You are on page 1of 68

Gondar University Grand Summary Cancer Treatment Center

GRAND SUMMARY
GONDAR UNIVERSITY CANCER TREATMENT CENTER
TOTAL PRICE
ITEM NO.OF UNIT PRICE
PROJECT TYPE (ETB) with
NO. BLOCKS (ETB) with VAT
VAT
1 MAIN BUILDING & BUNKER 1 513,228,131.70 513,228,131.70
2 TREATMENT PLANT 1
- -
3 SITE WORK 1
- -
4 FENCE WORK 1
- -
5 MISCELLANEOUS 1
- -
GRAND TOTAL 513,228,131.70

Yohannes Abbay consulting Architects and Engineers February, 2017 1


Gondar University Summary Cancer Treatment Center

SUMMARY OF BILL OF QUANTITIES


CANCER TREATMENT CENTER
A. SUB STRUCTURE

1 Excavation and Earth work............................................................


Birr 8,296,171.02
2 Concrete Work...........................................................................
Birr 16,852,480.29
3 Masonry Work ...........................................................................
Birr 957,785.00

Total A........................ Birr 26,106,436.31

B. SUPER STRUCTURE

1 Concrete Work........................................................................Birr 99,754,716.68


2 Block Work..............................................................................Birr 15,195,935.51
3 Carpentry and Joinery..................................................................
Birr 3,407,797.45
4 Steel Structural & Metal Work.........................................................
Birr 206,400.00
5 Aluminum Work...........................................................................
Birr 49,294,830.11
6 Roof water & damp proofing work Birr 2,616,621.24
7 Roof Work ……………………………………………………… Birr 2,917,712.94
8 Plastering and Pointing ..............................................................
Birr 14,058,925.26
9 Floor & Wall Finishing ..............................................................
Birr 98,820,020.60
10 Painting ..................................................................................Birr 1,669,799.50
11 Electrical Installation,.............................................................. Birr 69,251,032.84
12 Sanitary Installation...................................................................
Birr 23,056,815.98
13 Mechanical Installation...............................................................
Birr 39,928,287.50

Total B .......................... Birr 420,178,895.61

Total A + B ......................... Birr 446,285,331.92

VAT 15% .......................... Birr 66,942,799.79

GRAND SUMMARY .......................... Birr 513,228,131.70

Yohannes Abbay Consulting Architects And Engineers June, 2017 2


ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
A. SUB-STRUCTURE
1. EXCAVATION & EARTH WORK
1.01 Site clearing to remove the top soil to an average depth
of 20 cm for ordinary soil m2 4,761.38 5.00 23,806.90
1.02 Bulk excavation in ordinary soil to a depth not exceeding
1500mm from reduced level. m3 5,672.00 60.00 340,320.00
1.03 Ditto as item No. 1.02, but in soft rock . m3 13,232.73 70.00 926,291.10
1.04 Bulk excavation in hard rock to a depth over 1500mm not
exceeding 3000mm. m3 2,351.00 1,763.00 4,144,813.00
1.05 Pit Excavation in ordinary soil to depth not exceeding
1500mm starting from reduced level. m3 1,085.00 60.00 65,100.00
1.06 Ditto as item No.1.05 but over 1500mm not exceeding
3000mm for soft rock. m3 120.00 75.00 9,000.00
1.07 Ditto item No.1.06, but in hard rock . m3 386.00 1.00 386.00
1.08 Excavation for continuous trench to a depth not
exceeding 1500mm.starting from reduced level. m3 557.28 40.00 22,291.28
1.09 Ditto item No. 1.08, but in soft rock . m3 105.04 120.00 12,604.92
1.10 Fill around foundation and building in non expansive
selected material from quarry site well rolled and
compacted in layers not exceeding 200 mm thick. m3 2,557.81 150.00 383,671.43
1.11 Ditto as item No. 1.10, but from Site m3 2,557.81 55.00 140,679.52
1.12 Fill under hard core with imported selected material from
quarry waste well rolled and compacted in layers not
exceeding 200 mm thick. m3 1,842.03 200.00 368,406.00
1.13 Ditto as item No.1.12, but from Site m3 1,842.03 55.00 101,311.65
1.14 Cart away surplus excavated material and dispose at a
distance not exceeding 2km.from site as per the
Engineers Direction. m3 21,499.29 65.00 1,397,453.72
1.15 25cm thick basaltic or equivalent stone hardcore well
rolled, consolidated and blinded with crushed stone. m2 3,273.05 110.00 360,035.50
TOTAL CARRIED TO SUMMARY
8,296,171.02
2.CONCRETE WORKS
2.01 50mm thick lean concrete quality C-5, with minimum
cement content of 150kg of cement /m3 concrete.
a) Under Footing pads m2 741.02 110.00 81,512.20
b) Under Basement & Ground Floor beam m2 643.91 110.00 70,830.10
c) Under Stone masonry wall m2 255.79 90.00 23,021.10
2.02 Reinforced concrete quality C-30,400kg of cement/ m3
filled into form work and vibrated around rod
reinforcement.(Reinforcement bar and formwork
measured separately) Use OPC 42.5N Or Above
(Ordinary Portland Cement)
-
a) In Footing Pads m3 553.79 3,050.00 1,689,059.50
b) In Matt Foundation m3 481.00 3,050.00 1,467,050.00
c) In Foundation & Basement Floor Elevation Column m3 156.58 3,050.00 477,569.00
d) In Basement Floor Beam m3 46.20 3,050.00 140,910.00
e) In Ground Floor Beam m3 181.71 3,050.00 554,215.50
f) In 10cm thick Basement floor slab. m2 1,080.60 305.00 329,583.00
g) In 15cm thick Suspended solid slab m2 618.53 457.50 282,977.48
h) In Shear Wall m3 68.99 3,050.00 210,419.50
i) In Stair case m3 3.86 3,050.00 11,773.00
2.03 Provide, cut and fix in position sawn structural wood or
steel formwork whichever is appropriate; -
a) To Footing Pads m2 746.52 150.00 111,978.00
b) To Matt Foundation m2 111.20 150.00 16,680.00
c) To Foundation & Basement Floor Elevation Column m2 923.35 150.00 138,502.50
d) To Basement Floor Beam m2 307.91 150.00 46,186.50
e) To Ground Floor Beam m2 1,211.25 150.00 181,687.50
f) To Suspended Solid Slab m2 618.53 150.00 92,779.50
g) To Shear Wall m2 336.83 150.00 50,524.50
h) To stair case m2 28.09 150.00 4,213.50
2.04 Mild Steel reinforcement according to Structural
Drawings and Technical Specifications. Price includes
cutting, bending, placing in position and tying wires.
-
a) Dia 8mm deformed bar kg 21,782.36 32.00 697,035.52
b) Dia10mm deformed bar kg 4,665.58 32.00 149,298.41
c) Dia 12mm deformed bar kg 12,694.92 36.00 457,017.03
d) Dia 14mm deformed bar kg 16,632.14 36.00 598,756.94
e) Dia 16mm deformed bar kg 8,616.07 36.00 310,178.49
f) Dia 20mm deformed bar kg 92,604.49 84.58 7,832,487.84
g) Dia 24mm deformed bar kg 9,768.66 84.58 826,233.68
2.05 Supply and fix 10mm thick and 100mm high Styrofoam
for the expansion joint in between the basement or grade
beam and the basement or ground floor slab. ml 1,448.34 -
TOTAL CARRIED TO SUMMARY 16,852,480.29
3. MASONRY WORKS
3.01 Construct 50cm thick trachytic or equivalent stone
masonry foundation wall bedded in cement sand mortar
ratio 1:3
a) Below Natural Ground Level (BNGL) m3 234.47 1,100.00 257,917.00
b) Above Natural Ground Level (ANGL) m3 126.36 1,300.00 164,268.00
c) Construct retaining wall from basaltic or equivalent
stone masonry wall bedded in cement sand mortar ratio
1:3 m3 412.00 1,300.00 535,600.00
TOTAL CARRIED TO SUMMARY 957,785.00
B. SUPER-STRUCTURE
1. CONCRETE WORK
1.01 Reinforced concrete quality C-30,400kg of cement/ m3
filled into form work and vibrated around rod
reinforcement.(Reinforcement bar and formwork
measured separately) Use OPC 42.5N Or Above
(Ordinary Portland Cement)

a) In Elevation column m3 913.34 3,350.00 3,059,689.00


b) In Floor Beams m3 979.94 3,350.00 3,282,799.00
c) In Roof Beam m3 149.51 3,350.00 500,858.50
d) In 15cm thick Suspended solid slab m2 17,417.74 502.50 8,752,414.35
e) In Suspended Slab (Bunker) m3 877.18 3,744.12 3,284,267.18
f) In Walls (Bunker) m3 876.50 3,744.12 3,281,721.18
g) In Stair case m3 100.72 3,350.00 337,412.00
h) In Shear wall m3 289.54 3,350.00 969,959.00
1.02 Provide, cut and fix in position sawn structural wood or
steel formwork whichever is appropriate; Formwork for
walls of Bunker should be a combination of 'She-bolts'
and 'Push-pull' -
a) To Elevation column m2 6,459.72 150.00 968,958.00
b) To Floor Beams m2 8,524.32 220.00 1,875,350.40
c) To Roof Beam m2 1,347.88 10.00 13,478.80
d) To Suspended Floor solid slab m2 17,417.74 220.00 3,831,902.80
e) To Suspended Flat slab (Bunker) m2 1,351.87 356.26 481,617.21
f) To Stair case m2 711.03 150.00 106,654.50
g) To Walls (Bunker) m2 1,279.23 356.26 455,738.48
h) To Shear wall m2 3,378.69 150.00 506,803.50
1.03 Mild Steel reinforcement according to Structural Drawings
and Technical Specifications. Price includes cutting
bending, placing in position and tying wires.
-
a) Dia 8mm deformed bar kg 49,785.87 32.00 1,593,147.79
b) Dia 10mm deformed bar kg 86,777.27 32.00 2,776,872.60
c) Dia12mm deformed bar kg 342,864.41 36.00 12,343,118.63
d) Dia 14mm deformed bar kg 133,036.44 36.00 4,789,311.67
e) Dia 16mm deformed bar kg 60,166.85 36.00 2,166,006.71
f) Dia 20mm deformed bar kg 100,749.92 84.58 8,521,427.90
g) Dia 24mm deformed bar kg 423,920.64 84.58 35,855,207.48
TOTAL CARRIED TO SUMMARY 99,754,716.68
2. BLOCK & MASONRY WORK
2.01 Construct 20cm thick Class B, H.C.B. wall bedded in 1:3
cement mortar both sides left for further finish internal
and external wall. The H.C.B. shall be tested by a
recognized laboratory for the specified quality. All testing
expenses shall be covered by the contractor. Price shall
include all civil works.
m2 23,639.00 518.07 12,246,656.73
2.02 Ditto as item 2.01, but 150mm thick m2 3,421.00 475.23 1,625,761.83
2.03 40cm thick Hard,localy natural Dressed Stone Wall:
beded in cement sand mortar 1:3 internalIy left for
plastering and externaIly left for pointing m3 572.50 2,311.82 1,323,516.95
TOTAL CARRIED TO SUMMARY 15,195,935.51
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
3. CARPENTERY & JOINERY
3.01 Supply and fix flush type of internal wooden doors 4cm
thick with semi solid core frame and covered with best
quality HPLD veneer, with aluminlum frames according to
door schedule. Price includes orginal 'ASSA loock or
equivalent', three coats of varnish paint , 3pcs hinges(all
are aproved quality), finishe shall be anti-microbial suited
mechanical facilities and provide automatic door closers,
holders including the necessary door hard ware.

a) Type:- D1, Size:- 120 x 230cm. No 145.00 10,133.93 1,469,419.85


b) Type:- D2, Size:- 100 x 230cm. No 4.00 7,710.60 30,842.40
c) Type:- D3, Size:- 90 x 210cm. No 110.00 6,336.10 696,971.00
d) Type:- D4, Size:- 140 x 210cm. No 44.00 10,794.84 474,972.96
e) Type:- D5, Size:- 180 x 210cm. No 53.00 13,879.08 735,591.24
TOTAL CARRIED TO SUMMARY 3,407,797.45
4. STEEL STRUCTURE & METAL WORK
4.01 Supply and fix 200cm high corner protection on exposed
RC column edges, made specifically for this purpose with
metal sheet, centrally bent for corner and the side flanges
are perforated as mesh to be imbedded in cement mortar
(1:3) plaster and to be further finished. The sample shall
be approved before installation. The price shall include all
civil works. Size= 30x30x3mm

ml 3,440.00 60.00 206,400.00


TOTAL CARRIED TO SUMMARY 206,400.00
5. ALUMINUM WORK
Supply and fix ALLCO-5 Aluminum framed window
doors,windows and doors. Price shall include glazing.
- All accessories shall be best
quality and fullfill ASTM/EN quality standard requirment
and to be approved by engineer prior to fixing.
- Thickness of Aluminum Profiles
should be 1.8mm thick and 3mm thick aluminum plate.
- Anodization thickness should be
15-20micrometer. - Price includes all
accessories,locks,hinges etc... - Thickness of the
glass( non refelective tinted glass) should be 6mm thick.

5.01 I) Doors
a) Type:- D3, Size:- 90 x 210cm. No 39.00 12,264.73 478,324.47
b) Type:- D6, Size:- 180 x 230cm. Sliding Glass Doors
No 23.00 26,865.60 617,908.80
c) Type:- D7, Size:- 120 x 220cm. Sliding Glass Doors
No 8.00 17,131.69 137,053.52
d) Type:- D8, Size:- 80 x 195cm. No 28.00 10,123.27 283,451.56
e) Type:- D9, Size:- 70 x 195cm. No 56.00 8,857.86 496,040.16
ii) Windows: -
a) Type:- W1, Size:- 223 x 100cm. No 7.00 14,471.08 101,297.56
b) Type:- W2, Size:- 150 x 100cm. No 3.00 9,733.91 29,201.73
ii) Window Door -
a) Type:- WD1-WD6, Size:- 100 x 220cm. Sliding Glass
No 45.00 14,276.41 642,438.45
b) Type:- WD14, Size:- 90 x 148cm. No 3.00 8,643.71 25,931.13
c) Type:- WD15, Size:- 150 x 195cm. No 3.00 18,981.13 56,943.39
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
5.02 Door For Bunker as per the following Specification

a) Size 200x250cm

MF5 Type Hermetically sealing sliding Door


sets lead lined X Ray protect
Door: □ Flush 60mm core faced with
1mm plastic laminate. Framed in anodised aluminum
profile
□ Core: 48mm PU core
faced both sides with 1mm hard plastic laminate

□ Facing: 1mm hard plastic


laminate on 5mm board

□ Door leaf: 60mm thick.

□ Finish: hard plastic laminate

□ Color: standard white orchoice of 20 colors see


chart or RAL/BS order

□ Door frame: Anodised aluminum corner profile

□ Fire Rating: As building regulations and fire Officer


requirements tested to BS 476 PART 22
□ X Ray Protection: 3mm lead sheet under surface of
door dependent on code regulations

□ Ironmongery: Stainless Steel lever handle


both sides
□ Track:
MF5 Anodised aluminum track with nylon bearings No 2.00 912,000.00 1,824,000.00
b) Size 220x250cm

MF5 Type Hermetically sealing sliding Door


sets lead lined X Ray protect
Door: □ Flush 60mm core faced with
1mm plastic laminate. Framed in anodised aluminum
profile
□ Core: 48mm PU core
faced both sides with 1mm hard plastic laminate

□ Facing: 1mm hard plastic


laminate on 5mm board

□ Door leaf: 60mm thick.

□ Finish: hard plastic laminate

□ Color: standard white orchoice of 20 colors see


chart or RAL/BS order

□ Door frame: Anodised aluminum corner profile

□ Fire Rating: As building regulations and fire Officer


requirements tested to BS 476 PART 22
□ X Ray Protection: 3mm lead sheet under surface of
door dependent on code regulations

□ Ironmongery: Stainless Steel lever handle


both sides
□ Track:
MF5 Anodised aluminum track with nylon bearings No 2.00 996,648.00 1,993,296.00
5.03 Staircase:
Supply and fix 90cm high hand rail to staircase on sides
of concrete steps made from Dia 40mm, t= 2mm stainless
steel pipe baluster at c/c1000mm and handrail and four
rows Dia.20mm,t=2mm stainless steel guardrails. Price
shall include 5mm thick metal plates,antirust and
synthetic enamel spray paint to metal parts and all other
neccessary works and materials needed for anchorage.

ml 198.00 3,625.23 717,795.54


5.04 Guard rail
Ditto as an item 5.03, but guardrail ml 664.00 3,625.23 2,407,152.72
5.05 Curtain Wall

Supply and fix curtain wall made of:


- Concealed aluminum semi structural frame of
(Mullion and Transom type) 50*80* 2 mm tubular section
to safely bear the expected load,
- Covered with double glazed glass sheets
(6mm thick non reflective tinted glass on both sides),
- With 12mm wide spacer ,vacuum, in
between for thermal and sound insulation and
-The frames shall be anchored to
reinforced concrete slab and wall by means of
appropriate anchoring devices with contraction allowance
slots. - curtain wall shall
have edge covers, skirting and cornice at connection to
floor slabs. -Top and
bottom of curtain walls above the roof shall be covered
with aluminum coping and flashing including the concrete
parapet. - Price
shall include glazing and all accessories as per the
approval of the Engineer.
m2 4,724.00 8,358.17 39,483,995.08
TOTAL CARRIED TO SUMMARY 49,294,830.11
6.ROOF WATER &DAMP PROOFING WORK
6.01 Average 10cm thick light weight concrete spread and
levelled over roof slab with a given slab. m2 2,693.59 100.00 269,359.00
6.02 3cm thick mass concrete with 01 aggregate in 1:2:3 ratio,
finished surface is as per the supplier instruction. m2 2,693.59 100.00 269,359.00
6.03 Supply and apply two coats of xypex or equivalent
concentrated water proofing material strictly following the
manufacturer instruction. The construction shall be
carried out by the supplier with a certified personnel all in
accordance with the manufacturers detail and instruction.
m2 2,693.59 500.00 1,346,795.00
6.04 Apply Cementatious water proofing material which shall
seal void by crystallization for upper floor wet areas (toilet
rooms) upto a height of 50cm on walls and columns as
per the manufacturer's instruction. The cost shall include
cleaning of all dirt's, trace of grease, oil and loose
particles. The work shall be done on sub contractual
bases with the supplier of the material which will give
material & construction guarantee to the client.
m2 1,906.41 383.50 731,108.24
TOTAL CARRIED TO SUMMARY 2,616,621.24
7. ROOF WORK
7.01 Supply and fix glass or equivalent Sky light material with
complete Aluminum framing,50x80x2mm, & 5mm thick
flexy glass according to drawing and the manufacturers
recommendation. Price shall include sky light material,
recommended aluminum frames,glazing and all
necessary accessaries to complete the work.

m2 258.83 11,272.70 2,917,712.94


TOTAL CARRIED TO SUMMARY 2,917,712.94
8. PLASTERING & POINTING
8.01 Apply two coats of plastering in cement sand mortar (1:3)
to walls surfaces as per the drawings and. Price shall
include pre-cleaning and preparation of the surface.

a) To internal wall surface. m2 37,572.70 120.00 4,508,724.00


b) To external wall surface. m2 16,547.30 130.00 2,151,149.00
c) To concrete ceiling m2 16,232.00 150.00 2,434,800.00
d) To exposed beam and column m2 13,065.54 130.00 1,698,519.68
e) To staircase & Shear Wall m2 255.44 150.00 38,316.60
8.02 Apply 3mm thick final coat of gypsum plaster to internal
wall surface as per the drawing. Price shall include all
the necessary incidental works to complete the work:

a) To internal wall surface. m2 37,572.70 45.00 1,690,771.50


b) To concrete ceiling m2 15,898.30 46.00 731,321.80
c) To exposed beam and column m2 13,065.54 46.00 601,014.66
d) To staircase & Shear Wall m2 255.44 46.00 11,750.42
8.03 Apply pointing to stone masonry wall recessed joint in
cement sand mortar mix (1:2). m2 975.72 80.00 78,057.60
8.04 Ditto but for dressed stone wall m2 1,431.25 80.00 114,500.00
TOTAL CARRIED TO SUMMARY 14,058,925.26
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
9. FLOOR & WALL FINISHING
9.01 Apply 48mm thick rough cement sand screed floor finish
in mortar mix ratio on the concrete surface. Cement slurry
bond coat shall be scrubbed to prepare slab prior to
placing mortar bed. Price shall include all other
incidental works to complete the work.
m2 16,232.00 190.29 3,088,787.28
9.02 Supply and lay 2mm thick self leveling chemical &
abrasion resistant Pigmented epoxy floor & wall finish in
accordance with the drawings & manufacturer's
recommendations, and the concrete surface suitable for
Epoxy application and having the required strength
achieved consistancy.And other incidental works to
complete the installation. The color should be approved
by the architect. The price shall include all civil works.

