Professional Documents
Culture Documents
GRAND SUMMARY
GONDAR UNIVERSITY CANCER TREATMENT CENTER
TOTAL PRICE
ITEM NO.OF UNIT PRICE
PROJECT TYPE (ETB) with
NO. BLOCKS (ETB) with VAT
VAT
1 MAIN BUILDING & BUNKER 1 513,228,131.70 513,228,131.70
2 TREATMENT PLANT 1
- -
3 SITE WORK 1
- -
4 FENCE WORK 1
- -
5 MISCELLANEOUS 1
- -
GRAND TOTAL 513,228,131.70
B. SUPER STRUCTURE
5.01 I) Doors
a) Type:- D3, Size:- 90 x 210cm. No 39.00 12,264.73 478,324.47
b) Type:- D6, Size:- 180 x 230cm. Sliding Glass Doors
No 23.00 26,865.60 617,908.80
c) Type:- D7, Size:- 120 x 220cm. Sliding Glass Doors
No 8.00 17,131.69 137,053.52
d) Type:- D8, Size:- 80 x 195cm. No 28.00 10,123.27 283,451.56
e) Type:- D9, Size:- 70 x 195cm. No 56.00 8,857.86 496,040.16
ii) Windows: -
a) Type:- W1, Size:- 223 x 100cm. No 7.00 14,471.08 101,297.56
b) Type:- W2, Size:- 150 x 100cm. No 3.00 9,733.91 29,201.73
ii) Window Door -
a) Type:- WD1-WD6, Size:- 100 x 220cm. Sliding Glass
No 45.00 14,276.41 642,438.45
b) Type:- WD14, Size:- 90 x 148cm. No 3.00 8,643.71 25,931.13
c) Type:- WD15, Size:- 150 x 195cm. No 3.00 18,981.13 56,943.39
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
5.02 Door For Bunker as per the following Specification
a) Size 200x250cm
No 1 129,824.50 129,824.50
11.11.1 FIRE ALARM SYSTEM
a Flush mounted Fire alarm addressable ionization type
smoke detector. No 635 5,176.60 3,287,141.00
b Flush mounted Fire alarm addressable type heat detector.
No 2 5,176.60 10,353.20
c Surface mounted Fire alarm addressable manual call
point non-breakable with plastic cover and reset key. No 83 5,176.60 429,657.80
d Fire alarm addressable sounder on loop with relay base
and indicating light. No 64 6,120.56 391,715.84
e Fire alarm system (which includes all the equipments)
point fed through fire alarm system cable of 2x1.5sq. mm
inside pvc conduit of 20mm diameter No 701 2,749.50 1,927,399.50
f IP based Intelligent digital addressable fire control ,voice
evacuation and Appliance Circuit Modules,Control Relay
Module , indicating panel, including Notification auxilary
contact and under mentioned specification
at least 72Hr
-Intelligent signaling line circuit
-voice alarm system interface
-Trouble acknowledge and alarm silence switch
-Visual and audiable trouble alarm by zone
-Manual acknowlage function
-Minimum of 40 zones digital
-LCD display (80 characters)
-Program keypad
-LED indicators
-13 relay outputs
-25 Auxilary relay outputs
-3 loops
-Compatible devices
-Compatible intelligent devices
with all necessary accessories as BS EN 54
standards to make the system No. 1 325,771.88 325,771.88
g Testing and commissioning as per the manufacturers
instruction. L.S 1 65,000.00 65,000.00
11.12 Light Fittings and Lamps
(Specified type or equivalent)
b Surface mounted fluorescent luminaire LITECH 11-8102
T8 1x18W IP20 No. 160 1,381.63 221,060.80
c Surface mounted fluorescent luminaire LITECH 11-8102
T8 1x18W IP20 No. 130 1,381.63 179,611.90
d Recessed mounted fluorescent luminaire LITECH 11-
8102 T8 4x18W IP20 No. 880 2,764.66 2,432,900.80
e Surface mounted fluorescent luminaire LITECH 11-8102
T8 2x18W IP20 No. 480 2,099.54 1,007,779.20
f Toilet Ceiling RZB 25129. 962 TC-D 18W IP43 No. 110 1,794.43 197,387.30
g Toilet Ceiling RZB 25129. 962 TC-D 2x18W IP43 No. 20 2,602.08 52,041.60
h Toilet wall for mirror RZB 21146. 962 TC-D 13W IP44 No. 25 1,381.63 34,540.75
i Toilet wall linear for mirror 401001.912.79 TC-EL 13W
IP44 No. 100 1,381.63 138,163.00
k Indoor half recessed down light LITECH 12-8006-005
E27 2XPLE 18W IP23 No. 120 1,884.17 226,100.40
l Indoor recessed down light LITECH 12-6386-003 E27
2XPLE 18W IP44 No. 20 1,884.17 37,683.40
m Indoor recessed down light LITECH 12-6386-003 E27
1XPLE 18W IP44 No. 80 1,389.39 111,151.20
n Outdoor wall RZB 58138.923 TC-D 18W IP54 No. 10 1,285.39 12,853.90
o Fluorescent 2x18W lamp, ceiling fitting Exit light with
pictogram No. 65 3,104.61 201,799.65
p Fluorescent 2x18W lamp, wall fitting Exit light with
pictogram No. 50 3,104.61 155,230.50
11.13 Grounding System
Complete grounding system for Main distrubution board
as per IEC,EN or BS standards attain 5 ohms with
complete inspection pits as per the detail drawings bare
copper wire, copper rods of approprate size conducting
materials and approved type of networks complete
accessories.
1 63,180.00 63,180.00
b) TV point fed through RG6 75ohms broad band Co- No.
axial cable (47-2500MHz) suitable for TV/FM/SAT signal
distribution inside PVC conduit of 20mm diameter,
including junction boxes with covers, insulating screw cap
connectors
70 270.00 18,900.00
TV Terminal Box No.
32 398.23 12,743.36
Flush mounting terminal SAT/TV/FM outlet. No.
70 230.00 16,100.00
11.15 Standby Diesel Generator
a 630KVA Diesel generating set output at 2500m above
sea level with, ATS, 380/230V,50Hz,1500rpm,0.8pf,3ph,
self exited, insulation class H for stator and rotor, with
base mounted fuel tank, skid mounted including
residential rated exhaust silencer, electric fuel transfer
pump, as indicated in the specification and with weather
proof and sound proof canopy with sound level
approprate for hospital use.And also external fule tank
system with all accesaaeries with fuel capacity of 8 hours
supply of the generator at full load.
Nº 71 1,948.57 138,348.47
12.1.02 Hand Wash Basin (Wall hung basin)
Supply and fix Hand Wash Basin , made of white
vitreous China (BS3402) ,Wall hung basin. The fixture
shall conform to BS5506-3 or equivalent institution. Size
560 x 450 mm. The waste fittings, connecting pieces,
fixing and supporting element and other accessories
which complete the set shall comply with the relevant
clauses of BS standard or equivalent institution. The tap
ware shall comply to BS2878:1980 and fix all the
necessary accessories must be provided.
Nº 24 1,800.00 43,200.00
12.1.03 Hand Wash Basin (Above the counter)
Supply and fix Hand Wash Basin , made of white
vitreous China (BS3402) ,granite counter top
mounting. The fixture shall conform to BS5506-3 or
equivalent institution. Size 550 x 470 mm. The waste
fittings, connecting pieces, fixing and supporting element
and other accessories which complete the set shall
comply with the relevant clauses of BS standard or
equivalent institution. The tap ware shall comply to
BS2878:1980 and fix all the necessary accessories must
be provided.
Nº 73 27,479.44 2,005,999.12
12.1.04 Disabled Hand Wash Basin
Supply and Fix white vitreous China (BS3402) Wall hung
basin. The fixture shall conform to BS5506-3 or
equivalent institution. Size 700 x 405 mm. The waste
fittings, connecting pieces, fixing and supporting element
and other accessories which complete the set shall
comply with the relevant clauses of BS standard or
equivalent institution. The tap ware shall comply to
BS2878:1980 with Rails:-600mm Support Rails (x 3)
Nº 34 25,707.80 874,065.20
12.1.05 Water closet
Supply and fix water closet , of wash down action, floor
mounted , vertical outlet (floor drainage), close
coupled ,made of white vitreous China (BS3402).The
fixture shall conform to BS5503-2 or equivalent institution.
The waste fittings, connecting pieces, fixing and
supporting element and other accessories which
completes the set shall comply with the relevant clauses
of BS standards or equivalent institution. with P-trap and
Strap.
Nº 131 5,000.00 655,000.00
12.1.06 Disabled Water closet
Supply and fix Disabled water closet ,of wash down
action, floor mounted , vertical outlet (floor drainage),
close coupled, made of white vitreous China
(BS3402).The fixture shall conform to BS5503-2 or
equivalent institution. The waste fittings, connecting
pieces, fixing and supporting element and other
accessories which completes the set shall comply with
the relevant clauses of BS standards or equivalent
institution.
