double set-point for both
clear choices within which the real contributions to the The ease of maintenance of Uniflair units is a fundamental temperature and humidity
equipment cooling capacity must be clearly identified. factor in reducing operating costs and avoiding downtime. • The facility to change fan speed directly from the user
Schneider Electric has made technical choices aimed at The front panels can be opened without the need for terminal (units with EC fans)
solutions that optimize the real contribution of removing special tools and all normal maintenance operations can
• Flexible configurability of alarm outputs
heat from the space — the net sensible capacity (sensible be carried out from the front of the unit. A push-button
cooling minus fan motor heat gains). • The facility to calibrate temperature and humidity
catch ensures easy access to the controls compartment
sensors
while the cover of the electrical panel inside is fitted with a
safety interlocked mains isolator in compliance with safety • The facility to interface with a wide range of BMS
regulations. What is more, the units can be carried out systems
while in operation and without disrupting the airflow.

Versatile Configurations
A wide range of configurations has been developed to
give building services engineers maximum design freedom
without the need for expensive solutions.
Versatility is at the heart of the Schneider Electric units,
including:
• Different fan configurations to cover a wide range of
requirements
• A range of filter types and grades
• Different acoustic linings for the panels of the unit casing
• Adaptability to a variety of plant configurations
• Versions available with one or two independent
refrigerant circuits
• Minimal footprint with frontal access for all maintenance
• Minimal service clearance
• Adaptability to a wide range of supervision and network
languages and protocols
• Simple on-site implementation of a variety of
configurations

12 | High-efficiency Room Air Conditioners 13 | High-efficiency Room Air-Conditioners


Uniflair Benefits

Tandem Energy-saving Units (Free-cooling)


In many applications the room load can vary enormously Energy consumption continues to be a major constituent in the operating costs of modern systems. Guaranteeing maximum
during the course of a single day or from season to reliability in operation at the same time as reducing energy consumption to the minimum is the result of technical product
season. This will cause wide variations in the amount choices.
Condenser Condenser
of cooling required at any given moment. In these The energy-saving versions have been designed to apply this concept to the best effect. The operating principle is based on
circumstances it is very important to use precision air the ability to provide free cooling for a space when the outdoor temperature is below that of the space itself; the lower the
A B

Tcondensing
conditioning units that are highly energy efficient at outdoor temperature, the greater the energy saving.
part-load. Uniflair LE models (with suffix **21, **42) are Free-cooling is provided without the need to operate compressors and does not depend upon pulling outside air into the
specifically designed with part-load environments in 70°C space (indirect free-cooling). This guarantees stable humidity and air quality in the space.
mind; fitted with two compressors operating in parallel Evaporator Evaporator
on the same circuit, these models offer two stages 60°C 3
COP
4
of cooling on a single circuit of refrigeration. As the A 5
50°C
B 6
evaporator coil surface area (designed for the capacity
Tcondensing Tcondensing
of two compressors) is fixed, one single compressor in 16000
operation (fig. B) benefits from the availability of a “double
5°C 10°C 15°C
Tevaporating

Pressure

Pressure

Power absorption [KWh]


sized” evaporator coil. This maximization of the cooling 14000
effect leads to increases in part load efficiencies and a 12000
rise in the part-load COP (Coefficient of Performance). To Tevaporating Tevaporating
compare part-load efficiencies of different units, a number 10000
of parameters have been developed which take into Enthalpy Enthalpy
account the COP at 25, 50, 75, and 100 per cent load 8000
and calculate a weighted mean. These parameters (IPLV: A. 100% Operation
6000
Integrated Partial Load Value, EMPE: Efficienza Media
Ponderata in Regime Estivo, and SEER: Seasonal Energy 4000
Efficiency Ratio) differ in their weightings and the operating
conditions at which the different COPs are calculated, but
2000
Condenser Condenser
they all follow the same formula. 0

35
33
31
29
27
25
23
21
19
17
15
13
11
9
7
5
3
1
-1
-3
-5
-7
-9
-11
-13
A B

Tcondensing
External Temperature [°C] Standard unit LEONARDO Energy-saving Unit
(W100%x COP100%) + (W75%x COP75%) + (W50%x COP50%) + (W25%x COP25%)

70°C
100 Evaporator Evaporator
60°C 3
COP
A
4 Comparison of annual power consumption between a standard unit and a unit without a free-cooling system (Space conditions
50°C
B
5
6
24°C, 50% RH at costant load, TDER1822A + 2 x RAL3600 - Frankfurt).
Tcondensing Tcondensing
Tcondensing

5°C 10°C 15°C


Tevaporating Total Control
Pressure

Pressure

Uniflair AM-LE units are equipped with sophisticated controls and management software conceived, developed,
implemented, and tested by Schneider Electric. In addition to guaranteeing maximum flexibility in application to any specific
70°C
Tevaporating Tevaporating
project, every control solution is designed to maximize the performance and reliability of the type of unit to which it is fitted.
rator Every component of the unit is monitored in real time, its performance optimized and kept within design parameters. As
Enthalpy Enthalpy
60°C 3 sophisticated as the control algorithms may be, the interface is user friendly and intuitive with an easy-to-read backlit display.
COP
4 B. Part-load Operation The result is a control system that is reliable, flexible, and high performing.
A 5
50°C
B 6

5°C 10°C 15°C


Tevaporating

14 | High-efficiency Room Air Conditioners 15 | High-efficiency Room Air-Conditioners


Uniflair Benefits

EC Fans Automatic Floor Pressurization R-410A


Every component of Uniflair AM and LE ranges has been 8 -50 % System (AFPS) R-410A is similar to a mono-component refrigerant (which
-47%
chosen in accordance with the design criteria of energy Maintaining correct pressurization of the floor space is is near azeotropic), as it is characterized by the absence
7 -45 %
saving for maximum efficiency. Just one example is the -40% a key factor to ensure that the cooling system operates of glide during the change of state, which occurs at a
selection of EC (Electronically Commutated) direct current -40 % with maximum efficiency and that cool air is available constant temperature without energy losses. Thanks to a

Absorbed power [kW]


motors. This new type of fan-motor combination offers a 6 greater heat exchange capacity and a notable decrease
-33% -33% -35 %
where needed. This process must be guaranteed for the
number of advantages over traditional types: entire lifetime of a server room that may be upgraded and in pressure drops, it is possible to maximize the size of
• Lower power consumption on the fan side 5 -27% the exchangers while increasing efficiency. Moreover,
-30 % changed over time.
• High part-load efficiency performance is not affected by separation of the gas
-27% The AFPS, developed and tested by Schneider Electric,
4 -25 % components over time. In fact, any refrigerant leaks and
• Fan speed adjustment via the microprocessor control enables structural flexibility through automatic adjustment
-20% -24% subsequent integrations do not affect performance and
while the unit is running -20 % of the airflow according to the servers which have been
3 -18% can be managed quickly and effectively without replacing
• Ability to regulate airflow depending on the actual installed. AFPS automatically adjusts the airflow of
-15 % the whole refrigerant charge and without changing the
thermal load the perimeter units that are fitted with EC fans during
2 initial composition.
standard and emergency maintenance, maintaining a
-10 %
constant pressure under the raised floor and avoiding the
1 creation of hot spots.
-5 %

0 0%
35 42 60 70 85 89 110 125 160
Cooling capacity [kW]
Radical Fans EC fan Traditional fan % Energy-saving
Uniflair LE Chilled Water units are equipped with the latest
generation Radical EC Fans for maximum efficiency. Comparison of power consumption between a unit fitted with EC
Impellers are made of high-tech compound material with fans and one with traditional fans (space conditions 24°C, 50%
optimized flow control and high-efficiency GreenTech EC RH at constant load, series TDCR and TDCV).
motors.

Room Occupancy (%)

% Savings with AFPS

8 EC Electronic Expansion Valve (EEV)


Power Consumption [kW]

7 Radical
EEVs can be integrated with the microprocessor range in all Uniflair models. This innovation provides highly-efficient electronic control of
6 the flow of refrigerant that is unmatched by any traditional mechanical expansion valve. Under the control of the Schneider Electric Control
System, the EEV provides accurate control of the refrigerant superheat to ensure an increase in the COP at low external temperatures;
5 it enables the unit to operate at much lower condensing pressures than would be possible with a traditional mechanical valve. The
4 dehumidification function is also controlled through the operation of the EEV. In this way dehumidification is achieved without a reduction
in the airflow rate, ensuring continuous and uniform air distribution in the space and avoiding any sudden variations in discharge air
3 temperature.
2
Percentage annual reduction in energy consumption of
1 -9,0%
a unit fitted with EEV compared to a traditional version
0 (cooling capacity: 60 kW, Space conditions: 24°C, 50%
RH at constant load, TDAV1822A + 2 x CAL0801).
4500

5000
2700A
1000A

1200A

1700A

2000A

2500A

3400A

4000A

4300A

Model -8,0% -8,3%


-8,6% -8,9%
-7,8%
-6,9%
-6,9%

-5,6%
-6,4% -4,1%

16 | High-efficiency Room Air Conditioners 17 | High-efficiency Room Air-Conditioners


Uniflair AM-LE Configurations

Upflow unit with Upflow unit with


Upflow Units suction from the suction from the base. Energy-saving Units
front.
Upflow units (with air discharge from the top) are designed to Energy-saving units, available only on Uniflair LE range, represent the ultimate energy-efficient solution in cool or temperate climates.
distribute the conditioned air by means of a plenum, through The operating principle exploits the free-cooling effect available when the outside air temperature is lower than that in the conditioned space
a system of ducts, or via a suspended ceiling. Air intake is — the lower the outside temperature, the greater the energy saving. The sophisticated microprocessor control manages operation of the
normally through the front of the unit, but versions are also unit automatically in three different situations.
available with air return through the rear or via the base. In summer the unit operates as a normal closed circuit glycol-cooled system (Fig. A). As the external temperature falls, the coolant can be
Upflow unit with Upflow unit with
used directly for the free-cooling of the air. In this case the coolant is circulated in the coil inside the unit (Fig. B) and both the refrigerant
suction from the rear.
Downflow Units front discharge
plenum and suction circuit and the glycol circuit contribute to cooling, reducing the energy used by the compressor. If the outside temperature falls further to a
from the front. level where the coolant can dissipate the entire heat load from the room, then the refrigerant circuit is shut down completely and the unit
Downflow units are designed to distribute the conditioned air
functions as a traditional chilled water unit with a modulating valve (Fig. C). With this technology, Energy-saving units provide significant
by means of a raised floor, through a system of ducts, or via a
reductions in operating costs and payback periods.
discharge plenum beneath the unit.

DXA Series Air-cooled Direct Expansion


Units
Air-cooled direct expansion units extract heat from the room
and transfer it to the outside air using air-cooled refrigerant
heat exchangers (condensers). Once installed, the room unit
and external condenser form an autonomous sealed circuit.
The remote condensers used with DX units include precise
electronic fan-speed condensing pressure control to ensure
trouble-free operation of the unit throughout the year under a
very wide range of external air temperatures. Special attention
has been paid to the acoustic design of the condensers Fig. A: Mechanical cooling operation Fig. B: Mixed cooling operation Fig. C: Free-cooling operation
to minimize noise levels. A wide range of combinations is
available to meet different site requirements.
CW Chilled Water Units
DXW Series Water-cooled Direct CW units use the availability of chilled water to control room conditions. CW units have a relatively simple construction and provide
Expansion Units outstanding reliability. The microprocessor controls the modulating action of the 3-way (or optional 2-way) chilled water valve to give
accurate capacity control. Careful sizing of the heat exchanger coils yields a high sensible-to-total cooling ratio under most operating
In water-cooled units the heat extracted from the room is conditions at the appropriate chilled water temperatures.
transferred to water via stainless steel brazed-plate heat
exchangers within the unit.

The cooling water may be fed from the mains supply (where
permitted), a cooling tower or a well (i.e. open circuit), or
circulated in a closed loop cooled by external dry-coolers.
In the latter case, an anti-freeze mixture of water and
ethylene glycol is normally used. Water-cooled units have the
advantage that the refrigerant circuits are pre-charged and
sealed in the factory.
This makes system installation extremely simple, eliminating
the need for any site-installed refrigerant pipework.

Twin-cool Units Chilled Water Units with Underfloor Fans


Twin-Cool units, available only on Uniflair LE range, are fitted CW units with fans located underneath the floor allow for more coil area in the unit and less internal air-side pressure drop. The fan module
with two independent cooling circuits: beneath the unit can be configured in many different airflow patterns as well as be placed beneath or above the raised floor for total
• Chilled water flexibility. More heat exchanger coil and less pressure drop equals less power consumption and more capacity inside a compact footprint.
• Air-cooled or water-cooled direct expansion
This unit is usually used where an installation has a chilled
water source which cannot be relied on to guarantee
continuous service. In this case function priority is given
to the chilled water circuit, with the microprocessor control
automatically starting direct expansion operation if the
chilled water supply fails or if the water is not cold enough to
dissipate the entire heat load.
Alternatively, the unit controls can be set to prioritize direct
expansion cooling, activating chilled water operation only in
the event of a compressor malfunction.
Note: These configurations are shown only as an example.
Twin-Cool units therefore provide a very high level of security,
ensuring continuous system operation at all times and with the
flexibility to manage the cooling resources in the best way for
the particular installation.

18 | High-efficiency Room Air Conditioners 19 | High-efficiency Room Air-Conditioners


EcoBreeze

20 | High-efficiency Room Air Conditioners 21 | High-efficiency Room Air-Conditioners


EcoBreeze

The industry’s only modular, indirect economizer, Modularity


EcoBreeze, is one of several Schneider Electric data
centre facility modules, which help make large data centre • Reduction in CapEx results from right-sizing your cooling
deployment fast and easy. capacity based on current load with the flexibility to
expand later.
• EcoBreeze provides indirect evaporative cooling or air-
• Built-in redundancy from modular form factor allows
to-air heat exchange in one footprint.
extra capacity to be incorporated into the system from the
• Right-sized cooling is made possible by individual
module level to ensure availability at the system level.
modules that can be scaled to capacity as needed.
• Modular design reduces single point of failure issues
The IT airstream is isolated from the outdoor ambient
from the component to the control level.
airstream.
• The modular design prevents routine maintenance or
• Deployment is flexible and cost effective since the unit is break/fix repairs from interfering with system operation.
modular and uses no data centre space.
• The pre-engineered modules can be deployed
according to the data centre’s specific redundancy needs.
Flexible, Easy Installation and
Servicing
• Flexible and cost-effective deployment since the unit
uses zero white space within the data centre Environmentally Friendly
• Easy installation because of a single point of connection • No chemical treatment required due to on-board water
treatment system
EcoBreeze Features and Benefits
for water, power, and communications
• Adaptable installation because it can be deployed with • Zero ozone-depleting proportional R-410A refrigerant
raised or non-raised floor applications system
Innovative Answer to Cooling Efficient and Effective Cooling • Safe and easy capacity expansion and servicing via
Challenges • Right-sized cooling made possible by individual 50 kW individual isolation of air, power, and communications
modules that can be grouped up to a maximum of 200 between the frame and modules
Today’s data centres face unprecedented cooling
challenges brought on by high-density computing. kW and 400 kW of sensible cooling per frame
Blade servers, for example, generate risky hot spots and • Fully adaptable cooling via EC fan technology Internal Isolation of IT Airstream
require a highly efficient, cost-effective cooling solution • Efficient and effective cooling via total internal isolation of
the IT airstream from the outdoor ambient airstream • Isolation of the airstreams prevents airborne pollutants from entering the data centre environment.
to safeguard availability while also streamlining cooling
costs. Cooling also presents environmental challenges. • Regulatory compliance with recommendations and • Maintenance costs are reduced since enhanced filtration requirements aren’t necessary when outside air is not being
With local, regional, and federal standards and regulations requirements for economization and efficiency (e.g. introduced into the data centre environment.
related to energy efficiency, now is the time for data ASHRAE 90.1 in North America) • Operating costs are less from not needing to pretreat the Data Centre air due to variations in outside air dew points
centres to adopt economization (free-cooling) as an associated with 100 per cent outside air.
innovative way to reduce energy consumption. EcoBreeze Adaptability
is the Schneider Electric answer to meeting the latest
cooling and energy efficiency requirements facing today’s
• Ability to address any cooling requirement worldwide via Air-side Free-cooling Map
multiple module and frame voltages/frequencies
Data Centres. This innovative cooling approach employs Estimate of full air-side economizer hours for data centres
a modular design for capacity, redundancy, and service • Adaptability via the integration of multiple cooling options
flexibility. The efficiency of the system is rationalized in in one module footprint (indirect evaporative, air-to-air heat
exchange, and proportional direct expansion) 8500 Hours
three forms of cooling to maximize localized climate
conditions and ensure the most efficient and effective • Ability to control redundancy from the frame down to the 8000 Hours
form of cooling year round. EcoBreeze employs the fully individual module level
adaptable cooling of electronically commutated (EC) fan 7500 Hours
technology, along with an ozone-friendly proportional
refrigerant circuit, making it one of the most efficient forms
7000 Hours
of cooling on the market today. 6500 Hours