m2 1,566.85 822.00 1,287,949.71


9.03 PVC Skirting: 10cm high 2mm thick pvc skirting stuck to
wall with approved type of adhessive. ml 183.46 29.91 5,487.29
9.04 Supply and fix 300mmx300mmx10mm thick non Slippery
ceramic tile flooring bedded in cement sand ratio (1:3)
including mortar bedding, Price shall include 30mm thick
cement mortar bedding. Color and pattern of tile shall be
approved by the Engineer.
m2 1,054.90 759.62 801,323.14
9.05 Supply and fix 6mm thick & 300x200mm white glazed
Ceramic wall tiles stuck to wall with approved quality
type of adhesive and 2 mm joints to be grouted in
appropriate color filler material. m2 216.00 400.00 86,400.00
9.06 Supply and fix 3mm thick Solid Vinyl floor tile (SVT). The
tile installer should be experienced in the installation of
SVT as demonstrated by previous successful
installations, and shall be approved by the manufacturer
in writing. Protect adjacent work areas and finish surfaces
from damage while installing. Prepare substrate to be
free of paint, old adhesive, sealers, coatings, finishes,
dirt, film-forming curing compounds, or other substances
which may affect the adhesion of floor covering to the
substrate.
Submit the following before instalation

a) Product Data: Submit product data, including


manufacturer's specification summary sheet for specified
products.
b) Shop Drawings: Submit shop drawings showing layout,
finish colors, patterns and textures.
c) Samples: Submit selection and verification samples for
finishes, colors, and textures.
d) Quality Assurance Submittals: Submit the following
1. Test Reports: Certified test reports showing
compliance with specified performance
characteristics and physical properties.
2. Manufacturer's Instructions: Manufacturer's installation
and maintenance instructions.
e) Maintenance Information: Maintenance information for
installed products in accordance with
1. Methods for maintaining installed products.
2. Precautions against cleaning materials and methods
detrimental to finishes and performance.
f) Warranty: Warranty documents specified herein.
Size and
color should approved by the Engineer. Price includes
recommended adhesive 100mm high skirting to walls and
all incidental works.
m2 4,429.70 4,265.38 18,894,353.79
9.07 Supply & fix high quality 100 % Polyamide Pile material
Carpet flooring as per the detail drawing. The carpet shall
have structured Loop Surface, commercial heavy
Wearability, good Comfort class. it should be with PP-
fabric Primary backing & synthetic textile Secondary
backing. Color, thickness and quality shall be approved
by the Engineer. The price shall include all the necessary
civil works & fixing material.

m2 5,043.50 4,467.45 22,531,584.08


9.08 Supply and fix 4mm thick Welded seam sheet flooring
(Heat welded with rod) welding is mandatory, since it
prevents ingress of dirt and bacteria in to seams and
provides a floor surface which is impermeable to water.
The sheet flooring installer should be experienced in the
installation of WSF as demonstrated by previous
successful installations, and shall be approved by the
manufacturer in writing. Size and color should approved
by the Engineer. Price includes recommended adhesives,
100mm high skirting to walls and all incidental works.

m2 2,405.70 4,589.00 11,039,757.30


9.09 Supply and fix 4mm thick Resilient sheet flooring
(Chemically welded seam). The sheet flooring installer
should be experienced in the installation of chemically
welded seam as demonstrated by previous successful
installations, and shall be approved by the manufacturer
in writing. Size and color should approved by the
Engineer. Submit Product data, Shop drawings, Samples,
Quality Assurance certificates, Test Reports,
Manufacturers instruction, Maintenance information and
warranty before installation and to be approved by the
Engineer. Price includes recommended adhesives,
100mm high skirting to walls and all incidental works.

m2 1,294.80 4,745.00 6,143,826.00


9.10 Supply & fix 50mm thick high quality Moisture-resistant
Gypsum board partition wall for Toilet & shower rooms as
per the drawing. Material quality & color shall be
approved by the Engineer. Price shall include all the
necessary fixing materials. Price shall include all
accessories.
m2 136.00 4,680.00 636,480.00
9.11 Supply & fix 50mm thick high quality Moisture-resistant
PVC board partition wall as per the drawing. Material
quality & color shall be approved by the Engineer. Price
shall include all the necessary fixing materials & all
accessories.
m2 1,025.00 4,030.00 4,130,750.00
9.12 Supply and fix 10mm thick Granite cladding to lift shaft
bedded on & including approved type of addhesive. Price
shall include approved type of adhessive. Colour ,size
and pattern of tile shall be approved by the Engineers.
m2 375.72 2,730.45 1,025,884.67
9.13 270x30mm Marble window sill cut to appropriate size,
weathered and mounted on & including 30mm thick
cement mortar (1:3) bedding. Price includes bull nosing
and making water drip as shown on the detail drawing.
ml 773.01 450.00 347,854.50
9.14 Supply & fix high quality Marble tile flooring. The tile
should be resistant to Abrasion, frost, stain, chemical
attack & color resistant to light. Color and quality shall be
approved by the architect. The price shall include cement
sand mortar (1:3) backing, grouting with matching color
and other incidental works.
-
a) Treads 330mmx30mm thickness ml 788.40 822.00 648,064.80
b) Risers 160mmx20mm thickness ml 817.20 822.00 671,738.40
c) Landing 30mm thickness m2 119.52 822.00 98,245.44
d) Skirting 100mm high & 20mm thick ml 229.80 822.00 188,895.60
e) 20mm thick marble copping ml 181.30 822.00 149,028.60
9.15 Supply and fix 2.5mm thick Resilient Tile Flooring (Vinyl
Composition Tile, VCT). The tile installer should be
experienced in the installation of VCT as demonstrated
by previous successful installations, and shall be
approved by the manufacturer in writing.

Remove excess adhesive from floor, base, and


wall surfaces without causing damage to surfaces due to
cleaning operations, and repair damage to adjacent
materials caused by resilient tile installation using
methods recommended by adjacent material
manufacturers. Clean floors taking care not to wash floors
prior to adhesive set. Apply floor finish in accordance with
manufacturer’s recommendations. Price includes
recommended adhesives, 100mm high skirting to walls
and all incidental works.
m2 203.00 5,057.00 1,026,571.00
9.16 Supply and fix Resilient Athletic Flooring (RAF). The tile
installer should be experienced in the installation of RAF
as demonstrated by previous successful installations, and
shall be approved by the manufacturer in writing. Size
and color should approved by the Engineer. Submit
Product data, Shop drawings, Samples, Quality
Assurance certificates, Test Reports, Manufacturers
instruction, Maintenance information and warranty before
installation and to be approved by the Engineer Price
includes recommended adhesives, 100mm high skirting
to walls and all incidental works.

m2 67.00 4,771.00 319,657.00


9.17 100mm thick wide Precast concrete pavement all
around the building on and including 400mm thick
selected compacted fill , 100mm thick red ash base and
joints pointed in cement mortar (1:2). m2 760.00 900.14 684,106.40
9.18 supply and fix 150 x 300 Cm plaque as per the design.
Plaque shall be made of 10 mm glass material held
suspended 10 cm outward from the wall and fixed.
Amharic & English fonts type and sizes shall be
determined by the Engineer & the client. Price shall
include all accessories.
Ls 1.00 58,500.00 58,500.00
9.19 Supply & fix high quality white color fiberglass with
acoustically transparent membrane; CAC backing
Armstrong or other equivalent Ceiling Systems under
concrete slab as per the detail drawings. The size is 1200
x 1200 x 25 mm with 15x1200 x 25 mm technical panels
for alternate continuous lights and diffusers with other
services for a monolithic, uncluttered visual effect. The
panel shall be factory-applied latex painted with Class A
Fire Performance. The price shall include suspension
systems and all other accessories.

m2 2,693.59 4,697.55 12,653,273.70


ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
9.20 Supply and fix approved type Clinker tiles for external
wall cladding. Price shall include approved water proof
adhessive, grouting and other incidental works. Color size
and texture should be approved by the Engineer.
m2 16,547.30 660.00 10,921,218.00
9.21 Supply and fix high quality Wet-formed mineral fiber
Armstrong or equivalent Ceiling Systems for Toilets/
Janitor rooms as per the detail drawing. The panels
shall have Brighter visual with 20% more light reflectance
than vinyl-covered gypsum, Durable – Water-repellent,
Washable, Scratch-resistant, Soil-resistant. Factory-
applied vinyl latex paint Surface Finish and ASTM E84
and CAN/ULC S102 surface burning characteristics Fire
performance. Flame Spread Index 25 or less. Smoke
Developed Index 50 or less. (UL labeled) Fire Class A
ASTM E1264. Price shall include all accessories.

m2 1,054.90 1,308.45 1,380,283.91


TOTAL CARRIED TO SUMMARY 98,820,020.60
10. PAINTING
The specification of the manufacturer approved by the
Engineer shall govern for selection of paint materials and
coatings. The products specified hereunder shall be
obtained only from manufacturers approved by the
Engineer. All paint materials shall generally be obtained
from approved suppliers only. Surface sealers, primers
and under coats shall generally be in accordance with the
paint manufacturer's recommendation. Paint strippers,
abrasive papers, cleaning agents, etching solution and
fillers shall be as recommended by the paint
manufacturer.

10.01 Apply three coats of approved quality plastic emulsion


paint. Price shall include pre-cleaning and preparation of
surfaces.
a) To Internal wall surfaces.. m2 37,572.70 25.00 939,317.50
b) To Concrete Ceiling m2 15,898.30 25.00 397,457.50
c) To Stair case & Shear Wall m2 255.44 25.00 6,386.10
d) To exposed beam and column m 2
13,065.54 25.00 326,638.40
TOTAL CARRIED TO SUMMARY 1,669,799.50
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
11.ELECTRICAL INSTALLATION
SUPPLY AND INSTALL
All electrical materials shall be 3rd party certified.
From internationally recognized institutions

11.1 Distribution boards


All main boards shall be type tested
11.1.1 Floor standing type tested distribution board, MDB MB,
IP54, made of steel with center opening lockable door
including earthing lead, front cover all fixing and
connection accessories, complete and consisting of:-

1 pc main MCCB of 1600A, 3ph


2 pc main MCCB of 1000A, 3ph For Mechanical load
1pc MCB of 80A, 3-ph
6pcs MCB of 63A, 3-ph
6pcs MCB of 50A, 3-ph
11pcs MCB of 40A, 3-ph
3pcs MCB of 32A, 3-ph
1pc MCB of 20A, 3-ph
2pcs MCB of 16A, 3-ph
1pc surge arrestor of 75KA
3pcs ammeters with 3pcs pilot lamps: 0-1250A
3pcs current transformers: 1700/5A
1pc of voltmeter with selector switch (0-500V)
with 4P+E busbar 1250A
1pc factory made drawing pocket, Himel PP-A4
equivalent. use DIN rail mounted terminal blocks with end
brackets and marking tags for all outgoings. All complete
with 25% reserve spaces. No. 1.00 319,665.00 319,665.00
11.1.1.01 Flush mounted metal enclosures SDB- Lift with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 80A, 3-ph


3pcs MCB of 25A, 3-ph
with busbar 90A and 25% reserve space No. 1.00 14,581.00 14,581.00
11.1.1.02 Flush mounted metal enclosures SDB- Pump with
lockable door, earthing lead, cable terminal,
labeling ,connectors and all the necessary accessories
consisting of:-
1pc main MCB of 63A, 3-ph
1pc MCB of 25A, 1-ph
3pcs MCB of 20A, 3-ph
with busbar 70A and 25% reserve space No. 1.00 7,518.10 7,518.10
11.1.1.03 Flush mounted metal enclosures SBD- CL with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 16A, 3-ph


5pcs MCB of 16A, 1-ph
with busbar 20A and 25% reserve space No. 1.00 5,500.50 5,500.50
11.1.1.04 Flush mounted metal enclosures SBD- BA with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 16A, 3-ph


2pcs MCB of 10A, 1-ph
3pcs MCB of 16A, 1-ph
with busbar 20A and 25% reserve space No. 1.00 5,504.40 5,504.40
11.1.1.05 Flush mounted metal enclosures SBD- BB with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 20A, 3-ph


7pcs MCB of 10A, 1-ph
4pcs MCB of 16A, 1-ph
with busbar 25A and 25% reserve space No. 1.00 5,789.10 5,789.10
11.1.1.06 Flush mounted metal enclosures SBD- GA with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


9pcs MCB of 10A, 1-ph
10pcs MCB of 16A, 1-ph
with busbar 50A and 25% reserve space
No. 1.00 7,018.90 7,018.90
11.1.1.07 Flush mounted metal enclosures SBD- GB with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 50A, 3-ph


10pcs MCB of 10A, 1-ph
20pcs MCB of 16A, 1-ph
2pcs MCB of 25A, 1-ph
with busbar 63A and 25% reserve space No. 1.00 9,854.20 9,854.20
11.1.1.08 Flush mounted metal enclosures SBD- GC with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


10pcs MCB of 10A, 1-ph
9pcs MCB of 16A, 1-ph
1pc MCB of 6A, 1-ph
with busbar 50A and 25% reserve space No. 1.00 8,604.90 8,604.90
11.1.1.09 Flush mounted metal enclosures SBD- 1A with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


9pcs MCB of 10A, 1-ph
10pcs MCB of 16A, 1-ph
with busbar 50A and 25% reserve space
No. 1.00 8,318.90 8,318.90
11.1.1.10 Flush mounted metal enclosures SBD- 1B with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 32A, 3-ph


8pcs MCB of 10A, 1-ph
9pcs MCB of 16A, 1-ph
with busbar 40A and 25% reserve space No. 1.00 6,820.00 6,820.00
11.1.1.11 Flush mounted metal enclosures SBD- 1C with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 32A, 3-ph


9pcs MCB of 10A, 1-ph
6pcs MCB of 16A, 1-ph
with busbar 40A and 25% reserve space No. 1.00 6,690.00 6,690.00
11.1.1.12 Flush mounted metal enclosures SBD- 2A with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 63A, 3-ph


8pcs MCB of 10A, 1-ph
9pcs MCB of 16A, 1-ph
2pcs MCB of 20A, 1-ph
1pc MCB of 6A, 1-ph
2pcs MCB of 16A, 3-ph
with busbar 70A and 25% reserve space No. 1.00 10,570.94 10,570.94
11.1.1.13 Flush mounted metal enclosures SBD- 2B with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


9pcs MCB of 10A, 1-ph
12pcs MCB of 16A, 1-ph
1pc MCB of 6A, 1-ph
with busbar 50A and 25% reserve space No. 1.00 8,129.54 8,129.54
11.1.1.14 Flush mounted metal enclosures SBD- 2C with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 63A, 3-ph


8pcs MCB of 10A, 1-ph
7pcs MCB of 16A, 1-ph
4pcs MCB of 20A, 1-ph
4pcs MCB of 16A, 3-ph
with busbar 70A and 25% reserve space No. 1.00 11,838.44 11,838.44
11.1.1.15 Flush mounted metal enclosures SBD- 3A with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


9pcs MCB of 10A, 1-ph
7pcs MCB of 16A, 1-ph
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
1pcs MCB of 16A, 3-ph
with busbar 50A and 25% reserve space No. 1.00 7,264.60 7,264.60
11.1.1.16 Flush mounted metal enclosures SBD- 3B with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


8pcs MCB of 10A, 1-ph
11pcs MCB of 16A, 1-ph
1pc MCB of 6A, 1-ph
with busbar 50A and 25% reserve space No. 1.00 7,564.90 7,564.90
11.1.1.17 Flush mounted metal enclosures SBD- 3C with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 32A, 3-ph


9pcs MCB of 10A, 1-ph
4pcs MCB of 16A, 1-ph
1pc MCB of 16A, 3-ph
with busbar 40A and 25% reserve space No. 1.00 6,782.30 6,782.30
11.1.1.18 Flush mounted metal enclosures SBD- 4A with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 50A, 3-ph


10pcs MCB of 10A, 1-ph
16pcs MCB of 16A, 1-ph
1pc MCB of 6A, 1-ph
with busbar 63A and 25% reserve space No. 1.00 9,280.04 9,280.04
11.1.1.19 Flush mounted metal enclosures SBD- 4B with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 63A, 3-ph


10pcs MCB of 10A, 1-ph
26pcs MCB of 16A, 1-ph
2pcs MCB of 6A, 1-ph
with busbar 70A and 25% reserve space No. 1.00 11,230.04 11,230.04
11.1.1.20 Flush mounted metal enclosures SBD- 4C with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 50A, 3-ph


9pcs MCB of 10A, 1-ph
17pcs MCB of 16A, 1-ph
1pc MCB of 6A, 1-ph
with busbar 63A and 25% reserve space No. 1.00 10,320.04 10,320.04
11.1.1.21 Flush mounted metal enclosures SBD- 5A with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 50A, 3-ph


10pcs MCB of 10A, 1-ph
19pcs MCB of 16A, 1-ph
1pc MCB of 6A, 1-ph
with busbar 63A and 25% reserve space No. 1.00 11,699.34 11,699.34
11.1.1.22 Flush mounted metal enclosures SBD- 5B with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 63A, 3-ph


10pcs MCB of 10A, 1-ph
26pcs MCB of 16A, 1-ph
2pcs MCB of 6A, 1-ph
with busbar 70A and 25% reserve space No. 1.00 10,762.04 10,762.04
11.1.1.23 Flush mounted metal enclosures SBD- 5C with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 50A, 3-ph


9pcs MCB of 10A, 1-ph
20pcs MCB of 16A, 1-ph
1pc MCB of 6A, 1-ph
with busbar 63A and 25% reserve space No. 1.00 9,853.34 9,853.34
11.1.1.24 Flush mounted metal enclosures SBD- 6A with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 63A, 3-ph


8pcs MCB of 10A, 1-ph
9pcs MCB of 16A, 1-ph
4pcs MCB of 25A, 1-ph
2pcs MCB of 16A, 3-ph
1pc MCB of 6A, 1-ph
with busbar 70A and 25% reserve space No. 1.00 11,045.44 11,045.44
11.1.1.25 Flush mounted metal enclosures SBD- 6B with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


9pcs MCB of 10A, 1-ph
10pcs MCB of 16A, 1-ph
with busbar 50A and 25% reserve space No. 1.00 8,318.90 8,318.90
11.1.1.26 Flush mounted metal enclosures SBD- 6C with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 50A, 3-ph


8pcs MCB of 10A, 1-ph
16pcs MCB of 16A, 1-ph
1pc MCB of 6A, 1-ph
with busbar 63A and 25% reserve space No. 1.00 10,093.84 10,093.84
11.1.1.27 Flush mounted metal enclosures SBD- 1 with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


1pc MCB of 16A, 1-ph
3pcs MCB of 25A, 1-ph
2pcs MCB of 16A, 3-ph
with busbar 50A and 25% reserve space No. 1.00 6,752.40 6,752.40
11.1.1.28 Flush mounted metal enclosures SBD- 2 with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


1pc MCB of 16A, 1-ph
3pcs MCB of 25A, 1-ph
2pcs MCB of 16A, 3-ph
with busbar 50A and 25% reserve space No. 1.00 6,752.40 6,752.40
11.1.1.29 Flush mounted metal enclosures SBD- 3 with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


1pc MCB of 16A, 1-ph
3pcs MCB of 25A, 1-ph
2pcs MCB of 16A, 3-ph
with busbar 50A and 25% reserve space No. 1.00 6,752.40 6,752.40
11.1.1.30 Flush mounted metal enclosures SBD- 4 with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1pc main MCB of 40A, 3-ph


1pc MCB of 16A, 1-ph
3pcs MCB of 25A, 1-ph
2pcs MCB of 16A, 3-ph
with busbar 50A and 25% reserve space No. 1.00 6,752.40 6,752.40
11.1.2 Floor standing type tested distribution board, MDB BK,
IP54, made of steel with center opening lockable door
including earthing lead, front cover all fixing and
connection accessories, complete and consisting of:-
1 pc main MCCB of 500A, 3ph
2pcs MCB of 80A, 3-ph
3pcs MCB of 63A, 3-ph
2pcs MCB of 40A, 3-ph
2pcs MCB of 25A, 3-ph
1pc surge arrestor of 75KA
3pcs ammeters with 3pcs pilot lamps: 0-500A
3pcs current transformers: 1700/5A
1pc of voltmeter with selector switch (0-500V)
with 4P+E busbar 500A
1pc factory made drawing pocket, Himel PP-A4
equivalent. use DIN rail mounted terminal blocks with end
brackets and marking tags for all outgoings. All complete
with 25% reserve spaces. No. 1.00 124,789.07 124,789.07
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
11.1.2.01 Flush mounted metal enclosures SDB- BK with lockable
door, earthing lead, cable terminal, labeling ,connectors
and all the necessary accessories consisting of:-

