You are on page 1of 90

DESIGN AND ANALYSIS REPORT

OF OVERHEAD VMS GANTRY STRUCTURE

CLIENT: M/S QUALIX INFORMATION SYSTEM LLP.

PROJECT: OVERHEAD VMS GANTRY

OBJECTIVE: STRUCTUTRE IS DESIGNED TO CARRY VMS BOARD LOAD WITH WIND


PRESSURE.

BASIS OF THE DESIGN AND ANALYSIS OF THE STRUCTUTRE WAS


CALCULATION: ACCOMPLISHED USING "STAAD-Pro" SOFTWARE. WIND
LOADS ARE CALCULATED AS PER IS 875: 2015 PART 3.
DESIGN CALCULATION ARE PERFORMED IN ACCORDANCE
WITH IS 800-2007.

ZCC TECHNO PVT. LTD.


UNIT NO 452,
FOURTH FLOOR, JMD
MEGAPOLIS.
SEC 48, SOHNA ROAD
GURUGRAM-122018,
HARYANA
www.zcctechno.com

REVISION DATE DESCRIPTION DESIGN BY CHECKED BY APPROVED BY


0 28-04-2022 NARVINDER JKR BSS
TABLE OF CONTENTS

SECTION DESCRIPTION

1 INTRODUCTION

2 DESIGN SPECIFICATIONS

3 SUMMARY

4 FOUNDATION REACTIONS

5 BASE PLATE DESIGN

6 CONNECTION DESIGN

7 STAAD REPORT

8 STAAD OUTPUT

9 DWG & BOM


SECTION 1

INTRODUCTION

This report covers the analysis & design of Overhead VMS Gantry Structure
The scope of this report includes the checking the structural adequacy of member section
sizes for the loading which includes dead, wind and Live loads on the structure.
SECTION 2

DESIGN SPECIFICATIONS

STRUCTURE DETAILS:
STRUCTURE SPAN 18.5 m
DESIGN LIFE 25 Yrs
STRUCTURE TYPE GROUND BASE

WIND LOADING PARAMETERS:


BASIC WIND SPEED 47 m/s
TERRAIN CATEGORY 2
PROBABILITY FACTOR K1 0.9
HEIGHT FACTOR K2 1.0
TOPOGRAPHY FACTOR K3 1.0
IMPORTANCE FACTOR K4 1.0

DESIGN STANDARD:

WIND LOAD ON STRUCTURE BODY &


IS 875-PART 3-2015
APPURTENANCES:
DESIGN OF MEMBERS: IS800:2007
MATERIAL PROPERTIES:

CODE FOR BOLTS: IS 1367:1987


GRADE OF BOLTS 5.6 FOR STRUCTURE

CODE FOR OTHER MATERIALS 2062 (GRADE A)

MIN. YIELD STRESS (TUBE) 2550 kg/cm^2

DESIGN CRITERIA:

MIN. F.O.S. 1.50


PERMISSIBLE < H/150 (AT SERVICE LOAD)
PERMISSIBLE SWAY 7320/150 = 48.8MM
ACTUAL SWAY 41.524MM
HENCE OKAY
SECTION 3

SUMMARY

The Overhead VMS Gantry Structure has been designed based on the loadings & material
properties as specified under the Design Specifications section and has been found to be safe
SECTION 4

FOUNDATION REACTION (FACTORED)


Horizontal Vertical Horizontal Moment
My Mz
Node L/C Fx kN Fy kN Fz kN Mx kNm kNm kNm
1 4 1.5DL+1.5LL 0.405 18.759 0.017 0 0 0
5 1.5DL+1.5WL 1.438 124.898 9.121 0 0 0
6 1.2DL+1.2LL+1.2WL 1.341 105.83 7.297 0 0 0
2 4 1.5DL+1.5LL 0.535 24.057 -0.017 0 0 0
5 1.5DL+1.5WL -0.911 -94.927 10.573 0 0 0
6 1.2DL+1.2LL+1.2WL -0.581 -71.577 8.458 0 0 0
3 4 1.5DL+1.5LL -0.407 26.721 0.017 0 0 0
5 1.5DL+1.5WL -1.463 124.605 9.065 0 0 0
6 1.2DL+1.2LL+1.2WL -1.362 111.765 7.252 0 0 0
4 4 1.5DL+1.5LL -0.533 31.399 -0.017 0 0 0
5 1.5DL+1.5WL 0.936 -94.14 10.507 0 0 0
6 1.2DL+1.2LL+1.2WL 0.602 -65.269 8.406 0 0 0

FOUNDATION REACTION @FOUNDATION DESIGN


Horizontal Vertical Horizontal Moment
My Mz
Node L/C Fx kN Fy kN Fz kN Mx kNm kNm kNm
1 7 1.0DL+1.0LL 0.27 12.506 0.011 0 0 0
8 1.0DL+1.0WL 0.959 83.265 6.081 0 0 0
9 1.0DL+0.8LL+0.8WL 0.894 70.553 4.865 0 0 0
10 1.0DL+1.0LL+1.0WL 1.117 88.192 6.081 0 0 0
2 7 1.0DL+1.0LL 0.357 16.038 -0.011 0 0 0
8 1.0DL+1.0WL -0.608 -63.285 7.049 0 0 0
9 1.0DL+0.8LL+0.8WL -0.387 -47.718 5.639 0 0 0
10 1.0DL+1.0LL+1.0WL -0.484 -59.647 7.048 0 0 0
3 7 1.0DL+1.0LL -0.271 17.814 0.011 0 0 0
8 1.0DL+1.0WL -0.975 83.07 6.043 0 0 0
9 1.0DL+0.8LL+0.8WL -0.908 74.51 4.835 0 0 0
10 1.0DL+1.0LL+1.0WL -1.135 93.137 6.044 0 0 0
4 7 1.0DL+1.0LL -0.355 20.932 -0.011 0 0 0
8 1.0DL+1.0WL 0.624 -62.76 7.005 0 0 0
9 1.0DL+0.8LL+0.8WL 0.401 -43.513 5.604 0 0 0
10 1.0DL+1.0LL+1.0WL 0.502 -54.391 7.005 0 0 0
SECTION 5

BASE PLATE & ANCHOR BOLT DESIGN


Design of Anchor Bolts
Max. Factored Moment = 0.00 KNm
Max. Factored Compression = 124.90 KN
Max. Factored Tension= 94.93 KN
Maximum Factored shear= 10.57 KN
Grade of Concrete = M25
Dia/Size of Base Plate 332 332 mm
Size of Concrete Pedestal 500 500 mm
Diameter of Pipe 132 132 mm
C/c Distance of bolt to Bolt 212 212 mm

Design of anchor bolts

No. Dia
Bolt Dia. Nos.
4 30

Maximum Shear = 10.57 KN


Shear in one bolt(V)= 2.64 KN
Permissible shear in 5.6 grade bolt(vb)= 219.00 KN (Refer IS802:2016,PART 1 SEC 2 Table-1)