6000 Hours

5500 Hours

5000 Hours

4500 Hours

4000 Hours
3500 Hours

Hours of operation based on fully populated 3000 Hours


EcoBreeze (40 ft Frame, 8 modules)
Supply air setpoint of 27°C
2500 Hours
Temperature change across EcoBreeze 17”K 2000 Hours
Full Airflow Capacity 370kW
Operating Load of 247 kW (2/3 Full Airflow)
22 | High-efficiency Room Air Conditioners 23 | High-efficiency Room Air-Conditioners
Uniflair Mobile Telecom Air Conditioners

Modern telephone technology uses equipment that is Intelligent Free-cooling Continuous Operation During
usually housed in shelters or in small- to medium-sized
rooms. These sites form effective technological rooms, The microprocessor control continuously monitors Emergencies
with common needs from which a series of particular the room temperature and the outside environmental Telephone shelters are constructed to guarantee
requirements arise. conditions: if these conditions allow the dissipation of the continuous operation even during power failures.
thermal load, free-cooling is then activated. The free-cooling damper, microprocessor control and
Round the clock operation every day of the year Unlike traditional systems, the free-cooling start-up evaporator fan can also be powered by the UPS in the
temperature varies as the thermal load in the conditioned shelter. During power failures the room is cooled by the
• Highly-reliable equipment
room varies. outside air through the free-cooling damper. Without air
• Reduced running costs
conditioning, the temperature in the racks rises from 45°C
High breakdown costs
to 70°C in less than 15 minutes.
• Rapid intervention Cooling Mechanical Free-cooling Mixed
• Avoidance of critical conditions Compressor ON OFF OFF
Evaporator fan
Expensive equipment Evaporator fan ON ON ON

• Guaranteed control of the environmental conditions Condenser fan ON OFF ON Microprocessor


48VCC control
• Management of critical situations ~
Damper Closed Open Modulating =
• Long life for the system Supply Free-cooling
damper
Unmanned sites 48VCC

• Autonomous control of emergencies Minimal discharge air temperature with modulating Condenser fan

damper Rack
• Elimination only of the sensible heat
Compressor
Reduced space
Rack
• High density of thermal loads
Electric heaters
• Protection of the space dedicated to the instruments Rack
Applications in various environments
• Easy installation
• Adaptable for any site

To satisfy these needs, Schneider Electric has designed


Stand-By Control
various product families to ensure: Up to 10 units can be installed in each shelter, which
• Operational accuracy are linked to each other through the local LAN network,
• Continuous service offering the following benefits:
• Flexibility • Equal wear to the units that are rotated on a timed basis
• Low running costs • The stand-by unit turns on if there is an alarm in the
working unit

Uniflair Mobile telecom air conditioners provide the features • Automatic power turns on if there is an exceptional
of the most advanced cooling units. thermal load
• Control of the combined operating phases with excellent
energy savings
Connection to Supervision Systems
All the units can be connected to a RS485 serial line by
using an additional card, ensuring complete monitoring of
system. This allows for:
• Control through the Uniflair Netvisor supervision system or
• Connection to a centralised supervision system.
Furthermore, all the units are fitted with digital alarm outputs
(between three and six depending on the model), which
makes it easier to control the status of the cooling unit and
the connection to the external control PLC.

Stand-by operation

24 | High-efficiency Room Air Conditioners 25 | High-efficiency Room Air-Conditioners


Room Air Conditioners Portfolio
Monoblock Wall Mounted External
Chilled Water Units Air-cooled Units Water-cooled Units Twin Cool Units Energy-saving Units Monoblock External Installation Units Splitted Units Economizers
Installation Units

Upflow Downflow Upflow Downflow Upflow Downflow Upflow Downflow Upflow Downflow Upflow Downflow Upflow Downflow Ceiling Mounted Wall Mounted

Small

Uniflair AM Uniflair AM Uniflair AM Uniflair AM Uniflair AM Uniflair AM Uniflair WM Uniflair WM Uniflair MB Uniflair MB Uniflair SP Uniflair SP
SUC(C-V) SDC(C-V) SUA(C-V) SDA(C-V) SUW(C-V) SDW(C-V)Page WMA-WDF WDA-WDF- XMA-XMF XDA-XDF UCA-UCF UWA-UWF
Page 28, 30 Page 28, 30 Page 20, 22 Page 20, 22 Page 32, 34 24, 26 Page 59 Page 58 Page 60 Page … Page 62 Page 62

Medium

Uniflair LE Uniflair

LE
Uniflair LE Uniflair LE Uniflair LE Uniflair LE TUT(R-V) TDT(R-V) Uniflair LE Uniflair LE
TUA(R-V) TDA(R-V) TUW(R-V)Page TDW(R-V) [Air-cooled] [air-cooled] TUE(R-V) TDE(R-V)
Page 32, 34 Page 32, 34 36, 38 Page 36, 38 TUD(R-V) TDD(R-V) Page 44, 46 Page 44, 46
Water-cooled] [Water-cooled]
Page 50, 48, Page 50, 48,
52, 54 52, 54

Uniflair LE Uniflair LE
TUC(R-V) TDC(R-V)
Page 40, 42 Page 40, 42

Large

Extra-large

Uniflair LE
HDCV
Page 56 EcoBreeze
Page 65

26 | High-efficiency Room Air Conditioners 27 | High-efficiency Room Air-Conditioners


Direct Expansion air-cooled units with asynchronous motor fans

Uniflair AM
SDAC – SUAC

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 5 ÷ 20 kW SDAC –SUAC MODEL 0151B 0251B 0151A 0251A 0331A 0351A 0501A 0601A
net cooling data.
Fan type Forward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 230/1/50Hz 400/3/50Hz
Available Versions: conditions : room at 24°C-
Fans Nr. 1 1 1 1 2 2 2 2
50% RH , 45°C condensing
Airflow m3/h 1600 1750 1600 1750 3000 3300 4500 4500
- Downflow (SDAC) temperature, and ESP = 20Pa.
N° of compressors 1 1 1 1 1 1 1 1
- Upflow (SUAC) with bottom, front and rear suction Refrigerating Circuits 1 1 1 1 1 1 1 1
Gross Total Cooling
kW 6,6 8,0 6,4 7,9 10,0 13,3 16,9 18,8
Capacity(1) (2)
Gross Sensible Cooling
kW 5,3 6,1 5,2 6,0 9,1 10,6 14,4 15,4
Capacity(1) (2)
DIMENSIONS
Height mm 1740 1740 1740 1740 1740 1740 1740 1740
Length mm 550 550 550 550 850 850 1200 1200
Depth mm 450 450 450 450 450 450 450 450

Standard Features • Total front access is available for unit maintenance.


• Advanced microprocessor control system is included • Electrical panel is situated in a compartment
local or remote user terminal. separatedfrom the air flow and complies with the
• The units are equipped with forward-curved fans and 2006/95/EC directive and related standards.
directly-coupled asynchronuos motor. • Microprocessor control system includes:
• The structure of the unit is characterized by a self- - Local user terminal with external accessibility
supporting frame in galvanized steel with panels. The - Integrated LAN card for local network connection of a
external panels are coated with RAL9003 epoxy-polyester group of CRACs
paint* and internally lined with heat and sound-proofing - Rotation and active stand-by managementt
insulation. - Free contact for general alarm and two for addressable
• The cooling coil is designed for an elevated SHR and alarms
reduced pressure drops in the air section. The coil is - Remote on/off switch
made from copper tubes mechanically expanded on - Ability to interface with Modbus protocol directly on
aluminum fins, complete with a hydrophilic treatment. RS485 serial card
• Uniflair AM units are in conformity with the following - Ability to interface with main external communication
directives: 2006/42/EC, 2004/108/EC, 2006/95/EC, protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
97/23/EC, 842/2006/EC F-GAS regulation. SNMP, and StruxureWareTM platform
• High-efficiency, EU4-pleated air filters are housed in a
metal frame and equipped with a dirty filter differential *RAL5013 may be used during transition period.
pressure switch and low airflow differential pressure Construction Options Accessories
switch. • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with safety thermostat and • Remote, semi-graphic user terminal
manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Electronic expansion valve is controlled by the • LON FTT10 serial adaptor to communicate with external
microprocessor and a dedicated software that increases BMS managed with LON protocol
the precision of the cooling and the energy efficiency of • TCP/IP serial adaptor to communicate with external
the cooling cycle BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

28 | High-efficiency Room Air Conditioners 29 | High-efficiency Room Air-Conditioners


Direct Expansion air-cooled units with EC motor fans

Uniflair AM
SDAV – SUAV

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 5 ÷ 20 kW SDAV –SUAV MODEL 0151B 0251B 0151A 0251A 0331A 0351A 0501A 0601A
net cooling data.
Fan type EC Backward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 230/1/50Hz 400/3/50Hz
EC Fans conditions : room at 24°C-
Fans Nr. 1 1 1 1 2 2 2 2
50% RH , 45°C condensing
Airflow m3/h 1600 1750 1600 1750 3000 3300 4500 4500
Available Versions: temperature, and ESP = 20Pa.
N° of compressors 1 1 1 1 1 1 1 1
- Downflow (SDAV) Refrigerating Circuits 1 1 1 1 1 1 1 1
- Upflow (SUAV) with bottom, front, and rear suction Gross Total Cooling
kW 6,4 8,0 6,4 7,9 10,0 13,3 16,9 18,8
Capacity(1) (2)
Gross Sensible Cooling
kW 5,2 6,1 5,2 6,0 9,1 10,6 14,4 15,4
Capacity(1) (2)
DIMENSIONS
Height mm 1740 1740 1740 1740 1740 1740 1740 1740
Length mm 550 550 550 550 850 850 1200 1200
Depth mm 450 450 450 450 450 450 450 450

Standard Features • Total front access is available for unit maintenance.


• Advanced microprocessor control system is included • Electrical panel is situated in a compartment separate
local or remote user terminal. from the air flow and in compliance with the 2006/95/EC
• The units are equipped with EC fans for efficiency directive and related standards.
maximization. • Microprocessor control system includes:
• The structure of the unit is characterized by a self- - Local user terminal with external accessibility
supporting frame in galvanized steel with panels. The - Integrated LAN card for local network connection of a
external panels are coated with RAL9003 epoxy-polyester group of CRACs
paint* and internally lined with heat and sound-proofing - Rotation and active stand-by management
insulation. - Free contact for general alarm and two for addressable
• The cooling coil is designed for an elevated SHR and alarms
reduced pressure drops in the air section. The coil is - Remote on/off switch
made from copper tubes mechanically expanded on - Ability to interface with Modbus protocol directly on
aluminum fins, complete with a hydrophilic treatment. RS485 serial card
• Uniflair AM units are in conformity with the following - Ability to interface with main external communication
directives: 2006/42/EC, 2004/108/EC, 2006/95/EC, protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
97/23/EC, 842/2006/EC F-GAS regulation. SNMP, and StruxureWareTM platform
• High-efficiency, EU4-pleated air filters are housed in a
metal frame and equipped with a dirty filter differential *RAL5013 may be used during transition period.
pressure switch and low airflow differential pressure Construction Options Accessories
switch. • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with safety thermostat and • Remote, semi-graphic user terminal
manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Electronic expansion valve is controlled by the • LON FTT10 serial adaptor to communicate with external
microprocessor and a dedicated software that increases BMS managed with LON protocol
the precision of the cooling and the energy efficiency of • TCP/IP serial adaptor to communicate with external
the cooling cycle BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

30 | High-efficiency Room Air Conditioners 31 | High-efficiency Room Air-Conditioners


Direct Expansion water-cooled units with asynchronous motor fans

Uniflair AM
SDWC – SUWC

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 5 ÷ 20 kW SDWC –SUWC MODEL 0151B 0251B 0151A 0251A 0331A 0351A 0501A 0601A
net cooling data.
Fan type Forward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 230/1/50Hz 400/3/50Hz
Available Versions: conditions : room at 24°C°
Fans Nr. 1 1 1 1 2 2 2 2
-50% RH, water temperatures
Airflow m3/h 1600 1750 1600 1750 3000 3300 4500 4500
- Downflow (SDWC) 30-35°C, And ESP = 20Pa.
N° of compressors 1 1 1 1 1 1 1 1
- Upflow (SUWC) with bottom, front, and rear Refrigerating Circuits 1 1 1 1 1 1 1 1
suction Gross Total Cooling
kW 6,9 8,3 6,9 8,3 9,8 13,6 17,7 19,4
Capacity(1) (2)
Gross Sensible Cooling
kW 5,4 6,2 5,4 6,2 8,7 10,6 14,7 15,6
Capacity(1) (2)
DIMENSIONS
Height mm 1740 1740 1740 1740 1740 1740 1740 1740
Length mm 550 550 550 550 850 850 1200 1200
Depth mm 450 450 450 450 450 450 450 450

Standard Features • Total front access is available for unit maintenance.


• Advanced microprocessor control system is included • The electrical panel is situated in a compartment
with local or remote user terminal. separated from the air flow and complies with the
• The units are equipped with forward-curved fans and 2006/95/EC directive and related standards.
directly-coupled asynchronuos motor. • Microprocessor control system includes:
• The structure of the unit is characterized by a self- - Local user terminal with external accessibility
supporting frame in galvanized steel with panels. The - Integrated LAN card for local network connection of a
external panels are coated with RAL9003 epoxy-polyester group of CRACs
paint* and internally lined with heat and sound-proofing - Rotation and active stand-by management
insulation. - Free contact for general and two for addressable
• The cooling coil is designed for an elevated SHR and alarms
reduced pressure drops in the air section. The coil is - Remote on/off switch
made from copper tubes mechanically expanded on - Ability to interface with Modbus
aluminum fins, complete with a hydrophilic treatment. protocol directly on RS485 serial card
• Uniflair AM units are in conformity with the following - Ability to interface with main external communication
directives: 2006/42/EC, 2004/108/EC, 2006/95/EC, protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
97/23/EC, 842/2006/EC F-GAS regulation. SNMP, and StruxureWareTM platform
• High-efficiency, EU4-pleated air filters are housed in a
metal frame and equipped with a dirty filter differential *RAL5013 may be used during transition period.
pressure switch and low airflow differential pressure Construction Options Accessories
switch. • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with safety thermostat and • Remote, semi-graphic user terminal
manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Electronic expansion valve is controlled by the • LON FTT10 serial adaptor to communicate with external
microprocessor and a dedicated software that increase BMS managed with LON protocol
sthe precision of the cooling and the energy efficiency of • TCP/IP serial adaptor to communicate with external
the cooling cycle BMS managed with SNMP protocol
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

32 | High-efficiency Room Air Conditioners 33 | High-efficiency Room Air-Conditioners


Direct Expansion water-cooled units with EC motor fans

Uniflair AM
SDWV – SUWV

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 5 ÷ 20 kW SDWV –SUWV MODEL 0151B 0251B 0151A 0251A 0331A 0351A 0501A 0601A
net cooling data.
Fan type EC Backward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 230/1/50Hz 400/3/50Hz
EC Fans conditions: room at 24°C° -50%
Fans Nr. 1 1 1 1 2 2 2 2
RH, water temperatures 30-
Airflow m3/h 1600 1750 1600 1750 3000 3300 4500 4500
Available Versions: 35°C, and ESP = 20Pa.
N° of compressors 1 1 1 1 1 1 1 1
- Downflow (SDWV) Refrigerating Circuits 1 1 1 1 1 1 1 1
- Upflow (SUWV) with bottom, front, and rear suction Gross Total Cooling
kW 6,9 8,4 6,9 8,3 9,8 13,6 17,7 19,4
Capacity(1) (2)
Gross Sensible Cooling
kW 5,4 6,2 5,4 6,2 8,7 10,6 14,7 15,6
Capacity(1) (2)
DIMENSIONS
Height mm 1740 1740 1740 1740 1740 1740 1740 1740
Length mm 550 550 550 550 850 850 1200 1200
Depth mm 450 450 450 450 450 450 450 450