1 pc main MCCB of 63A, 3ph


7pcs MCB of 10A, 1-ph
12pcs MCB of 16A, 1-ph
1pc MCB of 20A, 1-ph
1pc MCB of 25A, 3-ph
1pc MCB of 20A, 3-ph
with busbar 70A and 25% reserve space No. 1.00 10,200.00 10,200.00
11.1.2.02 Flush mounted metal enclosures SDB- CCP-A with
lockable door, earthing lead, cable terminal,
labeling ,connectors and all the necessary accessories
consisting of:-
1 pc main MCCB of 25A, 3ph
4pcs MCB of 10A, 1-ph
7pcs MCB of 16A, 1-ph
with busbar 32A and 25% reserve space No. 1.00 5,841.10 5,841.10
11.1.2.03 Flush mounted metal enclosures SDB- CCP-B with
lockable door, earthing lead, cable terminal,
labeling ,connectors and all the necessary accessories
consisting of:-
1 pc main MCCB of 25A, 3ph
4pcs MCB of 10A, 1-ph
7pcs MCB of 16A, 1-ph
with busbar 32A and 25% reserve space No. 1.00 5,841.10 5,841.10
11.1.2.04 Flush mounted metal enclosures SDB- CCP-C with
lockable door, earthing lead, cable terminal,
labeling ,connectors and all the necessary accessories
consisting of:-
1 pc main MCCB of 40A, 3ph
1pc MCB of 10A, 1-ph
1pc MCB of 16A, 1-ph
1pc MCB of 20A, 1-ph
1pc MCB of 25A, 1-ph
2pcs MCB of 16A, 3-ph
with busbar 50A and 25% reserve space No. 1.00 8,380.00 8,380.00
11.1.2.05 Flush mounted metal enclosures SDB- CCP-D with
lockable door, earthing lead, cable terminal,
labeling ,connectors and all the necessary accessories
consisting of:-
1 pc main MCCB of 40A, 3ph
1pc MCB of 10A, 1-ph
1pc MCB of 16A, 1-ph
1pc MCB of 20A, 1-ph
1pc MCB of 25A, 1-ph
2pcs MCB of 16A, 3-ph
with busbar 50A and 25% reserve space No. 1.00 8,380.00 8,380.00
11.1.2.06 Flush mounted metal enclosures SDB- MCBP with
lockable door, earthing lead, cable terminal,
labeling ,connectors and all the necessary accessories
consisting of:-
1 pc main MCCB of 80A, 3ph
with busbar 90A and 25% reserve space No. 1.00 9,420.00 9,420.00
11.1.2.07 Flush mounted metal enclosures SDB- MCBP with
lockable door, earthing lead, cable terminal,
labeling ,connectors and all the necessary accessories
consisting of:-
1 pc main MCCB of 80A, 3ph
with busbar 90A and 25% reserve space No. 1.00 9,420.00 9,420.00
11.1.2.08 Flush mounted metal enclosures SDB-OBI-CBP with
lockable door, earthing lead, cable terminal,
labeling ,connectors and all the necessary accessories
consisting of:-
1 pc main MCCB of 63A, 3ph
with busbar 70A and 25% reserve space No. 1.00 9,420.00 9,420.00
11.1.2.09 Flush mounted metal enclosures SDB-OBI-CBP with
lockable door, earthing lead, cable terminal,
labeling ,connectors and all the necessary accessories
consisting of:-
1 pc main MCCB of 63A, 3ph
with busbar 70A and 25% reserve space No. 1.00 9,030.00 9,030.00
11.2 LIGHT POINTS
3rd party certified
11.2.1 Light points in medium duty rigid thermoplastic conduit of
16mm fed by PVC insulated copper cable of 3x2.5sq.mm.
color coded and labled No. 2,250.00 270.00 607,500.00
11.3 EXTRA OVER LIGHT POINTS :-
10A/1ph flush mounted Gewiss Eco 0 range cloud white
range or equivalent with appropriate cover plate, frame
and box
Note: use modular back box Gewiss (GW 24 232) for
concrete & masonry wall and Gewiss (GW 24 234) for
light or gypsum wall.or approved equivqlent 3rd party
certified
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
(TYPE LEGRAND SUNO OR EQUIVALENT)
11.3.1 Flush mounting single switch No. 299 125.00 37,375.00
11.3.2 Flush mounting double switch No. 487 140.00 68,180.00
11.3.3 Flush mounting two way switch No. 154 135.00 20,790.00
11.3.4 Flush mounting intermediate switch No. 33 180.00 5,940.00
11.4 SOCKET OUTLET POINTS
11.4.1 socket outlet points in medium duty rigid thermoplastic
conduit of 16mm fed by PVC insulated copper cable of
3x2.5sq.mm. color coded and labled No.
11.4.1.1 16A/1P flush mounted socket outlet point fed through
PVC insulated conductors of 3x2.5mm² inside PVC
conduts of 16mm diameter includeing junction boxes with
covers and insulating screw cap connectors. No. 1238 500.00 619,000.00
11.4.1.2 Ditto as above but for water heater incorporating 16A
isolator (on-off) switch to be fixed at a height of 1.8m
above finished floor level.Type of socket outlet shall be
LEGRAND Decor 718 20 or equivalent. No. 86 500.00 43,000.00
11.4.1.3 25A/1P flush mounted socket outlet point fed through
PVC insulated conductors of 3x6mm² inside PVC conduts
of 20mm diameter including junction boxes with covers
and insulating screw cap connectors for electric oven
incorporating 25A isolator (on-off) switch to be fixed at a
height of 1.0m above finished floor level.
No. 7 498.58 3,490.06
11.4.1.4 Ditto as above but 16A/3P flush mounted socket outlet
point fed through PVC insulated cable of 5x2.5mm² inside
PVC conduts of 20mm diameter including junction boxes
with covers and insulating screw cap connectors for
electric oven incorporating 16A isolator (on-off) switch to
be fixed at a height of 1.0m above finished floor level.

No. 4 585.12 2,340.48


11.4.2 EXTRA OVER SOCKET OUTLETS (TYPE LEGRAND,
SUNO OR EQUIVALENT)
11.4.2.1 Flush mounted single socket outlet of 16A/1P No. 1013 175.50 177,781.50
11.4.2.2 Flush mounted double socket outlet of 16A/1P No. 108 305.50 32,994.00
11.4.2.3 Flush mounted water proof single socket outlet of 16A/1P
No. 117 878.80 102,819.60
11.5 POWER OUTLETS
a 20A/1P power outlet point fed through PVC insulated
and PVC sheathed cable of 3x4 sq.mm of 25mm
diameter including junction box with cover. No. 6 978.90 5,873.40
b 25A/1P power outlet point fed through PVC insulated
and PVC sheathed cable of 3x6 sq.mm of 25mm
diameter including junction box with cover. No. 4 498.58 1,994.32
c 16A/3P power outlet point fed through PVC insulated
and PVC sheathed cable of 5x2.5 sq.mm of 25mm
diameter including junction box with cover. No. 10 585.12 5,851.20
d 20A/3P power outlet point fed through PVC insulated
and PVC sheathed cable of 5x4 sq.mm of 25mm
diameter including junction box with cover. No. 1 1,426.10 1,426.10
11.6 TELE & DATA SYSTEM
3rd party certified
Note: use modular back Gewiss (GW 24 232) for
concrete &masonry wall and Gewiss (GW 24 234) for
light or gypsum wall.or approved equivalent
11.6.1 Tel/data points fed by cable category 6 UTP 2 pair cable
telephone cable inside medium duty corrugated PVC No.
conduit of 20mm. 270 487.96 131,749.20
11.6.2 RJ 45 outlets type LEGRAND 2(74213) category 6E with
8 contacts complete with clip on support frame. No. 270 728.00 196,560.00
11.6.3 Telephone/Data Terminal Blocks(Distrubution frames)
with coressponding box and frames
3rd party certified
11.6.3.1 Flush mounted 100 pairs main telephone/Data terminal
blocks (telephone distrubution frame) or Punch down
blocks with plastic cover of similar color to the adjacent
wall support structure complete accessories(or eqivalent
pair as ETC standards)
No. 13 3,955.90 51,426.70
11.6.3.2 Flush mounted 10 pairs telephone /Data terminal
blocks(telephone distrubution frame) or Punch down
blocks with plastic cover of similar color to the adjacent
wall support structure complete accessories
No. 11 1,355.90 14,914.90
11.6.4 Telephone/ Data Distrubution cables
3rd party certified
Tentative measurments only ,actual on site
11.6.4.1 CAT 5 UTP telephone cable ml 2500 75.98 189,950.00
11.6.4.2 CAT 6 UTP data cable ml 2500 75.98 189,950.00
11.7 POWER CABLES
3rd party certified
PVC sheathed NYY insulated cable type euro cable or
equivalent rating of 0.6/ 1KV
Tentative measurments only ,actual on site
11.7.1 2X(3X240/1x120/1x120sq mm) EEPCO INTAKE ml 100 5,275.21 527,521.00
11.7.2 (3X185/1x95/1x95sq mm) EEPCO INTAKE ml 200 2,072.63 414,526.00
11.7.3 5x2.5 sq.mm with PVC pipe of diameter 32mm ml 110 115.51 12,706.10
11.7.4 5x4 sq.mm with PVC pipe of diameter 50mm ml 60 133.56 8,013.60
11.7.5 5x6sq.mm with PVC pipe of diameter 50mm ml 20 300.00 6,000.00
11.7.6 5x10 sq.mm with PVC pipe of diameter 70mm ml 800 237.28 189,824.00
11.7.7 5x16 sq.mm with PVC pipe of diameter 70mm ml 320 318.70 101,984.00
11.7.8 3x25/16+16 sq.mm with PVC pipe of diameter 70mm ml 95 425.44 40,416.80
11.8 CABLE WAYS AND MANHOLES
Tentative measurments only ,actual on site
11.8.1 Underground PVC pipes of diameter 110mm for Tele
intake. Price to include cost all necessary accessories.
ml 2540 100.00 254,000.00
11.8.2 Rigid PVC pipes of diameter 110mm for feeder cable.
Price to include cost all necessary accessories. ml 40 100.00 4,000.00
11.7.3 PVC pipe of diameter 32mm ml 110 32.33 3,556.30
11.7.4 PVC pipe of diameter 50mm ml 80 35.00 2,800.00
11.7.6 PVC pipe of diameter 70mm ml 3715 100.10 371,871.50
11.9 Man holes Double Brick wall
11.9.1 Manhole 120x120x80cm removable cast iron cover "EL
& TEL MH" No. 3 20,737.52 62,212.56
11.10 NURSE CALL SYSTEM
Supply install, testing and commission as per the
manufacturers instruction.
a 2nd & 3rd Floor
Nurse call system with accessories type
LEGRAND or equivalent and consisting of :-
1 pc power supply, 782 89
2 pc table-control unit for 36 numbers,782 14
11 pcs 6-way call display unit, 76660
22 pcs 3-way management module,78212
32 pc dual display corridor bulkhead, 78263
32 pc door unit, 782 04
32 pcs Bath room call unit, 766 64
42 pcs Push button cord, 766, 63 + 78362 SET 2 1,135,811.82 2,271,623.64
b 4th Floor
Nurse call system with accessories type
LEGRAND or equivalent and consisting of :-
2 pc power supply, 782 89
4 pc table-control unit for 36 numbers,782 14
22 pcs 6-way call display unit, 76660
44 pcs 3-way management module,78212
48 pc dual display corridor bulkhead, 78263
48 pc door unit, 782 04
48 pcs Bath room call unit, 766 64
84 pcs Push button cord, 766, 63 + 78362 SET 1 2,242,237.14 2,242,237.14
c 5th Floor
Nurse call system with accessories type
LEGRAND or equivalent and consisting of :-
2 pc power supply, 782 89
4 pc table-control unit for 36 numbers,782 14
22 pcs 6-way call display unit, 76660
44 pcs 3-way management module,78212
48 pc dual display corridor bulkhead, 78263
48 pc door unit, 782 04
48 pcs Bath room call unit, 766 64
84 pcs Push button cord, 766, 63 + 78362 SET 1 2,242,237.14 2,242,237.14
d 6th Floor
Nurse call system with accessories type
LEGRAND or equivalent and consisting of :-
2 pc power supply, 782 89
2 pc table-control unit for 36 numbers,782 14
4 pcs 6-way call display unit, 76660
8 pcs 3-way management module,78212
8 pc dual display corridor bulkhead, 78263
8 pc door unit, 782 04
8 pcs Bath room call unit, 766 64
12 pcs Push button cord, 766, 63 SET 1 479,536.20 479,536.20
11.11 PUBLIC ADDRESS
Supply install, testing and commission as per the
manufacturers instruction.
N.B The speaker at every floor is accessable from
every nurse station on the building .
a IP based Voice alarm and PA system controller
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
100 zone system controller
expandable up to 150 zones
built in 11x240W booster amplifier
digital pre-recorded messages
emergency microphone input on the front panel
25 priority levels including emergency
Individual BGM volume control for each zone
Standard and emergency control input and outputs No.
1 173,641.00 173,641.00
b Voice alarm 120W booster No.
13 63,362.00 823,706.00
c Voice alarm call stations No.
13 16,055.00 208,715.00
d Voice Alarm Remote Control Panel No.
1 100,438.00 100,438.00
e Voice Alarm BGM(back ground music source) No.
1 86,372.00 86,372.00
f Voice Alarm digital Message Manager No.
13 50,518.00 656,734.00
g Supply install, testing and commission software pakege
for the PA system L.S 1 94,302.00 94,302.00
h 6W ceiling recessed speaker with fixing accessories No.
109 5,252.00 572,468.00
i Softwares, documentation, instruction of owner's staff,
power supplies. LS 1 98,020.00 98,020.00
j Flush mounting PA point fed through twin flat speaker
cable of 2x1.0mm² inside PVC conduit of 16mm diameter
including junction box with cover and insulating screw cap
connector. No 123 2,112.50 259,837.50
k Voice alarm and PA system controller networking
system , installed, connected, tested and commissioned
including , category 6 4pair data cables, subswiches,
programming soft wares, conduits and all necessary
accessories , complete as manufactured requirment with
complete shop drawings and .analysis made before
manufacturing and instillation

No 1 129,824.50 129,824.50
11.11.1 FIRE ALARM SYSTEM
a Flush mounted Fire alarm addressable ionization type
smoke detector. No 635 5,176.60 3,287,141.00
b Flush mounted Fire alarm addressable type heat detector.
No 2 5,176.60 10,353.20
c Surface mounted Fire alarm addressable manual call
point non-breakable with plastic cover and reset key. No 83 5,176.60 429,657.80
d Fire alarm addressable sounder on loop with relay base
and indicating light. No 64 6,120.56 391,715.84
e Fire alarm system (which includes all the equipments)
point fed through fire alarm system cable of 2x1.5sq. mm
inside pvc conduit of 20mm diameter No 701 2,749.50 1,927,399.50
f IP based Intelligent digital addressable fire control ,voice
evacuation and Appliance Circuit Modules,Control Relay
Module , indicating panel, including Notification auxilary
contact and under mentioned specification

-Input power 220VAC, 50 Hz


-Capable of networked connection RS485
-Capable of wirless integration
-Programmable internal hard ware and output circuits
-Programmable soft ware zones
-Accessories for out put connection for telephone circuit

-Sealed battery capable of supply to all equipments for

at least 72Hr
-Intelligent signaling line circuit
-voice alarm system interface
-Trouble acknowledge and alarm silence switch
-Visual and audiable trouble alarm by zone
-Manual acknowlage function
-Minimum of 40 zones digital
-LCD display (80 characters)
-Program keypad
-LED indicators
-13 relay outputs
-25 Auxilary relay outputs
-3 loops
-Compatible devices
-Compatible intelligent devices
with all necessary accessories as BS EN 54
standards to make the system No. 1 325,771.88 325,771.88
g Testing and commissioning as per the manufacturers
instruction. L.S 1 65,000.00 65,000.00
11.12 Light Fittings and Lamps
(Specified type or equivalent)
b Surface mounted fluorescent luminaire LITECH 11-8102
T8 1x18W IP20 No. 160 1,381.63 221,060.80
c Surface mounted fluorescent luminaire LITECH 11-8102
T8 1x18W IP20 No. 130 1,381.63 179,611.90
d Recessed mounted fluorescent luminaire LITECH 11-
8102 T8 4x18W IP20 No. 880 2,764.66 2,432,900.80
e Surface mounted fluorescent luminaire LITECH 11-8102
T8 2x18W IP20 No. 480 2,099.54 1,007,779.20
f Toilet Ceiling RZB 25129. 962 TC-D 18W IP43 No. 110 1,794.43 197,387.30
g Toilet Ceiling RZB 25129. 962 TC-D 2x18W IP43 No. 20 2,602.08 52,041.60
h Toilet wall for mirror RZB 21146. 962 TC-D 13W IP44 No. 25 1,381.63 34,540.75
i Toilet wall linear for mirror 401001.912.79 TC-EL 13W
IP44 No. 100 1,381.63 138,163.00
k Indoor half recessed down light LITECH 12-8006-005
E27 2XPLE 18W IP23 No. 120 1,884.17 226,100.40
l Indoor recessed down light LITECH 12-6386-003 E27
2XPLE 18W IP44 No. 20 1,884.17 37,683.40
m Indoor recessed down light LITECH 12-6386-003 E27
1XPLE 18W IP44 No. 80 1,389.39 111,151.20
n Outdoor wall RZB 58138.923 TC-D 18W IP54 No. 10 1,285.39 12,853.90
o Fluorescent 2x18W lamp, ceiling fitting Exit light with
pictogram No. 65 3,104.61 201,799.65
p Fluorescent 2x18W lamp, wall fitting Exit light with
pictogram No. 50 3,104.61 155,230.50
11.13 Grounding System
Complete grounding system for Main distrubution board
as per IEC,EN or BS standards attain 5 ohms with
complete inspection pits as per the detail drawings bare
copper wire, copper rods of approprate size conducting
materials and approved type of networks complete
accessories.

a 800 x 800 x 700 mm single brick inspection pit with the


cover top inscribed "Earthing" No. 2 6,706.98 13,413.96
b (1 x 95)sq.mm bare copper wire ml 15 2,198.00 32,970.00
c (1 x 120)sq.mm bare copper wire ml 15 2,901.45 43,521.75
d Diameter 20mm and 3000mm long copper rod No. 2 7,690.65 15,381.30
11.14 MATV system
3rd party certified
Note :-The TV points shall orginate from respective floor
TAP off /splitter units and terminate at the room wall out
lets as per detail drawing & the riser or the feeders shall
orginate from head end eqiypment rooms and terminate
at the floors' TAP off /splitter units

a) Supply and install sattelite dish 2.0m diameter with No.


universal LNB per sattelite station including roof mounting
bracket and SAT-IF cable up to head end equipment.

1 63,180.00 63,180.00
b) TV point fed through RG6 75ohms broad band Co- No.
axial cable (47-2500MHz) suitable for TV/FM/SAT signal
distribution inside PVC conduit of 20mm diameter,
including junction boxes with covers, insulating screw cap
connectors
70 270.00 18,900.00
TV Terminal Box No.
32 398.23 12,743.36
Flush mounting terminal SAT/TV/FM outlet. No.
70 230.00 16,100.00
11.15 Standby Diesel Generator
a 630KVA Diesel generating set output at 2500m above
sea level with, ATS, 380/230V,50Hz,1500rpm,0.8pf,3ph,
self exited, insulation class H for stator and rotor, with
base mounted fuel tank, skid mounted including
residential rated exhaust silencer, electric fuel transfer
pump, as indicated in the specification and with weather
proof and sound proof canopy with sound level
approprate for hospital use.And also external fule tank
system with all accesaaeries with fuel capacity of 8 hours
supply of the generator at full load.

No. 1 7,497,302.49 7,497,302.49


ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
b 260KVA Diesel generating set output at 2500m above
sea level with, ATS, 380/230V,50Hz,1500rpm,0.8pf,3ph,
self exited, insulation class H for stator and rotor, with
base mounted fuel tank, skid mounted including
residential rated exhaust silencer, electric fuel transfer
pump, as indicated in the specification and with weather
proof and sound proof canopy with sound level
approprate for hospital use.And also external fule tank
system with all accesaaeries with fuel capacity of 8 hours
supply of the generator at full load.