Rails:-600mm Support Rails (x 1),765mm Hinged
Support Rail (x2)
Nº 34 25,122.80 854,175.20
12.1.07 Urinals
Supply and fix approved quality wall mounted concealed
steel hanger, concealed flush pipes, built in p-trap
500mmx700mcm,15mm thick ceramics urinal partition
wall complete with all necessary accessories. Unit price
shall include all the necessary assistances to the
installation works.
Nº 21 2,000.00 42,000.00
12.1.08 Toilet Paper Holder
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Supply and fix toilet paper holder , made from white
vitreous china(BS3402) ,concealed/surface mounted of
approved quality complete with all the necessary
accessories. Nº 165 250.00 41,250.00
12.1.09 Crystal glass mirror
Supply and fix approved quality frameless crystal glass
mirror ,back-silvered ,minimum 6mm thick Size 600mm x
500mmComplete with thief resistant concealed wall
fastening fittings and other accessories.
Nº 168 1,560.00 262,080.00
12.1.10 Soap Holder
Supply and fix soap holder leassed type of approved
quality ,made of white vitreous china , European
standard or equivalent institution, complete with all the
necessary accessories. Nº 168 260.00 43,680.00
12.1.11 Floor Drain & Shower Drain
supply and fix 80mm diameter enameled cast iron floor
drain conform to ASME standards, A112.6.3(heavy duty)
or equivalent institution complete wit P-smel trap and all
the necessary accessories.
Nº 128 500.00 64,000.00
12.1.12 Disabled shower
Supply and Fix with SHOWER VALVE AND KIT:-
Concealed Shower Valve, Diverter Riser Rail, Hose,
Handset, Elbow and Short Projection Overhead Shower,
and adjustable and detachable shower head with shower
tip up seat with back support, Rails:-600mm Support
Rails (x 3),765mm Hinged Support Rail (x2) 450mm
Support Rail (x1),Robe Hook (x1).
SHOWER RAIL & CURTAIN:-1200mm x 1200mm
Angled Shower Rail With Celling Support and 1000 x
1200 Shower Curtain (x2).
Nº 8 20,176.30 161,410.40
12.1.13 Tower hanger
Supply and fix towel hanger 610 x 25 mm with chrome
plated tubular towel rail complete with the necessary
accessories. Nº 136 260.00 35,360.00
12.1.14 Kitchen Sink
Supply and fix double bowl stainless steel kitchen sink
with brass chrome plate trap. The waste fittings,
connecting pieces, fixing and supporting element and
other accessories which complete the set shall comply
with BSEN 695;1997 or the relevant clauses of BS
standards or equivalent institution. The tap ware shall
comply to BS2878:1980
Size 1500 x 600 x 150mm (bowl depth)
Nº 4 3,216.99 12,867.96
12.1.15 Fire Extinguisher
Supply and fix 9kg Dry Powder fire extinguisher for
ABCE class of fire. The material shall comply ,with TUV
or,BSI or ,NFPA or equivalent institution certification and
approval. Complete with approved standard hanging and
fixing materials.
Nº 40 2,099.70 83,988.00
12.1.16 Sluice Sinks
Supply and fix a wall mounted stainless steel sink unit
with continuous flushing rim and conical bowl for the
disposal of liquid and solid waste. The unit has a raised
anti-drip rim and 50mm sides turned down all round. This
unit also features a 500 x 400 x 250 sink bowl. Available
with TOP INLET for exposed cistern or REAR INLET for
concealed cistern. Complete with stainless steel flush
pipe, chrome plated front operating lever, syphon, ball
valve and float, and side entry inlet connection.
Available with drain board to the left or right of the unit.
Dimensions:
1600mm x 600mm x 365mm (LxWxH) this includes:-
1600 x 600mm DU H Sluice Sink, 2x Stainless steel
heavy duty wall brackets,110mm polypropylene waste
trap (choice of ‘P’ or ‘S’ trap),Sink waste fitting, Stainless
steel 9ltr cistern (TOP INLET MODEL ONLY),or
Concealed plastic cistern.600mm stainless steel fall pipe
(TOP INLET MODEL ONLY).
Nº 9 66,865.80 601,792.20
12.1.17 ICU Sinks
Supply and fix Vitreous china
• Permanent Ever Clean® surface inhibits the growth of
stain & odor causing bacteria, mold & mildew
• Deep basin & sloped ledges minimize splashing
• Sink drain is offset so that the water stream does not
fall directly on the grid drain
• Sink is designed with sealed overflow to eliminate
an area for water to pool
• Includes removable acrylic shroud (with mounting
hardware) to allow access to the faucet electronics
• Includes offset grid drain & P-Trap with
Saniguard®** coating.
SELECTRONIC® FAUCET:
Hygienic hands-free operation
• Rigid gooseneck spout with 5" reach
• 1.5 gpm laminar flow restrictor in spout shank - No mix
of
air & water
• Plain spout end - Nothing on the end of the spout to
collect lime & debris. With power option pluge in and DC
(battery)
• Fully enclosed, water resistant &
hermetically sealed
electronic controls
• Vandal-resistant durable brass construction
• Integral in-line strainer prevents clogging
• Factory-installed 15" long S.S. flex hose with 3/8"
compression connection
• Lead Free: Faucet contains ≤ 0.25% total lead content
by weighted average
• Optional thermostatic mixing valve (605XTMV) is
available & must be ordered separately
Nominal Fixture
Dimensions:
509 x 432 x 663mm Nº 5 48,964.80 244,824.00
11.1.18 Scrub Sinks
Type 304 Stainless steel construction with welded
compartments and coved corners for easy cleaning
Stainless Steel Construction. With removable
bay(Station) Panels.. Equipped with infrared operated
water control as well as a manual bypass for knee
operated water control. The main operation is via the
infrared sensor located between the knee panels. The
knee operation for water control is on standby as a
backup. Field upgradeable knee operated soap
dispenser or foot pump accessory. Digital timer: ensuring
adequate scrubbing time, Removable Shower Head,•
Adjustable thermostatic controlled pressure regulating
mixing valve, one per station,: the built-in thermostatically
controlled mixing valve provides water temperature up to
115° F (46° C),Adjustable Pressure Regulator Laminar
flow faucet: delivering a consistent stream of non-splash
water, Digital Timer,o Eye-wash station: safety option is
turned on by activating the knee panel and a pull of the
center knob, releasing both safety caps to provide instant
flushing .
Dimensions: 2438mm x 692mm x 1308 mm)
(LxWxH) Three station
Nº 4 223,342.90 893,371.60
12.1.19 Ditto Item, but Dimensions: 813mm x 692mm x 1308
mm)(LxWxH) One Station Nº 2 147,810.30 295,620.60
12.1.20 Emergency Shower -Eye Wash
Supply and fix Type 316 Stainless steel Combination
Shower & eye Face wash station plastic triple aerated
eye-face wash nozzle assemblies to provide the
optimum facial and eye irrigation. Shower Flow Control
Regulator. All Pratt Combination Shower Units are fitted
with a flow control regulator, which limits the flow output
to 90LPM. This ensures the
shower will exceed the minimum required flow rate and
allow the eye
wash to operate simultaneously as required by the
Standards. Adjustable Eye Wash Flow Control All Pratt
Combination, Eye-Face Wash and Eye Wash Stations
incorporate an adjustable flow control.
A)shower:-Hands-free valve
activates in one second or less and remains open until
manually closed, Height of water column is between
(208.3 cm) and(243.8 cm) above the floor. FF Center of
the water pattern is at least (40.6 cm) from any
obstruction.FF Easily located, accessible actuator is no
more than (173.3 cm) above floor.
Nº 2 63,342.80 126,685.60
12.1.21 Lab Sink
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Supply and fix Radioactive sink that coved to the back
wall with rounded upstanding front edges. A splash back
should be fitted to the back wall using similar finishes.
Small bore u-shaped or bottle traps should be used, large
traps and catch pots are to be avoided. With Lead
warping of piping Taps should be provided which can be
operated without using hands. The pressure of the water
should be regulated such that at full flow (tap full on)with
all the necessary accessories.
Dimensions: 660mm x 460mm x 273mm (LxWxH)
Nº 5 62,692.80 313,464.00
12.1.22 Electric Water Heater
Supply and fix approved quality storage type water
heaters, complete with insulation, one way valve and
safety valve, including all fixing accessories.
*
made from steel :-highly resistance to any deformation
caused by variation in temperature and internal pressure.
* With
Glass lining treatment:- The lining of the tank is
subjected to a treatment with titanium or equivalent glass
lining.