Standard Features • Total front access is available for unit maintenance


• Advanced microprocessor control system is included • The electrical panel is situated in a compartment
with local or remote user terminal. separated from the air flow and complies with the
• The units are equipped with EC Fans for efficiency 2006/95/EC directive and related standards.
maximization. • Microprocessor control system includes:
• The structure of the unit is characterized by a self- - Local user terminal with external accessibility
supporting frame in galvanized steel with panels. The - Integrated LAN card for local network connection of a
external panels are coated with RAL9003 epoxy-polyester group of CRACs
paint* and internally lined with heat and sound-proofing - Rotation and active stand-by management
insulation. - Free contact for general and two for addressable
• The cooling coil is designed for an elevated SHR and alarms
reduced pressure drops in the air section. The coil is - Remote on/off switch
made from copper tubes mechanically expanded on - Ability to interface with Modbus protocol directly on
aluminum fins, complete with a hydrophilic treatment. RS485 serial card
• Uniflair AM units are in conformity with the following - Ability to interface with main external communication
directives: 2006/42/EC, 2004/108/EC, 2006/95/EC, protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
97/23/EC, 842/2006/EC F-GAS regulation SNMP, and StruxureWareTM platform
• High-efficiency, EU4-pleated air filters are housed in a
metal frame and equipped with a dirty filter differential *RAL5013 may be used during transition period.
pressure switch and low airflow differential pressure Construction Options Accessories
switch • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with safety thermostat and • Remote, semi-graphic user terminal
manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Electronic expansion valve is controlled by the • LON FTT10 serial adaptor to communicate with external
microprocessor and a dedicated software that increases BMS managed with LON protocol
the precision of the cooling and the energy efficiency of • TCP/IP serial adaptor to communicate with external
the cooling cycle BMS managed with SNMP protocol
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

34 | High-efficiency Room Air Conditioners 35 | High-efficiency Room Air-Conditioners


Chilled water units with asynchronous motor fans

Uniflair AM
SDCC – SUCC

Range TECHNICAL DATA 1. Data refers to nominal


conditions: room at 24°C-50%
Cooling capacity: 5 ÷ 20 kW SDCC–SUCC MODEL 0200A(3) 0250A(3) 0300A(3) 0400A(3) 0600A(3)
RH,water temperature 7/12°C,
Fan type Forward-curved centrifugal motor fan
Refrigerant Chilled Water and glycol 0%, and ESP = 20Pa.
Power supply V/ph/Hz 400/3/50Hz
Available Versions: 2. Gross Cooling capacities;
Fans Nr. 1 1 1 2 2
fans must be deduced to obtain
Airflow m3/h 1600 2300 2300 3350 4500
- Downflow (SDCC) net cooling data.
Gross Total Cooling
- Upflow (SUCC) with bottom, front, and rear suction kW 7,2 10,0 11,3 14,1 20,6 3. Equipped with standard
Capacity(1) (2)
electrical heaters.
Gross Sensible Cooling
kW 6,4 8,9 9,9 12,9 18,2
Capacity(1) (2)
DIMENSIONS
Height mm 1740 1740 1740 1740 1740
Length mm 550 850 850 850 1200
Depth mm 450 450 450 450 450
SDCC–SUCC MODEL 0200B 0250B 0300B 0400B 0600B
Fan type Forward-curved centrifugal motor fan
Power supply V/ph/Hz 230/1/50Hz
Standard Features • Total front access is available for unit maintenance.
Fans 1 1 1 2 2
• Advanced microprocessor control system is available • The electrical panel is situated in a compartment
Airflow m3/h 1600 2300 2300 3350 4500
with local or remote user terminal. separated from the air flow and complies with the
Gross Total Cooling
• The units are equipped with forward-curved fans With 2006/95/EC directive and related standards kW 7,2 10,0 11,3 14,1 20,6
Capacity(1) (2)
directly-coupled asynchronuos motor. • Microprocessor control system includes: Gross Sensible Cooling
• The structure of the unit is characterized by a self- - Local user terminal with external accessibility kW 6,4 8,9 9,9 12,9 18,2
Capacity(1) (2)
supporting frame in galvanized steel with panels. The - Integrated LAN card for local network connection
DIMENSIONS
external panels are coated with RAL9003 epoxy-polyester of a group of CRACs
Height mm 1740 1740 1740 1740 1740
paint* and internally lined with heat and sound-proofing - Rotation and active stand-by management
Length mm 550 850 850 850 1200
insulation. - Free contact for general and two for addressable
Depth mm 450 450 450 450 450
• The unit can be selected with a two-way or three-way alarms
valve and an actuator integrated with the microprocessor - Remote on/off switch
• The cooling coil is designed for an elevated SHR and - Ability to interface with Modbus protocol directly on
reduced pressure drops in the air section. The coil is RS485 serial card
made from copper tubes mechanically expanded on - Ability to interface with main external communication
aluminum fins, complete with a hydrophilic treatment. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
• High-efficiency, EU4-pleated air filters are housed in a SNMP, and StruxureWareTM platform
metal frame and equipped with a dirty filter differential
pressure switch and low airflow differential pressure *RAL5013 may be used during transition period.
switch.

Construction Options Accessories


• Double power supply with automatic, integrated The units can be supplied with the following external
management on the active line accessories:
• Immersed electrode humidifier (D/U versions) • Remote, semi-graphic user terminal
• Low surface temperature electrical heaters with • RS485 serial adaptor to communicate with external
extended fans, complete with double safety thermostat BMS
and manual resetting (T/H versions) • LON FTT10 serial adaptor to communicate with external
• Discharge temperature sensor integrated with the BMS managed with LON protocol
microprocessor to grant discharge temperature control; in • TCP/IP serial adaptor to communicate with external
combination with D and U version, moisture control can BMS managed with SNMP protocol
be selected • Motorized damper
• Suction from the top or front discharge plenums
• Adjustable floor stands

36 | High-efficiency Room Air Conditioners 37 | High-efficiency Room Air-Conditioners


Chilled water units with EC motor fans

Uniflair AM
SDCV – SUCV

Range TECHNICAL DATA 1. Data refer to nominal


conditions: Room at 24°C-50%
Cooling capacity: 5 ÷ 20 kW SDCV -SUCV MODEL 0200A(3) 0250A(3) 0300A(3) 0400A(3) 0600A(3)
RH,water temperature 7/12°C,
Fan type EC Backward-curved centrifugal motor fan
Refrigerant Chilled Water and glycol 0%, and ESP = 20Pa.
Power supply V/ph/Hz 400/3/50Hz
EC Fans 2. Gross Cooling capacities;
Fans Nr. 1 1 1 2 2
fans must be deduced to obtain
Airflow m3/h 1600 2100 2100 3350 5000
Available Versions: net cooling datas.
Gross Total Cooling
- Downflow (SDCV) kW 7,2 9,4 10,6 14,1 22,1 3. Equipped with standard
Capacity(1) (2)
electrical heaters.
- Upflow (SUCV) with bottom, front, and rear suction Gross Sensible Cooling
kW 6,4 8,3 9,2 12,9 19,7
Capacity(1) (2)
DIMENSIONS
Height mm 1740 1740 1740 1740 1740
Length mm 550 850 850 850 1200
Depth mm 450 450 450 450 450
SDCV -SUCV MODEL 0200B 0250B 0300B 0400B 0600B
Fan type EC Backward-curved centrifugal motor fan
Power supply V/ph/Hz 230/1/50Hz
Standard Features • Total front access is included for unit maintenance.
Fans 1 1 1 2 2
• Advanced microprocessor control system is available • The electrical panel is situated in a compartment
Airflow m3/h 1600 2100 2100 3350 5000
with local or remote user terminal. separated from the air flow and complies with the
Gross Total Cooling
• The units are equipped with EC fans for efficiency 2006/95/EC directive and related standards. kW 7,2 9,4 10,6 14,1 22,1
Capacity(1) (2)
maximization. Gross Sensible Cooling
• The structure of the unit is characterized by a self- • Microprocessor control system includes: kW 6,4 8,3 9,2 12,9 19,7
Capacity(1) (2)
supporting frame in galvanized steel with panels. The - Local user terminal with external accessibility
DIMENSIONS
external panels are coated with RAL9003 epoxy-polyester - Integrated LAN card for local network connection of a
Height mm 1740 1740 1740 1740 1740
paint* and internally lined with heat and sound-proofing group of CRACs
Length mm 550 850 850 850 1200
insulation. - Rotation and active stand-by management
Depth mm 450 450 450 450 450
• The unit can be selected with a two-way or three-way - Free contact for general and two for addressable alarms
valve and an actuator integrated with the microprocessor. - Remote on/off switch
• The cooling coil is designed for an elevated SHR and - Ability to interface with Modbus protocol directly on
reduced pressure drops in the air section. The coil is RS485 serial card
made from copper tubes mechanically expanded on - Ability to interface with main external communication
aluminum fins, complete with a hydrophilic treatment. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
• High-efficiency, EU4-pleated air filters are housed in a SNMP, and StruxureWareTM platform
metal frame and equipped with a dirty filter differential
pressure switch and low airflow differential pressure *RAL5013 may be used during transition period.
switch.

Construction Options Accessories


• Double power supply with automatic, integrated The units can be supplied with the following external
management on the active line accessories:
• Immersed electrode humidifier (D/U versions) • Remote, semi-graphic user terminal
• Low surface temperature electrical heaters with • RS485 serial adaptor to communicate with external
extended fans, complete with double safety thermostat BMS
and manual resetting (T/H versions) • LON FTT10 serial adaptor to communicate with external
• Discharge temperature sensor integrated with the BMS managed with LON protocol
microprocessor to allow discharge temperature control; • TCP/IP serial adaptor to communicate with external
in combination with D and U version can be selected BMS managed with SNMP protocol
moisture control • AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Suction from the top or front discharge plenums
• Adjustable floor stands

38 | High-efficiency Room Air Conditioners 39 | High-efficiency Room Air-Conditioners


Direct Expansion air-cooled units with backward-curved fans

Uniflair LE
TDAR – TUAR

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 20 ÷ 100 kW TDAR –TUAR MODEL 0511A 0611A 0721A 0722A 0921A 0922A 1021A
net cooling data.
Fan type Backward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 400/3/50Hz
Available Versions: conditions : room at 24°C-
Fans Nr. 1 1 1 1 1 1 1
50% RH , 45°C condensing
Airflow m3/h 5833 5833 7933 7933 7933 7933 7933
- Downflow (TDAR) temperature, and ESP = 20Pa.
N° of compressors 1 1 2 2 2 2 2
- Upflow (TUAR) Refrigerating Circuits 1 1 1 2 1 2 1
3. Data refers to downflow unit.

Gross Total Cooling


kW 20,4 25,0 25,8 25,6 34,1 33,9 37,1
Capacity(1) (2)
Gross Sensible Cooling
kW 19,8 22,2 25,2 23,9 28,1 27,2 28,7
Capacity(1) (2)
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1010 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865
TDAR –TUAR MODEL 1022A 1121A 1122A 1321A 1322A 1422A 1622A
Standard Features - Rotation and active stand-by management
Fans Nr. 1 1 2 2 2 2 2
• Advanced microprocessor control system is included - Free contact for general and two for addressable alarms
Airflow m3/h 7933 12267 12267 12267 12267 16406 16406
with local or remote user terminal. - Remote on/off switch
N° of compressors 2 2 2 2 2 2 2
• The units are equipped with backward-curved fans with - Ability to interface with Modbus protocol directly on
Refrigerating Circuits 2 1 2 1 2 2 2
directly-coupled asynchronous motor. RS485 serial card (adding this option)
Gross Total Cooling
• The structure of the unit is characterized by a self- - Ability to interface with main external communication kW 36,9 37,8 37,9 48,0 47,7 51,6 57,5
Capacity(1) (2)
supporting frame in galvanized steel with panels. The protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
Gross Sensible Cooling
external panels are coated with RAL9003 epoxy-polyester SNMP, and StruxureWareTM platform kW 28,0 36,8 36,2 39,3 38,0 51,0 56,8
Capacity(1) (2)
paint* and internally lined with heat and sound-proofing
DIMENSIONS
insulation. *RAL5013 may be used during transition period.
Height mm 1960 1960 1960 1960 1960 1960 1960
• Electronic expansion valve is controlled by the
Construction Options Length mm 1010 1720 1720 1720 1720 2170 2170
microprocessor with a dedicated software that
• Immersed electrode humidifier (D/U versions) Depth mm 865 865 865 865 865 865 865
increases the precision of the cooling and the energy
• Low surface temperature electrical heaters with TDAR –TUAR MODEL 1822A 2222A(3) 2242A(3) 2522A(3) 2542A(3) 2842A(3) 3342A(3)
efficiency of the cooling cycle.
extended fans, complete with double safety thermostat Fans Nr. 2 3 3 3 3 3 3
• The cooling coil is designed for an elevated SHR and
and manual resetting (T/H versions) Airflow m3/h 16406 21656 21656 21656 22046 22055 22055
reduced pressure drops in the air section. The coil is
• Hot gas and hot water reheating N° of compressors 2 2 4 2 4 4 4
made from copper tubes mechanically expanded on
Refrigerating Circuits 2 2 2 2 2 2 2
aluminum fins, complete with a hydrophilic treatment.
• High-efficiency, EU4-pleated air filters are housed in a Accessories Gross Total Cooling
kW 63,9 75,1 81,2 86,7 88,1 97,4 107,6
The units can be supplied with the following external Capacity(1) (2)
metal frame and equipped with a dirty filter differential
accessories: Gross Sensible Cooling
pressure switch and low airflow differential pressure kW 57,3 75,1 80,3 83,3 84,5 90,8 92,9
• Remote, semi-graphic user terminal Capacity(1) (2)
switch.
• Total front access is included for unit maintenance • RS485 serial adaptor to communicate with external DIMENSIONS

• The electrical panel is situated in a compartment BMS Height mm 1960 2150 2150 2150 2150 2150 2150
separated from the air flow and complies with the • LON FTT10 serial adaptor to communicate with external Length mm 2170 2580 2580 2580 2580 2580 2580
2006/95/EC directive and related standards. BMS managed with LON protocol Depth mm 865 865 865 865 865 865 865
• Microprocessor control system includes: • TCP/IP serial adaptor to communicate with external TUAR MODEL 2222A 2242A 2522A 2542A 2842A 3342A
- Regulation logic of cooling capacity and airlow BMS managed with SNMP protocol Fans Nr. 3 3 3 3 3 3
integration • AFPS (Automatic Floor Pressurization System) that Airflow m3/h 22154 22154 23467 23467 23068 23068
- Local user terminal with external accessibility permits to adapt its availability as a kit with installation N° of compressors 2 4 2 4 4 4
- Integrated LAN card for local network connection of a instructions Refrigerating Circuits 2 2 2 2 2 2
group of CRACs • Motorized damper Gross Total Cooling
• Suction from the top or front discharge plenums kW 75,4 82,7 86,5 87,5 97,9 108,2
Capacity(1) (2)
• Adjustable floor stands Gross Sensible Cooling
kW 75,4 81,8 85,5 86,4 93,8 95,6
Capacity(1) (2)
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960
Length mm 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865

40 | High-efficiency Room Air Conditioners 41 | High-efficiency Room Air-Conditioners


Direct Expansion air-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
TDAV – TUAV

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 20 ÷ 100 kW TDAV –TUAV MODEL 0511A 0611A 0721A 0722A 0921A 0922A 1021A
net cooling data.
Fan type EC Backward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 400/3/50Hz
EC Fans conditions : room at 24°C-
Fans Nr. 1 1 1 1 1 1 1
50% RH , 45°C condensing
Airflow m3/h 5700 5700 8600 8600 8600 8600 8600
Available Versions: temperature, and ESP = 20Pa.
N° of compressors 1 1 2 2 2 2 2
- Downflow (TDAV) Refrigerating Circuits 1 1 1 2 1 2 1
3. Data refers to downflow unit.