No. 1 2,981,529.29 2,981,529.29


11.16 UTILITY CONNECTION
a Fee for power connection works by EEPCo including
Compact Transformer of 630KVA and all the necessary
material and work to full fill the job. No. 1 1,298,534.91 1,298,534.91
b Fee for power connection works by EEPCo including
Compact Transformer of 260KVA and all the necessary
material and work to full fill the job. No. 1 844,047.69 844,047.69
11.17 LIFT
a Supply, install and commission of duplex MRL Bed
lift,1.0m/s speed and 8 stopes, capacity of 21 persons
with all accessories in accordance with technical
specification. No. 1 12,377,551.28 12,377,551.28
b Supply, install and commission of simplex MRL Pasenger
lift,1.6 0m/s speed and 7 stopes,capacity of 13 person
with all accessories in accordance with technical
specification. No. 2 6,009,200.85 12,018,401.70
11.18 UPS
a SCHNEIDER MGE ups system type Galaxy 5000 or
equvalent 120KVA/3phase output at 2500m above sea
level which must supply the power for 15 minutes from
UPS battery. No 1 2,434,900.00 2,434,900.00
11.19 Lightning Protection System
a ERITECH SI INTERCEPTOR Ref:code SI40 Part No.
701536 ERITECH SI INTERCEPTOR, ESE-∆T=40(µsec)
No 2 68,250.00 136,500.00
b Air terminal base type ERITECH Ref:code ER2-BASE-
SS Part No. 702290 Stainless Steel Mast Base section-2
No 2 13,650.00 27,300.00
c Ref.code ER1-1000SS Part No.702255 Upper stainless
steel mast-1m long section 1 No 2 11,700.00 23,400.00
d Ref.code ER2-2000SS Part No.702265 Lower stainless
steel mast-2m long section 2 No 2 13,650.00 27,300.00
e Ref.code GUYKIT4 Part No.701300 KEVLAR®GUYKIT
up to 4m Masts No 2 11,310.00 22,620.00
f Bare copper Tape on roof of dia. 16mm
M 380 936.00 355,680.00
g Pvc covered copper Tape for down conductor Ref.code
CTGN 256-30 Part No.710620,including all fixing
accessories. M 80 1,014.00 81,120.00
h Earth test clamp for tape Ref.No CCJ-70-CA Part No.
102700 No 2 3,315.00 6,630.00
i Earthing rod copper bond 3000x16mm inside
700x700x700 mm pit (measured elsewhwre). with clamp
for copper tape including coupling and driving stud.
No 2 1,911.00 3,822.00
j Test junction box at 1.5m above ground level No 2 3,315.00 6,630.00
k Lightning strick counter No 2 8,190.00 16,380.00
11.20 CABLE LADDER SYSTEM
Imported Galvanized steel Cable ladder of 100mm
loading depth, 5mm thickness, heavy duty type, supplied
installed and tested, including all accessories, hangers,
suppports, brackets, bends, T and earth bonding,
complete all as specified and/or shown on drawings.

a 400 mm width (Installation as per detail on plans) ML 105 2,696.98 283,182.90


11.21 CABLE TRAY SYSTEM
Imported Galvinzed steel solid bottom with cover Cable
tray of 50mm loading depth, 5mm thickness, heavy duity
type, supplied installed and tested, including all
accessories, hangers, suppports, brackets, bends, T and
earth bonding, complete all specified and/or shown on
drawings.

a 400 mm width (for power cables) ML 70 2,696.98 188,788.60


b 300 mm width (for low current systems) ML 533 1,632.28 870,005.24
11.22 MANHOLES
a Manhole in brick or masonry, internally of
800x800x600mm including reinforced concrete cover with
lifting lug. No 6 5,795.70 34,774.20
11.23 LOW VOLTAGE SYSTEM EARTHING
a 3000x16mm copper bond earthing rod inside
700x700x700 mm manhole (measured elsewhwre). Low
voltage system earthing 10m of 1x240 mm² bare copper
conductor from equipotential earth bar in generator house
to copper bond earthing rod.
No 1.00 6,198.50 6,198.50
b Medical equipment earthing/grounding system as the
manufacturere requirment with all the necessary material
and job to meet the expected oms reading of the supplier
standard. Ls 5.00 63,700.00 318,500.00
TOTAL CARRIED TO SUMMARY 69,251,032.84
12.SANITARY INSTALLATION
12.1 All fixtures which specified below is subjected to the
consultant approval, based on samples ,catalogues
and brochures presented by the contractor.

12.1.01 Hand Wash Basin (with pedestal)


Supply and fix Hand Wash Basin , made of white
vitreous China (BS3402) ,with pedestal fixed back to
wall. The fixture shall conform to BS5506-3 or equivalent
institution. Size 660 x 480 mm. The waste fittings,
connecting pieces, fixing and supporting element and
other accessories which complete the set shall comply
with the relevant clauses of BS standard or equivalent
institution. The tap ware shall comply to BS2878:1980

Nº 71 1,948.57 138,348.47
12.1.02 Hand Wash Basin (Wall hung basin)
Supply and fix Hand Wash Basin , made of white
vitreous China (BS3402) ,Wall hung basin. The fixture
shall conform to BS5506-3 or equivalent institution. Size
560 x 450 mm. The waste fittings, connecting pieces,
fixing and supporting element and other accessories
which complete the set shall comply with the relevant
clauses of BS standard or equivalent institution. The tap
ware shall comply to BS2878:1980 and fix all the
necessary accessories must be provided.
Nº 24 1,800.00 43,200.00
12.1.03 Hand Wash Basin (Above the counter)
Supply and fix Hand Wash Basin , made of white
vitreous China (BS3402) ,granite counter top
mounting. The fixture shall conform to BS5506-3 or
equivalent institution. Size 550 x 470 mm. The waste
fittings, connecting pieces, fixing and supporting element
and other accessories which complete the set shall
comply with the relevant clauses of BS standard or
equivalent institution. The tap ware shall comply to
BS2878:1980 and fix all the necessary accessories must
be provided.
Nº 73 27,479.44 2,005,999.12
12.1.04 Disabled Hand Wash Basin
Supply and Fix white vitreous China (BS3402) Wall hung
basin. The fixture shall conform to BS5506-3 or
equivalent institution. Size 700 x 405 mm. The waste
fittings, connecting pieces, fixing and supporting element
and other accessories which complete the set shall
comply with the relevant clauses of BS standard or
equivalent institution. The tap ware shall comply to
BS2878:1980 with Rails:-600mm Support Rails (x 3)

Nº 34 25,707.80 874,065.20
12.1.05 Water closet
Supply and fix water closet , of wash down action, floor
mounted , vertical outlet (floor drainage), close
coupled ,made of white vitreous China (BS3402).The
fixture shall conform to BS5503-2 or equivalent institution.
The waste fittings, connecting pieces, fixing and
supporting element and other accessories which
completes the set shall comply with the relevant clauses
of BS standards or equivalent institution. with P-trap and
Strap.
Nº 131 5,000.00 655,000.00
12.1.06 Disabled Water closet
Supply and fix Disabled water closet ,of wash down
action, floor mounted , vertical outlet (floor drainage),
close coupled, made of white vitreous China
(BS3402).The fixture shall conform to BS5503-2 or
equivalent institution. The waste fittings, connecting
pieces, fixing and supporting element and other
accessories which completes the set shall comply with
the relevant clauses of BS standards or equivalent
institution.
Rails:-600mm Support Rails (x 1),765mm Hinged
Support Rail (x2)
Nº 34 25,122.80 854,175.20
12.1.07 Urinals
Supply and fix approved quality wall mounted concealed
steel hanger, concealed flush pipes, built in p-trap
500mmx700mcm,15mm thick ceramics urinal partition
wall complete with all necessary accessories. Unit price
shall include all the necessary assistances to the
installation works.
Nº 21 2,000.00 42,000.00
12.1.08 Toilet Paper Holder
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Supply and fix toilet paper holder , made from white
vitreous china(BS3402) ,concealed/surface mounted of
approved quality complete with all the necessary
accessories. Nº 165 250.00 41,250.00
12.1.09 Crystal glass mirror
Supply and fix approved quality frameless crystal glass
mirror ,back-silvered ,minimum 6mm thick Size 600mm x
500mmComplete with thief resistant concealed wall
fastening fittings and other accessories.
Nº 168 1,560.00 262,080.00
12.1.10 Soap Holder
Supply and fix soap holder leassed type of approved
quality ,made of white vitreous china , European
standard or equivalent institution, complete with all the
necessary accessories. Nº 168 260.00 43,680.00
12.1.11 Floor Drain & Shower Drain
supply and fix 80mm diameter enameled cast iron floor
drain conform to ASME standards, A112.6.3(heavy duty)
or equivalent institution complete wit P-smel trap and all
the necessary accessories.
Nº 128 500.00 64,000.00
12.1.12 Disabled shower
Supply and Fix with SHOWER VALVE AND KIT:-
Concealed Shower Valve, Diverter Riser Rail, Hose,
Handset, Elbow and Short Projection Overhead Shower,
and adjustable and detachable shower head with shower
tip up seat with back support, Rails:-600mm Support
Rails (x 3),765mm Hinged Support Rail (x2) 450mm
Support Rail (x1),Robe Hook (x1).
SHOWER RAIL & CURTAIN:-1200mm x 1200mm
Angled Shower Rail With Celling Support and 1000 x
1200 Shower Curtain (x2).
Nº 8 20,176.30 161,410.40
12.1.13 Tower hanger
Supply and fix towel hanger 610 x 25 mm with chrome
plated tubular towel rail complete with the necessary
accessories. Nº 136 260.00 35,360.00
12.1.14 Kitchen Sink
Supply and fix double bowl stainless steel kitchen sink
with brass chrome plate trap. The waste fittings,
connecting pieces, fixing and supporting element and
other accessories which complete the set shall comply
with BSEN 695;1997 or the relevant clauses of BS
standards or equivalent institution. The tap ware shall
comply to BS2878:1980
Size 1500 x 600 x 150mm (bowl depth)
Nº 4 3,216.99 12,867.96
12.1.15 Fire Extinguisher
Supply and fix 9kg Dry Powder fire extinguisher for
ABCE class of fire. The material shall comply ,with TUV
or,BSI or ,NFPA or equivalent institution certification and
approval. Complete with approved standard hanging and
fixing materials.
Nº 40 2,099.70 83,988.00
12.1.16 Sluice Sinks
Supply and fix a wall mounted stainless steel sink unit
with continuous flushing rim and conical bowl for the
disposal of liquid and solid waste. The unit has a raised
anti-drip rim and 50mm sides turned down all round. This
unit also features a 500 x 400 x 250 sink bowl. Available
with TOP INLET for exposed cistern or REAR INLET for
concealed cistern. Complete with stainless steel flush
pipe, chrome plated front operating lever, syphon, ball
valve and float, and side entry inlet connection.
Available with drain board to the left or right of the unit.
Dimensions:
1600mm x 600mm x 365mm (LxWxH) this includes:-
1600 x 600mm DU H Sluice Sink, 2x Stainless steel
heavy duty wall brackets,110mm polypropylene waste
trap (choice of ‘P’ or ‘S’ trap),Sink waste fitting, Stainless
steel 9ltr cistern (TOP INLET MODEL ONLY),or
Concealed plastic cistern.600mm stainless steel fall pipe
(TOP INLET MODEL ONLY).

Nº 9 66,865.80 601,792.20
12.1.17 ICU Sinks
Supply and fix Vitreous china
• Permanent Ever Clean® surface inhibits the growth of
stain & odor causing bacteria, mold & mildew
• Deep basin & sloped ledges minimize splashing
• Sink drain is offset so that the water stream does not
fall directly on the grid drain
• Sink is designed with sealed overflow to eliminate
an area for water to pool
• Includes removable acrylic shroud (with mounting
hardware) to allow access to the faucet electronics
• Includes offset grid drain & P-Trap with
Saniguard®** coating.
SELECTRONIC® FAUCET:
Hygienic hands-free operation
• Rigid gooseneck spout with 5" reach
• 1.5 gpm laminar flow restrictor in spout shank - No mix
of
air & water
• Plain spout end - Nothing on the end of the spout to
collect lime & debris. With power option pluge in and DC
(battery)
• Fully enclosed, water resistant &
hermetically sealed
electronic controls
• Vandal-resistant durable brass construction
• Integral in-line strainer prevents clogging
• Factory-installed 15" long S.S. flex hose with 3/8"
compression connection
• Lead Free: Faucet contains ≤ 0.25% total lead content
by weighted average
• Optional thermostatic mixing valve (605XTMV) is
available & must be ordered separately

Nominal Fixture
Dimensions:
509 x 432 x 663mm Nº 5 48,964.80 244,824.00
11.1.18 Scrub Sinks
Type 304 Stainless steel construction with welded
compartments and coved corners for easy cleaning
Stainless Steel Construction. With removable
bay(Station) Panels.. Equipped with infrared operated
water control as well as a manual bypass for knee
operated water control. The main operation is via the
infrared sensor located between the knee panels. The
knee operation for water control is on standby as a
backup. Field upgradeable knee operated soap
dispenser or foot pump accessory. Digital timer: ensuring
adequate scrubbing time, Removable Shower Head,•
Adjustable thermostatic controlled pressure regulating
mixing valve, one per station,: the built-in thermostatically
controlled mixing valve provides water temperature up to
115° F (46° C),Adjustable Pressure Regulator Laminar
flow faucet: delivering a consistent stream of non-splash
water, Digital Timer,o Eye-wash station: safety option is
turned on by activating the knee panel and a pull of the
center knob, releasing both safety caps to provide instant
flushing .
Dimensions: 2438mm x 692mm x 1308 mm)
(LxWxH) Three station

Nº 4 223,342.90 893,371.60
12.1.19 Ditto Item, but Dimensions: 813mm x 692mm x 1308
mm)(LxWxH) One Station Nº 2 147,810.30 295,620.60
12.1.20 Emergency Shower -Eye Wash
Supply and fix Type 316 Stainless steel Combination
Shower & eye Face wash station plastic triple aerated
eye-face wash nozzle assemblies to provide the
optimum facial and eye irrigation. Shower Flow Control
Regulator. All Pratt Combination Shower Units are fitted
with a flow control regulator, which limits the flow output
to 90LPM. This ensures the
shower will exceed the minimum required flow rate and
allow the eye
wash to operate simultaneously as required by the
Standards. Adjustable Eye Wash Flow Control All Pratt
Combination, Eye-Face Wash and Eye Wash Stations
incorporate an adjustable flow control.

A)shower:-Hands-free valve
activates in one second or less and remains open until
manually closed, Height of water column is between
(208.3 cm) and(243.8 cm) above the floor. FF Center of
the water pattern is at least (40.6 cm) from any
obstruction.FF Easily located, accessible actuator is no
more than (173.3 cm) above floor.

B)Eye/Face Wash:-Controlled, low


velocity flow completely rinses eyes and face and is not
injurious to user, Water flow is sufficiently high to allow
user to hold eyes open while rinsing, Spray heads are
protected from airborne contaminants. Covers are
removed by water flow, Unit delivers at least 3.0 gallons
(11.4 liters) of water per minute for 15 minutes.

Water Temperature: Water delivered by both Shower &


eye/face wash shall be tepid (60-100°F).

Nº 2 63,342.80 126,685.60
12.1.21 Lab Sink
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Supply and fix Radioactive sink that coved to the back
wall with rounded upstanding front edges. A splash back
should be fitted to the back wall using similar finishes.
Small bore u-shaped or bottle traps should be used, large
traps and catch pots are to be avoided. With Lead
warping of piping Taps should be provided which can be
operated without using hands. The pressure of the water
should be regulated such that at full flow (tap full on)with
all the necessary accessories.
Dimensions: 660mm x 460mm x 273mm (LxWxH)

Nº 5 62,692.80 313,464.00
12.1.22 Electric Water Heater
Supply and fix approved quality storage type water
heaters, complete with insulation, one way valve and
safety valve, including all fixing accessories.

The water heater shall


also be :-

*
made from steel :-highly resistance to any deformation
caused by variation in temperature and internal pressure.

* With
Glass lining treatment:- The lining of the tank is
subjected to a treatment with titanium or equivalent glass
lining.
Nº 93 4,500.00 418,500.00
12.1.23 Ditto Item No 21,but 80Liters Nº 3 5,509.06 16,527.18
12.1.24 Janitors Sink
Construct Janitors sink out of single brick wall,450mm
high on the base of 150mm thick mass concrete/C-25/,
plastered both internal and with white ceramics.
Size :- 1500 x 500mm Nº 2 4,043.49 8,086.98
internal dimension
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
PPR-Pipes
12.1.25 POLYPROPYLENE RANDOM CO-POLYMER (PP-R
TYPE3)pressure pipes ,(PN20),for cold and hot water
supply system to sanitary fixtures which comply with BS
6920:part 2&3 or DIN 8078 and equivalent institution
complete with all the necessary connecting pieces such
as bends, Ys, Tees, reducers, nipples, Teflon, unions,
threaded male or female with de-indication resistance
(DZR)brass inserts complying with BS 6920 or
equivalent institution, hangers(as per manufacturer's
recommendation) & supporters (if any) etc…The
installation shall be tested at a pressure of 10kg/cm2 or
DIN 1988 part 2 or Supply, lay and connect outer
diameter 20mm BS 6700 . Unit price shall
include ,disinfection of the pipes with Chlorine, painting all
exposed PP-R pipes with UV Reflexive oil paint,
installation works any all additional works there to .

ml 228 65.09 14,840.52


12.1.26 Ditto Item No 24, but 25mm diameter ml 697 73.01 50,887.97
12.1.27 Ditto Item No 24, but 32mm diameter ml 311 155.64 48,404.04
12.1.28 Ditto Item No 24, but 40mm diameter ml 545 399.04 217,476.80
12.1.29 Ditto Item No 24, but 50mm diameter ml 236 437.59 103,271.24
12.1.30 Supply and fix chrome plated service (angle) valves of
approved standard, before sink, shower and other
fixtures complete with unions, elastic water proofing,
hand wheels of normal quality and with all other
necessary accessories.
Diameter:1/2''(20mm OD)
Nº 1016 565.50 574,548.00
Bronze Gate Valve
12.1.31 Supply and fix bronze gate valves (PN 16 ),diameter 32
mm of approved standards, on internal branch water
pipes, pipe inlet to buildings at where shown on the
drawing complete with all the necessary accessories .
Nº 59 800.00 47,200.00
12.1.32 Ditto Item No 29, but 40mm diameter Nº 110 1,200.00 132,000.00
12.1.33 Ditto Item No 29, but 50mm diameter Nº 48 2,500.00 120,000.00
uPVC Foul Water Pipe
12.1.34 Supply and lay 50mm(2'') diameter uPVC pipes minimum
wall thickness 2.0mm for foul water collection and vent
system. The pipes shall be supported with galvanized
clips screwed to slab, beam columns ... etc. at every
joints, bends and at 0.5meters interval in straight line. All
exposed pipes shall be painted with UV reflective oil
paint, similar to the walls,slabs,beams…etc. it is fixed on
& complete with all necessary fittings and clean out. The
pipes, to BS 5255 or Equivalent Institution. Unit price
shall include all the necessary assistance to the
installation works there to.

ml 250 70.00 17,500.00


12.1.35 Ditto Item No 32, but 110mm diameter ml 1460 250.00 365,000.00
12.1.36 uPVC Down Pipe
Supply and fix Diameter 150mm uPVC Down pipes, min.
wall thickness 3.2mm ,with mass concrete support at
ground level & complete with UV reflective oil painting,
basket strainer at inlet ,galvanized clips at every
1.0meters interval and all accessories .The
pipes ,accessories, fittings &method of welding shall
comply with the requirement of BS 4514or equivalent
Institution. Unit price shall include all the necessary
assistances to the installation works there to.
ml 891 170.00 151,470.00
12.1.37 Vent Cape
Supply and fix 110 mm uPVC vent pipe for toilets,
minimum wall thickness 3.2 mm, painted with UV
reflective oil paint. Unit price shall include all the
necessary assistance to the installation work. Nº 71 150.00 10,650.00
12.1.38 Galvanized Steel Pipes
Supply, lay , test and commission 110mm (4'')GSP
/Galvanized Steel Pipe/,(PN16) for Fire Fighting water
supply as shown on the drawing. The GS pipes shall be
supplied complete with all the necessary accessories
connecting pieces such as
bends,Tees,reducers,adaptors,sockets,unions or
standard approved type metallic clamps. The installation
shall be tested at a pressure of 16kg/cm2.The GS
pipes,accessories,fittings & method of connection shall
comply with the requirement BS 4991& BS6920 part 2 &3
or equivalent institution.

ml 60 519.96 31,197.60
12.1.39 Ditto Item No 36, but diameter 65mm ml 108 151.00 16,308.00
12.1.40 Ditto Item No 36, but diameter 40mm ml 3 104.00 312.00
12.1.41 Ditto Item No 36, but diameter 20mm ml 3 57.00 171.00
12.1.42 Supply and fix BS ,NFPA or DIN standard ,surface
mounted with full metal door model, fire hose reel
cabinet . Cabinet and door leaf made of stainless steel
2mm thick sheets with full 180 degree swinging action
and painted with electro--statics powder paint oven baked
to temperatures between 160-200 oc.Hose is made of
100% synthetic Jacket ,the outer fabric is made of circular
woven SYNTHETIC FIBER and root proof yarn, while
inner layer is a substrate of tropical rubber, with working
pressure 20 bar and bursting pressure 60 bar with
standard red color. Nozzle is made of brass with Chrome
plated with three way control .Cabinet:-W=65cm,H=65cm
and D=19cm The installation shall be tested at a pressure
of 16kgf/cm2. The hose shall be compatible to
Galvanized Steel pipes, accessories & fittings.GS pipe
installation & method of connection shall comply with the
requirement of BS 4991 & BS 6920 part 2 &3 or
equivalent institution. Unit price shall include all the
necessary assistance to the installation works.

