Professional Documents
Culture Documents
No Discussion
-0- 40
0 40 80 120 160 200 O 40 80 120 160 200 0 40 80 120' 160200
TIME SECONDS TIME SECONDS TIME SECONDS
(A) (B)
(C)
Figure 3. Time temperature characteristics at 41 5 amperes on locked saturation tests
Figure 1. Damper currents in the rotor surface
and location of thermocouples numbers 1, 6, A. Thermocouple number 7 retaining ring 1 inch from rotor body
and 7 B. Thermocouple number 6 wedge 1 inch from retaining ring
C. Thermocouple number 1 pole face-center 111/2 inches from retaining ring
held in place by metal wedges, each about taining rings across the metal to metal Xd = 148 per cent
6 inches long, which are driven into joint. Tdo'= 4.4 seconds
milled grooves in the rotor teeth. The 4. To a limited extent some current flows wedge material = aluminum alloy
coil ends are held against centrifugal in the rotor winding. As the damper cur- It can be seen from Figure 2 that the
rents tend to crowd to the rotor surface,
force by steel retaining rings of very high this component is usually very small. The rotor would be subjected to 17,500
strength which are assembled on the rotor location of these currents and the various kilowatt-seconds in 10 seconds. If the
with a heavy shrink fit at the body of rotor parts are shown in Figure 1. entire mass of the rotor could dissipate
the rotor and this fit supports the whole the heat uniformly, the total rise in tem-
end winding structute. The surface of Heat Input to the Rotor During perature would be about 9 degrees centi-
the rotor body is grooved with a small a Single-Phase Short Circuit grade. Obviously the hot-spot tempera-
spiral groove to reduce pole face and tures are much higher than this.
load losses. It has been shown by Wagner' that the
When an unbalance in the 3-phase losses in the rotor due to negative-phase A Criterion of Rotor Heating
stator currents occurs causing negative- sequence currents will be supplied from
phase sequence currents 12 to flow in the two sources. Half the losses will come The American Standards Association
stator, a backward rotating flux field cuts through the shaft from the prime mover subcommittee working on this problem
the rotor producing damper currents to while the other half will come through of rotor heating for various kinds of
flow there at double the machine fre- the stator. This latter half may be synchronous machines decided that the
quency. Currents then flow in: evaluated as most suitable criterion for the effects of
1. The surface of the solid forging. The the single-phase operation on rotor heat-
222(r2- ri)
crowding of the damper currents to the ing for short periods of time might be
surface of both pole center and teeth is due where expressed by
to the so-called skin effect which is par-
ticularly marked in magnetic steel. 12= negative-phase sequence component of I2equiv2t = constant
armature current where
2. The rotor wedges and metallic strips r2=negative-phase sequence resistance
beneath the wedges used to protect the ri = positive-phase sequence resistance, or
insulation when driving the wedges. the effective stator resistance I2equiv = l __Jr 'I
3. The retaining rings. To reach the re-
taining rings the currents must flow from If therefore the heat input from the t= time in seconds.
the rotor forging or the wedges to the re- stator is evaluated and this value is
doubled to account for the power coming This expression assumes that all the
through the shaft, the total heat input to heat generated in the rotor can be con-
the rotor due to damper currents is then sidered to be stored in the rotor surface
obtained. for short periods say up to 30 seconds.
To illustrate this the heat input to the Depending upon the severity of the short
rotor during the line-to-line short circuit circuit the allowable time for such faults
4.0 _ i would be defined by this expression. For
z at 105-per-cent voltage fi-om full load
a:
STORED HEAT
KW SECONDS with an automatic regulator in service turbine generators an expression I22t = 30
cr
3.0 1 Iv_-
.-,
15,000) is shown in Figure 2 for a generator with where 12 is in per-unit values and t is in
z I--,' 11-11" the following characteristics seconds has been agreed upon to define
ci. 2.0 ==,PI-,
I--,"
.10,0 0
the limits of single-phase operation with-
-,- - -
short circuit, see Figure 6(A) and 6(B). possible wedge failure. 1000 .11,500 KW
AIR COOLED
On the same curve is included an average
and maximum test rise of the wedge of
Conclusions
0r 10 )0
-12 1.35 Pu
2000 3000
-
_-I 4000 5000
the air-cooled unit corrected to a local The following conclusions are drawn TIME-SECONDS
ambient of 85 degrees centigrade. The (A)
as to the allowable time of a single-phase 0
temperature is representative of wedge 1. The most severe fault so far as rotor 700 H2 COOLED
temperatures several inches away from heating is concerned is likely to be a line-to- :
cr 600 t12PU
line fault. 4
D 400
tests indicate the surface temperatures at a ~~11,500
The results must be considered in the number of points but do not indicate the 1-j 300
AIR COOLED-
1. The test results as shown in Table I measure of the buming at such joints. The 100I
and Figure 6(B) must be treated with the joint temperatures are obviously higher 0
O_ b Z-TEST
10 20 30 40 50 60 70 80
POINTS
a
= degree References
Appendix I covered a method of calcu- perature drop
lating the losses due to negative-phase through body in centigrade/watt 1. MACHINE: CONSTANTS, c. E. Wagner. Elec-
trical Transmission and Distribution Reference
sequence currents in the rotor. Once these which no loss is gen- Book, Westinghouse Electric Corporation, East
losses are determined it is possible to obtain erated Pittsburgh, Pa., third edition, 1950, page 143.
No Discussion