- Upflow (TUAV) Gross Total Cooling


kW 20,3 24,9 25,6 25,8 34,5 34,2 37,6
Capacity(1) (2)
Gross Sensible Cooling
kW 19,7 21,9 25,4 25,3 29,6 28,4 30,1
Capacity(1) (2)
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1010 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865
TDAV –TUAV MODEL 1022A 1121A 1122A 1321A 1322A 1422A 1622A
Standard Features - Rotation and active stand-by management
Fans Nr. 1 1 2 2 2 2 2
• Advanced microprocessor control system is available - Free contact for general and two for addressable
Airflow m3/h 8600 12320 12320 12320 12320 16300 16500
with local or remote user terminal. alarms
N° of compressors 2 2 2 2 2 2 2
• The units are equipped with EC fans for efficiency - Remote on/off switch
Refrigerating Circuits 2 1 2 1 2 2 2
maximization. - Ability to interface with Modbus protocol directly
Gross Total Cooling
• The structure of the unit is characterized by a self- on RS485 serial card kW 37,3 37,6 37,9 48,1 47,7 51,5 41,3
Capacity(1) (2)
supporting frame in galvanized steel with panels. The - Ability to interface with main external communication
Gross Sensible Cooling
external panels are coated with RAL9003 epoxy-polyester protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP, kW 29,2 36,7 36,3 39,4 38,0 50,9 40,1
Capacity(1) (2)
paint* and internally lined with heat and sound-proofing SNMP, and StruxureWareTM platform
DIMENSIONS
insulation.
Height mm 1960 1960 1960 1960 1960 1960 1960
• Electronic expansion valve is controlled by the *RAL5013 may be used during transition period.
Length mm 1010 1720 1720 1720 1720 2170 2170
microprocessor and a dedicated software that increases
Construction Options Depth mm 865 865 865 865 865 865 865
the cooling precision and the energy efficiency of the
• Immersed electrode humidifier (D/U versions) TDAV –TUAV MODEL 1822A 2222A(3) 2242A(3) 2522A(3) 2542A(3) 2842A(3) 3342A(3)
cooling cycle.
• Low surface temperature electrical heaters with Fans Nr. 2 3 3 3 3 3 3
• The cooling coil is designed for an elevated SHR and
extended fans, complete with double safety thermostat Airflow m3/h 16500 21500 21500 21500 21500 21500 21500
reduced pressure drops in the air section. The coil is
and manual resetting (T/H versions) N° of compressors 2 2 4 2 4 4 4
made from copper tubes mechanically expanded on
• Hot gas and hot water reheating Refrigerating Circuits 2 2 2 2 2 2 2
aluminum fins, complete with a hydrophilic treatment.
Gross Total Cooling
• Uniflair LE units meet the following directives: 2006/42/ kW 64,0 75,0 82,7 86,6 87,8 94,8 104,8
Accessories Capacity(1) (2)
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC
The units can be supplied with the following external Gross Sensible Cooling
F-GAS regulation. kW 57,5 75,0 81,8 82,8 83,0 87,5 89,6
accessories: Capacity(1) (2)
• High-efficiency, EU4-pleated air filters are housed in a
metal frame and equipped with a dirty filter differential • Remote, semi-graphic user terminal DIMENSIONS

pressure switch and low airflow differential pressure • RS485 serial adaptor to communicate with external Height mm 1960 2175 2175 2175 2175 2175 2175
switch. BMS Length mm 2170 2580 2580 2580 2580 2580 2580
• The Uniflair LE range offers the possibility to select • LON FTT10 serial adaptor to communicate with external Depth mm 865 865 865 865 865 865 865
units equipped with two compressors (tandem) for each BMS managed with LON protocol TUAV MODEL 2222A 2242A 2522A 2542A 2842A 3342A
circuit,, granting better efficiency and regulation capacity • TCP/IP serial adaptor to communicate with external Fans Nr. 3 3 3 3 3 3
at partial loads (models with the **21 or **42 suffix). BMS managed with SNMP protocol Airflow m3/h 22000 22000 22500 22500 23000 23000
• Total front access is available for unit maintenance. • AFPS (Automatic Floor Pressurization System) that N° of compressors 2 4 2 4 4 4
• The electrical panel is situated in a compartment permits to adapt its availability as a kit with installation Refrigerating Circuits 2 2 2 2 2 2
separated from the air flow and complies with the instructions Gross Total Cooling
• Motorized damper kW 75,3 82,6 86,8 88,3 95,6 105,6
2006/95/EC directive and related standards. Capacity(1) (2)
• Microprocessor control system includes: • Condensate drain pump Gross Sensible Cooling
• Suction from the top or front discharge plenums kW 75,3 81,7 85,8 85,7 91,8 93,6
- Integrated management of the EEV Capacity(1) (2)
and refrigerating circuit parameters • Adjustable floor stands DIMENSIONS
- Local user terminal with external accessibility Height mm 1960 1960 1960 1960 1960 1960
- Integrated LAN card for local network connection Length mm 2580 2580 2580 2580 2580 2580
of a group of CRACs Depth mm 865 865 865 865 865 865

42 | High-efficiency Room Air Conditioners 43 | High-efficiency Room Air-Conditioners


Direct Expansion water-cooled units with backward-curved fans

Uniflair LE
TDWR – TUWR

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 20 ÷ 100 kW TDWR-TUWR MODEL 0611A 0921A 1321A 1622A 1822A
net cooling data.
Fan type Backward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 400/3/50Hz
Available Versions: conditions : room at 24°C°
Fans Nr. 1 1 2 2 2
-50% RH, water temperatures
Airflow m3/h 5833 7933 12267 16406 16406
- Downflow (TDWR) 30-35°C, and ESP = 20Pa.
N° of compressors 1 2 2 2 2
- Upflow (TUWR) Refrigerating Circuits 1 1 1 2 2
Gross Total Cooling
kW 24,1 32,1 45,5 56,8 62,5
Capacity(1) (2)
Gross Sensible Cooling
kW 21,7 27,2 38,0 55,2 56,1
Capacity(1) (2)
DIMENSIONS
Height mm 1960 1960 1960 1960 1960
Length mm 1010 1310 1720 2170 2170
Depth mm 750 865 865 865 750
TDWR MODEL 2242A 2542A 2842A 3342A
Standard Features • The Uniflair LE range offers the possibility to select units
Fans Nr. 3 3 3 3
• Advanced microprocessor control system is available equipped with two compressors (tandem) for each circuit,
Airflow m3/h 21656 22046 22055 22055
with local or remote user terminal. which grants better efficiency and regulation capacity at
N° of compressors 4 4 4 4
• The units are equipped with backward-curved fans and partial loads (models with the **21 or **42 suffix).
Refrigerating Circuits 2 2 2 2
directly-coupled asynchronuos motor. • Total front access is available for unit maintenance.
Gross Total Cooling
• The structure of the unit is characterized by a self- • The electrical panel is situated in a compartment kW 85,7 92,6 99,9 111,1
Capacity(1) (2)
supporting frame in galvanized steel with panels. The separated from the air flow and complies with the
Gross Sensible Cooling
external panels are coated with RAL9003 epoxy-polyester 2006/95/EC directive and related standards. kW 82,1 84,2 90,3 92,2
Capacity(1) (2)
paint* and internally lined with heat and sound-proofing • Microprocessor control system includes:
DIMENSIONS
insulation. - Integrated management of the EEV
• Electronic expansion valve is controlled by the and refrigerating circuit parameters Height mm 2150 2150 2150 2150
microprocessor and a dedicated software that increases - Local user terminal with external accessibility Length mm 2580 2580 2580 2580
the precision of the cooling and the energy efficiency of - Integrated LAN card for local network connection Depth mm 865 865 865 865
the cooling cycle. of a group of CRACs TUWR MODEL 2242A 2542A 2842A 3342A
• The cooling coil is designed for an elevated SHR and - Rotation and ctive stand-by management Fans Nr. 3 3 3 3
reduced pressure drops in the air section. The coil is - Free contact for general and two for addressable Airflow m3/h 22154 23467 23068 23069
made from copper tubes mechanically expanded on alarms N° of compressors 4 4 4 4
aluminum fins, complete with a hydrophilic treatment. - Remote on/off switch Refrigerating Circuits 2 2 2 2
• Internal water-cooled condenser braze is welded and - Ability to interface with Modbus protocol directly Gross Total Cooling
kW 86,0 93,4 100,5 111,7
made of AISI 304 stainless steel. on RS485 serial card Capacity(1) (2)
• Uniflair LE units meet the following directives: 2006/42/ - Ability to interface with main external communication Gross Sensible Cooling
kW 83,4 87,9 93,1 94,7
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP, Capacity(1) (2)
F-GAS regulation. SNMP, and StruxureWareTM platform DIMENSIONS
• High-efficiency, EU4-pleated air filters are housed in a Height mm 1960 1960 1960 1960
metal frame and equipped with a dirty filter differential *RAL5013 may be used during transition period.
Length mm 2580 2580 2580 2580
pressure switch and low airflow differential pressure Depth mm 865 865 865 865
switch.

Construction Options • RS485 serial adaptor to communicate with external


• Immersed electrode humidifier (D/U versions) BMS
• Low surface temperature electrical heaters with • LON FTT10 serial adaptor to communicate with external
extended fans, complete with double safety thermostat BMS managed with LON protocol
and manual resetting (T/H versions) • TCP/IP serial adaptor to communicate with external
• Hot gas and hot water reheating BMS managed with SNMP protocol
• Condensation control on refrigerant side with constant • AFPS (Automatic Floor Pressurization System) that
water flow permits to adapt its availability as a kit with installation
instructions
Accessories • Motorized damper
The units can be supplied with the following external • Condensate drain pump
accessories: • Suction from the top or front discharge plenums
• Remote, semi-graphic user terminal • Adjustable floor stands

44 | High-efficiency Room Air Conditioners 45 | High-efficiency Room Air-Conditioners


Direct Expansion water-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
TDWV – TUWV
TECHNICAL DATA 1. Gross Cooling capacities;
fans must be deduced to obtain
TDWV –TUWV MODEL 0611A 0921A 1321A 1622A 1822A
Range net cooling data.
Fan type EC Backward-curved centrifugal motor fan
Cooling capacity: 20 ÷ 100 kW Power supply V/ph/Hz 400/3/50Hz 2. Data refers to nominal
conditions : room at 24°C°
Fans Nr. 1 1 2 2 2
Refrigerant R-410A -50% RH, water temperatures
Airflow m3/h 5700 8600 12320 16000 16000
30-35°C, and ESP = 20Pa.
EC Fans N° of compressors 1 2 2 2 2
Available Versions: Refrigerating Circuits 1 1 1 2 2
Gross Total Cooling
- Downflow (TDWV) kW 24,0 32,5 45,6 56,7 62,3
Capacity(1) (2)
- Upflow (TUWV) Gross Sensible Cooling
kW 21,3 28,6 38,1 54,3 55,2
Capacity(1) (2)
DIMENSIONS
Height mm 1960 1960 1960 1960 1960
Length mm 1010 1310 1720 2170 2170
Depth mm 750 865 865 865 750
TDWV MODEL 2242A 2542A 2842A 3342A
Fans Nr. 3 3 3 3
Airflow m3/h 21500 21500 21500 21500
Standard Features equipped with two compressors (tandem) for each circuit,
N° of compressors 4 4 4 4
• Advanced microprocessor control system with a local or which grants better efficiency and regulation capacity at
Refrigerating Circuits 2 2 2 2
remote user terminal. partial loads (models with the **21 or **42 suffix).
Gross Total Cooling
• The units are equipped with EC fans for efficiency • Total front access is available for unit maintenance. kW 85,7 92,3 99,5 110,7
Capacity(1) (2)
maximization. • The electrical panel is situated in a compartment
Gross Sensible Cooling
• The structure of the unit is characterized by a self- separated from the air flow and complies with the kW 81,6 82,8 88,8 90,8
Capacity(1) (2)
supporting frame in galvanized steel with panels. The 2006/95/EC directive and related standards.
DIMENSIONS
external panels are coated with RAL9003 epoxy-polyester • Microprocessor control system includes:
paint* and internally lined with heat and sound-proofing - Integrated management of the EEV Height mm 1960 2150 2150 2150

insulation. and refrigerating circuit parameters Length mm 2580 2580 2580 2580

• Electronic expansion valve is controlled by the - Local user terminal with external accessibility Depth mm 865 865 865 865
microprocessor and a dedicated software that increases - Integrated LAN card for local network connection TUWV MODEL 2242A 2542A 2842A 3342A
the precision of the cooling and the energy efficiency of of a group of CRACs Fans Nr. 3 3 3 3
the cooling cycle. - Rotation and active stand-by management Airflow m3/h 22000 22500 23000 23000
• The cooling coil is designed for an elevated SHR and - Free contact for general and two for addressable N° of compressors 4 4 4 4
reduced pressure drops in the air section. The coil is alarms Refrigerating Circuits 2 2 2 2
made from copper tubes mechanically expanded on - Remote on/off switch Gross Total Cooling
kW 85,9 92,9 100,4 111,7
aluminum fins, complete with a hydrophilic treatment. - Ability to interface with Modbus protocol directly Capacity(1) (2)

• Internal water-cooled condenser braze is welded and on RS485 serial card Gross Sensible Cooling
kW 83,0 85,4 92,9 94,6
Capacity(1) (2)
made of AISI 304 stainless steel. - Ability to interface with main external communication
• Uniflair LE units meet the following directives: 2006/42/ protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP, DIMENSIONS
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC SNMP, and StruxureWareTM platform Height mm 1960 1960 1960 1960
F-GAS regulation. Length mm 2580 2580 2580 2580
• High-efficiency, EU4-pleated air filters are housed in a *RAL5013 may be used during transition period. Depth mm 865 865 865 865
metal frame and equipped with a dirty filter differential
pressure switch and low airflow differential pressure
switch. Construction Options Accessories
• The Uniflair LE range offers the possibility to select units • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Condensation control on refrigerant side with constant • LON FTT10 serial adaptor to communicate with external
water flow BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
46 | High-efficiency Room Air Conditioners 47 | High-efficiency Room Air-Conditioners
Chilled water units with backward-curved fans

Uniflair LE
TDCR – TUCR

Range TECHNICAL DATA 1. Data refers to nominal


conditions: Room at 24°C-50%
Cooling capacity: 20 ÷ 160 kW TDCR –TUCR MODEL 0600B 0700B 0600A 0700A 1000A 1200A 1700A
RH,water temperature 7/12°C;
Fan type Backward-curved centrifugal motor fan
Refrigerant Chilled Water glycol 0% ESP = 20Pa.
Power supply V/ph/Hz 230/1/50Hz 400/3/50Hz
Available Versions: 2. Gross Cooling capacities;
Fans Nr. 1 1 1 1 1 1 2
fans must be deduced to obtain
Airflow m3/h 5936 6193 5936 6193 10148 10723 14297
- Downflow (TDCR) net cooling data.
Gross Total Cooling
- Upflow (TUCR) kW 23,7 26,7 23,7 26,7 33,8 42,7 56,7 3. Only Downflow version is
Capacity(1) (2)
available.
Gross Sensible Cooling
kW 21,6 24,0 21,6 24,0 32,5 39,3 51,5
Capacity(1) (2)
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1010 1010 1010 1310 1310 1720
Depth mm 750 750 750 750 865 865 865
TDCR –TUCR MODEL 2000A 2500A 2700A 3400A 4000A 4300A(3)
Fan type Backward-curved centrifugal motor fan
Power supply V/ph/Hz 400/3/50Hz
Standard Features separated from the air flow and complies with the
Fans Nr. 2 2 2 3 3 3
• Advanced microprocessor control system is available 2006/95/EC directive and related standards.
Airflow m3/h 18498 18615 19052 24422 25834 27984
with a local or remote user terminal. • Microprocessor control system includes:
Gross Total Cooling
• The units are equipped with backward-curved fans and - Local user terminal with external accessibility kW 70,2 86,4 90,4 110,9 126,0 161,8
Capacity(1) (2)
directly-coupled asynchronuos motor. - Integrated LAN card for local network connection Gross Sensible Cooling
• The structure of the unit is characterized by a self- of a group of CRACs kW 63,5 76,1 82,7 100,4 112,6 131,9
Capacity(1) (2)
supporting frame in galvanized steel with panels. The - Rotation and active stand-by management
DIMENSIONS
external panels are coated with RAL9003 epoxy-polyester - Free contact for general and two for addressable
Height mm 1960 1960 1960 1960 1960 2170
paint* and internally lined with heat and sound-proofing alarms
Length mm 2170 2170 2170 2582 2582 2582
insulation. - Remote on/off switch
Depth mm 865 865 865 865 865 865
• The unit can be selected with a two-way or three-way - Ability to interface with Modbus protocol directly
TDCR –TUCR DUAL COIL 0700A 1000A 1700A 2000A 4000A 4300A(3)
valve and an actuator integrated with the microprocessor. on RS485 serial card
Fans Nr. 1 1 2 2 3 3
• The cooling coil is designed for an elevated SHR and - Ability to interface with main external communication
Airflow m3/h 5817 10073 14619 19834 26463 28226
reduced pressure drops in the air section. The coil is protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
Gross Total Cooling
made from copper tubes mechanically expanded on SNMP, and StruxureWareTM platform kW 22,3 37,9 58,8 74,3 103,3 109,0
Capacity(1) (2)
aluminum fins, complete with a hydrophilic treatment.
Gross Sensible Cooling
• High-efficiency, EU4-pleated air filters are housed in a *RAL5013 may be used during transition period. kW 22,1 37,6 56,5 72,7 98,9 103,7
Capacity(1) (2)
metal frame and equipped with a dirty filter differential
DIMENSIONS
pressure switch and low airflow differential pressure
Height mm 1960 1960 1960 1960 1960 2170
switch.
Length mm 1010 1310 1720 2170 2582 2582
• Total front access is available for unit maintenance.
Depth mm 865 865 865 865 865 865
• The electrical panel is situated in a compartment