Nº 14 21,790.65 305,069.10
12.1.43 Supply and fix bronze gate valves (PN 16 ),inner -
diameter 50 mm(2''),for Air release Valve Nº 2 2,500.00 5,000.00
12.2 SANITARY SITE WORK INSTALLATION
All plumbing and drainage components which
specified below are subjected to the consultant
approval, based on samples , catalogues brochures,
test reports, product quality certificates presented
by the contractor . All sanitary appliances shall be
best quality and European made or equivalent.

WATER SUPPLY SYSTEM


12.2.01 Pipes
Supply, lay, test and commission 32mmHDPE water
supply pipe having PN16 for site water supply system
complete with all the necessary connecting pieces
such as bends, unions, Unit price shall include excavation
of trenches to a depth of 800mm, backfilling and all the
necessary assistance to the installation works...etc. The
installation shall be tested at a pressure of
10kg/cm2 .The Pipes and fittings shall conform to
BS6347/DIN8047 or equivalent institution. The product
quality assurance certificate has to be submitted along
with the material for approval.
ml 82 126.31 10,357.42
12.2.02 Ditto Item No 01, but 40 diameter. ml 150 139.18 20,877.00
12.2.03 Ditto Item No 01, but 50 diameter. ml 140 154.78 21,669.20
12.2.04 Ditto Item No 01, but 65diameter. ml 95 184.81 17,556.95
12.2.05 Ditto Item No 01, but 75diameter. ml 42 213.41 8,963.22
12.2.06 Ditto Item No 01, but 90 diameter. ml 105 272.04 28,564.20
WASTE WATER DRAINAGE SYSTEM
12.2.07 Pipes
Supply, lay & connect diameter 160mm Upvc pipe
(DIN 8062) for waste water drainage with the working
pressure of 6 bars, minimum wall thickness 4.7mm and
complete with all the necessary accessories. Unit price
shall include excavation of trench(minimum depth
60cm),back fill with selected material, compacting and all
the necessary assistance to the installation works …etc.
The pipes should be laid with slope as indicated on the
profile table.

ml 360 284.58 102,448.80


12.2.08 Radioactive waste water drainage pipe
Supply, lay & connect diameter 160mm pipe for
Radioactive waste water drainage Lead warpped Pipe
with the working pressure of 10 bars, with sufficient
resistant to radioactive element and complete with all the
necessary accessories. Unit price shall include
excavation of trench(minimum depth 60cm),back fill with
selected material, compacting and all the necessary
assistance to the installation works …etc. The pipes
should be laid with slope as indicated on the profile
table.
ml 138 3,025.70 417,546.60
RADIOACTIVE LEAD LINED MANHOLE
12.2.09 Size:- (600*600)mm( Av.depth 600 -1000mm )
Construct Lead lined radioactive rectangular manhole
out of 250mm R.C concrete C-25 walls internal dimension
(600*600)mm & average depth (600-1000mm) on a base
of R.C.slab, size,1700x1700x300mm, including benching
and bottom channeling with mass concrete. Cover slab
shall be 100mm thick R.C. concrete reinforced with
12mm R.bar 110mm c/c and bottom slab shall be
reinforced with 10mm reinforcement bar c/c 150mm. and
250mm thick walls are reinforced with 12mm R.bar
c/c180mm in both ways. Provide 150mm granular
materials under the base slab, on a compacted earth.
manhole cover shall be reinforced with 10mm R.bar
150mmc/c, and shall have Ø12mm bar handle. Unit price
shall include excavation of the pit and cart away of the
excavated soil, all in accordance with the given detail
drawing.

No 8 49,263.74 394,109.92
12.2.10 Size:-(1000*750)mm ( Av.depth 1000 -1750mm )
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Construct Lead lined radioactive rectangular manhole
out of 250mmR.C concrete C-30 walls internal dimension
(1000*750)mm & average depth (1000-1750mm)on a
base of R.C.slab, size, 2100x1850x300mm, including
benching and bottom channeling with mass concrete.
Cover slab shall be 100mm thick R.C. concrete reinforced
with 12mm R.bar 110mm c/c and bottom Slab shall be
250mm thick walls are reinforced with 12mm R.bar
c/c180 mm in both ways. Provide 150mm granular
materials under the base slab, on a compacted earth.
manhole cover shall be reinforced with 10mm R.bar
150mmc/c and shall have Ø12mm bar handle Unit price
shall include excavation of the pit and cart away of the
excavated soil, all in accordance with the given detail
drawing.

No 14 107,810.45 1,509,346.30
12.2.11 Size:-(1200*750)mm ( Av.depth 1750 -2500mm )
Construct Lead lined radioactive rectangular manhole
out of 250mm R.C concrete C-30 walls internal dimension
(1200*750)mm & average depth (1750-2500mm) on a
base of R.C.slab, size,2300x2300x300mm, including
benching and bottom channeling with mass concrete.
Cover slab shall be 100mm thick R.C. concrete reinforced
with 12mm R.bar 110mm c/c and bottom Slab shall be
reinforced with 10mm reinforcement bar c/c 150mm, and
250mm thick walls are reinforced with 12mm R.bar
c/c180 mm in both ways. Provide 150mm granular
materials under the base slab, one compacted earth.
manhole cover shall be reinforced with 10mm R.bar
150mmc/c and shall have Ø12mm bar handle. Unit price
shall include excavation of the pit and cart away of the
excavated soil, all in accordance with the given detail
drawing.

No 6 171,038.83 1,026,232.98
12.2.12 Size:-(1400*1200)mm ( aboveAv.depth 2500mm )
Construct Lead lined radio active rectangular manhole
out of 250mm R.C concrete C-30 walls internal dimension
(1400*1200)mm & average depth (above2500mm) on a
base of R.C.slabsize,2300x2300x300mm including
benching and bottom channeling with mass concrete
Cover slab shall be 100mm.thick R.C. concrete reinforced
with 12mm R.bar 110mm c/c and bottom Slab shall be
reinforced with 10mm reinforcement bar c/c 150mm, and
250mm thick walls are reinforced with 12mm R.bar
c/c180 mmin both ways Provide 150mm granular
materials under the base slab, one compacted earth.
manhole cover shall be reinforced with 10mmR.bar
150mmc/c and shall have Ø12mm bar handle. Unit price
shall include excavation of the pit and cart away of the
excavated soil, all in accordance with the given detail
drawing.

No 2 267,592.93 535,185.86
RECTANGULAR MANHOLE
12.2.13 Size:-(600*600)mm( Av.depth 600 -1000mm )
Construct rectangular manhole out of 250mm R.C
concrete C-25 walls internal dimension (600*600)mm &
average depth (600-1000mm) on a base of R.C.slab,
size,1700x1700x300mm, including benching and bottom
channeling with mass concrete. Cover slab shall be
100mm thick R.C. concrete reinforced with 12mm R.bar
110mm c/c and bottom slab shall be reinforced with
10mm reinforcement bar c/c 150mm. and 250mm thick
walls are reinforced with 12mm R.bar c/c180mm in both
ways. Provide 150mm granular materials under the base
slab, on a compacted earth. manhole cover shall be
reinforced with 10mm R.bar 150mmc/c, and shall have
Ø12mm bar handle. Unit price shall include excavation of
the pit and cart away of the excavated soil, all in
accordance with the given detail drawing.

Nº 14 12,258.07 171,612.98
12.2.14 Size:-(1000*750)mm ( Av.depth 1000 -1750mm )
Construct rectangular manhole out of 250mmR.C
concrete C-30 walls internal dimension (1000*750)mm &
average depth (1000-1750mm)on a base of R.C.slab,
size, 2100x1850x300mm, including benching and bottom
channeling with mass concrete. Cover slab shall be
100mm thick R.C. concrete reinforced with 12mm R.bar
110mm c/c and bottom Slab shall be 250mm thick walls
are reinforced with 12mm R.bar c/c180 mm in both ways.
Provide 150mm granular materials under the base slab,
on a compacted earth. manhole cover shall be reinforced
with 10mm R.bar 150mmc/c and shall have Ø12mm bar
handle Unit price shall include excavation of the pit and
cart away of the excavated soil, all in accordance with
the given detail drawing.

Nº 21 18,115.82 380,432.22
12.2.15 Size:-(1200*750)mm ( Av.depth 1750 -2500mm )
Construct rectangular manhole out of 250mm R.C
concrete C-30 walls internal dimension (1200*750)mm &
average depth (1750-2500mm) on a base of R.C.slab,
size,2300x2300x300mm, including benching and bottom
channeling with mass concrete. Cover slab shall be
100mm thick R.C. concrete reinforced with 12mm R.bar
110mm c/c and bottom Slab shall be reinforced with
10mm reinforcement bar c/c 150mm, and 250mm thick
walls are reinforced with 12mm R.bar c/c180 mm in both
ways. Provide 150mm granular materials under the
base slab, one compacted earth. manhole cover shall be
reinforced with 10mm R.bar 150mmc/c and shall have
Ø12mm bar handle. Unit price shall include excavation of
the pit and cart away of the excavated soil, all in
accordance with the given detail drawing.

Nº 18 28,336.69 510,060.42
12.2.16 Size:-(1400*1200)mm ( aboveAv.depth 2500mm )
Construct rectangular manhole out of 250mm R.C
concrete C-30 walls internal dimension (1400*1200)mm &
average depth (above2500mm) on a base of
R.C.slabsize,2300x2300x300mm including benching and
bottom channeling with mass concrete Cover slab shall
be 100mm.thick R.C. concrete reinforced with 12mm
R.bar 110mm c/c and bottom Slab shall be reinforced
with 10mm reinforcement bar c/c 150mm, and 250mm
thick walls are reinforced with 12mm R.bar c/c180 mmin
both ways Provide 150mm granular materials under the
base slab, one compacted earth. manhole cover shall be
reinforced with 10mmR.bar 150mmc/c and shall have
Ø12mm bar handle. Unit price shall include excavation of
the pit and cart away of the excavated soil, all in
accordance with the given detail drawing.

Nº 21 38,342.10 805,184.10
STORM WATER DRAINAGE SYSTEM
12.2.18 Construct dia 400mm semi-circular drainage channel out
of concrete. Price shall include excavation of the
trench,cartaway,provision of 50mm thick sand bedding,
side support with masonry stone as requiered to make
the work complete, etc.
ml 154 409.35 63,039.90
12.2.17 Ditto item no 4.1 above but provided with Metal grill
removable cover at entrance to building. Use
L40*40*3mm for external and RHS 40*40*3mm for
internal part of grill. ml 146 1,055.51 154,104.46
PERFORATED PIPE
12.2.19 Supply, lay & connect 150mm diameter perforated
uPVC pipe (PN 6), minimum wall thickness 5.9mm
according to the detail drawing for ground water collection
according to the detail drawing for ground water collection
and drainage system complete with all the necessary
accessory the upvc pipes, accessories fittings and
welding shall comply the upvc pipes, accessories fittings
and welding shall comply with the requirement of BS-
4514 or DIN8062 or equivalent institution . Unit price shall
include excavation of treanch.and all the necessary
assistance to the installation works.

lm 137 276.19 37,838.03


FILTER MATERIAL
12.2.20 Aggregate

Supply and fill


aggregate(size 20-70mm)in layers according to the detail
drawing given. The materials shall be Washed and clear,
free of any dust, mud,sespended materials,etc not to
reduce the void area of the filter materials. m3 475 759.44 360,734.00
12.2.21 Redash

Supply and fill red ash in layers


according to the detail drawing given. The materials shall
be Washed and clear, free of any dust, mud,sespended
m3 76 302.33 22,977.08
materials,etc
GEOSYNTETIC MATERIAL
12.2.22 Apply Geosynthetic or woven SNW120 up to SNW 80
where shown on detail drawing unit include the necessary
assistance to the installation work Supply and Wrap a UV
stabilized, polypropylene, needle punched, woven,
Geotextile geosynthetic intended use for Filtration +
Separation + Drainage,inaccordance with the
m3 798 127.28 101,569.44
Sump
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
12.2.23 Construct Rectangular reinforced concrete
sump(chamber) for submersible electric driven wall /C-
30/.Reinforced concrete wall shall be reinforced by
dia.8mm and 6mm as per minimum ERA specification
requirement, internal diameter 1000mm and depth
1200mm well finished internally ,on a base dewatering
pump out of 100mm thick concrete of precast reinforced
concrete slab150mm thick and diameter of 1400mm.It
shall have precast R.C cover slab,dia.1100mm and
150mm thick reinforced with diameter 8mm
reinforcement bar c/c 140mm bothways.Provide 150mm
thick granular materials beneath the slab, on a
compacted earth all in accordance to the given detail
drawing. Provide hole on slab cover for delivery end pipe
and electrical cable of dewatering pump as per the given
detail drawing. Unit price shall include excavation of the
pit to a depth of 1200mm (max.) and cart away of the
excavated soil and installing dewatering pump on holding
damp.

Nº 2 9,570.65 19,141.30
12.2.24 Supply and install submersible electric driven motor pump
for Sub-surface drainage with the following characteristics
:

Rated Discharge (Q)=5


l/sec

Head in water meter =6-8 meter;

Delivery End Pipe Diameter


=50mm

Rated power = 2KW(single phase/Unit Nº 1 38,399.88 38,399.88


WATER TANKSACCESSORIES
WATER STORAGE SYSTEM
12.2.25 Roof Water Tank
Supply and connect 10m3 capacity fiber glass
water tank. The internal surface of the tank shall be
smooth and the external surface shall be with good
apperance. Complete with all necessary accessories and
connections such as inlet pipes , vent pipes with mesh
cover, vent caps, manhole, etc, all according to the detail
drawing. diameter
80mm outlet, diameter
50mm inlet, diameter 50mm
approved quality float valve, diameter 32mm
drainage outlet diameter 32mm over flow
diameter 110mm uPVC
vent pipe with cape on the top of the water tank.
Inspection manhole 600*600cm

Nº 2 4,000.00 8,000.00
12.2.33 PIONEER WATER TANK
Supply and fix 216m³ pioneer or equivalent water tank,
made of Zinkalume steel panels (Grade 300 To
AS1397), four layer aqua liner,complete with ring beam,
level indicatortruss foot, scour drain, anti-corrosion
anode, roof ventilator, sliding access, concrete apron for
ladder, grade 8.8 high strength bolts, internal and
external ladders,scour basin and all other necessary
accessories.Unit Price shall include all civil works & water
supply pipes, fitting and accessories, excavation and
compacting of sand and all necessary works there to.

Nº 1 2,448,407.14 2,448,407.14
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
PUMPS
12.2.34 Potable Water Pump
Electric driven Closed Couple Centrifugal pump for
potable and sanitary water supply complete with all
accessories ( one of which is standby )

Discharge ,
Q = 40m3/hr.;
Head,H = 40m

Suction end pipe size


=65mm

Delivery end pipe


size =50mm
Nº 2 159,900.72 319,801.44
12.2.38 Fire protection Pumping system
Supply,install,test & commission factory assembled fire
protection pumps set as per NFPA-20 requirements &
specification given below.Pump shall be factory tested &
performance data to be recorded & submitted to
demonstrate its compliance with the pump specification).
(CALPEDA or equivalent

General requirement

The system shall comprise 1- main


electrical pump, one diesel driven motor . The unit shall
be fitted with a jocky pump, with which the system
pressure level can be maintained without having to start
the main pump. Complete with all accessories including,
electric control board housed in a metal cabinet, timer for
pumps stop after 20 minutes, manifold, coupling, etc.
Main pump

The main pump shall be


fitted with all accessories including: pressure and vacuum
gauge in the Suction section, butter fly valves on the
suction and delivery sides , adjusted diaphragm, pressure
switch to indicate the pump is operating, non return valve,
pressure gauge in the delivery section, etc.
Jocky pump

Jocky pump shall be fitted with all


accessories including: ball valve in the Suction section,
non return valve and ball valve in the delivery section,
Pump for firefighting-

Discharge , Q =
20m3/hr.;
Necessary Accessories for pump

installation each feed main pump shall include:-

a)
pressure and vacuumed gauge in the suction section,

b) butterfly valve in the suction section,

c) pressure gauge both in the delivery and suction


section
d)
adjusted diaphragm

e) pressure switch

g)
butterfly valve in the delivery section,

h) manual test circuit with pressure switch, pressure


guage,non-return and ball valve
Set 1 952,839.55 952,839.55
I) cylindrical 20 liter(15 bar) tank
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
12.2.39 125m3 SEPTIC TANK
Construct septic tank from reinforced concrete wall ,
bottom and top slab and man hole cover. Complete all
works as per Sanitary Drawing technical specification
and Engineers approval. Price includes all civil and
Sanitary works.

Size 125m3 No 1.00 2,122,212.81 2,122,212.81


TOTAL CARRIED TO SUMMARY 23,056,815.98
Gondar University Summary Cancer Treatment Center

SUMMARY OF BILL OF QUANTITIES


MECHANICAL WORKS
A. AIR CONDITIONING AND VENTILATION
1 Chillers................................................................................... Birr 14,160,000.00
2 Air Handling Units (AHUs).............................................................
Birr 18,552,000.00
3 Fans ...................................................................................... Birr 7,216,287.50
4 Ducts..................................................................................... Birr -
5 Terminal Inlet/Outlets..................................................................
Birr -
6 VCDs...................................................................................... Birr -
7 Chilled Water Pipes....................................................................
Birr -
Total A .......................... Birr 39,928,287.50

B. MEDICAL GAS PIPELINE SYSTEM

1 Medical Gas Pipeline System.........................................................


Birr -

Total B .......................... Birr -

Total A+B .......................... Birr 39,928,287.50

VAT 15% .......................... Birr 5,989,243.13

GRAND SUMMARY .......................... Birr 45,917,530.63

Yohannes Abbay Consulting Architects And Engineers June, 2017 21


A. AIR CONDITIONING AND VENTILATION
1. CHILLERS
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Technical Requirement
Supply and install air cooled chiller as shown on
the drawing to be installed at ground and roof top.
It should conform to ASHRAE standard. It includes
scroll compressor, evaporator, condenser and fan,
refrigerant circuit, water side piping, hydronic
module (isolating valve, automatic air vent, water
tank, expansion vessel, safety valve, ball valve,
strainer, twin pump, balancing valve, LWT sensor,
RWT sensor, electronic flow control, piping and
piping ancillaries, gages etc) control panel, micro-
processor based control system and water
treatment plant (fiberglass tank, electric actuated
valve, centrifugal pump, check valve, isolating
valve, strainer.. etc) Type- Super-quiet version.
Chlorine free internationally acceptable
environmentally friendly refrigerant preferably - R-
407. Power supply - 380V/ 3Ph/ 50Hz. Chiller
Capacity as specified below. Price shall include all
accessories to make the system complete.

1
Air Cooled Chiller ACCH - 1 as per specification
above Capacity: 295 kW No. 1.00 3,900,000.00 3,900,000.00
2
Air Cooled Chiller ACCH - 2 as per specification
above Capacity: 110 kW No. 1.00 2,880,000.00 2,880,000.00
3
Air Cooled Chiller ACCH - 3 as per specification
above Capacity: 100 kW No. 1.00 2,880,000.00 2,880,000.00
4
Air Cooled Chiller ACCH - 4 as per specification
above Capacity: 120 kW No. 1.00 3,000,000.00 3,000,000.00
5

Air Cooled Chiller ACCH - 5 as per specification


above Capacity: 35 kW No. 1.00 1,500,000.00 1,500,000.00
TOTAL CARRIED TO SUMMARY 14,160,000.00
2. AIR HANDLING UNITS (AHU)
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Technical Requirement
Supply and install outdoor air handling unit (AHU)
as shown complete with casing, plastic cover,
sensor mixing-box, louver, damper and screen,
filters , fan, motor and drive chilled water cooling
coil, variable frequency drive for fan motors and
completely prewired control panel, pre-filter and
bag-filter, whether proof type and super-quiet
version. Roof crab shall be provided for chiller and
air handling units. AHU shall be acoustically lined.
Sound attenuators must be installed. Manometer
shall be installed at the filters compartment. Fire
damper shall be installed at air supply and return
duct. Power supply - 380V/ 3Ph/ 50Hz.