FOS= 82.85 >1.5

Shear in one bolt


2.64 KN

For maximum tension in bolt(Pt) =p/n±m*r/(Σr^2)= 23.73 KN FORCES DISTRIBUTION ON ANCHOR BOLT
Permissible tensile force in 5.6 grade bolt(Pto)= 353.00 KN (Refer IS802:2016,PART 1 SEC 2 Table-1)
FOS=Pto/Pt= 14.87 >1.5
Check for combined stresses

(Refer IS800:2007, Cl 10.3.6)


(Pt/Pto)^2+(V/Vb)^2 0.00467 < 1.00 < Hence ok

Tensile force resisted by anchor bolt/concrete bond= 15.82 KN

Permissible bond stress as per IS456-2000 for M-25 Concrete = 0.9 N/Sqmm
Refer clause B-2.1.2 & B-2.3 From IS456:2000

3.14x30xLx0.9*1.33=15821.17 Provided
L= 139.96 MM 750 mm

So provide 4 Nos-30 mm Dia Anchor Bolts 900mm long with embedment length of 750 MM
Design of Base Plate
Factored Moment M= 0.66KNm
Unfactored Moment = 0.44KNm
Factored Compression= 124.90KN
Unfactored Compression= 83.27KN
Factored Tension= 94.93KN
Unfactored Tension= 63.28KN
Unfactored Side Thrust= 7.05KN
Factored Side Thrust= 10.57KN
Compressive strength of Concrete = 25.00 N/mm2
Dia/Size of Base Plate 340 340 mm
Size of Concrete Pedestal 550 550 mm
Diameter of Pipe 132 132 mm
C/C Distance of Bolt 212 212 mm
Edge Distance = 64.00 mm

2
Plate Area A 1,15,600.00 mm
2
Concrete Area = 550x550 3,02,500.00 mm

Check for Base plate Size


Axial Force P= 124.90 KN
Section modulus of Base plate Z=(340^3)/(6) 65,50,666.67 mm3
Pressure on concrete pedestal (P/A+M/Z) 1.15 N/mm2

Grade of Concrete= M25


Maximum Bearing Pressure below base plate = 0.6Xfck 15.00 N/mm2 Cl 7.4.1 IS 800:2007
< Hence ok

Design check for the thickness of plate;

As per IS800:2007, clause no 7.4.3.1

Total Vertical load (w) = 83.27 kn


Total Vertical Factored load = 124.90 kn (1.5 factor of safety has been taken)
Base plate area = 1,15,600.00 mm^2
w = 1.08 N/mm^2

Partial factor of safety (Ymo) = 1.25 as per table25 in IS 800:2007


Yield strength of material (fy) = 250 N/mm^2
a (larger projection) = 104 mm
b(smaller projection) = 104 mm

Thickness of base plate= = 10 mm Say 16 mm

Provide Base plate of Size 340 mm X 340 mm and Thickness 16 mm

WELD DESIGN
Max Factored Tensile/Compressive Force. 124.90 KN

Throat Thickness 3 MM
te 2.1 MM
lw 528 MM
Fu 410 N/mm^2
Ymw 1.5 Site Welding
Pdw = Fu*Lw*te/Sqrt(3)*Ymw N
Pdw = 174978.7008 N
Pdw = 174.9787008 KN
Hence Okay
SECTION 6

CONNECTION DESIGN
Design of Flange Plate (Item-31)
Factored Moment M= 0.71 KNm
Unfactored Moment = 0.48 KNm
Factored Compression= 0.00 KN
Unfactored Compression= 0.00 KN
Factored Tension= 28.90 KN
Unfactored Tension= 19.27 KN
Unfactored Side Thrust= 1.43 KN
Factored Side Thrust= 2.15 KN

Dia/Size of Flange Plate 280 280 mm


Size of Pipe/Tube 132 132 mm
C/C Distance of Bolt 192 192 mm
Edge Distance = 44.00 mm

Design of bolts

No. Dia
Bolt Dia. Nos.
4 16

Maximum Shear = 2.15 KN


Shear in one bolt(V)= 0.54 KN
Permissible shear in 5.6 grade bolt(vb)= 62.00 KN (Refer IS802:2016,PART 1 SEC 2 Table-1)

FOS= 115.46 >1.5

Shear in one bolt 0.54 KN

For maximum tension in bolt(Pt) =p/n±m*r/(Σr^2)= 14.45 KN FORCES DISTRIBUTION ON ANCHOR BOLT
Permissible tensile force in 5.6 grade bolt(Pto)= 100.50 KN (Refer IS802:2016,PART 1 SEC 2 Table-1)
FOS=Pto/Pt= 6.96 >1.5
Check for combined stresses
(Refer IS800:2007, Cl 10.3.6)
(Pt/Pto)^2+(V/Vb)^2 0.02075 < 1.00 < Hence ok

Thickness of Flange Plate=

Yield strength of material (fy) 250 N/mm^2


treq = SQRT((6*M)/(fy*b))
= 7.81756265 mm
Say 10 mm

Provide flange plate of Size 280 mm X 280 mm and Thickness 10 mm

WELD DESIGN
Max Factored Tensile/Compressive Force. 28.90 KN

Throat Thickness 3 MM
te 2.1 MM
lw 528 MM
Fu 410 N/mm^2
Ymw 1.5 Site Welding
Pdw = Fu*Lw*te/Sqrt(3)*Ymw N
Pdw = 174978.7008 N
Pdw = 174.9787008 KN
Hence Okay
Design of Flange Plate (Item-33)
Factored Moment M= 0.06 KNm
Unfactored Moment = 0.04 KNm
Factored Compression= 99.53 KN
Unfactored Compression= 66.35 KN
Factored Tension= 99.53 KN
Unfactored Tension= 66.35 KN
Unfactored Side Thrust= 0.88 KN
Factored Side Thrust= 1.32 KN

Dia/Size of Flange Plate 240 240 mm


Size of Pipe/Tube 100 100 mm
C/C Distance of Bolt 160 160 mm
Edge Distance = 40.00 mm

Design of bolts

No. Dia
Bolt Dia. Nos.
4 16

Maximum Shear = 1.32 KN


Shear in one bolt(V)= 0.33 KN
Permissible shear in 5.6 grade bolt(vb)= 62.00 KN (Refer IS802:2016,PART 1 SEC 2 Table-1)

FOS= 188.45 >1.5

Shear in one bolt 0.33 KN

For maximum tension in bolt(Pt) =p/n±m*r/(Σr^2)= 24.88 KN FORCES DISTRIBUTION ON ANCHOR BOLT
Permissible tensile force in 5.6 grade bolt(Pto)= 100.50 KN (Refer IS802:2016,PART 1 SEC 2 Table-1)
FOS=Pto/Pt= 4.04 >1.5
Check for combined stresses
(Refer IS800:2007, Cl 10.3.6)
(Pt/Pto)^2+(V/Vb)^2 0.06133 < 1.00 < Hence ok