Construction Options Options


• Double power supply with automatic integrated The units can be supplied with the following external
management on the active line accessories:
• Immersed electrode humidifier (D/U versions) • Remote, semi-graphic user terminal
• Low surface temperature electrical heaters with • RS485 serial adaptor to communicate with external
extended fans, complete with double safety thermostat BMS
and manual resetting (T/H versions) • LON FTT10 serial adaptor to communicate with external
• Discharge temperature sensor integrated with the BMS managed with LON protocol
microprocessor to allow discharge temperature control; in • TCP/IP serial adaptor to communicate with external
combination with D and U version, moisture control can BMS managed with SNMP protocol
be selected • Motorized damper
• Suction from the top or front discharge plenums
• Adjustable floor stands

48 | High-efficiency Room Air Conditioners 49 | High-efficiency Room Air-Conditioners


Chilled water units with backward-curved fans equipped with EC motor

Uniflair LE
TDCV – TUCV

Range TECHNICAL DATA 1. Data refers to nominal


conditions: Room at 24°C-50%
Cooling capacity: 20 ÷ 160 kW TDCV –TUCV MODEL 0600A 0700A 1000A 1200A 1700A 2000A
RH,water temperature 7/12°C,
Fan type EC Backward-curved centrifugal motor fan
Refrigerant Chilled Water glycol 0%, and ESP = 20Pa
Power supply V/ph/Hz 400/3/50Hz
EC Fans 2. Gross Cooling capacities;
Fans Nr. 1 1 1 1 2 2
fans must be deduced to obtain
Airflow m3/h 5950 6200 10200 10700 15000 18800
Available Versions: net cooling data.
Gross Total Cooling
- Downflow (TDCV) kW 23,7 26,7 33,9 42,7 58,5 70,9 3. Only Downflow version is
Capacity(1) (2)
available.
- Upflow (TUCV) Gross Sensible Cooling
kW 21,6 24,0 32,6 39,3 53,3 64,2
Capacity(1) (2)
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960
Length mm 1010 1010 1310 1310 1720 2170
Depth mm 750 750 865 865 865 865
TDCR –TUCR MODEL 2500A 2700A 3400A 4000A 4300A(3)
Fans Nr. 2 2 3 3 3
Airflow m3/h 18800 18800 24800 25200 29500
Standard Features • The electrical panel is situated in a compartment
Gross Total Cooling
• Advanced microprocessor control system is included separated from the air flow and complies with the kW 86,9 89,5 112,1 123,7 168,5
Capacity(1) (2)
with local or remote user terminal. 2006/95/EC directive and related standards. Gross Sensible Cooling
• The units are equipped with the latest generation • Microprocessor control system includes: kW 76,7 81,8 101,6 110,4 138,0
Capacity(1) (2)
Radical EC Fans for efficiency maximization. Impellers - Regulation logic of cooling capacity and airlow
DIMENSIONS
are made of high-tech compound material with optimized integration
Height mm 1960 1960 1960 1960 2170
flow control, combined with or highly efficient GreenTech - Regulation logic of cooling capacity and airflow
Length mm 2170 2170 2582 2582 2582
EC motors. integration
Depth mm 865 865 865 865 865
• The structure of the unit is characterized by a self- - Local user terminal with external accessibility
TDCV –TUCV DUAL COIL 0700A 1000A 1700A 2000A 4000A 4300A(3)
supporting frame in galvanized steel with panels. The - Integrated LAN card for local network connection
Fans Nr. 1 1 2 2 3 3
external panels are coated with RAL9003 epoxy-polyester of a group of CRACs
Airflow m3/h 5875 10000 14400 19000 27500 29500
paint* and internally lined with heat and sound-proofing - Rotation and active stand-by management
Gross Total Cooling
insulation. - Free contact for general and two for addressable kW 22,5 37,7 58,2 72,3 105,8 112,2
Capacity(1) (2)
• The unit can be selected with a two-way or three-way alarms
Gross Sensible Cooling
valve and an actuator integrated with the microprocessor. - Remote on/off switch kW 22,3 37,4 55,9 70,6 101,5 107,0
Capacity(1) (2)
• The cooling coil is designed for an elevated SHR and - Ability to interface with Modbus protocol directly
DIMENSIONS
reduced pressure drops in the air section. The coil is on RS485 serial card
Height mm 1960 1960 1960 1960 1960 2170
made from copper tubes mechanically expanded on - Ability to interface with main external communication
Length mm 1010 1310 1720 2170 2582 2582
aluminum fins, complete with a hydrophilic treatment. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
Depth mm 865 865 865 865 865 865
• High-efficiency, EU4-pleated air filters are housed in a SNMP, and StruxureWareTM platform
metal frame and equipped with a dirty filter differential
pressure switch and low airflow differential pressure *RAL5013 may be used during transition period.
switch.
• Total front access is available for unit maintenance.

Construction Options Accessories


• Double power supply with automatic integrated The units can be supplied with the following external
management on the active line accessories:
• Immersed electrode humidifier (D/U versions) • Remote, semi-graphic user terminal
• Low surface temperature electrical heaters with • RS485 serial adaptor to communicate with external
extended fans, complete with double safety thermostat BMS
and manual resetting (T/H versions) • LON FTT10 serial adaptor to communicate with external
• Discharge temperature sensor integrated with the BMS managed with LON protocol
microprocessor to allow discharge temperature control; • TCP/IP serial adaptor to communicate with external
in combination with D and U version moisture control can BMS managed with SNMP protocol
be selected • AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Suction from the top or front discharge plenums
• Adjustable floor stands

50 | High-efficiency Room Air Conditioners 51 | High-efficiency Room Air-Conditioners


Energy-saving units with backward-curved fans TECHNICAL DATA 1. Gross Cooling capacities;
fans must be deduced to obtain
TDER –TUER MODEL 0511A 0611A 0721A 0722A 0921A 0922A 1021A
net cooling data.
Fan type Backward-curved centrifugal motor fan

Uniflair LE Power supply


Fans
V/ph/Hz
Nr. 1 1 1
400/3/50Hz
1 1 1 1
2. Data refers to nominal
conditions : room at 24°C°
-50% RH, water temperatures
TDER – TUER Airflow m3/h 5827 5827 8541 8541 8541 8541 8541
30-35°C, and ESP = 20Pa.
N° of compressors 1 1 2 2 2 2 2
3. Data refers to nominal
Refrigerating Circuits 1 1 1 2 1 2 1
conditions: room at 24°C-50%
Gross Total Cooling

CW MODE DX MODE
kW 19,2 23,8 27,0 28,5 30,4 32,1 34,6 RH,water temperature 7/12°C;
Range Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 19,2 21,1 27,0 28,5 28,5 27,9 30,3
Cooling capacity: 20 ÷ 100 kW Capacity(1) (2) 4. Data refers to Downflow unit.

Gross Total Cooling


Refrigerant R-410A kW 20,5 20,5 28,3 28,3 28,3 28,3 28,3
Capacity(1) (3)
Available Versions: Gross Sensible Cooling
kW 20,4 20,4 28,2 28,2 28,2 28,2 28,2
Capacity(1) (3)
- Downflow (TDER)
DIMENSIONS
- Upflow (TUER) Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1010 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865
TDER –TUER MODEL 1022A 1121A 1122A 1321A 1322A 1422A 1622A
Fans Nr. 1 1 2 2 2 2 2
Airflow m3/h 8541 13277 13277 13277 13277 15906 15906
N° of compressors 2 2 2 2 2 2 2
Refrigerating Circuits 2 1 2 1 2 2 2
Gross Total Cooling

CW MODE DX MODE
kW 37,1 37,3 39,3 47,0 50,2 49,6 55,9
Standard Features • Microprocessor control system includes: Capacity(1) (2)
• Advanced microprocessor control system is available - Integrated management of the EEV and Gross Sensible Cooling
kW 30,3 37,3 39,3 42,3 41,5 49,6 55,9
with local or remote user terminal. refrigerating circuit parameters Capacity(1) (2)

• The units are equipped with backward-curved fans with - Local user terminal with external accessibility Gross Total Cooling
kW 28,3 41,9 41,9 41,9 41,9 54,0 54,0
Capacity(1) (3)
directly-coupled asynchronous motor. - Integrated LAN card for local network connection
Gross Sensible Cooling
• The structure of the unit is characterized by a self- of a group of CRACs kW 28,2 41,7 41,7 41,7 41,7 53,7 53,7
Capacity(1) (3)
supporting frame in galvanized steel with panels. The - Rotation and active stand-by management
DIMENSIONS
external panels are coated with RAL9003 epoxy-polyester - Free contact for general and two for addressable
Height mm 1960 1960 1960 1960 1960 1960 1960
paint* and internally lined with heat and sound-proofing alarms
Length mm 1010 1720 1720 1720 1720 2170 2170
insulation. - Remote on/off switch
Depth mm 750 750 865 865 865 865 865
• Electronic expansion valve is controlled by the - Ability to interface with Modbus protocol directly
TDER MODEL 1822A 2222A(4) 2242A(4) 2522A(4) 2542A(4) 2842A(4)
microprocessor and a dedicated software that increases on RS485 serial card
Fans Nr. 2 3 3 3 3 3
the precision of the cooling and the energy efficiency of - Ability to interface with main external communication
Airflow m3/h 15906 21809 21809 21809 21809 21809
the cooling cycle. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
N° of compressors 2 2 4 2 4 4
• The cooling coil is designed for an elevated SHR and SNMP, and StruxureWareTM platform
Refrigerating Circuits 2 2 2 2 2 2
reduced pressure drops in the air section. The coil is
Gross Total Cooling

CW MODE DX MODE
made from copper tubes mechanically expanded on *RAL5013 may be used during transition period. kW 60,5 78,4 83,6 86,2 87,9 96,0
Capacity(1) (2)
aluminum fins, complete with a hydrophilic treatment.
Gross Sensible Cooling
• The cooling coil is characterized by chilled water Construction Options Capacity(1) (2)
kW 55,8 72,0 78,3 75,0 75,5 77,7
and direct expansion circuits interlaced to increase the • Immersed electrode humidifier (D/U versions) Gross Total Cooling
• Low surface temperature electrical heaters with kW 54,0 97,6 97,6 97,6 97,6 97,6
efficiency of the unit in all running conditions. Capacity(1) (3)
• Unit is equipped with an indirect free cooling system extended fans, complete with double safety thermostat Gross Sensible Cooling
kW 53,7 96,7 96,7 96,7 96,7 96,7
that provides the required cooling capacity when the and manual resetting (T/H versions) Capacity(1) (3)

external temperature is lower than the internal ambient. • Hot gas and hot water reheating DIMENSIONS
Compressor power consumption is minimized while • Condensation control on refrigerant side with constant
Height mm 1960 2150 2150 2150 2150 2150
internal and external environments are kept separate. water flow
Length mm 2170 2580 2580 2580 2580 2580
• Internal water-cooled condenser braze is welded and Depth mm 750 750 865 865 865 865
made of AISI 304 stainless steel. Accessories
TUER MODEL 2222A 2242A 2522A 2542A 2842A
• Uniflair LE units meet the following directives: 2006/42/ The units can be supplied with the following external
Fans Nr. 3 3 3 3 3
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC accessories:
Airflow m3/h 22160 22160 23194 23194 23194
F-GAS regulation. • Remote, semi-graphic user terminal
N° of compressors 2 4 2 4 4
• High-efficiency, EU4-pleated air filters are housed in a • RS485 serial adaptor to communicate with external
Refrigerating Circuits 2 2 2 2 2
metal frame and equipped with a dirty filter differential BMS
Gross Total Cooling
CW MODE DX MODE

pressure switch and low airflow differential pressure • LON FTT10 serial adaptor to communicate with external kW 78,5 83,8 86,8 88,7 96,8
Capacity(1) (2)
switch. BMS managed with LON protocol
Gross Sensible Cooling
• TCP/IP serial adaptor to communicate with external kW 72,7 79,2 77,8 78,3 80,4
• The Uniflair LE range offers the possibility to select units Capacity(1) (2)
equipped with two compressors (tandem) for each circuit, BMS managed with SNMP protocol Gross Total Cooling
kW 98,8 98,8 102,3 102,3 102,3
• AFPS (Automatic Floor Pressurization System) that Capacity(1) (3)
which grants better efficiency and regulation capacity at
partial loads (models with the **21 or **42 suffix). permits to adapt its availability as a kit with installation Gross Sensible Cooling
kW 97,9 97,9 101,3 101,3 101,3
instructions Capacity(1) (3)
• Total front access is available for unit maintenance.
• Motorized damper DIMENSIONS
• The electrical panel is situated in a compartment
separated from the air flow and complies with the • Condensate drain pump Height mm 1960 1960 1960 1960 1960

2006/95/EC directive and related standards. • Suction from the top or front discharge plenums Length mm 2580 2580 2580 2580 2580
• Adjustable floor stands Depth mm 750 865 865 865 865

52 | High-efficiency Room Air Conditioners 53 | High-efficiency Room Air-Conditioners


1. Gross Cooling capacities;
Energy-saving units with backward-curved fans equipped with EC motor TECHNICAL DATA
fans must be deduced to obtain
TDEV –TUEV MODEL 0511A 0611A 0721A 0722A 0921A 0922A 1021A
net cooling data.
Fan type EC Backward-curved centrifugal motor fan

Uniflair LE Power supply


Fans
V/ph/Hz
Nr. 1 1 1
400/3/50Hz
1 1 1 1
2. Data refers to nominal
conditions : room at 24°C°
-50% RH, water temperatures
TDEV – TUEV Airflow m3/h 5700 5700 8600 8600 8600 8600 8600 30-35°C, and ESP = 20Pa.
N° of compressors 1 1 2 2 2 2 2
3. Data refers to nominal
Refrigerating Circuits 1 1 1 2 1 2 1
conditions: room at 24°C-50%
Gross Total Cooling

CW MODE DX MODE
kW 19,1 23,7 27,0 28,4 30,4 32,2 34,6 RH,water temperature 7/12°C;
Capacity(1) (2)
Range glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 19,1 20,8 27,0 28,4 28,7 28,0 30,5 4. Data refers to Downflow unit.
Cooling capacity: 20 ÷ 100 kW Capacity(1) (2)
Gross Total Cooling
Refrigerant R-410A kW 20,2 20,2 28,5 28,5 28,5 28,5 28,5
Capacity(1) (3)
EC Fans Gross Sensible Cooling
kW 20,1 20,1 28,3 28,3 28,3 28,3 28,3
Capacity(1) (3)
Available Versions:
DIMENSIONS
- Downflow (TDEV) Height mm 1960 1960 1960 1960 1960 1960 1960
- Upflow (TUEV) Length mm 1010 1010 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865
TDEV –TUEV MODEL 1022A 1121A 1122A 1321A 1322A 1422A 1622A
Fans Nr. 1 1 2 2 2 2 2
Airflow m3/h 8600 12320 12320 12320 12320 16000 16000
N° of compressors 2 2 2 2 2 2 2
Refrigerating Circuits 2 1 2 1 2 2 2
Gross Total Cooling

