This is a load bearing structure the load from POLE base is transferred to the wall.Then the checking of load bearing structure
wall A-A & B-B are manually done.
During design & analysis the dead load, live load & Pole support reaction only to be considered .
IS: 1905-1987
IS : 875 Part 1
IS : 875 Part 2
SP 20 : 1991
= [(0.75*5.1)/ 27]
= 0.14
Therefore thickness of wall Tw = 0.23 > 0.14
Hence (O.K.)
Slab load distributed on wall = Effective area of Slab load X (slab load on wall)
Slab load distributed on wall = Effective area of Slab load X (slab load on wall)