Thickness of Flange Plate=

Yield strength of material (fy) 250 N/mm^2


treq = SQRT((6*M)/(fy*b))
= 0.04 mm
Say 10 mm

Provide flange plate of Size 240 mm X 240 mm and Thickness 10 mm

WELD DESIGN
Max Factored Tensile/Compressive Force. 99.53 KN

Throat Thickness 3 MM
te 2.1 MM
lw 400 MM
Fu 410 N/mm^2
Ymw 1.5 Site Welding
Pdw = Fu*Lw*te/Sqrt(3)*Ymw N
Pdw = 132559.6218 N
Pdw = 132.5596218 KN
Hence Okay
SECTION 7

STAAD REPORT
Job No Sheet No Rev
1
Part
Software licensed to
Job Title Ref

By Date28-Mar-22 Chd

Client File Date/Time 29-Apr-2022 11:38


STAAD@QUALIX-18.5M GANTRY.std

Job Information
Engineer Checked Approved

Name:
Date: 28-Mar-22

Structure Type SPACE FRAME

Number of Nodes 199 Highest Node 88


Number of Elements 227 Highest Beam 242
Number of Plates 100 Highest Plate 342

Number of Basic Load Cases 3


Number of Combination Load Cases 7

Included in this printout are data for:


All The Whole Structure

Included in this printout are results for load cases:


Type L/C Name

Primary 1 DL
Primary 2 LL
Primary 3 WIND LOAD BODY
Combination 4 1.5DL+1.5LL
Combination 5 1.5DL+1.5WL
Combination 6 1.2DL+1.2LL+1.2WL
Combination 7 1.0DL+1.0LL
Combination 8 1.0DL+1.0WL
Combination 9 1.0DL+0.8LL+0.8WL
Combination 10 1.0DL+1.0LL+1.0WL

Primary Load Cases


Number Name Type

1 DL Dead
2 LL Live
3 WIND LOAD BODY Wind

Print Time/Date: 29/04/2022 15:51 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 1 of 7
Job No Sheet No Rev
2
Part
Software licensed to
Job Title Ref

By Date28-Mar-22 Chd

Client File Date/Time 29-Apr-2022 11:38


STAAD@QUALIX-18.5M GANTRY.std

Combination Load Cases


Comb. Combination L/C Name Primary Primary L/C Name Factor

4 1.5DL+1.5LL 1 DL 1.50
2 LL 1.50
5 1.5DL+1.5WL 1 DL 1.50
3 WIND LOAD BODY 1.50
6 1.2DL+1.2LL+1.2WL 1 DL 1.20
2 LL 1.20
3 WIND LOAD BODY 1.20
7 1.0DL+1.0LL 1 DL 1.00
2 LL 1.00
8 1.0DL+1.0WL 1 DL 1.00
3 WIND LOAD BODY 1.00
9 1.0DL+0.8LL+0.8WL 1 DL 0.80
2 LL 0.80
3 WIND LOAD BODY 0.80
10 1.0DL+1.0LL+1.0WL 1 DL 1.00
2 LL 1.00
3 WIND LOAD BODY 1.00

Y
X
Z Load 1

Whole Structure

Print Time/Date: 29/04/2022 15:51 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 2 of 7
Job No Sheet No Rev
3
Part
Software licensed to
Job Title Ref

By Date28-Mar-22 Chd

Client File Date/Time 29-Apr-2022 11:38


STAAD@QUALIX-18.5M GANTRY.std

Y
X
Z Load 2

Whole Structure

Y
X
Z Load 3

Whole Structure

Print Time/Date: 29/04/2022 15:51 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 3 of 7
Job No Sheet No Rev
4
Part
Software licensed to
Job Title Ref

By Date28-Mar-22 Chd

Client File Date/Time 29-Apr-2022 11:38


STAAD@QUALIX-18.5M GANTRY.std

Y
X
Z Load 4

Whole Structure

Y
X
Z Load 5

Whole Structure

Print Time/Date: 29/04/2022 15:51 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 4 of 7
Job No Sheet No Rev
5
Part
Software licensed to
Job Title Ref

By Date28-Mar-22 Chd

Client File Date/Time 29-Apr-2022 11:38


STAAD@QUALIX-18.5M GANTRY.std

Y
X
Z Load 6

Whole Structure

Y
X
Z Load 7

Whole Structure

Print Time/Date: 29/04/2022 15:51 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 5 of 7
Job No Sheet No Rev
6
Part
Software licensed to
Job Title Ref

By Date28-Mar-22 Chd

Client File Date/Time 29-Apr-2022 11:38


STAAD@QUALIX-18.5M GANTRY.std

Y
X
Z Load 8

Whole Structure

Y
X
Z Load 9

Whole Structure

Print Time/Date: 29/04/2022 15:51 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 6 of 7
Job No Sheet No Rev
7
Part
Software licensed to
Job Title Ref

By Date28-Mar-22 Chd

Client File Date/Time 29-Apr-2022 11:38


STAAD@QUALIX-18.5M GANTRY.std

Y
X
Z Load 10

Whole Structure

Print Time/Date: 29/04/2022 15:51 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 7 of 7
SECTION 8

STAAD OUTPUT
Wednesday, July 13, 2022, 03:36 PM
PAGE NO. 1

****************************************************
* *
* STAAD.Pro V8i SELECTseries6 *
* Version 20.07.11.33 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= JUL 13, 2022 *
* Time= 15:36:11 *
* *
* LICENSED TO: *
****************************************************