CW MODE DX MODE
kW 37,1 36,9 39,2 46,6 49,7 49,7 55,9
Standard Features • Microprocessor control system includes: Capacity(1) (2)
• Evoluted microprocessor control system is available with - Integrated management of the cooling modes Gross Sensible Cooling
kW 30,4 36,9 37,4 40,3 39,9 49,7 55,9
Capacity(1) (2)
local or remote user terminal. monitoring room temperature, external temperature
Gross Total Cooling
• The units are equipped with EC fans for efficiency and glycol circuit temperature; kW 28,5 40,1 40,1 40,1 40,1 54,1 54,1
Capacity(1) (3)
maximization. - Integrated management of the EEV and
Gross Sensible Cooling
• The structure of the unit is characterized by a self- refrigerating circuit parameters kW 28,3 39,9 39,9 39,9 39,9 53,9 53,9
Capacity(1) (3)
supporting frame in galvanized steel with panels. The - Local user terminal with external accessibility DIMENSIONS
external panels are coated with RAL9003 epoxy-polyester - Integrated LAN card for local network connection
Height mm 1960 1960 1960 1960 1960 1960 1960
paint* and internally lined with heat and sound-proofing of a group of CRACs
Length mm 1010 1720 1720 1720 1720 2170 2170
insulation. - Rotation and active stand-by management
Depth mm 750 750 865 865 865 865 865
• Electronic expansion valve is controlled by the - Free contact for general and two for addressable
TDEV MODEL 1822A 2222A(4) 2242A(4) 2522A(4) 2542A(4) 2842A(4)
microprocessor and a dedicated software that increases alarms
Fans Nr. 2 3 3 3 3 3
the precision of the cooling and the energy efficiency of - Remote on/off switch
Airflow m3/h 16000 21500 21500 21500 21500 21500
the cooling cycle. - Ability to interface with Modbus protocol directly
N° of compressors 2 2 4 2 4 4
• Unit is equipped with an indirect free cooling system on RS485 serial card
Refrigerating Circuits 2 2 2 2 2 2
that provides the required cooling capacity when the - Ability to interface with main external communication
Gross Total Cooling

CW MODE DX MODE
external temperature is lower than the internal ambient. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP, kW 60,5 78,2 83,5 86,1 87,7 95,8
Capacity(1) (2)
Compressor power consumption is minimized while SNMP, and StruxureWareTM platform Gross Sensible Cooling
kW 56,0 71,3 77,6 74,4 74,9 77,1
internal and external environments are kept separate. Capacity(1) (2)
• The cooling coil is designed for an elevated SHR and *RAL5013 may be used during transition period. Gross Total Cooling
kW 54,1 96,6 96,6 96,6 96,6 96,6
reduced pressure drops in the air section. The coil is Capacity(1) (3)
made from copper tubes mechanically expanded on Construction Options Gross Sensible Cooling
kW 53,9 95,7 95,7 95,7 95,7 95,7
• Immersed electrode humidifier (D/U versions) Capacity(1) (3)
aluminum fins, complete with a hydrophilic treatment.
• The cooling coil is characterized by chilled water • Low surface temperature electrical heaters with DIMENSIONS
and direct expansion circuits interlaced to increase the extended fans, complete with double safety thermostat Height mm 1960 2150 2150 2150 2150 2150
efficiency of the unit in all running conditions. and manual resetting (T/H versions) Length mm 2170 2580 2580 2580 2580 2580
• Internal water-cooled condenser braze is welded and • Hot gas and hot water reheating Depth mm 750 750 865 865 865 865
made of AISI 304 stainless steel TUEV MODEL 2222A 2242A 2522A 2542A 2842A
• Uniflair LE units meet the following directives: 2006/42/ Accessories
Fans Nr. 3 3 3 3 3
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC The units can be supplied with the following external
Airflow m3/h 22000 22000 22000 22500 22500
F-GAS regulation accessories:
N° of compressors 2 4 2 4 4
• High-efficiency, EU4-pleated air filters are housed in a • Remote, semi-graphic user terminal
Refrigerating Circuits 2 2 2 2 2
metal frame and equipped with a dirty filter differential • RS485 serial adaptor to communicate with external
Gross Total Cooling
CW MODE DX MODE

BMS kW 78,4 83,7 86,3 88,3 96,4


pressure switch and low airflow differential pressure Capacity(1) (2)
switch • LON FTT10 serial adaptor to communicate with external Gross Sensible Cooling
kW 72,4 78,8 75,4 76,9 79,0
• The Uniflair LE range offers the possibility to select units BMS managed with LON protocol Capacity(1) (2)

equipped with two compressors (tandem) for each circuit, • TCP/IP serial adaptor to communicate with external Gross Total Cooling
kW 98,3 98,3 98,3 100,0 100,0
BMS managed with SNMP protocol Capacity(1) (3)
which grants better efficiency and regulation capacity at
• AFPS (Automatic Floor Pressurization System) that Gross Sensible Cooling
partial loads (models with the **21 or **42 suffix) kW 97,4 97,4 97,4 99,0 99,0
Capacity(1) (3)
• Total front access is available for unit maintenance permits to adapt its availability as a kit with installation
instructions DIMENSIONS
• The electrical panel is situated in a compartment
• Motorized damper Height mm 1960 1960 1960 1960 1960
separated from the air flow and complies with the
• Condensate drain pump Length mm 2580 2580 2580 2580 2580
2006/95/EC directive and related standards
• Suction from the top or front discharge plenums Depth mm 750 865 865 865 865
• Adjustable floor stands
54 | High-efficiency Room Air Conditioners 55 | High-efficiency Room Air-Conditioners
Twin cool air-cooled units with backward-curved fans

Uniflair LE
TDTR – TUTR

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 20 ÷ 100 kW TDTR MODEL 0611A 0921A 1321A 1622A 1822A 2242A(4) 2542A(4) 2842A(4)
net cooling data.
Fan type Backward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 400/3/50Hz
Available Versions: conditions : room at 24°C°
Fans Nr. 1 1 2 2 2 3 3 3
-50% RH, water temperatures
Airflow m3/h 5827 8541 11574 15905 15905 21809 21709 21809
- Downflow (TDTR) 30-35°C, and ESP = 20Pa.
N° of compressors 1 2 2 2 2 4 4 4
- Upflow (TUTR) Refrigerating Circuits 1 1 1 2 2 2 2 2
3. Data refers to nominal
conditions: room at 24°C-50%
Gross Total Cooling

DX MODE
kW 23,6 30,3 46,1 58,5 63,4 82,5 81,7 91,2 RH,water temperature 7/12°C;
Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 20,9 28,5 38,3 55,3 55,3 78,1 73,8 76,3 4. Data refers to Downflow unit.
Capacity(1) (2)
Gross Total Cooling

CW MODE
kW 20,5 28,3 38,6 53,9 53,9 97,6 97,3 97,6
Capacity(1) (3)
Gross Sensible Cooling
kW 20,4 28,2 38,4 53,7 53,7 96,7 96,4 96,7
Capacity(1) (3)
DIMENSIONS
Standard Features • The Uniflair LE range offers the possibility to select units Height mm 1960 1960 1960 1960 1960 2150 2150 2150
• Advanced microprocessor control system is available equipped with two compressors (tandem) for each circuit, Length mm 1010 1310 1720 2170 2170 2580 2580 2580
with local or remote user terminal. which grants better efficiency and regulation capacity at Depth mm 750 865 865 865 750 865 865 865
• The units are equipped with Backward-curved fans and partial loads (models with the **21 or **42 suffix). TUTR MODEL 2242A 2542A 2842A
directly-coupled asynchronuos motor. • Total front access is included for unit maintenance. Fans Nr. 3 3 3
• The structure of the unit is characterized by a self- • The electrical panel is situated in a compartment Airflow m3/h 22160 23194 23194
supporting frame in galvanized steel with panels. The separated from the air flow and complies with the N° of compressors 4 4 4
external panels are coated with RAL9003(*)epoxy- 2006/95/EC directive and related standards. Refrigerating Circuits 2 2 2
polyester paint* and internally lined with heat and sound- • Microprocessor control system includes: Gross Total Cooling

DX MODE
- Integrated management of the EEV and kW 82,7 82,5 91,9
proofing insulation. Capacity(1) (2)
• Unit is characterized by two independent cooling refrigerating circuit parameters Gross Sensible Cooling
kW 79,0 77,1 79,0
sources - one chilled water with related circuit and one - Local user terminal with external accessibility Capacity(1) (2)
direct expansion air cooled. - Integrated LAN card for local network connection Gross Total Cooling

CW MODE
kW 98,8 102,3 102,3
• Electronic expansion valve is controlled by the of a group of CRACs Capacity(1) (3)
microprocessor and a dedicated software that increases - Rotation and active stand-by management Gross Sensible Cooling
kW 97,9 101,3 101,3
the cooling precision and the energy efficiency of the - Free contact for general and two for addressable Capacity(1) (3)
cooling cycle. alarms DIMENSIONS
• The cooling coil is designed for an elevated SHR and - Remote on/off switch Height mm 1960 1960 1960
reduced pressure drops in the air section. The coil is - Ability to interface with Modbus protocol directly Length mm 2580 2580 2580
made from copper tubes mechanically expanded on on RS485 serial card Depth mm 865 865 865
aluminum fins, complete with a hydrophilic treatment. - Ability to interface with main external communication
• Uniflair LE units meet the following directives: 2006/42/ protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC SNMP, and StruxureWareTM platform
F-GAS regulation.
• High-efficiency, EU4-pleated air filters are housed in a *RAL5013 may be used during transition period.
metal frame and equipped with a dirty filter differential
pressure switch and low airflow differential pressure Construction Options Accessories
switch. • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• LON FTT10 serial adaptor to communicate with external
BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
56 | High-efficiency Room Air Conditioners 57 | High-efficiency Room Air-Conditioners
Twin cool air-cooled units with Backward-curved fans equipped with EC motor

Uniflair LE
TDTV – TUTV

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 20 ÷ 100 kW TDTV MODEL 0611A 0921A 1321A 1622A 1822A 2242A 2542A 2842A
net cooling data.
Fan type EC Backward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 400/3/50Hz
EC Fans conditions : room at 24°C-
Fans Nr. 1 1 2 2 2 3 3 3
50% RH , 45°C condensing
Airflow m3/h 5700 8600 12320 16000 16000 21500 21500 21500
Available Versions: temperature, and ESP = 20Pa.
N° of compressors 1 2 2 2 2 4 4 4
- Downflow (TDTV) Refrigerating Circuits 1 1 1 2 2 2 2 2
3. Data refer to nominal
conditions: Room at 24°C-50%
- Upflow (TUTV) Gross Total Cooling

DX MODE
kW 23,5 30,3 46,5 58,5 63,4 82,4 81,6 91,0 RH,water temperature 7/12°C;
Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 20,6 28,7 39,8 55,6 55,5 77,4 73,4 75,7
Capacity(1) (2)
Gross Total Cooling

CW MODE
kW 20,2 28,5 40,1 54,1 54,1 96,6 96,6 96,6
Capacity(1) (3)
Gross Sensible Cooling
kW 20,1 28,3 39,9 53,9 53,9 95,7 95,7 95,7
Capacity(1) (3)
DIMENSIONS
Standard Features pressure switch and low airflow differential pressure Height mm 1960 1960 1960 1960 1960 2150 2150 2150
• Advanced microprocessor control system is available switch. Length mm 1010 1310 1720 2170 2170 2580 2580 2580
with local or remote user terminal. • The Uniflair LE range offers the possibility to select units Depth mm 750 865 865 865 750 865 865 865
• The units are equipped with EC fans for efficiency equipped with two compressors (tandem) for each circuit, TUTV MODEL 2242A 2542A 2842A
maximization. which grants better efficiency and regulation capacity at Fans Nr. 3 3 3
• The structure of the unit is characterized by a self- partial loads (models with the **21 or **42 suffix). Airflow m3/h 22000 22500 22500
supporting frame in galvanized steel with panels. The • Total front access is included for unit maintenance. N° of compressors 4 4 4
external panels are coated with RAL9003(*)epoxy- • The electrical panel is situated in a compartment Refrigerating Circuits 2 2 2
polyester paint* and internally lined with heat and sound- separated from the air flow and complies with the Gross Total Cooling

DX MODE
2006/95/EC directive and related standards. kW 82,6 82,1 91,5
proofing insulation. Capacity(1) (2)
• Electronic expansion valve is controlled by the • Microprocessor control system includes: Gross Sensible Cooling
kW 78,6 75,5 77,6
microprocessor and a dedicated software that increases - Integrated management of the EEV and Capacity(1) (2)
the cooling precision and the energy efficiency of the refrigerating circuit parameters Gross Total Cooling

CW MODE
kW 98,3 100,0 100,0
cooling cycle. - Local user terminal with external accessibility Capacity(1) (3)
• Unit is characterized by two independent cooling - Integrated LAN card for local network connection Gross Sensible Cooling
kW 97,4 99,0 99,0
sources-one chilled water with related circuit and one of a group of CRACs Capacity(1) (3)
direct expansion air cooled. - Rotation and active stand-by management DIMENSIONS
• The cooling coil is designed for an elevated SHR and - Free contact for general and two for addressable Height mm 1960 1960 1960
reduced pressure drops in the air section. The coil is alarms Length mm 2580 2580 2580
made from copper tubes mechanically expanded on - Remote on/off switch Depth mm 865 865 865
aluminum fins, complete with a hydrophilic treatment. - Ability to interface with Modbus protocol directly
• The cooling coil is characterized by chilled water on RS485 serial card
and direct expansion circuits interlaced to increase the - Ability to interface with main external communication
efficiency of the unit in all running conditions. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
• The chilled water circuit is equipped with a three-way SNMP, and StruxureWareTM platform
valve and an actuator integrated with the microprocessor
• Uniflair LE units meet the following directives: 2006/42/ *RAL5013 may be used during transition period.
Construction Options Accessories
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
F-GAS regulation. • Low surface temperature electrical heaters with accessories:
• High-efficiency, EU4-pleated air filters are housed in a extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
metal frame and equipped with a dirty filter differential and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• LON FTT10 serial adaptor to communicate with external
BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
58 | High-efficiency Room Air Conditioners 59 | High-efficiency Room Air-Conditioners
Twin cool water-cooled units with backward-curved fans

Uniflair LE
TDDR – TUDR

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 20 ÷ 100 kW TDDR MODELS 611 921 1321 1622 1822 2242(4) 2542(4) 2842(4)
net cooling data.
Fan type Backward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 400/3/50Hz
Available Versions: conditions : room at 24°C°
Fans Nr. 1 1 2 2 2 3 3 3
-50% RH, water temperatures
Airflow m3/h 5827 8541 11574 15905 15905 21809 21709 21809
- Downflow (TDDR) 30-35°C, and ESP = 20Pa.
N° of compressors 1 2 2 2 2 4 4 4
- Upflow (TUDR) Refrigerating Circuits 1 1 1 2 2 2 2 2
3. Data refers to nominal
conditions: room at 24°C-50%
Gross Total Cooling

DX MODE
kW 23,8 30,4 46,2 55,9 60,5 90,5 87,8 96,0 RH,water temperature 7/12°C;
Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 21,1 28,5 38,8 55,9 55,8 79,7 75,3 77,7 4. Data refers to Downflow unit.
Capacity(1) (2)
Gross Total Cooling