1 Air Handling Unit AHU - 1


Supply air quantity:
2920 lps @ optimum fan speed, Cooling Capacity:
95 kW at 35ºC ambient, Static pressure:70 mmH2O No. 1.00 2,040,000.00 2,040,000.00
2
Supply air quantity: 1965 lps @ optimum fan
speed, Cooling Capacity: 87 kW at 35ºC ambient,
Static pressure: 80 mmH2O No. 1.00 2,040,000.00 2,040,000.00
3
Supply air
quantity: 1290 lps @ optimum fan speed, Cooling
Capacity: 75 kW at 35ºC ambient, Static pressure:
40 mmH2O No. 1.00 1,800,000.00 1,800,000.00
4
Supply air quantity:
1710 lps @ optimum fan speed, Cooling Capacity:
30 kW at 35ºC ambient, Static pressure: 50
mmH2O No. 1.00 1,200,000.00 1,200,000.00
5
Supply air quantity: 1710 lps @ optimum fan
speed, Cooling Capacity: 48 kW at 35ºC ambient,
Static pressure: 60 mmH2O No. 1.00 1,440,000.00 1,440,000.00
6
Supply air quantity: 845 lps @ optimum fan
speed, Cooling Capacity: 20 kW at 35ºC ambient,
Static pressure: 45 mmH2O No. 1.00 1,104,000.00 1,104,000.00
7
Supply air quantity: 1645 lps @ optimum fan
speed, Cooling Capacity: 31 kW at 35ºC ambient,
Static pressure: 65 mmH2O No. 1.00 1,320,000.00 1,320,000.00
8
Supply air quantity: 2540 lps @
optimum fan speed, Cooling Capacity: 39 kW at
35ºC ambient, Static pressure: 110 mmH2O No. 1.00 1,440,000.00 1,440,000.00
9
Supply air quantity: 2180 lps @ optimum
fan speed, Cooling Capacity: 37 kW at 35ºC
ambient, Static pressure: 50 mmH2O No. 1.00 1,440,000.00 1,440,000.00
10
Supply air quantity: 2500 lps @
optimum fan speed, Cooling Capacity: 88 kW at
35ºC ambient, Static pressure: 110 mmH2O No. 1.00 2,520,000.00 2,520,000.00
11
Supply air quantity: 2320 lps @
optimum fan speed, Cooling Capacity: 16 kW at
35ºC ambient, Static pressure: 85 mmH2O No. 2.00 1,104,000.00 2,208,000.00
TOTAL CARRIED TO SUMMARY 18,552,000.00
3. FANS
STATTIC PRESSURE
ITEM No. EQUIPMENT PURPOSE LPS QTY
(mmH2O)

Technical Requirement
Shall meet ANSI Z9.5, ASHRAE 110, NAPA 45,
UL 705, ISO5801:2004, BS848: Part 2,1985 and
All Applicable Ventilation Standards. Shall comply
UL555C and UL263 Fire Rated options. Shall
include quick fitting swing locks that keep the fan in
place in suspended ceilings or plasterboard walls
and ceilings. Fan house shall be manufactured
from ABS plastic.

Motors:
Type: External rotor, squirrel cage induction motor

Electricity supply: 220-240 V, Single phase, 50 Hz

Bearings-sealed for life, ball type


Speed controllable
Motor protection IP44
Shall be flameproof motor
1 EAF G-1 Extraction 1680 86 1.00
2 EAF G-2 Extraction 1085 55 1.00
3 FAF G-1 Fresh Air Supply 1085 45 1.00
4 EAF G-3,G-4 and G-5 Extraction 420 15 3.00
5 EAF 1-1 Extraction 2340 65 1.00
6 EAF 1-2 Extraction 1455 30 1.00
7 FAF 1-1 Fresh Air Supply 2340 65 1.00
8 EAF 2-1 Extraction 1420 40 1.00
9 EAF 2-2 Extraction 1250 40 1.00
10 EAF 3-1 Extraction 1420 40 1.00
11 EAF 3-2 Extraction 1250 40 1.00
12 EAF 4-1 Extraction 1350 55 1.00
13 EAF 4-2 and 4-3 Extraction 1080 45 2.00
14 FAF 4-1 Fresh Air Supply 1350 55 1.00
15 FAF 4-2 and 4-3 Fresh Air Supply 1080 45 2.00
16 FAF 4-4 Fresh Air Supply 1332 75 1.00
17 FAF 4-5 Fresh Air Supply 792 35 1.00
18 EAF 5-1 Extraction 1350 55 1.00
19 EAF 5-2 and 5-3 Extraction 1080 45 2.00
20 FAF 5-1 Fresh Air Supply 1350 55 1.00
21 FAF 5-2 and 5-3 Fresh Air Supply 1080 45 2.00
22 FAF 5-4 Fresh Air Supply 1332 75 1.00
23 FAF 5-5 Fresh Air Supply 792 35 1.00
24 EAF 6-1 Extraction 4520 60 1.00
25 FAF 6-1 Fresh Air Supply 2725 50 1.00
26 EAF 6-2 Extraction 1500 45 1.00
27 Toilet exhaust fan 1 Extraction 450 25 1.00
28 Toilet exhaust fan 2 Extraction 200 10 1.00
29 Toilet exhaust fan 3 at each floor Extraction 480 25 7.00
30 Toilet exhaust fan 5 at each floor Extraction 360 20 7.00
31 Toilet exhaust fan 6 at each floor Extraction 780 20 7.00
32 Ceiling Mounted Fans CMF at first, fourth and fifth
floors Extraction 230 15 12.00
33 Wall Mounted Fans WMF at fourth and fifth floors
Extraction 75 25 54.00
TOTAL CARRIED TO SUMMARY
4. DUCTS
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Technical Requirement
Supply and install galvanized steel sheet for supply
and return ducts as shown on the drawing
complete with insulated duct, transition duct,
hangers and supports, silencers, vibration isolator,
damper, turning and splitter vanes at each fitting,
stiffener, flanges. Acoustic linear insulation shall be
installed at straight duct and elbow. Unit price shall
include vanes at tees and elbows, hanger, bends,
reducers, flange, sealant, flexible duct and other
accessories to make the system complete as per
ASHRAE and SMACNA standards.

Heat Insulation
For concealed duct
25 mm *48 kg/m3, k= 0.033 W/m K fiber glass
insulation, vapor barrier and adehesive tape
covering.
For exposed duct
50 mm*48 kg/m3, k = 0.033 W/m K fiber glass
insulation, vapor barrier and 0.4 mm aluminum
cladding and fostering with canvas
close and foster.
Acoustic Insulation
25 mm thick and 0.52 sound absorption co-
efficients at 250 Hz.
Duct thickness:
For duct cross sectional area ≤ 0.178 m2 is 0.6
mm
For duct cross sectional area between 0.178 m2
and 0.334 m2 is 0.8 mm
For duct cross sectional area ≥ 0.334 m2 is 1.0 mm

Ground Floor
1 LINAC AHU-1 Supply
1.1 700x500 lm 5 8,640.00 38,880.00
1.2 600x500 lm 10 8,640.00 86,400.00
1.3 600x300 lm 26 6,600.00 168,960.00
1.4 500x400 lm 5 6,600.00 30,690.00
1.5 300x300 lm 8 4,440.00 36,408.00
1.6 300x200 lm 35 6,240.00 215,904.00
2 LINAC AHU-1 Return -
2.1 900x500 lm 8 10,440.00 86,130.00
2.2 800x500 lm 5 9,600.00 50,880.00
2.3 700x500 lm 2 8,640.00 13,824.00
2.4 700x400 lm 3 8,424.04 26,956.93
2.5 600x300 lm 8 6,240.00 52,416.00
2.6 500x300 lm 2 6,000.00 9,600.00
2.7 400x300 lm 12 5,360.76 63,793.04
2.8 300x300 lm 7 4,440.00 31,968.00
3 BRACHY AHU-2 Supply
3.1 500x500 lm 4 7,658.22 27,186.68
3.2 500x400 lm 6 6,892.40 39,286.68
3.3 500x300 lm 2 6,126.58 13,478.48
3.4 400x300 lm 12 5,360.76 64,061.08
3.5 300x300 lm 16 4,594.93 74,897.36
3.6 300x200 lm 21 3,829.10 80,985.47
3.7 200x200 lm 14 3,063.29 42,426.57
3.8 200x150 lm 3 2,680.37 9,247.28
4 BRACHY AHU-2 Return
4.1 500x500 lm 6 7,658.22 47,098.05
4.2 500x400 lm 3 6,892.40 18,609.48
4.3 500x300 lm 3 6,126.58 18,379.74
4.4 400x300 lm 4 5,360.76 20,370.89
4.5 300x300 lm 8 4,508.78 35,393.90
4.6 300x200 lm 8
4.7 200x200 lm 12
5 BRACHY OR AHU-3 Supply
5.1 600x400 lm 9
5.2 300x200 lm 12
6 BRACHY OR AHU-3 Return
6.1 600x400 lm 3
6.2 500x400 lm 12
6.3 400x300 lm 2
6.4 300x300 lm 10
6.5 300x200 lm 3
6.6 200x200 lm 13
7 PET CT AHU-4 Supply
7.1 600x400 lm 4
7.2 500x400 lm 3
7.3 500x300 lm 4
7.4 300x300 lm 3
7.5 300x200 lm 11
7.6 200x200 lm 6
8 PET CT AHU-4 Supply
8.1 600x400 lm 6
8.2 500x300 lm 4
8.3 300x300 lm 4
8.4 200x200 lm 7
9 SPECT AHU-5 Supply
9.1 600x400 lm 6
9.2 500x400 lm 4
9.3 400x400 lm 3
9.4 300x300 lm 8
9.5 200x200 lm 19
10 SPCET AHU-5 Return
10.1 600x400 lm 12
10.2 400x400 lm 6
10.3 400x300 lm 1
10.4 300x300 lm 3
10.5 300x200 lm 17
10.6 200x200 lm 8
11 CT Simulator AHU-6 Supply
11.1 500x300 lm 7
11.2 400x300 lm 4
11.3 300x200 lm 5
11.4 200x200 lm 9
12 CT Simulator AHU-6 Return
12.1 400x300 lm 6
12.2 300x300 lm 2
12.3 300x200 lm 15
13 EAF 1
13.1 600x400 lm 10
13.2 500x400 lm 11
13.3 400x400 lm 7
13.4 400x300 lm 1
13.5 400x200 lm 1
13.6 300x300 lm 2
13.7 200x200 lm 12
13.8 200x150 lm 13
14 EAF 2
14.1 500x400 lm 8
14.2 400x400 lm 8
14.3 400x300 lm 6
14.4 300x300 lm 6
14.5 300x200 lm 9
15 EAF 3
15.1 300x300 lm 7
15.2 300x200 lm 4
16 EAF 4
16.1 300x300 lm 7
16.2 300x200 lm 4
16.3 200x200 lm 6
17 EAF 5
17.1 400x300 lm 2
17.2 300x300 lm 7
17.3 300x200 lm 5
17.4 200x200 lm 7
18 FAF 1
18.1 500x400 lm 5
18.2 400x400 lm 6
18.3 400x300 lm 6
18.4 300x300 lm 8
18.5 300x200 lm 19
19 Toilet fan 1
19.1 300x300 lm 1
19.2 300x200 lm 3
19.3 200x200 lm 5
19.4 200x150 lm 6
20 Toilet fan 2
20.1 300x200 lm 1
20.2 200x200 lm 3
21 Toilet fan 3 (total for all floors)
21.1 300x300 lm 48
21.2 300x200 lm 33
21.3 200x200 lm 79
22 Toilet fan 5 (total for all floors)
22.1 300x300 lm 18
22.2 200x200 lm 69
23 Toilet fan 6 (total for all floors)
23.1 800x750 lm 5
23.2 800x650 lm 5
23.3 800x600 lm 5
23.4 700x600 lm 5
23.5 600x500 lm 5
23.6 500x500 lm 5
23.7 500x300 lm 42
23.8 300x300 lm 69
23.9 300x200 lm 26
24 200x200 lm 35
24.1 200x150 lm 78
24 Ceiling mounted fans CMF 1 and 2
24.1 300x200 lm 34
24.2 200x200 lm 5
First Floor
25.1 EAF 1-1
25.2 700x450 lm 12
25.3 600x450 lm 4
25.4 500x400 lm 5
25.5 400x400 lm 5
25.6 400x300 lm 4
25.7 300x250 lm 3
26 EAF 1-2
26.1 600x400 lm 2
26.2 500x400 lm 4
26.3 400x400 lm 4
26.4 300x300 lm 4
26.5 300x200 lm 2
27 FAF 1-1
27.1 700x450 lm 12
27.2 600x450 lm 4
27.3 500x400 lm 5
27.4 400x400 lm 5
27.5 400x300 lm 4
27.6 300x250 lm 3
28 Ceiling mounted fan CMF 1-1
28.1 300x200 lm 17
28.2 200x200 lm 1
29 Ceiling mounted fan CMF 1-2
29.1 300x200 lm 10
29.2 200x200 lm 1
29.3 200x150 lm 1
Second Floor
30 OR 1 AHU-7 Supply
30.1 600x400 lm 39
31 OR 1 AHU-7 Return
31.1 600x500 lm 38
31.2 500x400 lm 2
31.3 400x300 lm 23
31.4 300x300 lm 4
31.5 300x200 lm 2
31.6 200x200 lm 3
32 OR 2 AHU-8 Supply
32.1 600x500 lm 71
33 OR 2 AHU-8 Return
33.1 700x500 lm 54
33.2 500x500 lm 2
33.3 400x400 lm 19
33.4 400x300 lm 3
33.5 300x300 lm 5
33.6 300x200 lm 7
33.7 200x200 lm 3
34 OR 3 AHU-9 Supply
34.1 600x500 lm 58
35 OR 3 AHU-9 Return
35.1 600x500 lm 52
35.2 400x400 lm 19
35.3 400x300 lm 2
35.4 300x200 lm 9
36 EAF 2-1
36.1 600x400 lm 7
36.2 500x350 lm 3
36.3 400x300 lm 4
36.4 300x300 lm 3
37 EAF 2-2
37.1 500x400 lm 6
37.2 400x400 lm 3
37.3 400x300 lm 4
37.4 300x300 lm 3
Third Floor
38 ICU AHU-ICU Supply
38.1 700x500 lm 40
38.2 500x400 lm 14
38.3 400x400 lm 10
38.4 300x300 lm 11
39 ICU AHU-ICU Return
39.1 700x500 lm 46
39.2 600x500 lm 4
39.3 600x400 lm 3
39.4 400x300 lm 10
40 EAF 3-1
40.1 600x400 lm 7
40.2 500x350 lm 3
40.3 400x300 lm 4
40.4 300x300 lm 3
41 EAF 3-2
41.1 500x400 lm 6
41.2 400x400 lm 3
41.3 400x300 lm 4
41.4 300x300 lm 3
Fourth Floor
42 EAF 4-1
42.1 500x400 lm 14
42.2 500x300 lm 4
42.3 400x300 lm 4
42.4 300x200 lm 4
43 EAF 4-2
43.1 500x400 lm 11
43.2 500x300 lm 4
43.3 400x300 lm 2
43.4 300x200 lm 4
44 EAF 4-3
44.1 500x400 lm 10
44.2 500x300 lm 4
44.3 400x300 lm 4
44.4 300x200 lm 4
45 FAF 4-1
45.1 500x400 lm 14
45.2 500x300 lm 4
45.3 400x300 lm 4
45.4 300x200 lm 4
46 FAF 4-2
46.1 500x400 lm 11
46.2 500x300 lm 4
46.3 400x300 lm 2
46.4 300x200 lm 4
47 FAF 4-3
47.1 500x400 lm 10
47.2 500x300 lm 4
47.3 400x300 lm 4
47.4 300x200 lm 4
48 FAF 4-4
48.1 600x350 lm 6
48.2 500x350 lm 8
48.3 400x350 lm 4
48.4 400x300 lm 4
48.5 300x300 lm 4
48.6 300x200 lm 5
49 FAF 4-5
49.1 500x300 lm 7
49.2 400x300 lm 4
49.3 300x300 lm 4
49.4 200x200 lm 4
50 CMF 4-1
50.1 300x200 lm 21
50.2 200x200 lm 2
Fifth Floor
51 EAF 5-1
51.1 500x400 lm 14
51.2 500x300 lm 4
51.3 400x300 lm 4
51.4 300x200 lm 4
52 EAF 5-2
52.1 500x400 lm 11
52.2 500x300 lm 4
52.3 400x300 lm 2
52.4 300x200 lm 4
53 EAF 5-3
53.1 500x400 lm 10
53.2 500x300 lm 4
53.3 400x300 lm 4
53.4 300x200 lm 4
54 FAF 5-1
54.1 500x400 lm 14
54.2 500x300 lm 4
54.3 400x300 lm 4
54.4 300x200 lm 4
55 FAF 5-2
55.1 500x400 lm 11
55.2 500x300 lm 4
55.3 400x300 lm 2
55.4 300x200 lm 4
56 FAF 5-3
56.1 500x400 lm 10
56.2 500x300 lm 4
56.3 400x300 lm 4
56.4 300x200 lm 4
57 FAF 5-4
57.1 600x350 lm 6
57.2 500x350 lm 8
57.3 400x350 lm 4
57.4 400x300 lm 4
57.5 300x300 lm 4
57.6 300x200 lm 5
58 FAF 5-5
58.1 500x300 lm 7
58.2 400x300 lm 4
58.3 300x300 lm 4
58.4 200x200 lm 4
59 CMF 5-1
59.1 300x200 lm 21
59.2 200x200 lm 2
Sixth Floor
60 BMT AHU-BMT-1 Supply
60.1 600x500 lm 10
60.2 500x500 lm 3
60.3 400x400 lm 7
60.4 400x300 lm 3
61 BMT AHU-BMT-1 Return
61.1 600x500 lm 7
61.2 500x500 lm 8
61.3 500x400 lm 3
61.4 400x300 lm 8
61.5 200x200 lm 13
61.6 200x150 lm 12
62 BMT AHU-BMT-2 Supply
62.1 500x500 lm 12
62.2 400x400 lm 7
62.3 400x300 lm 3
63 BMT AHU-BMT-2 Return
63.1 600x500 lm 7
63.2 500x500 lm 8
63.3 500x400 lm 3
63.4 400x300 lm 8
63.5 200x200 lm 13
63.6 200x150 lm 12
64 EAF 6-1
64.1 800x700 lm 6
64.2 700x400 lm 3
64.3 600x500 lm 2
64.4 600x400 lm 10
64.5 500x400 lm 10
64.6 400x300 lm 10
65 EAF 6-2
65.1 600x400 lm 8
65.2 400x400 lm 3
65.3 300x300 lm 3
65.4 300x200 lm 11
66 FAF 6-1
66.1 700x500 lm 6
66.2 500x500 lm 3
66.3 500x400 lm 7
66.4 400x400 lm 10
66.5 400x300 lm 5
66.6 300x300 lm 5
66.7 300x250 lm 5
TOTAL CARRIED TO SUMMARY
5. TERMINAL INLET OUTLET
Technical Requirement
The contractor shall ensure that the diffusers and grilles offered are of required capacity, throw and terminal velocity. All diffusers, grilles and registers shal
coated. All diffusers, registers and grilles shall be selected to account for the noise levels as specified for various areas.
ITEM No. Location Purpose Type Designation LPS

235
270
Supply Air
SAD 185
Diffuser
255
Supply 220
Laminar
flow LFP 855
pannel
Fresh Air
FAD 275
Diffuser
Fresh Air 80
1 Linac and Bracky Inlet Louver FAL
255
235
Return Air 185
Return RAD
Diffuser 340
220
270
275
Exhaust 100
Extraction EAD
Air Diffuser 170
80
180
Supply Air
Supply SAD 245
Diffuser
2 AHU-3 220
Return Air 180
Return RAD
Diffuser 585
Supply Air 180
Supply SAD
Diffuser 135
3 AHU-4
Return Air 240
Return RAD
Diffuser 135
Supply Air 265
Supply SAD
Diffuser 145
4 AHU-5
Return Air 235
Return RAD
Diffuser 200

Exhast Air
Extraction EAD 210
Diffuser
5 EAF-3
Fresh Air
Supply FAL 210
Louver

Exhast Air
EAD 120
Diffuser
6 EAF-4 Extraction

Fresh Air 120


FAL
Louver 100

135
Exhast Air
EAD
Diffuser 195
7 EAF-5 Extraction
245
Fresh Air
FAL 200
Louver
180
Fressh Air 270
8 FAF B3 Supply FAD
Diffuser 145
135
Fressh Air 270
9 FAF B4 Supply FAD
Diffuser 385

Exhast Air
10 EAF 1-1 Extraction EAD 270
Diffuser

220
Exhast Air
11 EAF 1-2 Extraction EAD 375
Diffuser
320

Fresh Air
12 FAF 1-1 Supply FAD 270
Diffuser

Exhast Air
13 Toilet Fan 3 Extraction EAD 60
Diffuser

Exhast Air
14 Toilet Fan 5 Extraction EAD 90
Diffuser

Exhast Air
15 Toilet Fan 6 Extraction EAD 90
Diffuser
Laminar 1645
Supply Flow Laminar Flow Pannel
Pannel 1960
685
16 OR-1-2-3 270
Return Air
Return RAD 120
Diffuser
180
820

Exhast Air
EAD 355
Diffuser
17 EAF 2-1 Extraction
Fresh Air
FAL 355
Louver

Exhast Air
EAD 355
Diffuser

Exhast Air
EAD 270
18 EAF 2-2 Extraction Diffuser

Fresh Air
FAL 355
Louver
Fresh Air
FAL 270
Louver

Supply Air
Supply SAD 420
Diffuser
19 ICU
Return Air
Return RAD 625
Diffuser
Exhast Air
EAD 355
Diffuser
20 EAF 3-1 Extraction
Fresh Air
FAL 355
Louver