1. STAAD SPACE

2. START JOB INFORMATION


3. ENGINEER DATE 28-MAR-22
4. END JOB INFORMATION
5. INPUT WIDTH 79
6. UNIT METER KN
7. JOINT COORDINATES
8. 1 0 0 0; 2 0 0 1; 3 18.5 0 0; 4 18.5 0 1; 5 0 0.453 0; 6 0 0.453 1
9. 7 18.5 0.453 0; 8 18.5 0.453 1; 9 0 1.853 0; 10 0 1.853 1; 11 18.5 1.853 0
10. 12 18.5 1.853 1; 13 0 3.253 0; 14 0 3.253 1; 15 18.5 3.253 0; 16 18.5 3.253 1
11. 17 0 4.653 0; 18 0 4.653 1; 19 18.5 4.653 0; 20 18.5 4.653 1; 21 0 4.977 0
12. 22 0 4.977 1; 23 18.5 4.977 0; 24 18.5 4.977 1; 25 0 7.097 0; 26 0 7.097 1
13. 27 18.5 7.097 0; 28 18.5 7.097 1; 29 0.75 4.977 0; 30 0.75 4.977 1
14. 31 0.75 7.097 0; 32 0.75 7.097 1; 33 2.25 4.977 0; 34 2.25 4.977 1
15. 35 2.25 7.097 0; 36 2.25 7.097 1; 37 3.75 4.977 0; 38 3.75 4.977 1
16. 39 3.75 7.097 0; 40 3.75 7.097 1; 41 5.25 4.977 0; 42 5.25 4.977 1
17. 43 5.25 7.097 0; 44 5.25 7.097 1; 45 6.75 4.977 0; 46 6.75 4.977 1
18. 47 6.75 7.097 0; 48 6.75 7.097 1; 49 7.75 4.977 0; 50 7.75 4.977 1
19. 51 7.75 7.097 0; 52 7.75 7.097 1; 53 9.25 4.977 0; 54 9.25 4.977 1
20. 55 9.25 7.097 0; 56 9.25 7.097 1; 57 10.75 4.977 0; 58 10.75 4.977 1
21. 59 10.75 7.097 0; 60 10.75 7.097 1; 61 11.75 4.977 0; 62 11.75 4.977 1
22. 63 11.75 7.097 0; 64 11.75 7.097 1; 65 13.25 4.977 0; 66 13.25 4.977 1
23. 67 13.25 7.097 0; 68 13.25 7.097 1; 69 14.75 4.977 0; 70 14.75 4.977 1
24. 71 14.75 7.097 0; 72 14.75 7.097 1; 73 16.25 4.977 0; 74 16.25 4.977 1
25. 75 16.25 7.097 0; 76 16.25 7.097 1; 77 17.75 4.977 0; 78 17.75 4.977 1
26. 79 17.75 7.097 0; 80 17.75 7.097 1; 81 1.5 4.977 0; 82 17 4.977 0
27. 83 1.5 4.977 1; 84 17 4.977 1; 85 0 3.797 0; 86 0 3.797 1; 87 18.5 3.797 0
28. 88 18.5 3.797 1
29. MEMBER INCIDENCES
30. 1 1 5; 2 5 9; 3 9 13; 4 13 85; 5 17 21; 6 21 25; 7 2 6; 8 6 10; 9 10 14
31. 10 14 86; 11 18 22; 12 22 26; 13 3 7; 14 7 11; 15 11 15; 16 15 87; 17 19 23
32. 18 23 27; 19 4 8; 20 8 12; 21 12 16; 22 16 88; 23 20 24; 24 24 28; 27 5 6
33. 28 7 8; 29 9 10; 30 11 12; 31 13 14; 32 15 16; 33 17 18; 34 19 20; 35 21 22
34. 36 23 24; 37 25 26; 38 27 28; 39 21 29; 40 29 81; 41 33 37; 42 37 41; 43 41 45
35. 44 45 49; 45 49 53; 46 53 57; 47 57 61; 48 61 65; 49 65 69; 50 69 73; 51 73 82
36. 52 77 23; 53 22 30; 54 30 83; 55 34 38; 56 38 42; 57 42 46; 58 46 50; 59 50 54
37. 60 54 58; 61 58 62; 62 62 66; 63 66 70; 64 70 74; 65 74 84; 66 78 24; 67 25 31
38. 68 31 35; 69 35 39; 70 39 43; 71 43 47; 72 47 51; 73 51 55; 74 55 59; 75 59 63

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 1 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 2

39. 76 63 67; 77 67 71; 78 71 75; 79 75 79; 80 79 27; 81 26 32; 82 32 36; 83 36 40


40. 84 40 44; 85 44 48; 86 48 52; 87 52 56; 88 56 60; 89 60 64; 90 64 68; 91 68 72
41. 92 72 76; 93 76 80; 94 80 28; 99 29 31; 100 30 32; 101 33 35; 102 34 36
42. 103 37 39; 104 38 40; 105 41 43; 106 42 44; 107 45 47; 108 46 48; 109 49 51
43. 111 53 55; 113 57 59; 115 61 63; 116 62 64; 117 65 67; 118 66 68; 119 69 71
44. 120 70 72; 121 73 75; 122 74 76; 123 77 79; 124 78 80; 125 6 9; 126 9 14
45. 127 14 17; 128 8 11; 129 11 16; 130 16 19; 131 29 30; 132 31 32; 133 33 34
46. 134 35 36; 135 37 38; 136 39 40; 137 41 42; 138 43 44; 139 45 46; 140 47 48
47. 141 49 50; 142 51 52; 143 53 54; 144 55 56; 145 57 58; 146 59 60; 147 61 62
48. 148 63 64; 149 65 66; 150 67 68; 151 69 70; 152 71 72; 153 73 74; 154 75 76
49. 155 77 78; 156 79 80; 157 22 32; 158 32 34; 159 34 40; 160 40 42; 161 42 48
50. 166 64 66; 167 66 72; 168 72 74; 169 74 80; 170 80 24; 171 21 31; 172 31 33
51. 173 33 39; 174 39 41; 175 41 47; 176 47 49; 177 49 55; 178 55 57; 179 57 63
52. 180 63 65; 181 65 71; 182 71 73; 183 73 79; 184 79 23; 185 81 33; 186 82 77
53. 187 83 34; 188 84 78; 189 85 17; 190 86 18; 191 87 19; 192 88 20; 193 86 83
54. 194 85 81; 195 88 84; 196 87 82; 199 53 51; 200 53 59; 201 48 51; 202 47 52
55. 203 52 55; 204 51 56; 205 56 59; 206 55 60; 207 60 63; 208 59 64; 209 64 67
56. 210 63 68; 211 44 47; 212 43 48; 213 22 29; 214 29 34; 215 34 37; 216 37 42
57. 217 42 45; 218 45 50; 219 50 53; 220 53 58; 221 58 61; 222 61 66; 223 66 69
58. 224 69 74; 225 74 82; 226 82 78; 227 78 23; 228 21 30; 229 30 33; 230 33 38
59. 231 38 41; 232 41 46; 233 46 49; 234 49 54; 235 54 57; 236 57 62; 237 62 65
60. 238 65 70; 239 70 73; 240 73 84; 241 84 77; 242 77 24
61. SURFACE INCIDENCE
62. 46 48 64 62 SURFACE 1
63. START GROUP DEFINITION
64. MEMBER
65. _MAIN_1 1 TO 24 189 TO 192
66. _HORI_1 27 TO 94 99 TO 109 111 113 115 TO 124 131 TO 156 185 TO 188
67. _DIAG_1 125 TO 130 157 TO 161 166 TO 184
68. _MISC_1 137 TO 150 201 TO 212 217 TO 222 232 TO 237
69. _HB_1 43 TO 48 57 TO 62 71 TO 76 85 TO 90
70. _MAIN 7 TO 12 19 TO 24 190 192
71. _H11 100 102 104 120 122 124 157 TO 161 166 TO 170 193 195 213
72. _H22 53 TO 56 63 TO 66 81 TO 84 91 TO 94 187 188
73. _H33 57 TO 62 85 TO 90
74. _V11 106 108 116 118
75. _72X72X4 108 116
76. JOINT
77. END GROUP DEFINITION
78. DEFINE MATERIAL START
79. ISOTROPIC STEEL
80. E 2.05E+008
81. POISSON 0.3
82. DENSITY 76.8195
83. ALPHA 1.2E-005
84. DAMP 0.03
85. TYPE STEEL
86. STRENGTH FY 253200 FU 407800 RY 1.5 RT 1.2
87. ISOTROPIC CONCRETE
88. E 2.17185E+007
89. POISSON 0.17
90. DENSITY 23.5616
91. ALPHA 1E-005
92. DAMP 0.05
93. TYPE CONCRETE
94. STRENGTH FCU 27579