CW MODE
kW 20,5 28,3 38,6 53,9 53,9 97,6 97,3 97,6
Capacity(1) (3)
Gross Sensible Cooling
kW 20,4 28,2 38,4 53,7 53,7 96,7 96,4 96,7
Capacity(1) (3)
DIMENSIONS
Standard Features equipped with two compressors (tandem) for each circuit, Height mm 1960 1960 1960 1960 1960 2150 2150 2150
• Advanced microprocessor control system is available which grants better efficiency and regulation capacity at Length mm 1010 1310 1720 2170 2170 2580 2580 2580
with local or remote user terminal. partial loads (models with the **21 or **42 suffix). Depth mm 750 865 865 865 750 865 865 865
• The units are equipped with Backward-curved fans and • Total front access is included for unit maintenance. TUDR MODELS 2242A 2542A 2842A
directly-coupled asynchronuos motor. • The electrical panel is situated in a compartment Fans Nr. 3 3 3
• The structure of the unit is characterized by a self- separated from the air flow and complies with the Airflow m3/h 22160 23194 23194
supporting frame in galvanized steel with panels. The 2006/95/EC directive and related standards. N° of compressors 4 4 4
external panels are coated with RAL9003(*)epoxy- • Microprocessor control system includes: Refrigerating Circuits 2 2 2
polyester paint* and internally lined with heat and sound- - Integrated management of the EEV and Gross Total Cooling

DX MODE
refrigerating circuit parameters kW 90,6 88,7 96,8
proofing insulation. Capacity(1) (2)
• Electronic expansion valve is controlled by the - Local user terminal with external accessibility Gross Sensible Cooling
kW 80,5 78,3 80,4
microprocessor and a dedicated software that increases - Integrated LAN card for local network connection Capacity(1) (2)
the precision of the cooling and the energy efficiency of of a group of CRACs Gross Total Cooling

CW MODE
kW 98,8 102,3 102,3
the cooling cycle. - Rotation and active stand-by management Capacity(1) (3)
• The cooling coil is designed for an elevated SHR and - Free contact for general and two for addressable Gross Sensible Cooling
kW 97,9 101,3 101,3
reduced pressure drops in the air section. The coil is alarms Capacity(1) (3)
made from copper tubes mechanically expanded on - Remote on/off switch DIMENSIONS
aluminum fins, complete with a hydrophilic treatment. - Ability to interface with Modbus protocol directly Height mm 1960 1960 1960
• Internal water-cooled condenser braze is welded and on RS485 serial card Length mm 2580 2580 2580
made of AISI 304 stainless steel. - Ability to interface with main external communication Depth mm 865 865 865
• Uniflair LE units meet the following directives: 2006/42/ protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC SNMP, and StruxureWareTM platform
F-GAS regulation.
• High-efficiency, EU4-pleated air filters are housed in a *RAL5013 may be used during transition period.
metal frame and equipped with a dirty filter differential
pressure switch and low airflow differential pressure
switch. Construction Options Accessories
• The Uniflair LE range offers the possibility to select units • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Low surface temperature electrical heaters with accessories:
extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Condensation control on refrigerant side with constant • LON FTT10 serial adaptor to communicate with external
water flow BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
60 | High-efficiency Room Air Conditioners 61 | High-efficiency Room Air-Conditioners
Twin cool water-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
TDDV – TUDV

Range TECHNICAL DATA 1. Gross Cooling capacities;


fans must be deduced to obtain
Cooling capacity: 20 ÷ 100 kW TDDV MODEL 0611A 0921A 1321A 1622A 1822A 2242A(4) 2542A(4) 2842A(4)
net cooling data.
Fan type EC Backward-curved centrifugal motor fan
Refrigerant R-410A 2. Data refers to nominal
Power supply V/ph/Hz 400/3/50Hz
EC Fans conditions : room at 24°C°
Fans Nr. 1 1 2 2 2 3 3 3
-50% RH, water temperatures
Airflow m3/h 5700 8600 12320 16000 16000 21500 21500 21500
Available Versions: 30-35°C, and ESP = 20Pa.
N° of compressors 1 2 2 2 2 4 4 4
- Downflow (TDDV) Refrigerating Circuits 1 1 1 2 2 2 2 2
3. Data refers to nominal
conditions: room at 24°C-50%
- Upflow (TUDV) Gross Total Cooling

DX MODE
kW 23,7 30,4 46,6 55,9 60,5 90,3 87,7 95,8 RH,water temperature 7/12°C;
Capacity(1) (2) glycol 0%, and ESP = 20Pa.
Gross Sensible Cooling
kW 20,8 28,7 40,3 55,9 56,0 79,0 74,9 77,1 4. Data refers to Downflow unit.
Capacity(1) (2)
Gross Total Cooling

CW MODE
kW 20,2 28,5 40,1 54,1 54,1 96,6 96,6 96,6
Capacity(1) (3)
Gross Sensible Cooling
kW 20,1 28,3 39,9 53,9 53,9 95,7 95,7 95,7
Capacity(1) (3)
DIMENSIONS
Standard Features • High-efficiency, EU4-pleated air filters are housed in a Height mm 1960 1960 1960 1960 1960 2150 2150 2150
• Advanced microprocessor control system is available metal frame and equipped with a dirty filter differential Length mm 1010 1310 1720 2170 2170 2580 2580 2580
with local or remote user terminal. pressure switch and low airflow differential pressure Depth mm 750 865 865 865 750 865 865 865
• The units are equipped with EC fans for efficiency switch. TUDV MODEL 2242A 2542A 2842A
maximization. • The Uniflair LE range offers the possibility to select units Fans Nr. 3 3 3
• The structure of the unit is characterized by a self- equipped with two compressors (tandem) for each circuit, Airflow m3/h 22000 22500 22500
supporting frame in galvanized steel with panels. The which grants better efficiency and regulation capacity at N° of compressors 4 4 4
external panels are coated with RAL9003(*)epoxy- partial loads (models with the **21 or **42 suffix). Refrigerating Circuits 2 2 2
polyester paint* and internally lined with heat and sound- • Total front access is included for unit maintenance Gross Total Cooling

DX MODE
• The electrical panel is situated in a compartment kW 90,6 88,3 96,4
proofing insulation. Capacity(1) (2)
• Electronic expansion valve is controlled by the separated from the air flow and complies with the Gross Sensible Cooling
kW 80,1 76,9 79,0
microprocessor and a dedicated software that increases 2006/95/EC directive and related standards. Capacity(1) (2)
the precision of the cooling and the energy efficiency of • Microprocessor control system includes: Gross Total Cooling

CW MODE
kW 98,3 100,0 100,0
the cooling cycle. - Integrated management of the EEV and Capacity(1) (3)
• Unit is characterized by two independent cooling refrigerating circuit parameters Gross Sensible Cooling
kW 97,4 99,0 99,0
sources- one chilled water with related circuit and one - Local user terminal with external accessibility Capacity(1) (3)
direct expansion air cooled. - Integrated LAN card for local network connection DIMENSIONS
• The cooling coil is designed for an elevated SHR and of a group of CRACs Height mm 1960 1960 1960
reduced pressure drops in the air section. The coil is - Rotation and active stand-by management Length mm 2580 2580 2580
made from copper tubes mechanically expanded on - Free contact for general and two Depth mm 865 865 865
aluminum fins, complete with a hydrophilic treatment. for addressable alarms
• The cooling coil is characterized by chilled water - Remote on/off switch
and direct expansion circuits interlaced to increase the - Ability to interface with Modbus protocol directly
efficiency of the unit in all running conditions. on RS485 serial card
• Internal water-cooled condenser braze is welded and - Ability to interface with main external communication
made of AISI 304 stainless steel. protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP,
• The chilled water circuit is equipped with a three-way SNMP, and StruxureWareTM platform
Construction Options Accessories
valve and an actuator integrated with the microprocessor • Immersed electrode humidifier (D/U versions) The units can be supplied with the following external
• Uniflair LE units meet the following directives: 2006/42/ *RAL5013 may be used during transition period.
• Low surface temperature electrical heaters with accessories:
EC, 2004/108/EC, 2006/95/EC, 97/23/EC, 842/2006/EC extended fans, complete with double safety thermostat • Remote, semi-graphic user terminal
F-GAS regulation. and manual resetting (T/H versions) • RS485 serial adaptor to communicate with external
• Hot gas and hot water reheating BMS
• Condensation control on refrigerant side with constant • LON FTT10 serial adaptor to communicate with external
water flow BMS managed with LON protocol
• TCP/IP serial adaptor to communicate with external
BMS managed with SNMP protocol
• AFPS (Automatic Floor Pressurization System) that
permits to adapt its availability as a kit with installation
instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands
62 | High-efficiency Room Air Conditioners 63 | High-efficiency Room Air-Conditioners
Chilled water units with backward-curved fans equipped with EC motor; fan module can be installed under or above raised floor

Uniflair LE
HDCV

TECHNICAL DATA 1. Data refer to nominal


Range conditions: Room at 36°C-
HDCV MODEL 4500A 5000A 4500A 5000A
25%RH water temperature
Fan type EC Backward-curved centrifugal motor fan
Cooling Capacity: 160 ÷ 200 kW 18/24°C, fan module installed
Version Single Coil Dual Coil under a 900mm raised floor,
Refrigerant Chilled Water Power Supply V/ph/Hz 400/3/50Hz 400/3/50Hz and glycol 0%.
EC Fans Fans Nr. 3 4 3 4
2. Includes fan module.
Airflow m3/h 30,000 40,000 30,000 40,000
Available Versions: 3. Cooling performance refers
Net Sensible Cooling kW 136,1 166,5 109,6 (1)(3) 128,9 (1)(3)
to one running chilled water
- Downflow Single Coil DIMENSIONS circuit.
- Downflow Dual Coil Height (2) mm 2510 2510 2510 2510
Length mm 2582 3110 2582 3110
Depth mm 865 865 865 865

Standard Features • Immersed electrode humidifier is included.


• Unit is made of two sections for installation of fan • Electrical heaters included with aluminum finned heating Construction Options
module under the raised floor and increase the coil elements.
surface for energy efficiency maximization. • Phase sequence control.
Unit with fan plenum installed
• Advanced microprocessor control system UG50 is • Microprocessor control system in addition allows: under the raised floor
included. - Integration with Uniflair Chillers for optimized
• The units are equipped with the latest generation management logics
Radical EC fans for efficiency maximization. Impellers are - Free contact for general and two for addressable
made of high-tech compound material with optimized alarms
flow control, combined with highly efficient GreenTech EC - Remote on/off switch
motors. - Integrated RS485 serial card for direct connection to
• Large surface copper and aluminum cooling coil is external BMS (Modbus)
provided for pressure drop minimization. - Second slot for additional serial card for BMS
• EC fan module is equipped with a circular plug in connection (optional)
connectors for quick and failure-free installation; the - Clock card integrated in the unit
module is supplied with safety protection grills on the
sides in case of underfloor installation.
• Adjustable fan speed meets energy-saving and load- Accessories
sharing logics. The units can be supplied with the following external
• Electric panel conforms to EC standards (2006/95/EC accessories: Unit with fan plenum installed
and EMC 2004/108/EC directives) . • Double power supply with automatic changeover and above the raised floor
• High-efficiency, pleated air filters are housed in a metal manual selection with integrated ultra capacitor
frame and filter differential pressure switch. • Intelligent dehumidification with cooling capacity limiting
• A low airflow differential pressure alarm switch is device
included. • Automatic floor pressurization system
• Full frontal accessibility is available for maintenance • Chilled water outlet temperature measurement
• Chilled water inlet temperature measurement is integrated in the microprocessor
integrated in the microprocessor. • Energy meter and CO2 emissions calculator integrated
• Integrated Discharge Temperature Control and Room in the unit
Moisture Control. • Ultra capacitor for single power supply units

64 | High-efficiency Room Air Conditioners 65 | High-efficiency Room Air-Conditioners


Monoblock wall-mounted units for external installation with downflow air discharge Monoblock wall-mounted units for external installation with upflow air discharge

Uniflair WM Uniflair WM
WDA - WDF WMA – WMF

Range Range
Cooling capacity: 6 ÷ 15 kW Cooling capacity: 3.9 ÷ 16.9 kW
Refrigerant R407C Refrigerant R407C
Available Versions: Available Versions:
- Without direct free-cooling (WDA) - Without direct free-cooling (WMA)
- With direct free-cooling (WDF) - With direct free-cooling (WMF)

Standard Features • The external screws are stainless steel, anti-tamper and Standard Features can only be removed using special tools.
• Monoblock conditioning units can be installed on the can only be removed using special tools. • Monoblock conditioning units are installed on the • The double external paneling is available in galvanized,
outside wall of the air conditioned room. • The double external paneling is available in galvanized, outside wall of the air conditioned room painted sheet steel and gives separate access to the fan
• Built-in air condenser is included. The units can be painted sheet steel and gives separate access to the fan • Air condenser is built in. The units can be supplied compartment and electric board compartments. This
supplied completely assembled and filled with refrigerant; compartment and electric board compartments. This completely assembled and filled with refrigerant enables maintenance and regulation to be carried out
all the components are set in the factory for normal enables maintenance and regulation to be carried out • All the components are set in the factory for normal without having to turn the unit off.
working conditions and the electrical and cooling without having to turn the unit off. working conditions. Electrical and cooling functions • Power Supply:
functions are tested. Installation only requires simple • Power Supply: are all tested. Installation only requires simple electrical - 230V/1/50Hz or 400V/3+N/50Hz (standard, according
electrical wiring and mechanical fixing to the shelter, even - 400V/3+N/50Hz standard wiring and mechanical fixing to the shelter, even by non- to the model)
by non-specialized personnel. on Request specialized personnel - Main power supply + UPS 230V
• The direct free-cooling units (WMF) are supplied with a - 230V/1/50Hz on 221 and 341 models • The direct free-cooling units (WMF) are supplied with a - Main power supply + UPS
motorized damper. During free-cooling the excess air is - Main power supply + UPS 48VDC (evaporator DC-fan/s) motorized damper. During free-cooling the excess of air - 48VDC (evaporator DC-fan/s)
expelled from the room through the condenser section • Microprocessor control is expelled from the room through the condenser section • Microprocessor control
without using any extra over-pressure dampers. • Scroll compressor without using extra over-pressure dampers • Scroll compressor (rotary for 0121 model) housed in
• Complete access to all the components allows servicing • EU4 filter (optional) • Complete access to all the components so that compartment isolated from the airflow
entirely from the outside, without having to enter the room • Modulating condenser fan/s speed control servicing can be entirely done from the outside, without • EU4 filter (optional)
which is normally protected by controlled access. • Free-cooling metal pre-filter having to enter the room which is normally protected by • Modulating condenser fan/s speed control
controlled access • Free-cooling metal pre-filter
• The external screws are stainless steel, anti-tamper and

TECHNICAL DATA 1. Data refers to mechanical


operation: ambient TECHNICAL DATA 1. Room: 26°C / 40% r.h.;
WDA-WDF MODEL WDF0221A WDF0341A WDF0481A WDF0501A
temperature: 27°C / 40%rH, external temperature: 35°C;
Power supply V/ph/Hz 400/3 +N/50Hz WMA-WMF MODELS 0121 0181 0251 0281 0331 0551 0661
external temperature 35°C R407C.
Mechanical Cooling (1) Power supply V/ph/Hz 230/1/50Hz 400/3+N/50Hz
/ R407C (data consider inlet
Mechanical Cooling (1) 2. Room: 26°C; external
Sensible Cooling Capacity kW 6,0/6,0 9,0/9,0 12,0/12,0 15,0/15,0 and outlet evaporating
temperature: 14°C; R407C.
Air flow m³ / h 1650 2350 2900 4200 coil), and Maximum external Sensible Cooling Capacity kW 3,9/3,9 5,4/5,4 7,4/7,4 8,2/8,2 9,6/9,6 15,2/15,2 16,9/16,9
temperature 45°C. Air flow m³ / h 1240 1460 2240 2240 2670 4580 4580 3. ARI standard.
COMPONENT FEATURES
WMF MODEL 4. Optional.
N° of evaporator fans 1 2 2 2
Free-cooling (2)
N° of condenser fans 1 1 1 1 5. Measurements taken at 1
Sensible Cooling Capacity kW 5,0 5,8 8,5 8,5 9,2 17,4 17,4 metre above the floor and at a
Compressor power
kW 1,25 1,94 3,56 3,78 Air Flow m³ / h 1230 1430 2100 2100 2280 4310 4310 distance of 5 metres from the
consumption (1)
DIMENSIONS COMPONENT FEATURES unit in free field, mechanical
cooling.
Height mm 1800 1800 1800 1800 N° of evaporator fans 1 1 2 2 2 1 1
Width mm 950 950 950 1120 N° of condenser fans 1 1 1 1 2 1 1
Depth mm 650 650 650 650 Air filter efficiency EU2 EU2 EU2 EU2 EU2 EU2 EU2
Nominal compressor power (3) kW 1,2 1,8 2,2 2,5 3,0 4,4 5,2
Electric heating (4) kW 2,6 4,0 4,0 4,0 6,0 6,0 6,0
Noise pressure level (5) dB(A) 40,5 44,0 45,5 45,5 49,0 50,0 54,0
DIMENSIONS
Height mm 1790 1790 1940 1940 1940 2250 2250
Width mm 650 650 930 930 930 1050 1050
Depth mm 400 400 450 450 450 625 625