Exhast Air
EAD 355
Diffuser

Exhast Air
EAD 270
21 EAF 3-2 Extraction Diffuser

Fresh Air
FAL 355
Louver
Fresh Air
FAL 270
Louver

Exhast Air
EAF 4-1 Extraction EAD 270
Diffuser
22

Exhast Air
EAF 4-2 Extraction EAD 270
Diffuser
23

Exhast Air
EAF 4-3 Extraction EAD 270
Diffuser
24
Fresh Air
FAF 4-1 Supply FAD 270
25 Diffuser
Fresh Air
FAF 4-2 Supply FAD 270
26 Diffuser
Fresh Air
FAF 4-3 Supply FAD 270
27 Diffuser
255
FAD
Fresh Air 180
FAF 4-4 Supply
Diffuser 255
FAL
28 180
255
FAD
Fresh Air 180
FAF 4-5 Supply
Diffuser 255
FAL
29 180
Wall
30 4th Extraction mounted WMF 75
fan
Ceiling
CMF 4-1 Extraction mounted CMF 115
31 fan

Exhast Air
32 EAF 5-1 Extraction EAD 270
Diffuser

Exhast Air
33 EAF 5-2 Extraction EAD 270
Diffuser

Exhast Air
34 EAF 5-3 Extraction EAD 270
Diffuser

Fresh Air
35 FAF 5-1 Supply FAD 270
Diffuser
Fresh Air
FAF 5-2 Supply FAD 270
36 Diffuser
Fresh Air
FAF 5-3 Supply FAD 270
37 Diffuser
255
FAD
Fresh Air 180
38 FAF 5-4 Supply
Diffuser 255
FAL
180
255
FAD
Fresh Air
39 FAF 5-5 Supply
Diffuser
FAD
Fresh Air 180
39 FAF 5-5 Supply
Diffuser 255
FAL
180
255
FAD
Fresh Air 180
40 FAF 5-6 Supply
Diffuser 255
FAL
180
Wall
41 5th Extraction mounted WMF 75
fan
Ceiling
CMF 5-1 Extraction mounted CMF 115
42 fan

Supply Air
Diffuser
Supply SAD-H 520
with Hepa
filter
43 BMT
450
Return Air
Return RAD
Diffuser
43 BMT

Return Air
Return RAD 100
Diffuser
80

Exhast Air
44 EAF 6-1 Extraction EAD 565
Diffuser

Exhast Air
EAD 250
Diffuser
45 EAF 6-2 Extraction
Fresh Air
FAL 500
Louver
445
300
Fresh Air
FAD 350
Diffuser
240
315
46 FAF 6-1 Supply
445
300
Exhaust
EAL 350
Air Louver
240
315
TOTAL CARRIED TO SUMMARY
6. VOLUME CONTROL DAMPER
Technical Requirement
Shall be rectangular volume control damper (VCD) with multiple blade type. The blades shall be of aluminum aerofoil double skin type having a size specifi
recommended construction requirements. The volume control dampers shall be of opposed blade type for throttling and parallel acting blades for isolation.
Ratings:
Pressure up to 1000 Pa
Velocity up to 15.2 m/s
Temperature range from 20oC to 80oC
Features:
Casing: 16 Gage Galvanized Steel.
Blades: Airfoil Double Skin 22 Gage Galvanized Steel.
Linkage: Gage Galvanized Steel (Alternative Plastic Gear).
Axles: Zinc Plated Square Mild Steel, 12x12mm.
Bearings: Synthetic (acetal) Sleeve Type.
Quadrant: Galvanized Hand Locking Quadrant.
Static pressure
Item no. Location Duct Size (mmxmm) LPS
(mm-H2O)
0.6 0.40 1420 14.5
0.3 0.30 270 3.7
1 Bracky OR
0.3 0.20 210 4.0
0.3 0.20 270 4.4
0.6 0.3 1020 13.3
2 LINAC
0.3 0.2 255 4.6
0.2 0.2 145 2.7
3 CT- Simulator 0.3 0.3 470 3.1
0.4 0.3 670 11.1
0.6 0.4 1710 18.1
0.3 0.2 220 1.8
4 PET-CT
0.3 0.2 245 3.3
0.2 0.2 180 3.4
0.2 0.2 180 3.6
0.2 0.3 315 2.2
0.6 0.4 1710 18.5
5 SPET
0.3 0.2 240 4.3
0.3 0.3 480 8.9
0.2 0.2 135 3.3
0.6 0.4 1420 14.5
0.3 0.3 270 3.7
6 Bracky
0.3 0.2 210 4.0
0.3 0.2 270 4.4
0.2 0.2 170 3.1
7 EAF 1 0.4 0.2 320 3.4
0.2 0.15 80 2.5
8 EAF 2 0.3 0.2 205 3.2
9 EAF 3 0.3 0.3 420 9.0
0.3 0.3 480 9.4
10 EAF 4
0.2 0.2 120 4.2
0.4 0.3 710 11.5
11 EAF 5
0.3 0.2 245 3.0
0.3 0.2 205 3.2
12 FAF 1
0.3 0.2 275 4.5
0.2 0.2 150 3.4
13 Toilet fan 1
0.3 0.3 450 8.9
14 Toilet fan 2 0.3 0.2 200 6.1
15 Toilet fan 3 0.3 0.2 240 2.9
0.2 0.2 180 4.8
16 Toilet fan 5
0.3 0.3 360 8.1
0.20 0.15 60 1.8
0.2 0.2 120 1.6
17 Toilet fan 6
0.5 0.3 780 12.3
0.3 0.2 300 3.9
18 EAF1-1, FAF 1-1 0.7 0.45 2340 13.6
19 EAF 1-2 0.6 0.4 1455 10.3
20 EAF 2-1,2 EAF 3-1,2 0.60 0.4 1320 16.6
0.60 0.4 1645 20.1
0.4 0.3 685 8.4
0.6 0.5 2000 8.7
0.6 0.5 1960 21.7
21 OR
0.6 0.5 2240 22.7
0.4 0.3 540 7.5
0.3 0.3 360 5.0
0.3 0.2 270 4.2
0.7 0.4 2520 23.8
22 ICU 0.5 0.4 1260 9.5
0.4 0.3 625 7.8
23 4th & 5th ALL EAF and FAF 0.5 0.4 1350 10.5
0.6 0.5 2320 18.7
24 BMT 0.2 0.2 180 5.2
0.2 0.15 100 3.5
0.8 0.7 4520 29.8
25 EAF 6-1
0.6 0.5 2260 10.7
0.6 0.4 1500 17.2
26 EAF 6-2
0.3 0.2 250 5.1
0.7 0.5 2725 23.1
27 FAF 6-1
0.5 0.5 1540 10.6
TOTAL CARRIED TO SUMMARY
7. CHILLED WATER PIPES
Technical Requirement
Supply and install GS pipe with schedule number 40 as shown on the drawing. Price shall include hangers, shutt- off valves, flexible
connection, gages, insulation, regulating valves, non return valves, strainer, vent, automatic control valves fittings (elbow, fees, yees)
Heat insulation type- closed cell rubber tube insulation.
For concealed piping
- 25 mm x 48 kg/m3 insulation, vapour barrier and adhesive tape covering
For exposed piping
- 50 mm x 48kg/m3 insulation , vapour barrier and 0.4mm aluminum cladding.
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
1 ACCH-1 at Ground
1.1 Main branch m 16
1.2 Sub branch to AHU 2 and 3 m 10
1.3 Branch to AHU 1 m 60
1.4 Branch to AHU 2 m 16
1.5 Branch to AHU 3 m 16
2 ACCH-2 at bunker roof top
2.1 Main branch m 6
2.2 Sub branch to AHU 4 and 5 m 16
2.3 Branch to AHU 4 m 20
2.4 Branch to AHU 5 m 90
2.5 Branch to AHU 6 m 100
3 ACCH-3 at roof top
3.1 Main branch m 10
3.2 Sub branch to AHU 7 and 8 m 10
3.3 Branch to AHU 7 m 10
3.4 Branch to AHU 8 m 60
3.5 Branch to AHU 9 m 40
4 ACCH-4 at roof top
4.1 Main branch to AHU-ICU m 10
5 ACCH-5 at roof top
5.1 Main branch m 10
5.2 Branch to AHU-BMT 1 m 30
5.3 Branch to AHU-BMT 2 m 30
TOTAL CARRIED TO SUMMARY
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE

MEDICAL GAS PIPELINE SYSTEM


ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
Scope of Work
The scope of work shall cover all distribution
pipings, fiitings and terminal units for oxygen,
medical air and vacuum system. The work shall
include supply, installation and commissioning and
satisfactory demonstration of MGPS for designed
pressure and flow rates at the terminal units of the
required gases in each of the hospital units
described.

Technical Requirement: Pipe Material, Joining


and Supports
Material for pipes should be manufactured from
phosphorus deoxidised, non-arsenical copper to
BS EN 1412:1996 grade CW024A (Cu-DHP) in
metric outside diameters and to:
• BS EN 13348:2001 – R250 (half hard) for sizes
up to 54 mm; or
• BS EN 13348:2001 – R220 (annealed) for larger
sizes.
Except for mechanical joints, only copper-to-copper
joints will be permitted on site, made with brazing
filler rods that can be used without flux.

When brazing copper-to-copper joints: The brazed


joints should be made using a silver-copper-
phosphorus brazing alloy CP104 to BS EN ISO
17672: 2010. No flux should be used;
The pipeline should be adequately supported at
sufficient intervals in accordance with following
spacing to prevent sagging or distortion.
Pipeline outside diameter (mm)
Spacing (m)
Up to 15
1.5
22-28
2
35-54
2.5
>54
3
Technical Requirement: Terminal Units, AVSU
and Alarm Panels
All terminal units should conform to BS EN ISO
9170-1: 2008. Terminal units intended for wall
mounting where directly connected equipment
such as flow meters are to be used must include a
non-swivel device. Dimensions of probes are given
in BS5682: 1998. It is essential that probes be
machined from stainless steel. When installed in
pendants or similar, terminal units should be of a
type
All suitable
valves for mounting
should be of the within the type,
lever-ball specified
having
fitting. O-ring seal connections which open and
flanged
close with a 90º rotation: the handle should be in
line with the pipeline when open. Pressure
regulators and pressure regulators with flow-
metering devices confirm BS EN ISO 10524-1:
2006

All AVSUs should be labelled to identify the


individual rooms, sets of terminal units, etc.
controlled. They should be provided with flow
direction arrows. All AVSUs should be labelled to
identify the individual rooms, sets of terminal units
etc controlled
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
LVAs should be provided as follows:
a. at the connection of the pipeline to any source of
supply;
b. at the emergency inlet port (that is, it forms the
emergency inlet point);
c. at the pipeline entry to a building;
d. at the pipeline exit from a building;
e. at the connection of branches to the main
pipeline run;
f. at the connection to risers;
g. at branches from risers to serve a number of
similar departments;
h. upstream, downstream and in the branch
connection to a ring-main.

The placing of local alarm indicators should be


such that they are readily visible by staff; notices,
partitioning, screens etc should not obscure them.
A flashing red visual indicator and an audible
signal should operate on all panels when any of
the following conditions occur:
a. line fault from the initiating device;
b. communication fault or other wiring fault;
c. mains power failure.

Technical Requirement: Accessories


All accessoreies to make the MGPS complete that
includes any electro-mechanical units shall be
included by the contractor.
1 Medical Gas Pipe
1.1 Outside Diameter 12 mm meter 1,725.00
1.2 Outside Diameter 15 mm meter 1,375.00
1.3 Outside Diameter 22 mm meter 1,120.00
1.4 Outside Diameter 28 mm meter 395.00
1.5 Outside Diameter 35 mm meter 75.00
1.6 Outside Diameter 42 mm meter 75.00
1.7 Outside Diameter 76 mm meter 50.00
2 Bed Head Units for Operating Rooms

Dual Mount Dual Arm


Pendant

Each unit
consisting of:
2 - Medical Vacuum Outlets
2 - Medical Oxygen Outlets
2 - Medical Air Outlets
4 - Universal Electrical Receptacles
2 - Patient Light
1 - Oxygen Flow meter w/humidifier
1 - Medical Air Flow meter
1 - Vacuum Canister w/hosing
1 - Vacuum Regulator
1 - Over Flow Safety Trap
1 - Name Tag Holder Set 4.00
1 - IV Hook
ITEM No. DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
3 Bed Head Units for ICUs

Dual Wall Mounted

Each unit
consisting of:
4 - Medical Vacuum Outlets
4 - Medical Oxygen Outlets
4 - Medical Air Outlets
4 - Universal Electrical Receptacles
2 - Patient Light
1 - Oxygen Flow meter w/Humidifier
1 - Medical Air Flow meter
1 - Vacuum Canister w/Hosing
1 - Vacuum Regulator
1 - Over Flow Safety Trap
1 - Name Tag Holder Set 23.00
1 - IVHead
4 Bed HookUnits for in-patient wards and
examination rooms Single Wall Mounted

Each unit consisting of:


1 - Medical Vacuum Outlets
1 - Medical Oxygen Outlets
1 - Medical Air Outlets
2 - Universal Electrical Receptacles
1 - Patient Light
1 - Oxygen Flow meter w/humidifier
1 - Medical Air Flow meter
1 - Vacuum Canister w/hosing
1 - Vacuum Regulator
1 - Over Flow Safety Trap
1 - Name Tag Holder
1 - IV Hook Set 185.00
51 - Blood
Area Pressure
Valve Service Monitor
Unit AVSU with
alarm panel No. 10.00
6 Area Valve Service Unit AVSU
without alarm No. 4.00
7 Alarm panel only (for Nuclear Medicine rooms) No. 9.00
TOTAL CARRIED TO SUMMARY
3. FANS
TOTAL
UNIT PRICE
PRICE

108,000.00 108,000.00
96,000.00 96,000.00
96,000.00 96,000.00
57,216.00 171,648.00
138,660.17 138,660.17
111,167.62 111,167.62
138,171.37 138,171.37
111,167.62 111,167.62
98,400.00 98,400.00
98,400.00 98,400.00
98,400.00 98,400.00
98,400.00 98,400.00
98,400.00 196,800.00
10,012.07 10,012.07
98,400.00 196,800.00
109,747.16 109,747.16
84,784.63 84,784.63
98,400.00 98,400.00
98,400.00 196,800.00
104,012.08 104,012.08
99,024.84 198,049.68
109,747.16 109,747.16
84,784.63 84,784.63
322,609.26 322,609.26
251,304.10 251,304.10
111,168.11 111,168.11
76,301.51 76,301.51
27,900.54 27,900.54
76,301.51 534,110.57
57,216.31 400,514.17
84,784.63 593,492.41

37,331.93 447,983.16

31,417.62 1,696,551.48
7,216,287.50
5. TERMINAL INLET OUTLET

capacity, throw and terminal velocity. All diffusers, grilles and registers shall be of extruded aluminum construction, and epoxy powder
ise levels as specified for various areas.
Static
pressure Velocity QTY Unit Price
(mm-H2O)
3.3 2.5 6
3.8 4.0 1
3.1 2.9 3
3.4 3.5 8
3.3 3 2

5.3 12.0 1

3.5 2.0 5

4
3.4 2.8 2
3.3 3.0 3
3.2 1.6 3
3.7 3.6 6
3.3 3.0 4
3.5 3.0 4
3.5 2.9 5
2.8 2.4 2
3.1 2.5 14
2.6 2.0 4
3.1 2.8 2
3.4 2.8 4
3.3 1.5 1
3.1 2.6 3
3.8 3.2 2
3.1 3.1 8
2.9 2.7 2
3.4 3.6 6
2.9 2.7 2
3.5 3.8 4
2.9 2.1 1
3.2 2.8 2
3.2 2.6 1

3.2 2.6 2

2
2.0 2.8 1
8.0 3.7 1
3.0 3.4 1
4.0 2.8 1
2
1
5.0 2.9 1
3.0 3.5 1
10.0 4.0 1
3.0 3.4 1

1
2.8 3.1 2
3.8 3.5 1
2.6 3.0 1
4.6 2.9 1
6.5 3.5 5
4.4 3.8 2
4.5 3.5 1
5.4 4.2 1
5.2 4.8 1
8.5 5.3 1
7.0 5.7 1
4.6 5.9 1
4.8 6.0 1
3.5 3.9 2
4.4 4.6 1
3.6 5.0 2
4.5 3.5 1
5.4 4.2 1
5.2 4.8 1
8.5 5.3 1
7.0 5.7 1
4.6 5.9 1
4.8 6.0 1

16
1.8 3.3

4
1.6 2.7

91
1.4 2.4
15.6 5.5 1
15.6 5.8 2
3.2 4.4 2
6.7 4.3 4
3.7 2.8 6
4.2 3.3 3
9.8 4.6 4

4
3.8 3.7
4
3.8 3.7

2
3.8 3.7

2
9.4 5.2
2
3.8 3.7
2
9.4 5.2

5.8 3.9 6

5.5 3.9 3
4
3.8 3.7
4
3.8 3.7

2
3.8 3.7

2
9.4 5.2
2
3.8 3.7
2
9.4 5.2

5
5.5 3.5

4
5.5 3.5

4
5.5 3.5
5
5.5 3.5
4
5.5 3.5
4
5.5 3.5
9.0 4.6 1
4.2 3.1 6
9.0 4.6 1
4.2 3.1 6
9.0 4.6 1
4.2 3.1 3
9.0 4.6 1
4.2 3.1 3

28
5.0

2
5.0

5
5.5 3.5

4
5.5 3.5

4
5.5 3.5
5
5.5 3.5
4
5.5 3.5
4
5.5 3.5
9.0 4.6 1
4.2 3.1 6
9.0 4.6 1
4.2 3.1 6
9.0 4.6 1
4.2 3.1 3
9.0 4.6 1
4.2 3.1 3
9.0 4.6 1
4.2 3.1 4
9.0 4.6 1
4.2 3.1 4

28
5.0

2
5.0

4.1 4.2 8

9.6 4.2 8
3.5 2.6 8
7.8 3.7 8

8
8.0 4.2

6
5.1 3.4
3
5.1 4.1
3.9 4.7 2
4.4 5.1 1
10.6 5.4 1
7.7 5.1 1
6.0 4.3 3
3.9 4.7 2
4.4 5.1 1
10.6 5.4 1
7.7 5.1 1
6.0 4.3 3
TOTAL CARRIED TO SUMMARY
OLUME CONTROL DAMPER

e blades shall be of aluminum aerofoil double skin type having a size specified on the drawing. Shall meet SMACNA
of opposed blade type for throttling and parallel acting blades for isolation. Shall be made of out of extruded

Unit
Velocity QTY Total Price
Price
5.3 1
3.5 2
3.3 1
3.5 1
4.9 4
3.4 4
2.9 4
4.0 1
4.4 1
5.6 2
3.3 1
3.4 2
3.1 2
3.1 6
3.6 2
5.6 2
3.4 2
4.0 2
2.9 2
5.3 1
3.5 2
3.3 1
3.5 1
3.1 4
3.6 1
2.6 2
3.2 1
3.9 1
4.0 1
2.8 1
4.5 1
3.4 1
3.2 3
3.5 1
3.0 1
3.9 1
3.2 1
3.3 4
3.1 7
3.7 7
2.4 28
2.8 14
4.6 7
3.6 14
6.0 2
5.3 1
5.3 4
5.5 1
4.4 2
5.8 1
5.8 2
5.9 2
4.1 1
3.7 2
3.3 2
6.1 1
5.1 1
3.9 4
5.3 17
6.0 4
3.1 8
2.6 8
7.2 1
6.0 2
5.4 1
3.4 1
6.3 1
5.4 2
OTAL CARRIED TO SUMMARY
Gondar University Specification and BOQ Treatment Plant

SUMMARY OF BILL OF QUANTITIES


TREATMENT PLANT
A-CIVIL WORKS

1 Excavation and Earth Work................................................Birr -


2 Concrete Work.................................................................. Birr -
3 Plastering & finishing Work..................................................
Birr -
4 Sanitary instalation…………………………………….. Birr -
TOTAL A........................ Birr -

B. MEDICAL WASTE WATER TREATMENT PLANT

1 Medical Waste Water Treatment Plant......................................


Birr -

Total B ..........................
Birr -
Total A + B ............................
Birr -
VAT 15% ..........................
Birr -
GRAND SUMMARY ..........................
Birr -