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 2 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 3

95. END DEFINE MATERIAL


96. MEMBER PROPERTY INDIAN
97. 1 TO 24 189 TO 192 TABLE ST TUBE TH 0.0048 WT 0.132 DT 0.132
98. 27 TO 38 131 TO 156 TABLE ST TUBE TH 0.0036 WT 0.05 DT 0.05
99. 99 TO 104 119 TO 130 157 TO 161 166 TO 184 193 TO 196 199 200 213 TO 216 223 -
100. 224 TO 231 238 TO 242 TABLE ST TUBE TH 0.0036 WT 0.05 DT 0.05
101. 105 TO 107 109 111 113 115 117 118 201 TO 212 217 TO 222 232 TO 236 -
102. 237 TABLE ST TUBE TH 0.004 WT 0.072 DT 0.072
103. 39 TO 42 49 TO 56 63 TO 70 77 TO 84 91 TO 94 185 TO 187 -
104. 188 TABLE ST TUBE TH 0.0032 WT 0.08 DT 0.08
105. 43 TO 48 57 TO 62 71 TO 76 85 TO 90 TABLE ST TUBE TH 0.0032 WT 0.1 DT 0.1
106. 108 116 TABLE ST TUBE TH 0.0036 WT 0.0915 DT 0.0915
107. SURFACE PROPERTY
108. 1 THICKNESS 0.0001
109. CONSTANTS
110. MATERIAL STEEL MEMB 1 TO 24 27 TO 94 99 TO 109 111 113 115 TO 161 166 TO 196 -
111. 199 TO 242
112. SURFACE CONSTANTS
113. MATERIAL STEEL ALL
114. SUPPORTS
115. 1 TO 4 PINNED
116. *BASIC WIND SPEED VB = 47 M/S
117. * LOAD F = CF X AE X PD
118. * CF = 2
119. * K1 = 0.90 (DESIGN PEROID = 25YRS), K2 = 1.0 (TER. CAT.=2), K3 = 1.0, K4 = 1.0
120. * CF FOR MAIN LEG - 1.3
121. * CF FOR HORIZONTAL - 1.3
122. * CF FOR VERT - 1.3
123. * CF FOR VMS SHEET - 2.0
124. * REDUCTION FACTOR = 0.66 FOR VMS
125. * KD = 1.0, KA = 1.0, KC = 1.0
126. * VZ = VB*K1*K2*K3*K4 M/S, 42.3 M/S
127. * PZ = 0.6*VZ^2 N/M^2 = 1073.574 N/M^2
128. * PD = PZ*KA*KD*KC N/M^2 = 1073.574 N/M^2
129. * PD = 1.074 KN/M^2
130. * F = 1.3*0.132*1.074 =0.184 KN/M (FOR MAIN LEG)
131. * F = 1.3*0.08*1.074 =0.112 KN/M (FOR HORIZONTAL)
132. * F = 1.3*0.1*1.074 =0.139 KN/M (FOR HORIZONTAL)
133. * F = 1.3*0.050*1.074 =0.069 KN/M (FOR VER@DIAG)
134. * F = 1.3*0.072*1.074 =0.1 KN/M (FOR VER)
135. * F = 1.3*0.0915*1.074 =0.128 KN/M (FOR VER)
136. * F = 2*0.66*1.074 =1.42 KN/SQM (FOR VMS)
137. ***********************************************************
138. LOAD 1 LOADTYPE DEAD TITLE DL
139. SELFWEIGHT Y -1.1
140. FLOOR LOAD
141. YRANGE 4.977 4.977 FLOAD -0.04 XRANGE 6.75 18.5 ZRANGE 0 1 GY
**NOTE** about Floor/OneWay Loads/Weights.
Please note that depending on the shape of the floor you may
have to break up the FLOOR/ONEWAY LOAD into multiple commands.
For details please refer to Technical Reference Manual
Section 5.32.4.2 Note d and/or "5.32.4.3 Note f.

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 3 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 4

142. MEMBER LOAD


143. 108 116 CON GY -5.5
144. LOAD 2 LOADTYPE LIVE TITLE LL
145. FLOOR LOAD
146. YRANGE 4.977 4.977 FLOAD -1.5 XRANGE 6.75 18.5 ZRANGE 0 1 GY
147. LOAD 3 LOADTYPE WIND TITLE WIND LOAD BODY
148. MEMBER LOAD
149. *******MAIN LEG***********
150. 7 TO 12 19 TO 24 190 192 UNI GZ -0.184
151. *******HORIZONTAL***********
152. 100 102 104 120 122 124 157 TO 161 166 TO 170 193 195 213 UNI GZ -0.069
153. 53 TO 56 63 TO 66 81 TO 84 91 TO 94 187 188 UNI GZ -0.112
154. 57 TO 62 85 TO 90 UNI GZ -0.139
155. 106 118 UNI GZ -0.1
156. 108 116 UNI GZ -0.128
157. *******VMS LOAD***********
158. SURFACE LOAD
159. 1 PR GZ -1.42
160. ******************************************************************************
161. **LIMIT STATE COMBINATION
162. LOAD COMB 4 1.5DL+1.5LL
163. 1 1.5 2 1.5
164. LOAD COMB 5 1.5DL+1.5WL
165. 1 1.5 3 1.5
166. LOAD COMB 6 1.2DL+1.2LL+1.2WL
167. 1 1.2 2 1.2 3 1.2
168. ******************************************************************************
169. **SERVICE LOAD COMBINATION
170. LOAD COMB 7 1.0DL+1.0LL
171. 1 1.0 2 1.0
172. LOAD COMB 8 1.0DL+1.0WL
173. 1 1.0 3 1.0
174. LOAD COMB 9 1.0DL+0.8LL+0.8WL
175. 1 0.8 2 0.8 3 0.8
176. **LOAD COMBINATION FOR FOUNDATION****
177. LOAD COMB 10 1.0DL+1.0LL+1.0WL
178. 1 1.0 2 1.0 3 1.0
179. ******************************************************************************
180. PERFORM ANALYSIS

P R O B L E M S T A T I S T I C S
-----------------------------------

NUMBER OF JOINTS 199 NUMBER OF MEMBERS 227


NUMBER OF PLATES 100 NUMBER OF SOLIDS 0
NUMBER OF SURFACES 1 NUMBER OF SUPPORTS 4

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 4 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 5

SOLVER USED IS THE IN-CORE ADVANCED MATH SOLVER

TOTAL PRIMARY LOAD CASES = 3, TOTAL DEGREES OF FREEDOM = 1182


TOTAL LOAD COMBINATION CASES = 7 SO FAR.