66 | High-efficiency Room Air Conditioners 67 | High-efficiency Room Air-Conditioners


Monoblock units for internal installations

Uniflair MB
XMA - XMF – XDA - XDF

Range TECHNICAL DATA 1. Room: 26°C / 40% r.h.;


external temperature: 35°C;
Cooling capacity: XM* 5.7 ÷ 12.3 kW XD* 6.3-15.0 kW XDA-XDF MODELS 0221 0281 0341 0481 0501
R407C.
Power supply V/ph/Hz 230/1/50Hz 400/3+N/50Hz
Refrigerant R407C 2. Room: 26°C; external
Mechanical Cooling (1)
Available Versions: temperature: 14°C; R407C.
Total/Sensible Cooling
kW 6,3/5,8 7,0/6,4 9,0/9,0 12,0/12,0 14,9/14,9
Capacity 3. Optional.
- Upflow (XMA)
Air flow m³ / h 2230 2230 2900 3920 3920
- Upflow with free-cooling (XMF) Free-cooling (2)
- Downflow (XDA) Sensible Cooling Capacity kW 9 9 11,7 15,8 15,8
COMPONENT FEATURES
- Downflow with free-cooling (XDF)
N° of evaporator fans 1 1 1 1 1
N° of condenser fans 1 1 2 2 2
Air filter efficiency EU2 EU2 EU2 EU2 EU2
Electric heating (3) kW 2 2 4 4 4
DIMENSIONS
Height mm 1970 1970 2130 2130 2130
Width mm 850 850 1160 1160 1160
Standard Features - Scroll compressor with thermal protection
Depth mm 450 450 650 650 650
• Monoblock conditioning units are installed inside the - Ecological refrigerant R407C
XMF MODELS 0221 0281 0341 0401 0491 0555
installation. These units are ideal when the required - Modulating condenser fan speed regulation.
Power supply V/ph/Hz 230/1/50Hz 400/3+N/50Hz
solution is easy to install with all the refrigerant
• The microprocessor control manages the unit Mechanical Cooling (1)
components already installed.
autonomously and the free-cooling function and can be Total/Sensible Cooling
• The unit has a self-supporting steel structure finished kW 5,7/5,7 7,1/7,1 8,4/8,4 10,8/10,8 12,3/12,3 16,5/16,5
Capacity
in epoxy powder and external panels in steel finished in integrated with the most common BMSs. The control
Air flow m³ / h 1500 2000 2200 3700 3700 3710
epoxy powder; it’s lined internally with abrasion-resistant, includes:
Free-cooling (2)
self-extinguishing material for noise and heat insulation. - Microprocessor control board and user terminal
Sensible Cooling Capacity kW 6,1 8,1 8,9 15 15 15
• Units are supplied ready for installation, completely - Room temperature sensor
assembled and filled with refrigerant in the factory, where - Mixed air temperature sensor (X*F version only) COMPONENT FEATURES
they are calibrated and the electric and cooling systems - External temperature sensor (X*F version only) N° of evaporator fans 1 1 1 2 2 2
N° of condenser fans 1 1 1 2 2 2
are tested.
Air filter efficiency EU2 EU2 EU2 EU2 EU2 EU2
• Easy installation and connection to the outside is • Power Supply: Electric heating (3) kW 2 2 4 4 4 4
provided using rigid or flexible pipes that are fitted to the - 230V/ 1/ 50 Hz or 400V/3+N/50Hz (Standard, DIMENSIONS
window. according to the model) Height mm 1960 1960 1960 1960 1960 1960
• The air filtration is provided with an EU2-efficiency air - Main power supply + UPS 230V Width mm 1200 1200 1200 1200 1200 1200
filter in self-extinguishing material and a rigid metal frame; - Main power supply + UPS 48VDC (evaporator DC-fan/s, Depth mm 600 600 600 600 600 600
the free-cooling version is available with an additional available only for XMF)
free-cooling metal pre-filter. EU4 filters are available as an • Microprocessor control
option. • Scroll compressor with low noise level
• The evaporating and condensing fans are made of • EU4 filter (optional)
in galvanized steel. Double-inlet centrifugal fan(s) with • Modulating condenser fan/s speed control
forward-curved blower are keyed directly to motor shaft. • Free-cooling metal pre-filter
• The electrical panel is housed in a compartment isolated
from the airflow, complying with 73/23/CEE Norm.
Separate power supply for fans and microprocessor is
available as an option.
• Cooling circuit includes:
- Filter and flow sight glass
- Thermostatic expansion valve
- High- and low-pressure pressostats

68 | High-efficiency Room Air Conditioners 69 | High-efficiency Room Air-Conditioners


Spilt units for internal installations High-density cooling solutions

Uniflair SP Active Floor


UCA – UCF – UWA - UWF

Range Range

Cooling capacity: 5,9 ÷ 14,5 kW Cooling capacity: 6 ÷ 15 kW

Refrigerant R407C
Available Versions:
- Ceiling mounted (UCA)
- Ceiling mounted with direct free-cooling (UCF)
- Wall-mounted (UWA)
- Wall-mounted with direct free-cooling (UWF)

Standard Features using either rigged ducting or flexible piping.


• Units are made of two separate sections: the • The user terminal (on request) is fitted to the wall for Standard Features
evaporation section which is installed inside the the ceiling units and onboard for the wall fitted units, and • Active Floor is a flexible and modular system for cooling
conditioned room (UCA-UCF - UWA-UWF), and the gives complete control for the unit regarding changing Data Centres with medium- and high-density loads.
condensation section (MRA), which is installed on the and displaying the operating parameters. Integrated within a modular access floor in front of the
outside. • Internal and external units are powered separately. intake section of the rack, the Active Floor fits exactly
• The evaporator is designed to be fixed to the ceiling or • Power Supply: into a modular access floor panel measuring 600 mm
a wall and, with advanced microprocessor control, it is - 230V/ 1/ 50 Hz or 400V/3+N/50Hz (Standard, x 600 mm. The cold air produced by the Close Control
very precise in maintaining the set parameters inside the according to the model) perimeter units is directly channeled to the source of the
conditioned room. • Main power supply + UPS thermal load thanks to the advanced adjustment of the
• Servicing is very simple as different access is given to - 48VDC (evaporator DC-fan/s) direction of the airflow. The Active Floor creates a high-
the electrical board, the technical compartment, and the • Evaporator sections are equipped with: density bubble of air, which is maintained at a constant
servomotor for the free-cooling damper. - Microprocessor control temperature along the whole intake section of the rack,
• There is a special panel for the fan compartment, which - EU4 filter (optional) guaranteeing operation at the nominal design conditions.
means calibration and servicing can be carried out safely - Scroll compressor The air flow varies according to the actual thermal load
without having to turn the unit off. - Modulating condenser fan/s speed control and is detected by two sensors placed on the discharge
• UCF units have free-cooling which intakes air from the section of the servers.
back of the unit through a connection that can be made • Active Floor employs variable speed EC, motor-driven
fans to minimize energy consumption.
TECHNICAL DATA 1. Room: 26°C / 45% r.h.; • This solution may be used in stand-alone applications
MODELS CEILING UCA-UCF WALL UWA - UWF external temperature: 35°C; as well as with perimeter Close Control units equipped
R407C. with underfloor pressure control.
0341 0401 0481 0341 0401 0481
Power supply V/ph/Hz 230/1/50Hz 230/1/50Hz 2. Room: 26°C; external • The Active Floor guarantees optimum operation of high-
Mechanical Cooling (1)
temperature: 14°C; R407C. density equipment for loads installed in each module of 25
Sensible Cooling Cap. kW 5,9/5,9 7,1/7,1 8,1/8,1 10,4/10,4 14,5/14,5 5,9/5,9 7,1/7,1 8,1/8,1 10,4/10,4 14,5/14,5 3. ARI standard. kW and 40 kW with solutions featuring the two modules
Air flow m³ / h 1850 1850 220 2600 3900 1850 1850 2200 2600 3900
certified by TUV.
UCF-UWF 0341 0401 0481 0341 0401 0481
Free-cooling (2)
Sensible Cooling Cap. kW 6,7 6,7 6,9 9,5 14 6,7 6,7 6,9 9,5 14
TECHNICAL DATA
Air flow m³ / h 1850 1850 220 2600 3900 1850 1850 2200 2600 3900
ACTIVE FLOOR
DIMENSIONS
Power supply V/ph/Hz 220/1 + N/60
Height mm 330 330 330 410 410 1200 1200 1200 1300 1300 N° of condenser fans 1 / E.C
Width mm 950 950 950 1150 1150 980 980 980 1150 1150 Max air flow m³/h/CFM 4988/2936
Depth mm 1050 1050 1050 1300 1300 330 330 330 410 410 Nominal air flow m³/h/CFM 2880/1650
EXTERNAL UNIT MRA 0221 0281 0341 0401 0611 0211 0281 0341 0401 0611 Min air flow m³/h/CFM 1698/999
Power supply V/ph/Hz 230/1/50Hz 400/3 + N/50Hz 230/1/50Hz 400/3 + N/50Hz
DIMENSIONS
Nominal compressor
kW 1,7 2,1 2,6 3,1 4,6 1,7 2,1 2,6 3,1 4,6 Height mm/inch 230 / 9.1
power (3)
Air flow m³ / h 1800 2990 2990 6290 6290 1800 2990 2990 6290 6290 Width mm/inch 600 / 23.6
DIMENSIONS Depth mm/inch 600 / 23.6

Height mm 610 610 610 1230 1230 610 610 610 1230 1230
Width mm 850 850 850 1200 1200 850 850 850 1200 1200
Depth mm 345 345 345 80 80 345 345 345 480 480

70 | High-efficiency Room Air Conditioners 71 | High-efficiency Room Air-Conditioners


Air-cooled remote condensers Economizers

Uniflair CAP EcoBreeze

Range
Cooling capacity: 7 ÷ 160 kW Range

Refrigerant R-410A 50÷400 kW


Indirect Econimization

Standard Features Accessories Standard Features


• R-410A refrigerant. • Shut off valves • A modular economizer that meets the future cooling and
• Low noise axial fans with IP54 class F electric motor. • Leg support kit energy efficiency requirements of Data Centres today and
• Fan speed pressure switch regulator with protection • Manifold kit to make the unit single circuit tomorrow
grade IP55. • Coil protection treatment for use in aggressive
• Safety protection grills. environments
• Copper and aluminum condensing coil. • Low temperature versions down to -40°C with high-
TECHNICAL DATA *Approximate operating weight
• Low noise levels. resilience steel liquid receiver and flooding valve to control
with ducting
• Outdoor installation. the condensing temperature MODELS MODULE 200KW FRAME 400 KW FRAME

• High-efficiency, EU4-pleated air filter housed in a metal Weight 1247 kg 7704 kg* 14261 kg*

frame and filter differential pressure switch. Length 2,8 m 6,1 m 12,2 m

• Vertical or horizontal installation. Height 2,5 m 2,9 m 2,9 m

• Welded refrigeration connections for rapid and safe Width 1m 2,4 m 2,4 m
connection. IT airflow 5,000 CFM (2360 l/s) 20,000 CFM (9439 l/s) 40,000 CFM (18878 l/s)
• Condensers are powered by the internal unit to grant Outside airflow 7,000 CFM (3304 l/s) 28,000 CFM (13215 l/s) 56,000 CFM (26429 l/s)
operation at 208V - 230V with a tolerance of +/-10%. Nominal cooling capacity 50 kW 200 kW 400 kW

1. With external temperature ECONIMIZATION COMPARISONS 1. Hot aisle containment 38.6C°


TECHNICAL DATA
35°C and 50°C R-410A return to A/C
CAP MODEL 251 331 361 511 611 801 1011 1301 SYSTEM ARCHITECTURE PARTIAL PUE KW-HR/YR RELATIVE POWER
condensing temperature 2. Supply air/cold aisle 25C°
Fan type Axial EcoBreeze 1,09 466,518 45%

Power supply V/ph/Hz 208-230/1/50Hz 2. Measured in free field Air econ w/heat wheel 1,1 503,999 48% 3. Bin weather data Saint Louis,
conditions at 5 meters from Water cooled chiller with econ 1,14 728,195 70% MO, USA
Performance capacity (1) kW 8,2 9,8 12,8 16,6 20,2 27,6 33,7 44,5
the unit
Air flow rate at 0.08in.w (20Pa) m3/h 3050 2750 3300 6100 9150 9150 8250 10980 Air cooled chiller with econ 1,16 846,039 81%
4. Does not reflect humidification
Number of circuits 1 1 1 1 1 1 1 1 Fresh air econ 1,14 718,159 69% losses
Noise level (2) dB(A) 51 50,5 51,5 53,2 52,6 54,6 54,1 54,6 DX fluid cooled CRAC w/econ 1,2 1,044,073 100%
5.Fan control proportional to IT
DIMENSIONS Nominal cooling capacity 50 kW 200 kW 400 kW load of design
Height mm 732 732 1067 1227 1227 1877 1877 2277
Width mm 350 350 350 350 350 350 350 350
Depth mm 700 700 700 700 700 700 700 700
CAP MODEL 1802 2002 3002 4002 5002 6002 7002
Fan type Axial
Power supply V/ph/Hz 208-230/1/50Hz
Performance capacity (1) kW 61,3 67 88,7 96,4 127,9 145,8 166,7
Air flow rate at 0.08in.w (20Pa) m3/h 17500 16900 27500 26250 35000 45000 42250
Number of circuits 2 2 2 2 2 2 2
Noise level (2) dB(A) 61 61 63 63 64 65 65
DIMENSIONS
Height mm 2217 2217 3217 3217 4217 5217 5217
Width mm 400 400 400 400 400 400 400
Depth mm 700 700 700 700 700 700 700

72 | High-efficiency Room Air Conditioners 73 | High-efficiency Room Air-Conditioners


Data center infrastructure
management (DCIM)

Good design and quality construction alone do not ensure a highly available and
efficient data center. Data centers require ongoing monitoring and management
to ensure the facility lives up to its design intent. StruxureWare™ for Data
Centers is a software management suite designed to collect and manage data
about a data center’s assets, resource use, and operational status throughout
the life cycle of the facility. This information is then distributed, integrated, and
applied in ways that help managers optimize the data center’s performance
and meet IT, business, and service-oriented goals. From IT assets to racks,
rows, rooms, and buildings, StruxureWare for Data Centers delivers the right
information to the right users at the right time.

Control level
Experts, on-site or remotely, can control process performance
and ensure business continuity in real time, while tracking energy
consumption in a highly critical and secure environment.

Operations level
Functional managers can optimize operations, energy, and assets
through smart analytical tools, often spanning multiple sites.

Enterprise level
C-level executives can drive their sustainability strategy efficiently,
choosing the best scenario that meets their business objective to
conserve enterprise-wide resources.

StruxureWare for Data Centers allows for flexibility when requirements


and implementation strategies change over time. StruxureWare
software applications and suites simplify integration time, improve
reliability, enhance visibility to energy information, and streamline
operational efficiency.

Visit www.apc.com/software to learn more


about StruxureWare for Data Centers!

74 | High-efficiency Room Air Conditioners 75 | High-efficiency Room Air-Conditioners


High Efficiency Room Air Conditioners 76

To learn more about Schneider Electric cooling solution visit www.uniflair.co.uk

Make the most of your energy SM

Uniflair Ltd
33 Star Lane Estate
Southend-on-Sea
Essex
SS3 0PJ
Tel.: +44 (0)1702 219494
www.uniflair.co.uk

©2014 Schneider Electric. All Rights Reserved. Schneider Electric, Uniflair, EcoBreeze, StruxureWare, NetBotz, EcoStruxure, and InfraStruxure are trademarks owned by Schneider Electric Industries SAS