Nº 93 4,500.00 418,500.00
12.1.23 Ditto Item No 21,but 80Liters Nº 3 5,509.06 16,527.18
12.1.24 Janitors Sink
Construct Janitors sink out of single brick wall,450mm
high on the base of 150mm thick mass concrete/C-25/,
plastered both internal and with white ceramics.
Size :- 1500 x 500mm Nº 2 4,043.49 8,086.98
internal dimension
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
PPR-Pipes
12.1.25 POLYPROPYLENE RANDOM CO-POLYMER (PP-R
TYPE3)pressure pipes ,(PN20),for cold and hot water
supply system to sanitary fixtures which comply with BS
6920:part 2&3 or DIN 8078 and equivalent institution
complete with all the necessary connecting pieces such
as bends, Ys, Tees, reducers, nipples, Teflon, unions,
threaded male or female with de-indication resistance
(DZR)brass inserts complying with BS 6920 or
equivalent institution, hangers(as per manufacturer's
recommendation) & supporters (if any) etc…The
installation shall be tested at a pressure of 10kg/cm2 or
DIN 1988 part 2 or Supply, lay and connect outer
diameter 20mm BS 6700 . Unit price shall
include ,disinfection of the pipes with Chlorine, painting all
exposed PP-R pipes with UV Reflexive oil paint,
installation works any all additional works there to .
ml 60 519.96 31,197.60
12.1.39 Ditto Item No 36, but diameter 65mm ml 108 151.00 16,308.00
12.1.40 Ditto Item No 36, but diameter 40mm ml 3 104.00 312.00
12.1.41 Ditto Item No 36, but diameter 20mm ml 3 57.00 171.00
12.1.42 Supply and fix BS ,NFPA or DIN standard ,surface
mounted with full metal door model, fire hose reel
cabinet . Cabinet and door leaf made of stainless steel
2mm thick sheets with full 180 degree swinging action
and painted with electro--statics powder paint oven baked
to temperatures between 160-200 oc.Hose is made of
100% synthetic Jacket ,the outer fabric is made of circular
woven SYNTHETIC FIBER and root proof yarn, while
inner layer is a substrate of tropical rubber, with working
pressure 20 bar and bursting pressure 60 bar with
standard red color. Nozzle is made of brass with Chrome
plated with three way control .Cabinet:-W=65cm,H=65cm
and D=19cm The installation shall be tested at a pressure
of 16kgf/cm2. The hose shall be compatible to
Galvanized Steel pipes, accessories & fittings.GS pipe
installation & method of connection shall comply with the
requirement of BS 4991 & BS 6920 part 2 &3 or
equivalent institution. Unit price shall include all the
necessary assistance to the installation works.
Nº 14 21,790.65 305,069.10
12.1.43 Supply and fix bronze gate valves (PN 16 ),inner -
diameter 50 mm(2''),for Air release Valve Nº 2 2,500.00 5,000.00
12.2 SANITARY SITE WORK INSTALLATION
All plumbing and drainage components which
specified below are subjected to the consultant
approval, based on samples , catalogues brochures,
test reports, product quality certificates presented
by the contractor . All sanitary appliances shall be
best quality and European made or equivalent.
No 8 49,263.74 394,109.92
12.2.10 Size:-(1000*750)mm ( Av.depth 1000 -1750mm )
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Construct Lead lined radioactive rectangular manhole
out of 250mmR.C concrete C-30 walls internal dimension
(1000*750)mm & average depth (1000-1750mm)on a
base of R.C.slab, size, 2100x1850x300mm, including
benching and bottom channeling with mass concrete.
Cover slab shall be 100mm thick R.C. concrete reinforced
with 12mm R.bar 110mm c/c and bottom Slab shall be
250mm thick walls are reinforced with 12mm R.bar
c/c180 mm in both ways. Provide 150mm granular
materials under the base slab, on a compacted earth.
manhole cover shall be reinforced with 10mm R.bar
150mmc/c and shall have Ø12mm bar handle Unit price
shall include excavation of the pit and cart away of the
excavated soil, all in accordance with the given detail
drawing.
No 14 107,810.45 1,509,346.30
12.2.11 Size:-(1200*750)mm ( Av.depth 1750 -2500mm )
Construct Lead lined radioactive rectangular manhole
out of 250mm R.C concrete C-30 walls internal dimension
(1200*750)mm & average depth (1750-2500mm) on a
base of R.C.slab, size,2300x2300x300mm, including
benching and bottom channeling with mass concrete.
Cover slab shall be 100mm thick R.C. concrete reinforced
with 12mm R.bar 110mm c/c and bottom Slab shall be
reinforced with 10mm reinforcement bar c/c 150mm, and
250mm thick walls are reinforced with 12mm R.bar
c/c180 mm in both ways. Provide 150mm granular
materials under the base slab, one compacted earth.
manhole cover shall be reinforced with 10mm R.bar
150mmc/c and shall have Ø12mm bar handle. Unit price
shall include excavation of the pit and cart away of the
excavated soil, all in accordance with the given detail
drawing.
No 6 171,038.83 1,026,232.98
12.2.12 Size:-(1400*1200)mm ( aboveAv.depth 2500mm )
Construct Lead lined radio active rectangular manhole
out of 250mm R.C concrete C-30 walls internal dimension
(1400*1200)mm & average depth (above2500mm) on a
base of R.C.slabsize,2300x2300x300mm including
benching and bottom channeling with mass concrete
Cover slab shall be 100mm.thick R.C. concrete reinforced
with 12mm R.bar 110mm c/c and bottom Slab shall be
reinforced with 10mm reinforcement bar c/c 150mm, and
250mm thick walls are reinforced with 12mm R.bar
c/c180 mmin both ways Provide 150mm granular
materials under the base slab, one compacted earth.
manhole cover shall be reinforced with 10mmR.bar
150mmc/c and shall have Ø12mm bar handle. Unit price
shall include excavation of the pit and cart away of the
excavated soil, all in accordance with the given detail
drawing.
No 2 267,592.93 535,185.86
RECTANGULAR MANHOLE
12.2.13 Size:-(600*600)mm( Av.depth 600 -1000mm )
Construct rectangular manhole out of 250mm R.C
concrete C-25 walls internal dimension (600*600)mm &
average depth (600-1000mm) on a base of R.C.slab,
size,1700x1700x300mm, including benching and bottom
channeling with mass concrete. Cover slab shall be
100mm thick R.C. concrete reinforced with 12mm R.bar
110mm c/c and bottom slab shall be reinforced with
10mm reinforcement bar c/c 150mm. and 250mm thick
walls are reinforced with 12mm R.bar c/c180mm in both
ways. Provide 150mm granular materials under the base
slab, on a compacted earth. manhole cover shall be
reinforced with 10mm R.bar 150mmc/c, and shall have
Ø12mm bar handle. Unit price shall include excavation of
the pit and cart away of the excavated soil, all in
accordance with the given detail drawing.
Nº 14 12,258.07 171,612.98
12.2.14 Size:-(1000*750)mm ( Av.depth 1000 -1750mm )
Construct rectangular manhole out of 250mmR.C
concrete C-30 walls internal dimension (1000*750)mm &
average depth (1000-1750mm)on a base of R.C.slab,
size, 2100x1850x300mm, including benching and bottom
channeling with mass concrete. Cover slab shall be
100mm thick R.C. concrete reinforced with 12mm R.bar
110mm c/c and bottom Slab shall be 250mm thick walls
are reinforced with 12mm R.bar c/c180 mm in both ways.
Provide 150mm granular materials under the base slab,
on a compacted earth. manhole cover shall be reinforced
with 10mm R.bar 150mmc/c and shall have Ø12mm bar
handle Unit price shall include excavation of the pit and
cart away of the excavated soil, all in accordance with
the given detail drawing.
Nº 21 18,115.82 380,432.22
12.2.15 Size:-(1200*750)mm ( Av.depth 1750 -2500mm )
Construct rectangular manhole out of 250mm R.C
concrete C-30 walls internal dimension (1200*750)mm &
average depth (1750-2500mm) on a base of R.C.slab,
size,2300x2300x300mm, including benching and bottom
channeling with mass concrete. Cover slab shall be
100mm thick R.C. concrete reinforced with 12mm R.bar
110mm c/c and bottom Slab shall be reinforced with
10mm reinforcement bar c/c 150mm, and 250mm thick
walls are reinforced with 12mm R.bar c/c180 mm in both
ways. Provide 150mm granular materials under the
base slab, one compacted earth. manhole cover shall be
reinforced with 10mm R.bar 150mmc/c and shall have
Ø12mm bar handle. Unit price shall include excavation of
the pit and cart away of the excavated soil, all in
accordance with the given detail drawing.