181. LOAD LIST 4 TO 10


182. PARAMETER 1
183. CODE IS800 LSD
184. FU 410000 ALL
185. FYLD 250000 ALL
186. CHECK CODE ALL

|----------------------------------------------------------------------------------|
| Member Number: 1 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.324 Critical Load Case: 2 Location: 0.45 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 2 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.320 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 3 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.182 Critical Load Case: 2 Location: 1.40 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 5 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 6

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 4 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.222 Critical Load Case: 2 Location: 0.54 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 5 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.186 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 6 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.091 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 7 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.180 Critical Load Case: 2 Location: 0.45 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 6 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 7

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 8 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.149 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 9 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.104 Critical Load Case: 2 Location: 1.40 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 10 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.104 Critical Load Case: 1 Location: 0.54 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 11 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.162 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 7 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 8

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 12 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.106 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 13 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.323 Critical Load Case: 2 Location: 0.45 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 14 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.319 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 15 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.186 Critical Load Case: 3 Location: 1.40 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 8 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 9

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 16 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.224 Critical Load Case: 3 Location: 0.54 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 17 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.184 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 18 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.090 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 19 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.179 Critical Load Case: 2 Location: 0.45 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 9 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 10

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 20 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.148 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 21 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.114 Critical Load Case: 1 Location: 1.40 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 22 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.117 Critical Load Case: 1 Location: 0.54 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 23 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.160 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 10 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 11

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 24 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.105 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 27 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.055 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 28 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.055 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 29 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.014 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 11 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 12

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 30 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.014 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 31 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.019 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 32 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.019 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 33 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.041 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 12 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 13

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 34 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.041 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 35 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.033 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 36 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.033 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 37 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.061 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 13 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 14

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 38 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.060 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 39 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.023 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 40 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.049 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 41 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.108 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 14 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 15

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 42 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.139 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 43 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.179 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 44 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.202 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 45 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.199 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 15 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 16

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 46 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.199 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 47 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.202 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 48 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.180 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 49 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.139 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 16 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 17

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 50 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.108 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 51 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.054 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 52 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.027 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 53 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.016 Critical Load Case: 2 Location: 0.75 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 17 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 18

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 54 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.045 Critical Load Case: 2 Location: 0.75 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 55 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.064 Critical Load Case: 2 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 56 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.095 Critical Load Case: 2 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 57 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.111 Critical Load Case: 2 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 18 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 19

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 58 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.111 Critical Load Case: 2 Location: 1.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 59 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.125 Critical Load Case: 2 Location: 0.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 60 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.125 Critical Load Case: 2 Location: 1.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 61 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.111 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 19 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 20

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 62 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.111 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 63 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.095 Critical Load Case: 2 Location: 0.12 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 64 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.064 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 65 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.048 Critical Load Case: 2 Location: 0.75 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 20 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 21

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 66 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.018 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 67 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.039 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 68 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.055 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 69 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.050 Critical Load Case: 2 Location: 1.50 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 21 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 22

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 70 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.092 Critical Load Case: 3 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 71 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.052 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 72 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.086 Critical Load Case: 1 Location: 1.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 73 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.078 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 22 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 23

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 74 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.080 Critical Load Case: 1 Location: 1.25 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 75 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.090 Critical Load Case: 1 Location: 0.33 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 76 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.065 Critical Load Case: 1 Location: 1.25 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 77 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.103 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 23 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 24

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 78 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.057 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 79 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.062 Critical Load Case: 3 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 80 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.038 Critical Load Case: 2 Location: 0.75 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 81 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.039 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 24 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 25

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 82 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.056 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 83 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.061 Critical Load Case: 2 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 84 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.104 Critical Load Case: 3 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 85 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.081 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 25 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 26

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 86 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.103 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 87 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.094 Critical Load Case: 3 Location: 0.25 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 88 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.094 Critical Load Case: 3 Location: 1.25 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 89 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.100 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 26 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 27

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 90 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.087 Critical Load Case: 3 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 91 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.113 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 92 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.066 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 93 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.060 Critical Load Case: 3 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 27 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 28

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 94 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.039 Critical Load Case: 2 Location: 0.75 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 99 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.008 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 100 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.009 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 101 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.009 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 28 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 29

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 102 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.009 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 103 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.013 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 104 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.013 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 105 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.038 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 29 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 30

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 106 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.035 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 107 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.018 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 108 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.026 Critical Load Case: 2 Location: 2.12 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 109 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.019 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 30 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 31

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 111 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.021 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 113 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.017 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 115 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.018 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 116 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.026 Critical Load Case: 2 Location: 2.12 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 31 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 32

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 117 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.038 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 118 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.035 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 119 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.013 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 120 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.013 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 32 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 33

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 121 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.010 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 122 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.010 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 123 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.008 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 124 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.010 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 33 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 34

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 125 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.081 Critical Load Case: 2 Location: 1.72 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 126 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.059 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 127 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.077 Critical Load Case: 2 Location: 1.72 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 128 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.081 Critical Load Case: 2 Location: 1.72 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 34 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 35

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 129 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.059 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 130 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.076 Critical Load Case: 2 Location: 1.72 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 131 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.010 Critical Load Case: 2 Location: 1.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 132 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.060 Critical Load Case: 2 Location: 1.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 35 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 36

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 133 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.019 Critical Load Case: 2 Location: 1.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 134 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.079 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 135 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.021 Critical Load Case: 3 Location: 1.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 136 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.073 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 36 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 37

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 137 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.037 Critical Load Case: 2 Location: 1.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 138 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.023 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 139 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.028 Critical Load Case: 1 Location: 1.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 140 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.024 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 37 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 38

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 141 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.033 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 142 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.027 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 143 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.041 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 144 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.033 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 38 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 39

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 145 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.034 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 146 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.028 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 147 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.032 Critical Load Case: 1 Location: 0.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 148 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.027 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 39 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 40

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 149 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.041 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 150 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.023 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 151 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.028 Critical Load Case: 1 Location: 0.50 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 152 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.073 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 40 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 41

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 153 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.016 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 154 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.079 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 155 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.008 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 156 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.060 Critical Load Case: 2 Location: 1.00 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 41 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 42

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 157 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.037 Critical Load Case: 1 Location: 2.25 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 158 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.041 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 159 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.047 Critical Load Case: 1 Location: 2.60 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 160 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.038 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 42 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 43