Yohannes Abbay Consulting Architects and Engineers June, 2017 1


ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
No.
A.TREATMENT PLANT
1. EXCAVATION & EARTH WORK
1.01 Site clearing to remove the top soil to an average depth
of 20 cm for ordinary soil m2 722.68
1.02 Bulk excavation to reduce level from NGL to a depth
not exceeding 1500mm. m3 636.74
1.03 Ditto as item No.1.02 but over 1500mm not exceeding
3000mm. m3 141.67
1.04 Ditto as item No.1.03 but over 3000mm not exceeding
4500mm. m3 37.19
1.05 Supply and fill aggregate(size 20-70mm)in layers
according to the detail drawing given. The materials
shall be Washed and clear,free of any dust,
mud,sespended materials,etc not to reduce the void
area of the filter materials.
m3 123.47
1.06 Fill under hard core with imported selected material
from quarry waste well rolled and compacted in layers
not exceeding 250 mm thick. m3 495.07
1.07 Cart away surplus excavated material and dispose at a
distance not exceeding 10km.from site as per the
Engineers Direction. m3 960.14
1.08 25cm thick hard basaltic or equivalent stone hardcore
well rolled, consolidated and blinded with crushed
stone. m2 618.84
TOTAL CARRIED TO SUMMARY
2.CONCRETE WORKS
2.01 50mm thick lean concrete quality C-5, with minimum
cement content of 150kg of cement /m3 concrete.

a) Under Ground Floor Slab m2 618.84


b) Under Pad m2 118.65
2.02 Reinforced concrete quality C-25,360kg of cement/ m3
filled into form work and vibrated around rod
reinforcement.(Reinforcement bar and formwork
measured separately)
a) In Tanker Wall & Slab m3 104.29
b) In Pad m3 44.88
c) In Concrete Pipe m3 35.08
d) In Ground Floor Slab m3 92.83
2.04 Provide, cut and fix in position sawn structural wood or
steel formwork whichever is appropriate;
a) To Tanker m2 729.39
b) To Pad m2 41.60
c) To Concrete Pipe m2 350.80
2.05 Mild Steel reinforcement according to Structural
Drawings and Technical Specifications. Price includes
cutting, bending, placing in position and tying wires.

a) Dia 6mm Plain bar kg 894.94


b) Dia 8mm deformed bar kg 2,222.44
c) Dia10mm deformed bar kg 5,790.18
d) Dia 12mm deformed bar kg 9,659.65
e) Dia 14mm deformed bar kg 5,605.48
TOTAL CARRIED TO SUMMARY
3. PLASTERING & FINISHING
3.01 Apply three coats of plastering in cement mortar (1:3)
up to fine finish. Price shall include pre-cleaning and
preparation of the surface.
a) To Tanker m2 1,458.78
ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
No.
3.02 Water Proofing
a) Apply Cementious water proofing material which
shall seal void by crystallization for inner floor wet areas
(Tankers) to a height of 400cm on walls as per the
manufacturer's instruction. The cost shall include
cleaning of all dirts, trace of grease, oil and loose
particles. The work shall be done on sub-contractual
bases with the supplier of the material which will give
material & construction gurantee to the client.

m2 729.39
b) Apply slated finish bitumen rich water proofing
membrane for externall shear wall which is submerged
in the ground asper the manufacturer instruction.
Special attention shall be given or the material shall
conform to the quality requirement of BS or other
equivalent institution. The construction shall be carried
out by the supplier with a certified personnel all in
accordance with the manufacturers details and
Instructions. Min. thickness 4mm
m² 729.39
3.03 Metal Plate 4mm Thick Size as per the drawing Pcs 3.00
3.04 Ditch
Construct rectangular grill cover open channel which
collect storm water at places located on the drawings
out of 400mm thick stone masonry plastered internally
in accordance with the detail drawing. Provide a
minimum slope of 0.5% or follow the natural ground
slope which ever is greater. Unit price shall include all
civil works and metal plate cover. Complete all works as
per the drawing and technical; specification. Size:- 400
x 400mm(average depth),

ml 99.84
TOTAL CARRIED TO SUMMARY
4. SANITARY INSTALLATION
4.01 Supply and fix High density polyethylene(HDPE) pipe
for the sewerage line . Price shall include all associated
civil works including concrete & steel supports if
nessery where requiered, adaptors,connecter and all
other necessary accessoris.

a) Dia. 25 mm ml 45
b) Dia. 65 mm ml 13
c) Dia. 110 mm ml 21
d) Dia. 160 mm ml 153
e) Dia. 200 mm ml 4
f) Dia. 250 mm ml 64
4.02 Brass Gate Valves,flanged
Supply ,lay ,test ,disinfect and commission approved
quality Gate valves or flanged which is grater than PN-
10 (Nominal pressure 10 ) with all nesseccery
accessories adaptors to High density
Polyethylene(HDPE) pipe of the following nominal size,
and all required accessories.

Brass gate valves , flanged


Dia 65 mm No 1
Dia 160 mm No 16
4.03 Sewarage Pump
a)Type one Pump
ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
No.
i) Supply ,fix, test and commission horizontal suction,
Horizontal discharge approved quality self primed
centrifugal Sewarage water pumps(WAS/RAS Pump )
with the necessary accessories as per the
manufacturer's instructions. Price shall include
connection of dry running preventors,control systems.
One Duty and one stand by Pump

Type : Groud Foss or Equivalent


Model: ………….
Q =18m3/h
H =……
Pump casing lantern bracket, impeller and shafts shall No
be made of stainless steel. 1.00
ii) Supply ,fix, test and commission horizontal suction,
Horizontal discharge approved quality self primed
centrifugal Hypochlorinet Dosing Pump with the
necessary accessories as per the manufacturer's
instructions. Price shall include connection of dry
running preventors,control systems. One Duty and one
stand by Pump

Type : Groud Foss or Equivalent


Model: ………….
Q =0.4lit/hr
H = 2 bar
Pump casing lantern bracket, impeller and shafts shall No
be made of stainless steel. 1.00
b)Type Two Pump
i) Supply ,fix, test and commission Vertical suction,
Horizontal discharge approved quality self primed
centrifugal Sewarage water Feed pumps with the
necessary accessories as per the manufacturer's
instructions. Price shall include connection of dry
running preventors,control systems. One Duty and one
stand by Pump

Type : Groud Foss or Equivalent


Model: ………….
Q =50m3/h
H =……..
Pump casing lantern bracket, impeller and shafts shall No
be made of stainless steel. 1.00
ii) Supply ,fix, test and commission Vertical suction,
Horizontal discharge approved quality self primed
centrifugal Sewarage water pumps(Proccesser Blower
pump) with the necessary accessories as per the
manufacturer's instructions. Price shall include
connection of dry running preventors,control systems.
One Duty and one stand by Pump

Type : Groud Foss or Equivalent


Model: ………….
Q =42m3/h
H =…………
Pump casing lantern bracket, impeller and shafts shall No
be made of stainless steel. 1.00
iii) Supply ,fix, test and commission Vertical suction,
Horizontal discharge approved quality self primed
centrifugal Mixing Blower Pump with the necessary
accessories as per the manufacturer's instructions.
Price shall include connection of dry running
preventors,control systems. One Duty and one stand by
Pump

Type : Groud Foss or Equivalent


Model: ………….
Q =12m3/min.
ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
No.
H =3.5m
Pump casing lantern bracket, impeller and shafts shall No
be made of stainless steel. 1.00
iv) Supply ,fix, test and commission Vertical suction,
Horizontal discharge approved quality self primed
centrifugal Sewarage filter water pumps with the
necessary accessories as per the manufacturer's
instructions. Price shall include connection of dry
running preventors,control systems. One Duty and one
stand by Pump

Type : Groud Foss or Equivalent


Model: ………….
Q =18m3/h
H =…………
Pump casing lantern bracket, impeller and shafts shall No
be made of stainless steel. 1.00
v) Supply ,fix, test and commission Vertical suction,
Horizontal discharge approved quality self primed
centrifugal Sewarage Back wash pumps with the
necessary accessories as per the manufacturer's
instructions. Price shall include connection of dry
running preventors,control systems. One Duty and one
stand by Pump

Type : Groud Foss or Equivalent


Model: ………….
Q =36m3/h
H =…….
Pump casing lantern bracket, impeller and shafts shall No
be made of stainless steel. 1.00
TOTAL CARRIED TO SUMMARY
B. MEDICAL WASTE WATER TREATMENT PLANT
Supply, install test and commision packaged type
medical waste water treatment plant as per the
specification. The price shall include all accessories
including spare part list to make the system complete.
set 1.00
TOTAL CARRIED TO SUMMARY
Gondar University Specification and BOQ Site work

SUMMARY OF BILL OF QUANTITIES


SITE WORK
1 EXCAVATION & EARTHWORK............................................. Birr -

2 CONCRETE WORK............................................................... Birr -

3 SUB BASES & PAVEMENT WORKS.............................................


Birr -

Total ......................... Birr -

VAT 15% .......................... Birr -

GRAND SUMMARY .......................... Birr -

Yohannes Abbay Consulting Architects and Engineers June, 2017 1


ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
1. EXCAVATION & EARTH WORK
1.01 Site clearing to remove the top soil to an average depth
of 20 cm for ordinary soil m2 10,000.00
1.02 Bulk excavation of ordinary soil to depth of 1200mm
From Reducing level. m3 8,000.00
1.03 Ditto item No. 1.2, but in soft rock . m3 800.00
1.06 Back fill with non-expansive selected material from
quarry and compact in layers not exceeding 200mm
thick under the Fertile soil for green Area by sprinkling
water to insure the required density as per the
inspection of the Engineer.
m3 600.00
1.07 Back fill with borrowed suitable non-expansive well
graded soil or granular material and compact in layers
not exceeding 200mm thick by sprinkling water under
road with no rock lumps imported from outside and
approved by the Engineer & to insure the requirement
of AASHTO dry density .
m3 3,148.80
1.08 Ditto as Item 1.7 but under Cobblestone by sprinkling
water to insure the requirement of AASHTO dry density
. m3 1,574.40
1.09 Cart away surplus excavated material and dispose at a
distance not exceeding 2km.from site as per the
Engineers Direction. m3 10,000.00
1.10 25cm thick basaltic or equivalent stone hardcore well
rolled, consolidated and blinded with crushed stone.
For fountain structure. m2 12.56
1.11 Preparing a Tree Pit by Excavating (500x500x500mm)
of soil per tree. Contractor to acquaint himself With soil
conditions and the scope of the works on site. Scarify
bottom of Excavation, before backfilling. All tree-holes
are location shall placed on the peripheral side that can
be parallel to the coble stone walk way to be inspected
by the Engineer/ Architect prior to filling with topsoil.

m3 8.75
1.12 Supply and spread compost as specified. Compost to
tree holes, shrub and Ground cover areas and lawn
areas. Provide 1kg sample and details of supplier With
quotation for Landscape Architect’s approval.

a) Trees : 0.05m² per tree hole m3 8.75


b) Grass m3 375.00
1.13 Planting

Provide,
temporary store, and plant sods directly on prepared
soil with reference to the sods, fertilizers, maintenance
(including watering of sods directly after planting)
a) Trees No 70.00
TOTALl CARRIED TO SUMMARY
2. CONCRETE WORK
2.01 Cast insitu Concrete curbing ,class A (40cm x15cm )
with chamfer as shown in the drawing (C-25
Concrete). Price includes all civil works. ml 1,314.00
TOTAL CARRIED TO SUMMARY
3. SUB BASES & PAVEMENT WORKS
3.1 Sub-bases
3.1.1 Sub-base Layer construction from gravel taken from
cut or borrow
ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
3.1.1.1 Gravel sub-base (unstabilised gravel) compacted to
97%MDD,AASHTO m3 1,968.00
ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
3.2 Base Course
3.2.1 Crushed stone
The rate includes full compensation for procuring,
breaking down, including the crusher fines or sand (if
approved) necessary for correcting the
grading of the crushed stone, for crushing and
screening, for hauling the material over an
unlimited free-haul distance, placing, rolling,
slushing, correcting the layers, compacting the
material, including transporting the material and its
removal, disposal and transporting of oversize material,
and the protection and maintenance of the layer and
the conducting of control tests, all as specified.

m3 1,312.00
3.3 Pavements
3.3.1 Cobblestones Paving for walkways as shown in
drawing. The stone should be shaped, and laid broken
- coursed on 2.5cm crushed sand. The cost includes
the sand bedding as indicated in the typical drawings.
Coble stone Size 10x10x10cm
m2 2,624.00
3.3.2 Supply and lay to the required level 40x20x10cm
shaped Flat stones made of hard rock as per the
layout, design and slope for the main body of the Flat
stones following the design pattern of the Flat stones
road pavement or instruction of the engineer.
m2 500.00
3.3.3 Priming, Primer Sealing and Sealing
3.3.3.1 Supply and Spray Primer, Primer-binder
MC-30 Litre 5,248.00
3.3.4 Hot Laid Asphalt
3.3.4.1 Supply and Application of Tack Coat RC 30
(application rate of 0.6L/M2) Litre 3,148.80
3.3.4.2 Dense Graded Asphalt (AC) in Binding Course(50mm)
m2 5,248.00
3.3.4.3 Dense Graded Asphalt (AC) in Wearing Course(50mm)
m2 5,248.00
TOTAL CARRIED TO SUMMARY
Gondar University Specification and BOQ Fence work

SUMMARY OF BILL OF QUANTITIES


FENCE
A-SUB STRUCTURE

1 Excavation and Earth Work................................................Birr -


2 Concrete Work.................................................................. Birr -
3 Masonry Work....................................................................Birr -
TOTAL A........................ Birr -

B. SUPER STRUCTURE

1 Concrete Work.................................................................. Birr -


2 Masonry Work................................................................... Birr -
3 Steel, Metal and Finishing work .........................................Birr -
4 Plastering and Pointing......................................................Birr -
5 Electrical Instalation..........................................................
Birr -

Total B ..........................
Birr -
Total A + B ............................
Birr -
VAT 15% ..........................
Birr -
GRAND SUMMARY ..........................
Birr -

Yohannes Abbay Consulting Architects and Engineers June, 2017 1


ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
A . SUB – STRUCTURE
1. EXCAVATION & EARTH WORK
1.01 Site clearing to remove the top soil to an average
depth of 20 cm. m2 656.00
1.02 Excavation for continuous Trench to a depth not
exceeding 1500mm.starting from reduced ground
level. m3 984.00
1.03 Back fill around masonry wall with non-expansive
selected material from quarry and compact in layers
not exceeding 200mm thick by sprinkling water to
insure the requirement of AASHTO dry density .
m3 721.60
1.04 Cart away surplus excavated material and dispose at
a distance not exceeding 10km.from site as per the
Engineers Direction. m3 1,115.20
TOTAL CARRIED TO SUMMARY
2. CONCRETE WORK
2.01 5cms.thick lean concrete quality in class C-5 with
minimum cement content of 150kg /m3.
A) Under masonry wall m2 393.60
2.02 Reinforced concrete in class C-25, with minimum
cement content of 360kg/m3 filled in into formwork
and vibrated around steel reinforcement, steel and
formwork measured separately:-

A. In grade beam m3 141.03


2.03 Provide, cut and fix in position sawn structural wood
or steel formwork whichever is appropriate;
A. For grade beam m2 800.10
2.04 Mild Steel reinforcement according to Structural
Drawings and Technical Specifications. Price
includes cutting, bending, placing in position and
tying wires.
A) Dia 8mm deformed bar kg 2,363.00
B) Dia 16mm deformed bar kg 7,025.07
TOTAL CARRIED TO SUMMARY
3. MASONRY WORK
3.01 Construct 50cm thick trachytic or equivalent stone
masonry foundation wall bedded in cement sand
mortar ratio 1:3
a) Below Natural Ground Floor Level (BNGL) m3 262.40
b) Above Natural Ground Floor Level (ANGL) m3 229.60
TOTAL CARRIED TO SUMMARY
B . SUPER – STRUCTURE
1. CONCRETE WORK
1.01 Reinforced concrete in class C-25, with minimum
cement content of 360kg/m3 filled in into formwork
and vibrated around steel reinforcement, steel and
formwork measured separately:-

a) In copping m3 16.40
b) Main Gate Column m3 30.19
1.02 Provide, cut and fix in position sawn seasoned timber
or steel form work made up of minimum 3mm thick
sheet metal & folded thickness of 50mm whichever is
appropriate; Contractor to submit formwork design;

a. For copping m2 131.20


ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
b. Main Gate column m2 442.73
TOTAL CARRIED TO SUMMARY
2. BLOCK WORK
2.01 Supply and construct class-B 200x200x400mm
HCB wall with cement mortar 1:3 mix ratio. m3 770.54
2.02 Construct 40cm thick fine Dressed stone type it
should lay horizontally left for 12mm.wide straight
pointing and vertically fix or inter locked to be look as
a single stone wall bedded in cement sand mortar
ratio 1:3 as per the drawing and inspection of the
Engineer. m3 64.52
TOTAL CARRIED TO SUMMARY
3. STEEL , METAL AND FINISHING WORK
3.01 Supply and fix in position 40x40x3mm verticals and
40x40x3mm horizontals RHS. Grill fence for space
above hallow concrete wall fabricated from approved
metal. Price include iron monger, fixing clips, mortar
bedding, one coat of anti rust and two coats of
synthetic enamel paint and all accessories. Complete
all works as per the drawing and as inspection of
the Engineer.
ml 2,867.00
3.02 Supply and fix in position spear and shield metal art
on fence made from 20mm CHS and conic shaped
decorated sheet metal. Size, shape and positions as
shown on the drawing. Price includes one coat of anti
rust and two coats of synthetic enamel paint and all
accessories. Complete all works as per the drawing
and as inspection of the Engineer.

No 131.00
TOTAL CARRIED TO SUMMARY
4. PLASTERING & POINTING
4.01 Apply two coats of plaster in cement sand mortar
mix [1:3] on Copping m2 524.80
4.02 Apply plastering in cement mortar mix(1:2) to fine
Hollow concrete block wall as where shown on the
Architectural drawing. Price shall include pre-cleaning
and preparation of the surface. m2 1,541.07
4.03 Apply pointing to exposed part above ground level
stone masonry foundation wall recessed joint in
cement sand mortar mix (1:2). m2 656.00
TOTAL CARRIED TO SUMMARY
5 ELECTRICAL INSTALATION
5.1 Compound Light
5.1.1 Compound light points fed through PVC insulated
conductors of 3x4mm2 inside PVC conduits of 25mm
diameter, including junction boxes with covers, screw
type insulating caps, all complete
No 135.00
5.2 Extra Over Light Points for Flush Mounted
Switches
Supply and fix Legrand Mosaic 45 or approved
equivalent 10/16A, 250V flush mounted light switch,
fed through PVC insulated conductor of 3 x 4mm²
inside thermo plastic conduit of ø 16mm, connected
and tested, complete with plate and including
appropriate wall boxes, all complete as specified
and/or shown on drawings.

5.2.1 Tumbler Switch No 6.00


ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
5.3 Compound Light Fittings/Fixtures With Lamps
Connected and tested lamps including wires, flexible
cables, conduits, boxes, mounting materials and
accessories complete, all as specified or described in
light fittings schedule and as shown on the drawings.

5.3.1 LAMP FOR COMPOUND LIGHTING: PHILIPS


GPS301 PCO-D 400 with EPS 300 SON-I 26W 230V
Lo Lamp or equivalent approved. Price shall include
pole, H= 300cm. No 135.00
TOTAL CARRIED TO SUMMARY
Gondar University Specification and BOQ Miscellaneous

SUMMARY OF BILL OF QUANTITIES


MISCELLANEOUS
1 GENERAL ITEM OF WORK………………………………. Birr -

Total ......................... Birr -

VAT 15% .......................... Birr -

GRAND SUMMARY .......................... Birr -

Yohannes Abbay Consulting Architects and Engineers June, 2017 1


Gondar University Specification and BOQ Miscellaneous

ITEM
DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE
NO.
1. GENERAL ITEM
1.01 Provide for client and Engineer personnel (6 in no.) on
all civil, electromechanical and computer networking
work with the manufacturers of equipment with all costs
covered by the contractor including 10 sets of
instruction, maintenance manual and instalation
manuals and certification from manufacturers soft and
hard copies for 3 weeks abroad the contractor shall
submit all the schedules of the training before starting
of these works. ( as per the recommendation of the
Engineer
Ls 1.00
1.02 Provide office space of moderately furnished room of
not less than 16 msq area and shall have secured
doors with locks, proper windows and must be with
proper artificial lighting and power outlets. The space
(room) provided must be furnished with filing cabinets,
proper tables, chairs for the Resident Engineer(s) and
additional four chairs for visitors. The office also have
proper and private WC room for the Resident
Engineer(s).
Ls 1.00
1.03 The Contractor shall purchase and provide 2 new latest
model double-cabin, four-wheel-drive pick-up ( Toyota
or Equivalent) with driver to provide transportation
facilities for the Resident Engineer(s) and Employers
Engineers from town to site and to any distance that
may be found necessary for the proper execution of the
supervision task. All expenses such as Fuel,
Lubricants, Servicing, Maintenance, and Repaire of
Vehicles shall be covered by the Contractor until the
provisional acceptance of the project. The vehicles
shall be the properties of the employer after provisional
acceptance of the project.

No. 2.00
1.04 Provision of Computers, Printers, Scanner, Fax
Machine, Mobile apparatus and lines, Soft wares, and
cost of stationeries in lump sum
Ls 1.00
TOTALl CARRIED TO SUMMARY

Yohannes Abbay Consulting Architects and Engineers June, 2017 68

You might also like