Nº 18 28,336.69 510,060.42
12.2.16 Size:-(1400*1200)mm ( aboveAv.depth 2500mm )
Construct rectangular manhole out of 250mm R.C
concrete C-30 walls internal dimension (1400*1200)mm &
average depth (above2500mm) on a base of
R.C.slabsize,2300x2300x300mm including benching and
bottom channeling with mass concrete Cover slab shall
be 100mm.thick R.C. concrete reinforced with 12mm
R.bar 110mm c/c and bottom Slab shall be reinforced
with 10mm reinforcement bar c/c 150mm, and 250mm
thick walls are reinforced with 12mm R.bar c/c180 mmin
both ways Provide 150mm granular materials under the
base slab, one compacted earth. manhole cover shall be
reinforced with 10mmR.bar 150mmc/c and shall have
Ø12mm bar handle. Unit price shall include excavation of
the pit and cart away of the excavated soil, all in
accordance with the given detail drawing.
Nº 21 38,342.10 805,184.10
STORM WATER DRAINAGE SYSTEM
12.2.18 Construct dia 400mm semi-circular drainage channel out
of concrete. Price shall include excavation of the
trench,cartaway,provision of 50mm thick sand bedding,
side support with masonry stone as requiered to make
the work complete, etc.
ml 154 409.35 63,039.90
12.2.17 Ditto item no 4.1 above but provided with Metal grill
removable cover at entrance to building. Use
L40*40*3mm for external and RHS 40*40*3mm for
internal part of grill. ml 146 1,055.51 154,104.46
PERFORATED PIPE
12.2.19 Supply, lay & connect 150mm diameter perforated
uPVC pipe (PN 6), minimum wall thickness 5.9mm
according to the detail drawing for ground water collection
according to the detail drawing for ground water collection
and drainage system complete with all the necessary
accessory the upvc pipes, accessories fittings and
welding shall comply the upvc pipes, accessories fittings
and welding shall comply with the requirement of BS-
4514 or DIN8062 or equivalent institution . Unit price shall
include excavation of treanch.and all the necessary
assistance to the installation works.
Nº 2 9,570.65 19,141.30
12.2.24 Supply and install submersible electric driven motor pump
for Sub-surface drainage with the following characteristics
:
Nº 2 4,000.00 8,000.00
12.2.33 PIONEER WATER TANK
Supply and fix 216m³ pioneer or equivalent water tank,
made of Zinkalume steel panels (Grade 300 To
AS1397), four layer aqua liner,complete with ring beam,
level indicatortruss foot, scour drain, anti-corrosion
anode, roof ventilator, sliding access, concrete apron for
ladder, grade 8.8 high strength bolts, internal and
external ladders,scour basin and all other necessary
accessories.Unit Price shall include all civil works & water
supply pipes, fitting and accessories, excavation and
compacting of sand and all necessary works there to.
Nº 1 2,448,407.14 2,448,407.14
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
PUMPS
12.2.34 Potable Water Pump
Electric driven Closed Couple Centrifugal pump for
potable and sanitary water supply complete with all
accessories ( one of which is standby )
Discharge ,
Q = 40m3/hr.;
Head,H = 40m
General requirement
Discharge , Q =
20m3/hr.;
Necessary Accessories for pump
a)
pressure and vacuumed gauge in the suction section,
e) pressure switch
g)
butterfly valve in the delivery section,
1
Air Cooled Chiller ACCH - 1 as per specification
above Capacity: 295 kW No. 1.00 3,900,000.00 3,900,000.00
2
Air Cooled Chiller ACCH - 2 as per specification
above Capacity: 110 kW No. 1.00 2,880,000.00 2,880,000.00
3
Air Cooled Chiller ACCH - 3 as per specification
above Capacity: 100 kW No. 1.00 2,880,000.00 2,880,000.00
4
Air Cooled Chiller ACCH - 4 as per specification
above Capacity: 120 kW No. 1.00 3,000,000.00 3,000,000.00
5
Technical Requirement
Shall meet ANSI Z9.5, ASHRAE 110, NAPA 45,
UL 705, ISO5801:2004, BS848: Part 2,1985 and
All Applicable Ventilation Standards. Shall comply
UL555C and UL263 Fire Rated options. Shall
include quick fitting swing locks that keep the fan in
place in suspended ceilings or plasterboard walls
and ceilings. Fan house shall be manufactured
from ABS plastic.
Motors:
Type: External rotor, squirrel cage induction motor
Heat Insulation
For concealed duct
25 mm *48 kg/m3, k= 0.033 W/m K fiber glass
insulation, vapor barrier and adehesive tape
covering.
For exposed duct
50 mm*48 kg/m3, k = 0.033 W/m K fiber glass
insulation, vapor barrier and 0.4 mm aluminum
cladding and fostering with canvas
close and foster.
Acoustic Insulation
25 mm thick and 0.52 sound absorption co-
efficients at 250 Hz.
Duct thickness:
For duct cross sectional area ≤ 0.178 m2 is 0.6
mm
For duct cross sectional area between 0.178 m2
and 0.334 m2 is 0.8 mm
For duct cross sectional area ≥ 0.334 m2 is 1.0 mm
Ground Floor
1 LINAC AHU-1 Supply
1.1 700x500 lm 5 8,640.00 38,880.00
1.2 600x500 lm 10 8,640.00 86,400.00
1.3 600x300 lm 26 6,600.00 168,960.00
1.4 500x400 lm 5 6,600.00 30,690.00
1.5 300x300 lm 8 4,440.00 36,408.00
1.6 300x200 lm 35 6,240.00 215,904.00
2 LINAC AHU-1 Return -
2.1 900x500 lm 8 10,440.00 86,130.00
2.2 800x500 lm 5 9,600.00 50,880.00
2.3 700x500 lm 2 8,640.00 13,824.00
2.4 700x400 lm 3 8,424.04 26,956.93
2.5 600x300 lm 8 6,240.00 52,416.00
2.6 500x300 lm 2 6,000.00 9,600.00
2.7 400x300 lm 12 5,360.76 63,793.04
2.8 300x300 lm 7 4,440.00 31,968.00
3 BRACHY AHU-2 Supply
3.1 500x500 lm 4 7,658.22 27,186.68
3.2 500x400 lm 6 6,892.40 39,286.68
3.3 500x300 lm 2 6,126.58 13,478.48
3.4 400x300 lm 12 5,360.76 64,061.08
3.5 300x300 lm 16 4,594.93 74,897.36
3.6 300x200 lm 21 3,829.10 80,985.47
3.7 200x200 lm 14 3,063.29 42,426.57
3.8 200x150 lm 3 2,680.37 9,247.28
4 BRACHY AHU-2 Return
4.1 500x500 lm 6 7,658.22 47,098.05
4.2 500x400 lm 3 6,892.40 18,609.48
4.3 500x300 lm 3 6,126.58 18,379.74
4.4 400x300 lm 4 5,360.76 20,370.89
4.5 300x300 lm 8 4,508.78 35,393.90
4.6 300x200 lm 8
4.7 200x200 lm 12
5 BRACHY OR AHU-3 Supply
5.1 600x400 lm 9
5.2 300x200 lm 12
6 BRACHY OR AHU-3 Return
6.1 600x400 lm 3
6.2 500x400 lm 12
6.3 400x300 lm 2
6.4 300x300 lm 10
6.5 300x200 lm 3
6.6 200x200 lm 13
7 PET CT AHU-4 Supply
7.1 600x400 lm 4
7.2 500x400 lm 3