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 161 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.040 Critical Load Case: 1 Location: 2.60 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 166 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.033 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 167 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.037 Critical Load Case: 1 Location: 2.60 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 168 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.052 Critical Load Case: 1 Location: 2.38 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 43 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 44

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 169 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.051 Critical Load Case: 1 Location: 2.60 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 170 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.050 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 171 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.036 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 172 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.038 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 44 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 45

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 173 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.047 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 174 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.033 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 175 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.031 Critical Load Case: 1 Location: 2.60 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 176 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.020 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 45 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 46

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 177 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.011 Critical Load Case: 2 Location: 2.60 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 178 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.011 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 179 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.009 Critical Load Case: 1 Location: 2.34 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 180 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.022 Critical Load Case: 1 Location: 2.60 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 46 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 47

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 181 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.032 Critical Load Case: 3 Location: 2.60 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 182 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.052 Critical Load Case: 3 Location: 2.60 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 183 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.048 Critical Load Case: 3 Location: 2.60 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 184 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.048 Critical Load Case: 3 Location: 2.25 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 47 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 48

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 185 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.043 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 186 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.042 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 187 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.041 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 188 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.032 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 48 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 49

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 189 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.214 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 190 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.140 Critical Load Case: 2 Location: 0.86 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 191 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.216 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 192 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.138 Critical Load Case: 2 Location: 0.86 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 49 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 50

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 193 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.009 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 194 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.013 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 195 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.010 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 196 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.015 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 50 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 51

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 199 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.014 Critical Load Case: 3 Location: 2.60 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 200 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.012 Critical Load Case: 2 Location: 2.60 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 201 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.019 Critical Load Case: 1 Location: 1.41 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 202 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.025 Critical Load Case: 3 Location: 1.41 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 51 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 52

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 203 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.036 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 204 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.037 Critical Load Case: 3 Location: 1.80 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 205 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.037 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 206 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.038 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 52 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 53

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 207 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.025 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 208 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.022 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 209 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.051 Critical Load Case: 3 Location: 1.80 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 210 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.034 Critical Load Case: 1 Location: 1.80 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 53 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 54

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 211 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.028 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 212 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.049 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 213 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.016 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 214 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.027 Critical Load Case: 2 Location: 1.80 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 54 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 55

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 215 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.028 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 216 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.017 Critical Load Case: 2 Location: 1.80 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 217 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.032 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 218 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.017 Critical Load Case: 2 Location: 1.41 |
| Critical Condition: Sec. 8.2.1.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 55 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 56

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 219 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.030 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 220 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.031 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 221 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.017 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 8.2.1.2 |

|----------------------------------------------------------------------------------|
| Member Number: 222 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.034 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 56 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 57

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 223 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.017 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 224 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.030 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 225 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.026 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 226 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.015 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 57 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 58

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 227 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.027 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 228 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.028 Critical Load Case: 2 Location: 1.25 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 229 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.023 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 230 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.015 Critical Load Case: 2 Location: 1.50 |
| Critical Condition: Sec. 9.3.2.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 58 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 59

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 231 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.026 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 232 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.028 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 233 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.017 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 234 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.030 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 59 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 60

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 235 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.030 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 236 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.018 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 237 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.030 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 238 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.027 Critical Load Case: 3 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 60 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 61

STAAD.PRO CODE CHECKING - IS-800-2007-LSD (V2.0)


****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 239 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.018 Critical Load Case: 1 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 240 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.014 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

|----------------------------------------------------------------------------------|
| Member Number: 241 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.020 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 |

|----------------------------------------------------------------------------------|
| Member Number: 242 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.016 Critical Load Case: 2 Location: 0.00 |
| Critical Condition: Sec. 6.2 |

187. STEEL TAKE OFF ALL

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 61 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 62

STEEL TAKE-OFF
--------------

PROFILE LENGTH(METE) WEIGHT(KN )

ST TUB E 28.39 5.326


ST TUB E 175.05 8.985
ST TUB E 42.00 3.172
ST TUB E 32.00 3.046
ST TUB E 59.24 4.951
ST TUB E 4.24 0.412
----------------
TOTAL = 25.892

************ END OF DATA FROM INTERNAL STORAGE ************

188. FINISH

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 62 of 63


Wednesday, July 13, 2022, 03:36 PM
STAAD SPACE -- PAGE NO. 63

*********** END OF THE STAAD.Pro RUN ***********

**** DATE= JUL 13,2022 TIME= 15:36:14 ****

************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://selectservices.bentley.com/en-US/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) 1997-2015 Bentley Systems, Inc.
* http://www.bentley.com *
************************************************************

C:\Users\Dell\Desktop\GANTRY GIRDER\STAAD\STAAD@QUALIX-18.5M GANTRY.anl Page 63 of 63


SECTION 9

STRUCTUTRE FABRICATION
DRAWING & BOM
NOTE :

27 27

28 28

B
30 30

20 20 20 20 20A 20A 20A 20A 20 20 20 20 20

A
20 25 29 29 25

1 26 30 30 26 2

20A

NATIONAL HIGHWAYS AUTHORITY OF INDIA


(Ministry of Road Transport & Highways)
14 14 (Government of India)

6 6
1B 1B
9 10 9
6 6 8 CHAITANYA PROJECTS
15 12 12 15
CONSULTANCY PVT. LTD.
16 16
RK Tower, Sector 4, Vaishali, Ghaziabad,
11 11 Uttar Pradesh-201010

5 5
15 15
11 11
M/s. RAVI INFRABUILS PROJECT
11 15A 15A 11
PVT.LTD.

13

13
1A 1A
95 Hiran Magri, Sec 11
5 5 8 Udaipur - 313002
36
A
9 10 9
B

QUALIX INFORMATION SYSTEM LLP.


B-29, Sector 4,
37 Noida, Uttar Pradesh 201301
17 17

ZCC TECHNO PVT.LTD.

4 4

CONSTRUCTION OF 6-LANE ACCESS CONTROLLED GREENFIELD


HIGHWAY AS A SECTION OF SANGARIYA-SANTALPUR NATIONAL
HIGHWAY NO. 754K COMMENCING AT CH. 4+888 AT RAJASTHAN/
GUJARAT BORDER (NEAR VANTDAU) AND ENDS AT CH. 35+000
(NEAR THARAD) AND PASSING THROUGH 20.782KM OF EXISTING
NH-68 AND 9.33KM GREENFIELD AREA IN THE STATE OF GUJARAT
AS A PART OF AMRITSAR-JAMNAGAR ECONOMIC CORRIDOR ON
EPC UNDER BHARATMALA PARIYOJANA (AJ/RJBS-PACKAGE-1)

3 BOTTOM OF BASE PL. LEVEL. 3


4 4
TITLE:
2 ROAD LEVEL. 2
OVERHEAD GANTRY STRUCTURE
DETAILS FOR VSDS
DWG. NO: PR/AJ/RGBS/PKG1/008
1 2

SHEET. : 1 OF 4

DATE : 07/04/2022 SCALE. : AS SHOWN

DRAWN BY CHKD. BY APPROVED BY


3
3 3 F. MANDAL J.K.R S. G
B
2 2
4 4 R0
4 4

A
3 3
1 1

1 2 3
NOTE :

14 14

6 6

A
9 10 9

15 12 16 19 19 12 15
16

11 11
12A

12A 12A 5
15 12A 15
11 11 NATIONAL HIGHWAYS AUTHORITY OF INDIA
18 (Ministry of Road Transport & Highways)
15A 19A 19 15A
11 11 (Government of India)

12A 18 19
A 19A A
9 10 9
B CHAITANYA PROJECTS
CONSULTANCY PVT. LTD.
RK Tower, Sector 4, Vaishali, Ghaziabad,
17 17 Uttar Pradesh-201010

M/s. RAVI INFRABUILS PROJECT


PVT.LTD.
95 Hiran Magri, Sec 11
Udaipur - 313002
4 4

QUALIX INFORMATION SYSTEM LLP.


B-29, Sector 4,
Noida, Uttar Pradesh 201301

BOTTOM OF BASE PL. LEVEL.


ZCC TECHNO PVT.LTD.
3 3

2 ROAD LEVEL. 2

CONSTRUCTION OF 6-LANE ACCESS CONTROLLED GREENFIELD


HIGHWAY AS A SECTION OF SANGARIYA-SANTALPUR NATIONAL
1 2 HIGHWAY NO. 754K COMMENCING AT CH. 4+888 AT RAJASTHAN/
GUJARAT BORDER (NEAR VANTDAU) AND ENDS AT CH. 35+000
(NEAR THARAD) AND PASSING THROUGH 20.782KM OF EXISTING
NH-68 AND 9.33KM GREENFIELD AREA IN THE STATE OF GUJARAT
AS A PART OF AMRITSAR-JAMNAGAR ECONOMIC CORRIDOR ON
EPC UNDER BHARATMALA PARIYOJANA (AJ/RJBS-PACKAGE-1)

TITLE:
OVERHEAD GANTRY STRUCTURE
27 27 DETAILS FOR VSDS
28 28
DWG. NO: PR/AJ/RGBS/PKG1/008
3A
SHEET. : 2 OF 4
B
22 24 23 24 24 23 30 30 23 24 24 23 24 22
DATE : 07/04/2022 SCALE. : AS SHOWN
20 20 20 20 20A 20A 20A 20A 20A 20 20 20 20 20
24 24
21 24 24 21 DRAWN BY CHKD. BY APPROVED BY
A
37
23 20 25 29 29 25 20 23 F. MANDAL J.K.R S. G
22 22
1 24 26 30 30 36
26 24 2 3A R0
NOTE :

6 6 6 6
7

33 33
34 35
33
7
7
5
5 5 5
34 35
7
34 35
CB1

32 5 5 32
31 31
8 NATIONAL HIGHWAYS AUTHORITY OF INDIA
(Ministry of Road Transport & Highways)
(Government of India)
7

31 31
37

8
32 32 CHAITANYA PROJECTS
CONSULTANCY PVT. LTD.
4 4 4 4
RK Tower, Sector 4, Vaishali, Ghaziabad,
Uttar Pradesh-201010

8
M/s. RAVI INFRABUILS PROJECT
8
PVT.LTD.
7 95 Hiran Magri, Sec 11
BOTTOM OF BASE PL. LEVEL. Udaipur - 313002
3 3
31

2 2 ROAD LEVEL.

QUALIX INFORMATION SYSTEM LLP.


32 B-29, Sector 4,
Noida, Uttar Pradesh 201301
CB1
A B A B

ZCC TECHNO PVT.LTD.

CONSTRUCTION OF 6-LANE ACCESS CONTROLLED GREENFIELD


HIGHWAY AS A SECTION OF SANGARIYA-SANTALPUR NATIONAL
HIGHWAY NO. 754K COMMENCING AT CH. 4+888 AT RAJASTHAN/
GUJARAT BORDER (NEAR VANTDAU) AND ENDS AT CH. 35+000
2 (NEAR THARAD) AND PASSING THROUGH 20.782KM OF EXISTING
NH-68 AND 9.33KM GREENFIELD AREA IN THE STATE OF GUJARAT
AS A PART OF AMRITSAR-JAMNAGAR ECONOMIC CORRIDOR ON
1
EPC UNDER BHARATMALA PARIYOJANA (AJ/RJBS-PACKAGE-1)

TITLE:
3
OVERHEAD GANTRY STRUCTURE
AB1 DETAILS FOR VSDS
36

DWG. NO: PR/AJ/RGBS/PKG1/008


SHEET. : 3 OF 4

DATE : 07/04/2022 SCALE. : AS SHOWN

DRAWN BY CHKD. BY APPROVED BY


F. MANDAL J.K.R S. G

B R0

A
37
38

1 2
NATIONAL HIGHWAYS AUTHORITY OF INDIA
(Ministry of Road Transport & Highways)
(Government of India)

CHAITANYA PROJECTS
CONSULTANCY PVT. LTD.
RK Tower, Sector 4, Vaishali, Ghaziabad,
Uttar Pradesh-201010

M/s. RAVI INFRABUILS PROJECT


PVT.LTD.
95 Hiran Magri, Sec 11
Udaipur - 313002

QUALIX INFORMATION SYSTEM LLP.


B-29, Sector 4,
Noida, Uttar Pradesh 201301

ZCC TECHNO PVT.LTD.

CONSTRUCTION OF 6-LANE ACCESS CONTROLLED GREENFIELD


HIGHWAY AS A SECTION OF SANGARIYA-SANTALPUR NATIONAL
HIGHWAY NO. 754K COMMENCING AT CH. 4+888 AT RAJASTHAN/
GUJARAT BORDER (NEAR VANTDAU) AND ENDS AT CH. 35+000
(NEAR THARAD) AND PASSING THROUGH 20.782KM OF EXISTING
NH-68 AND 9.33KM GREENFIELD AREA IN THE STATE OF GUJARAT
AS A PART OF AMRITSAR-JAMNAGAR ECONOMIC CORRIDOR ON
EPC UNDER BHARATMALA PARIYOJANA (AJ/RJBS-PACKAGE-1)

TITLE:
OVERHEAD GANTRY STRUCTURE
DETAILS FOR VSDS
DWG. NO: PR/AJ/RGBS/PKG1/008
SHEET. : 4 OF 4

DATE : 07/04/2022 SCALE. : AS SHOWN

DRAWN BY CHKD. BY APPROVED BY


F. MANDAL J.K.R S. G

R0