7.3 500x300 lm 4
7.4 300x300 lm 3
7.5 300x200 lm 11
7.6 200x200 lm 6
8 PET CT AHU-4 Supply
8.1 600x400 lm 6
8.2 500x300 lm 4
8.3 300x300 lm 4
8.4 200x200 lm 7
9 SPECT AHU-5 Supply
9.1 600x400 lm 6
9.2 500x400 lm 4
9.3 400x400 lm 3
9.4 300x300 lm 8
9.5 200x200 lm 19
10 SPCET AHU-5 Return
10.1 600x400 lm 12
10.2 400x400 lm 6
10.3 400x300 lm 1
10.4 300x300 lm 3
10.5 300x200 lm 17
10.6 200x200 lm 8
11 CT Simulator AHU-6 Supply
11.1 500x300 lm 7
11.2 400x300 lm 4
11.3 300x200 lm 5
11.4 200x200 lm 9
12 CT Simulator AHU-6 Return
12.1 400x300 lm 6
12.2 300x300 lm 2
12.3 300x200 lm 15
13 EAF 1
13.1 600x400 lm 10
13.2 500x400 lm 11
13.3 400x400 lm 7
13.4 400x300 lm 1
13.5 400x200 lm 1
13.6 300x300 lm 2
13.7 200x200 lm 12
13.8 200x150 lm 13
14 EAF 2
14.1 500x400 lm 8
14.2 400x400 lm 8
14.3 400x300 lm 6
14.4 300x300 lm 6
14.5 300x200 lm 9
15 EAF 3
15.1 300x300 lm 7
15.2 300x200 lm 4
16 EAF 4
16.1 300x300 lm 7
16.2 300x200 lm 4
16.3 200x200 lm 6
17 EAF 5
17.1 400x300 lm 2
17.2 300x300 lm 7
17.3 300x200 lm 5
17.4 200x200 lm 7
18 FAF 1
18.1 500x400 lm 5
18.2 400x400 lm 6
18.3 400x300 lm 6
18.4 300x300 lm 8
18.5 300x200 lm 19
19 Toilet fan 1
19.1 300x300 lm 1
19.2 300x200 lm 3
19.3 200x200 lm 5
19.4 200x150 lm 6
20 Toilet fan 2
20.1 300x200 lm 1
20.2 200x200 lm 3
21 Toilet fan 3 (total for all floors)
21.1 300x300 lm 48
21.2 300x200 lm 33
21.3 200x200 lm 79
22 Toilet fan 5 (total for all floors)
22.1 300x300 lm 18
22.2 200x200 lm 69
23 Toilet fan 6 (total for all floors)
23.1 800x750 lm 5
23.2 800x650 lm 5
23.3 800x600 lm 5
23.4 700x600 lm 5
23.5 600x500 lm 5
23.6 500x500 lm 5
23.7 500x300 lm 42
23.8 300x300 lm 69
23.9 300x200 lm 26
24 200x200 lm 35
24.1 200x150 lm 78
24 Ceiling mounted fans CMF 1 and 2
24.1 300x200 lm 34
24.2 200x200 lm 5
First Floor
25.1 EAF 1-1
25.2 700x450 lm 12
25.3 600x450 lm 4
25.4 500x400 lm 5
25.5 400x400 lm 5
25.6 400x300 lm 4
25.7 300x250 lm 3
26 EAF 1-2
26.1 600x400 lm 2
26.2 500x400 lm 4
26.3 400x400 lm 4
26.4 300x300 lm 4
26.5 300x200 lm 2
27 FAF 1-1
27.1 700x450 lm 12
27.2 600x450 lm 4
27.3 500x400 lm 5
27.4 400x400 lm 5
27.5 400x300 lm 4
27.6 300x250 lm 3
28 Ceiling mounted fan CMF 1-1
28.1 300x200 lm 17
28.2 200x200 lm 1
29 Ceiling mounted fan CMF 1-2
29.1 300x200 lm 10
29.2 200x200 lm 1
29.3 200x150 lm 1
Second Floor
30 OR 1 AHU-7 Supply
30.1 600x400 lm 39
31 OR 1 AHU-7 Return
31.1 600x500 lm 38
31.2 500x400 lm 2
31.3 400x300 lm 23
31.4 300x300 lm 4
31.5 300x200 lm 2
31.6 200x200 lm 3
32 OR 2 AHU-8 Supply
32.1 600x500 lm 71
33 OR 2 AHU-8 Return
33.1 700x500 lm 54
33.2 500x500 lm 2
33.3 400x400 lm 19
33.4 400x300 lm 3
33.5 300x300 lm 5
33.6 300x200 lm 7
33.7 200x200 lm 3
34 OR 3 AHU-9 Supply
34.1 600x500 lm 58
35 OR 3 AHU-9 Return
35.1 600x500 lm 52
35.2 400x400 lm 19
35.3 400x300 lm 2
35.4 300x200 lm 9
36 EAF 2-1
36.1 600x400 lm 7
36.2 500x350 lm 3
36.3 400x300 lm 4
36.4 300x300 lm 3
37 EAF 2-2
37.1 500x400 lm 6
37.2 400x400 lm 3
37.3 400x300 lm 4
37.4 300x300 lm 3
Third Floor
38 ICU AHU-ICU Supply
38.1 700x500 lm 40
38.2 500x400 lm 14
38.3 400x400 lm 10
38.4 300x300 lm 11
39 ICU AHU-ICU Return
39.1 700x500 lm 46
39.2 600x500 lm 4
39.3 600x400 lm 3
39.4 400x300 lm 10
40 EAF 3-1
40.1 600x400 lm 7
40.2 500x350 lm 3
40.3 400x300 lm 4
40.4 300x300 lm 3
41 EAF 3-2
41.1 500x400 lm 6
41.2 400x400 lm 3
41.3 400x300 lm 4
41.4 300x300 lm 3
Fourth Floor
42 EAF 4-1
42.1 500x400 lm 14
42.2 500x300 lm 4
42.3 400x300 lm 4
42.4 300x200 lm 4
43 EAF 4-2
43.1 500x400 lm 11
43.2 500x300 lm 4
43.3 400x300 lm 2
43.4 300x200 lm 4
44 EAF 4-3
44.1 500x400 lm 10
44.2 500x300 lm 4
44.3 400x300 lm 4
44.4 300x200 lm 4
45 FAF 4-1
45.1 500x400 lm 14
45.2 500x300 lm 4
45.3 400x300 lm 4
45.4 300x200 lm 4
46 FAF 4-2
46.1 500x400 lm 11
46.2 500x300 lm 4
46.3 400x300 lm 2
46.4 300x200 lm 4
47 FAF 4-3
47.1 500x400 lm 10
47.2 500x300 lm 4
47.3 400x300 lm 4
47.4 300x200 lm 4
48 FAF 4-4
48.1 600x350 lm 6
48.2 500x350 lm 8
48.3 400x350 lm 4
48.4 400x300 lm 4
48.5 300x300 lm 4
48.6 300x200 lm 5
49 FAF 4-5
49.1 500x300 lm 7
49.2 400x300 lm 4
49.3 300x300 lm 4
49.4 200x200 lm 4
50 CMF 4-1
50.1 300x200 lm 21
50.2 200x200 lm 2
Fifth Floor
51 EAF 5-1
51.1 500x400 lm 14
51.2 500x300 lm 4
51.3 400x300 lm 4
51.4 300x200 lm 4
52 EAF 5-2
52.1 500x400 lm 11
52.2 500x300 lm 4
52.3 400x300 lm 2
52.4 300x200 lm 4
53 EAF 5-3
53.1 500x400 lm 10
53.2 500x300 lm 4
53.3 400x300 lm 4
53.4 300x200 lm 4
54 FAF 5-1
54.1 500x400 lm 14
54.2 500x300 lm 4
54.3 400x300 lm 4
54.4 300x200 lm 4
55 FAF 5-2
55.1 500x400 lm 11
55.2 500x300 lm 4
55.3 400x300 lm 2
55.4 300x200 lm 4
56 FAF 5-3
56.1 500x400 lm 10
56.2 500x300 lm 4
56.3 400x300 lm 4
56.4 300x200 lm 4
57 FAF 5-4
57.1 600x350 lm 6
57.2 500x350 lm 8
57.3 400x350 lm 4
57.4 400x300 lm 4
57.5 300x300 lm 4
57.6 300x200 lm 5
58 FAF 5-5
58.1 500x300 lm 7
58.2 400x300 lm 4
58.3 300x300 lm 4
58.4 200x200 lm 4
59 CMF 5-1
59.1 300x200 lm 21
59.2 200x200 lm 2
Sixth Floor
60 BMT AHU-BMT-1 Supply
60.1 600x500 lm 10
60.2 500x500 lm 3
60.3 400x400 lm 7
60.4 400x300 lm 3
61 BMT AHU-BMT-1 Return
61.1 600x500 lm 7
61.2 500x500 lm 8
61.3 500x400 lm 3
61.4 400x300 lm 8
61.5 200x200 lm 13
61.6 200x150 lm 12
62 BMT AHU-BMT-2 Supply
62.1 500x500 lm 12
62.2 400x400 lm 7
62.3 400x300 lm 3
63 BMT AHU-BMT-2 Return
63.1 600x500 lm 7
63.2 500x500 lm 8
63.3 500x400 lm 3
63.4 400x300 lm 8
63.5 200x200 lm 13
63.6 200x150 lm 12
64 EAF 6-1
64.1 800x700 lm 6
64.2 700x400 lm 3
64.3 600x500 lm 2
64.4 600x400 lm 10
64.5 500x400 lm 10
64.6 400x300 lm 10
65 EAF 6-2
65.1 600x400 lm 8
65.2 400x400 lm 3
65.3 300x300 lm 3
65.4 300x200 lm 11
66 FAF 6-1
66.1 700x500 lm 6
66.2 500x500 lm 3
66.3 500x400 lm 7
66.4 400x400 lm 10
66.5 400x300 lm 5
66.6 300x300 lm 5
66.7 300x250 lm 5
TOTAL CARRIED TO SUMMARY
5. TERMINAL INLET OUTLET
Technical Requirement
The contractor shall ensure that the diffusers and grilles offered are of required capacity, throw and terminal velocity. All diffusers, grilles and registers shal
coated. All diffusers, registers and grilles shall be selected to account for the noise levels as specified for various areas.
ITEM No. Location Purpose Type Designation LPS
235
270
Supply Air
SAD 185
Diffuser
255
Supply 220
Laminar
flow LFP 855
pannel
Fresh Air
FAD 275
Diffuser
Fresh Air 80
1 Linac and Bracky Inlet Louver FAL
255
235
Return Air 185
Return RAD
Diffuser 340
220
270
275
Exhaust 100
Extraction EAD
Air Diffuser 170
80
180
Supply Air
Supply SAD 245
Diffuser
2 AHU-3 220
Return Air 180
Return RAD
Diffuser 585
Supply Air 180
Supply SAD
Diffuser 135
3 AHU-4
Return Air 240
Return RAD
Diffuser 135
Supply Air 265
Supply SAD
Diffuser 145
4 AHU-5
Return Air 235
Return RAD
Diffuser 200
Exhast Air
Extraction EAD 210
Diffuser
5 EAF-3
Fresh Air
Supply FAL 210
Louver
Exhast Air
EAD 120
Diffuser
6 EAF-4 Extraction
135
Exhast Air
EAD
Diffuser 195
7 EAF-5 Extraction
245
Fresh Air
FAL 200
Louver
180
Fressh Air 270
8 FAF B3 Supply FAD
Diffuser 145
135
Fressh Air 270
9 FAF B4 Supply FAD
Diffuser 385
Exhast Air
10 EAF 1-1 Extraction EAD 270
Diffuser
220
Exhast Air
11 EAF 1-2 Extraction EAD 375
Diffuser
320
Fresh Air
12 FAF 1-1 Supply FAD 270
Diffuser
Exhast Air
13 Toilet Fan 3 Extraction EAD 60
Diffuser
Exhast Air
14 Toilet Fan 5 Extraction EAD 90
Diffuser
Exhast Air
15 Toilet Fan 6 Extraction EAD 90
Diffuser
Laminar 1645
Supply Flow Laminar Flow Pannel
Pannel 1960
685
16 OR-1-2-3 270
Return Air
Return RAD 120
Diffuser
180
820
Exhast Air
EAD 355
Diffuser
17 EAF 2-1 Extraction
Fresh Air
FAL 355
Louver
Exhast Air
EAD 355
Diffuser
Exhast Air
EAD 270
18 EAF 2-2 Extraction Diffuser
Fresh Air
FAL 355
Louver
Fresh Air
FAL 270
Louver
Supply Air
Supply SAD 420
Diffuser
19 ICU
Return Air
Return RAD 625
Diffuser
Exhast Air
EAD 355
Diffuser
20 EAF 3-1 Extraction
Fresh Air
FAL 355
Louver
Exhast Air
EAD 355
Diffuser
Exhast Air
EAD 270
21 EAF 3-2 Extraction Diffuser
Fresh Air
FAL 355
Louver
Fresh Air
FAL 270
Louver
Exhast Air
EAF 4-1 Extraction EAD 270
Diffuser
22
Exhast Air
EAF 4-2 Extraction EAD 270
Diffuser
23
Exhast Air
EAF 4-3 Extraction EAD 270
Diffuser
24
Fresh Air
FAF 4-1 Supply FAD 270
25 Diffuser
Fresh Air
FAF 4-2 Supply FAD 270
26 Diffuser
Fresh Air
FAF 4-3 Supply FAD 270
27 Diffuser
255
FAD
Fresh Air 180
FAF 4-4 Supply
Diffuser 255
FAL
28 180
255
FAD
Fresh Air 180
FAF 4-5 Supply
Diffuser 255
FAL
29 180
Wall
30 4th Extraction mounted WMF 75
fan
Ceiling
CMF 4-1 Extraction mounted CMF 115
31 fan
Exhast Air
32 EAF 5-1 Extraction EAD 270
Diffuser
Exhast Air
33 EAF 5-2 Extraction EAD 270
Diffuser
Exhast Air
34 EAF 5-3 Extraction EAD 270
Diffuser
Fresh Air
35 FAF 5-1 Supply FAD 270
Diffuser
Fresh Air
FAF 5-2 Supply FAD 270
36 Diffuser
Fresh Air
FAF 5-3 Supply FAD 270
37 Diffuser
255
FAD
Fresh Air 180
38 FAF 5-4 Supply
Diffuser 255
FAL
180
255
FAD
Fresh Air
39 FAF 5-5 Supply
Diffuser
FAD
Fresh Air 180
39 FAF 5-5 Supply
Diffuser 255
FAL
180
255
FAD
Fresh Air 180
40 FAF 5-6 Supply
Diffuser 255
FAL
180
Wall
41 5th Extraction mounted WMF 75
fan
Ceiling
CMF 5-1 Extraction mounted CMF 115
42 fan
Supply Air
Diffuser
Supply SAD-H 520
with Hepa
filter
43 BMT
450
Return Air
Return RAD
Diffuser
43 BMT
Return Air
Return RAD 100
Diffuser
80
Exhast Air
44 EAF 6-1 Extraction EAD 565
Diffuser
Exhast Air
EAD 250
Diffuser
45 EAF 6-2 Extraction
Fresh Air
FAL 500
Louver
445
300
Fresh Air
FAD 350
Diffuser
240
315
46 FAF 6-1 Supply
445
300
Exhaust
EAL 350
Air Louver
240
315
TOTAL CARRIED TO SUMMARY
6. VOLUME CONTROL DAMPER
Technical Requirement
Shall be rectangular volume control damper (VCD) with multiple blade type. The blades shall be of aluminum aerofoil double skin type having a size specifi
recommended construction requirements. The volume control dampers shall be of opposed blade type for throttling and parallel acting blades for isolation.
Ratings:
Pressure up to 1000 Pa
Velocity up to 15.2 m/s
Temperature range from 20oC to 80oC
Features:
Casing: 16 Gage Galvanized Steel.
Blades: Airfoil Double Skin 22 Gage Galvanized Steel.
Linkage: Gage Galvanized Steel (Alternative Plastic Gear).
Axles: Zinc Plated Square Mild Steel, 12x12mm.
Bearings: Synthetic (acetal) Sleeve Type.
Quadrant: Galvanized Hand Locking Quadrant.
Static pressure
Item no. Location Duct Size (mmxmm) LPS
(mm-H2O)
0.6 0.40 1420 14.5
0.3 0.30 270 3.7
1 Bracky OR
0.3 0.20 210 4.0
0.3 0.20 270 4.4
0.6 0.3 1020 13.3
2 LINAC
0.3 0.2 255 4.6
0.2 0.2 145 2.7
3 CT- Simulator 0.3 0.3 470 3.1
0.4 0.3 670 11.1
0.6 0.4 1710 18.1
0.3 0.2 220 1.8
4 PET-CT
0.3 0.2 245 3.3
0.2 0.2 180 3.4
0.2 0.2 180 3.6
0.2 0.3 315 2.2
0.6 0.4 1710 18.5
5 SPET
0.3 0.2 240 4.3
0.3 0.3 480 8.9
0.2 0.2 135 3.3
0.6 0.4 1420 14.5
0.3 0.3 270 3.7
6 Bracky
0.3 0.2 210 4.0
0.3 0.2 270 4.4
0.2 0.2 170 3.1
7 EAF 1 0.4 0.2 320 3.4
0.2 0.15 80 2.5
8 EAF 2 0.3 0.2 205 3.2
9 EAF 3 0.3 0.3 420 9.0
0.3 0.3 480 9.4
10 EAF 4
0.2 0.2 120 4.2
0.4 0.3 710 11.5
11 EAF 5
0.3 0.2 245 3.0
0.3 0.2 205 3.2
12 FAF 1
0.3 0.2 275 4.5
0.2 0.2 150 3.4
13 Toilet fan 1
0.3 0.3 450 8.9
14 Toilet fan 2 0.3 0.2 200 6.1
15 Toilet fan 3 0.3 0.2 240 2.9
0.2 0.2 180 4.8
16 Toilet fan 5
0.3 0.3 360 8.1
0.20 0.15 60 1.8
0.2 0.2 120 1.6
17 Toilet fan 6
0.5 0.3 780 12.3
0.3 0.2 300 3.9
18 EAF1-1, FAF 1-1 0.7 0.45 2340 13.6
19 EAF 1-2 0.6 0.4 1455 10.3
20 EAF 2-1,2 EAF 3-1,2 0.60 0.4 1320 16.6
0.60 0.4 1645 20.1
0.4 0.3 685 8.4
0.6 0.5 2000 8.7
0.6 0.5 1960 21.7
21 OR
0.6 0.5 2240 22.7
0.4 0.3 540 7.5
0.3 0.3 360 5.0
0.3 0.2 270 4.2
0.7 0.4 2520 23.8
22 ICU 0.5 0.4 1260 9.5
0.4 0.3 625 7.8
23 4th & 5th ALL EAF and FAF 0.5 0.4 1350 10.5
0.6 0.5 2320 18.7
24 BMT 0.2 0.2 180 5.2
0.2 0.15 100 3.5
0.8 0.7 4520 29.8
25 EAF 6-1
0.6 0.5 2260 10.7
0.6 0.4 1500 17.2
26 EAF 6-2
0.3 0.2 250 5.1
0.7 0.5 2725 23.1
27 FAF 6-1
0.5 0.5 1540 10.6
TOTAL CARRIED TO SUMMARY
7. CHILLED WATER PIPES
Technical Requirement
Supply and install GS pipe with schedule number 40 as shown on the drawing. Price shall include hangers, shutt- off valves, flexible
connection, gages, insulation, regulating valves, non return valves, strainer, vent, automatic control valves fittings (elbow, fees, yees)
Heat insulation type- closed cell rubber tube insulation.
For concealed piping
- 25 mm x 48 kg/m3 insulation, vapour barrier and adhesive tape covering
For exposed piping
- 50 mm x 48kg/m3 insulation , vapour barrier and 0.4mm aluminum cladding.
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
1 ACCH-1 at Ground
1.1 Main branch m 16
1.2 Sub branch to AHU 2 and 3 m 10
1.3 Branch to AHU 1 m 60
1.4 Branch to AHU 2 m 16
1.5 Branch to AHU 3 m 16
2 ACCH-2 at bunker roof top
2.1 Main branch m 6
2.2 Sub branch to AHU 4 and 5 m 16
2.3 Branch to AHU 4 m 20
2.4 Branch to AHU 5 m 90
2.5 Branch to AHU 6 m 100
3 ACCH-3 at roof top
3.1 Main branch m 10
3.2 Sub branch to AHU 7 and 8 m 10
3.3 Branch to AHU 7 m 10
3.4 Branch to AHU 8 m 60
3.5 Branch to AHU 9 m 40
4 ACCH-4 at roof top
4.1 Main branch to AHU-ICU m 10
5 ACCH-5 at roof top
5.1 Main branch m 10
5.2 Branch to AHU-BMT 1 m 30
5.3 Branch to AHU-BMT 2 m 30
TOTAL CARRIED TO SUMMARY
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Each unit
consisting of:
2 - Medical Vacuum Outlets
2 - Medical Oxygen Outlets
2 - Medical Air Outlets
4 - Universal Electrical Receptacles
2 - Patient Light
1 - Oxygen Flow meter w/humidifier
1 - Medical Air Flow meter
1 - Vacuum Canister w/hosing
1 - Vacuum Regulator
1 - Over Flow Safety Trap
1 - Name Tag Holder Set 4.00
1 - IV Hook
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
3 Bed Head Units for ICUs
Each unit
consisting of:
4 - Medical Vacuum Outlets
4 - Medical Oxygen Outlets
4 - Medical Air Outlets
4 - Universal Electrical Receptacles
2 - Patient Light
1 - Oxygen Flow meter w/Humidifier
1 - Medical Air Flow meter
1 - Vacuum Canister w/Hosing
1 - Vacuum Regulator
1 - Over Flow Safety Trap
1 - Name Tag Holder Set 23.00
1 - IVHead
4 Bed HookUnits for in-patient wards and
examination rooms Single Wall Mounted
108,000.00 108,000.00
96,000.00 96,000.00
96,000.00 96,000.00
57,216.00 171,648.00
138,660.17 138,660.17
111,167.62 111,167.62
138,171.37 138,171.37
111,167.62 111,167.62
98,400.00 98,400.00
98,400.00 98,400.00
98,400.00 98,400.00
98,400.00 98,400.00
98,400.00 196,800.00
10,012.07 10,012.07
98,400.00 196,800.00
109,747.16 109,747.16
84,784.63 84,784.63
98,400.00 98,400.00
98,400.00 196,800.00
104,012.08 104,012.08
99,024.84 198,049.68
109,747.16 109,747.16
84,784.63 84,784.63
322,609.26 322,609.26
251,304.10 251,304.10
111,168.11 111,168.11
76,301.51 76,301.51
27,900.54 27,900.54
76,301.51 534,110.57
57,216.31 400,514.17
84,784.63 593,492.41
37,331.93 447,983.16
31,417.62 1,696,551.48
7,216,287.50
5. TERMINAL INLET OUTLET
capacity, throw and terminal velocity. All diffusers, grilles and registers shall be of extruded aluminum construction, and epoxy powder
ise levels as specified for various areas.
Static
pressure Velocity QTY Unit Price
(mm-H2O)
3.3 2.5 6
3.8 4.0 1
3.1 2.9 3
3.4 3.5 8
3.3 3 2
5.3 12.0 1
3.5 2.0 5
4
3.4 2.8 2
3.3 3.0 3
3.2 1.6 3
3.7 3.6 6
3.3 3.0 4
3.5 3.0 4
3.5 2.9 5
2.8 2.4 2
3.1 2.5 14
2.6 2.0 4
3.1 2.8 2
3.4 2.8 4
3.3 1.5 1
3.1 2.6 3
3.8 3.2 2
3.1 3.1 8
2.9 2.7 2
3.4 3.6 6
2.9 2.7 2
3.5 3.8 4
2.9 2.1 1
3.2 2.8 2
3.2 2.6 1
3.2 2.6 2
2
2.0 2.8 1
8.0 3.7 1
3.0 3.4 1
4.0 2.8 1
2
1
5.0 2.9 1
3.0 3.5 1
10.0 4.0 1
3.0 3.4 1
1
2.8 3.1 2
3.8 3.5 1
2.6 3.0 1
4.6 2.9 1
6.5 3.5 5
4.4 3.8 2
4.5 3.5 1
5.4 4.2 1
5.2 4.8 1
8.5 5.3 1
7.0 5.7 1
4.6 5.9 1
4.8 6.0 1
3.5 3.9 2
4.4 4.6 1
3.6 5.0 2
4.5 3.5 1
5.4 4.2 1
5.2 4.8 1
8.5 5.3 1
7.0 5.7 1
4.6 5.9 1
4.8 6.0 1
16
1.8 3.3
4
1.6 2.7
91
1.4 2.4
15.6 5.5 1
15.6 5.8 2
3.2 4.4 2
6.7 4.3 4
3.7 2.8 6
4.2 3.3 3
9.8 4.6 4
4
3.8 3.7
4
3.8 3.7
2
3.8 3.7
2
9.4 5.2
2
3.8 3.7
2
9.4 5.2
5.8 3.9 6
5.5 3.9 3
4
3.8 3.7
4
3.8 3.7
2
3.8 3.7
2
9.4 5.2
2
3.8 3.7
2
9.4 5.2
5
5.5 3.5
4
5.5 3.5
4
5.5 3.5
5
5.5 3.5
4
5.5 3.5
4
5.5 3.5
9.0 4.6 1
4.2 3.1 6
9.0 4.6 1
4.2 3.1 6
9.0 4.6 1
4.2 3.1 3
9.0 4.6 1
4.2 3.1 3
28
5.0
2
5.0
5
5.5 3.5
4
5.5 3.5
4
5.5 3.5
5
5.5 3.5
4
5.5 3.5
4
5.5 3.5
9.0 4.6 1
4.2 3.1 6
9.0 4.6 1
4.2 3.1 6
9.0 4.6 1
4.2 3.1 3
9.0 4.6 1
4.2 3.1 3
9.0 4.6 1
4.2 3.1 4
9.0 4.6 1
4.2 3.1 4
28
5.0
2
5.0
4.1 4.2 8
9.6 4.2 8
3.5 2.6 8
7.8 3.7 8
8
8.0 4.2
6
5.1 3.4
3
5.1 4.1
3.9 4.7 2
4.4 5.1 1
10.6 5.4 1
7.7 5.1 1
6.0 4.3 3
3.9 4.7 2
4.4 5.1 1
10.6 5.4 1
7.7 5.1 1
6.0 4.3 3
TOTAL CARRIED TO SUMMARY
OLUME CONTROL DAMPER
e blades shall be of aluminum aerofoil double skin type having a size specified on the drawing. Shall meet SMACNA
of opposed blade type for throttling and parallel acting blades for isolation. Shall be made of out of extruded
Unit
Velocity QTY Total Price
Price
5.3 1
3.5 2
3.3 1
3.5 1
4.9 4
3.4 4
2.9 4
4.0 1
4.4 1
5.6 2
3.3 1
3.4 2
3.1 2
3.1 6
3.6 2
5.6 2
3.4 2
4.0 2
2.9 2
5.3 1
3.5 2
3.3 1
3.5 1
3.1 4
3.6 1
2.6 2
3.2 1
3.9 1
4.0 1
2.8 1
4.5 1
3.4 1
3.2 3
3.5 1
3.0 1
3.9 1
3.2 1
3.3 4
3.1 7
3.7 7
2.4 28
2.8 14
4.6 7
3.6 14
6.0 2
5.3 1
5.3 4
5.5 1
4.4 2
5.8 1
5.8 2
5.9 2
4.1 1
3.7 2
3.3 2
6.1 1
5.1 1
3.9 4
5.3 17
6.0 4
3.1 8
2.6 8
7.2 1
6.0 2
5.4 1
3.4 1
6.3 1
5.4 2
OTAL CARRIED TO SUMMARY
Gondar University Specification and BOQ Treatment Plant
Total B ..........................
Birr -
Total A + B ............................
Birr -
VAT 15% ..........................
Birr -
GRAND SUMMARY ..........................
Birr -
m2 729.39
b) Apply slated finish bitumen rich water proofing
membrane for externall shear wall which is submerged
in the ground asper the manufacturer instruction.
Special attention shall be given or the material shall
conform to the quality requirement of BS or other
equivalent institution. The construction shall be carried
out by the supplier with a certified personnel all in
accordance with the manufacturers details and
Instructions. Min. thickness 4mm
m² 729.39
3.03 Metal Plate 4mm Thick Size as per the drawing Pcs 3.00
3.04 Ditch
Construct rectangular grill cover open channel which
collect storm water at places located on the drawings
out of 400mm thick stone masonry plastered internally
in accordance with the detail drawing. Provide a
minimum slope of 0.5% or follow the natural ground
slope which ever is greater. Unit price shall include all
civil works and metal plate cover. Complete all works as
per the drawing and technical; specification. Size:- 400
x 400mm(average depth),
ml 99.84
TOTAL CARRIED TO SUMMARY
4. SANITARY INSTALLATION
4.01 Supply and fix High density polyethylene(HDPE) pipe
for the sewerage line . Price shall include all associated
civil works including concrete & steel supports if
nessery where requiered, adaptors,connecter and all
other necessary accessoris.
a) Dia. 25 mm ml 45
b) Dia. 65 mm ml 13
c) Dia. 110 mm ml 21
d) Dia. 160 mm ml 153
e) Dia. 200 mm ml 4
f) Dia. 250 mm ml 64
4.02 Brass Gate Valves,flanged
Supply ,lay ,test ,disinfect and commission approved
quality Gate valves or flanged which is grater than PN-
10 (Nominal pressure 10 ) with all nesseccery
accessories adaptors to High density
Polyethylene(HDPE) pipe of the following nominal size,
and all required accessories.
m3 8.75
1.12 Supply and spread compost as specified. Compost to
tree holes, shrub and Ground cover areas and lawn
areas. Provide 1kg sample and details of supplier With
quotation for Landscape Architect’s approval.
Provide,
temporary store, and plant sods directly on prepared
soil with reference to the sods, fertilizers, maintenance
(including watering of sods directly after planting)
a) Trees No 70.00
TOTALl CARRIED TO SUMMARY
2. CONCRETE WORK
2.01 Cast insitu Concrete curbing ,class A (40cm x15cm )
with chamfer as shown in the drawing (C-25
Concrete). Price includes all civil works. ml 1,314.00
TOTAL CARRIED TO SUMMARY
3. SUB BASES & PAVEMENT WORKS
3.1 Sub-bases
3.1.1 Sub-base Layer construction from gravel taken from
cut or borrow
ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
3.1.1.1 Gravel sub-base (unstabilised gravel) compacted to
97%MDD,AASHTO m3 1,968.00
ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
3.2 Base Course
3.2.1 Crushed stone
The rate includes full compensation for procuring,
breaking down, including the crusher fines or sand (if
approved) necessary for correcting the
grading of the crushed stone, for crushing and
screening, for hauling the material over an
unlimited free-haul distance, placing, rolling,
slushing, correcting the layers, compacting the
material, including transporting the material and its
removal, disposal and transporting of oversize material,
and the protection and maintenance of the layer and
the conducting of control tests, all as specified.
m3 1,312.00
3.3 Pavements
3.3.1 Cobblestones Paving for walkways as shown in
drawing. The stone should be shaped, and laid broken
- coursed on 2.5cm crushed sand. The cost includes
the sand bedding as indicated in the typical drawings.
Coble stone Size 10x10x10cm
m2 2,624.00
3.3.2 Supply and lay to the required level 40x20x10cm
shaped Flat stones made of hard rock as per the
layout, design and slope for the main body of the Flat
stones following the design pattern of the Flat stones
road pavement or instruction of the engineer.
m2 500.00
3.3.3 Priming, Primer Sealing and Sealing
3.3.3.1 Supply and Spray Primer, Primer-binder
MC-30 Litre 5,248.00
3.3.4 Hot Laid Asphalt
3.3.4.1 Supply and Application of Tack Coat RC 30
(application rate of 0.6L/M2) Litre 3,148.80
3.3.4.2 Dense Graded Asphalt (AC) in Binding Course(50mm)
m2 5,248.00
3.3.4.3 Dense Graded Asphalt (AC) in Wearing Course(50mm)
m2 5,248.00
TOTAL CARRIED TO SUMMARY
Gondar University Specification and BOQ Fence work
B. SUPER STRUCTURE
Total B ..........................
Birr -
Total A + B ............................
Birr -
VAT 15% ..........................
Birr -
GRAND SUMMARY ..........................
Birr -
a) In copping m3 16.40
b) Main Gate Column m3 30.19
1.02 Provide, cut and fix in position sawn seasoned timber
or steel form work made up of minimum 3mm thick
sheet metal & folded thickness of 50mm whichever is
appropriate; Contractor to submit formwork design;
No 131.00
TOTAL CARRIED TO SUMMARY
4. PLASTERING & POINTING
4.01 Apply two coats of plaster in cement sand mortar
mix [1:3] on Copping m2 524.80
4.02 Apply plastering in cement mortar mix(1:2) to fine
Hollow concrete block wall as where shown on the
Architectural drawing. Price shall include pre-cleaning
and preparation of the surface. m2 1,541.07
4.03 Apply pointing to exposed part above ground level
stone masonry foundation wall recessed joint in
cement sand mortar mix (1:2). m2 656.00
TOTAL CARRIED TO SUMMARY
5 ELECTRICAL INSTALATION
5.1 Compound Light
5.1.1 Compound light points fed through PVC insulated
conductors of 3x4mm2 inside PVC conduits of 25mm
diameter, including junction boxes with covers, screw
type insulating caps, all complete
No 135.00
5.2 Extra Over Light Points for Flush Mounted
Switches
Supply and fix Legrand Mosaic 45 or approved
equivalent 10/16A, 250V flush mounted light switch,
fed through PVC insulated conductor of 3 x 4mm²
inside thermo plastic conduit of ø 16mm, connected
and tested, complete with plate and including
appropriate wall boxes, all complete as specified
and/or shown on drawings.
ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
1. GENERAL ITEM
1.01 Provide for client and Engineer personnel (6 in no.) on
all civil, electromechanical and computer networking
work with the manufacturers of equipment with all costs
covered by the contractor including 10 sets of
instruction, maintenance manual and instalation
manuals and certification from manufacturers soft and
hard copies for 3 weeks abroad the contractor shall
submit all the schedules of the training before starting
of these works. ( as per the recommendation of the
Engineer
Ls 1.00
1.02 Provide office space of moderately furnished room of
not less than 16 msq area and shall have secured
doors with locks, proper windows and must be with
proper artificial lighting and power outlets. The space
(room) provided must be furnished with filing cabinets,
proper tables, chairs for the Resident Engineer(s) and
additional four chairs for visitors. The office also have
proper and private WC room for the Resident
Engineer(s).
Ls 1.00
1.03 The Contractor shall purchase and provide 2 new latest
model double-cabin, four-wheel-drive pick-up ( Toyota
or Equivalent) with driver to provide transportation
facilities for the Resident Engineer(s) and Employers
Engineers from town to site and to any distance that
may be found necessary for the proper execution of the
supervision task. All expenses such as Fuel,
Lubricants, Servicing, Maintenance, and Repaire of
Vehicles shall be covered by the Contractor until the
provisional acceptance of the project. The vehicles
shall be the properties of the employer after provisional
acceptance of the project.
No. 2.00
1.04 Provision of Computers, Printers, Scanner, Fax
Machine, Mobile apparatus and lines, Soft wares, and
cost of stationeries in lump sum
Ls 1.00
TOTALl CARRIED TO SUMMARY