You are on page 1of 1

Reference: VISP-NDT-008-A

Velosi Integrity & Safety Pakistan Page: 1 of 1

Pvt. Ltd Rev. no: 00

ULTRASONIC EXAMINATION A-SCAN REPORT


ULTRASONIC A-SCAN Report No :
Client MPCL Date 3/28/2022

Drawing No. 2981-CMF-2-L1-001 Calibration Block V2 & Step Wedge

Line No. 10" EFL-II Meter Run Bypass Reference Code ASME Section V

Location CMF 2,MPCL Dahrki Field Couplant Gel

Material Pipe=ASTM A-106 Gr B, Fittings=A234 Gr-WPB Scanning Technique Pulse Echo

Surface Condition Painted Overlap 10%

Reference Code: ASME Section V Acceptance Criteria : ASME B31.3


Scan Plan
Search Units Sensitivity (Db)
Element size Echoes Height
Sr.# Freq MHz Probe Model Wave Type Wave Angle Gain (Db)
(mm)
1 5 D7906-SM 10 Longitudinal 0˚ 33 80%

Evaluation
Grid Minimum Thickness in Millimeter (mm) Remarks
Sr. # Grid No. Grid Description
Minimum Design
12 to 3 O'clock 3 to 6 O'clock 6 to 9 O'clock 9 to 12 O'clock Metal Loss
Thickness Thickness
1 16 Pipe 10" 13.36 14.47 14.08 13.45 13.36 - -
2 17 Pipe 10" 13.83 14.09 13.95 14.86 13.83 - -
3 18 Elbow 10" 10.51 10.22 11.72 12.17 10.22 - -
4 19 Pipe 10" 14.91 14.96 14.91 14.66 14.66 - -
5 20 Pipe 10" 14.08 14.16 14.64 14.61 14.08 - -
6 21 Pipe 10" 14.84 14.79 14.35 14.35 14.35 - -
7 22 Pipe 10" 15.29 14.38 14.78 14.77 14.38 - -
8 23 Pipe 10" 11.88 12.09 11.96 11.66 11.66 - -
9 24 Pipe 10" 11.30 11.24 11.58 12.37 11.24 - -
10 25 Pipe 10" 11.33 12.08 11.16 10.92 10.92 - -
11 26 Pipe 10" 11.64 11.87 11.72 11.49 11.49 - -
12 27 Pipe 10" 11.96 11.89 11.66 11.70 11.66 - -
13 28 Pipe 10" 11.69 11.82 11.78 11.67 11.67 - -
14 29 Pipe 10" 14.38 14.33 13.94 13.66 13.66 - -
15 30 Pipe 10" 12.66 12.00 11.90 12.71 11.90 - -
16 31 Reducer 10 x 8 11.79 11.62 12.66 12.97 11.62 - -
17 32 Reducer 10 x 8 13.27 12.17 14.66 13.98 12.17 - -
18 32A Elbow 8" 8.42 8.82 8.63 8.73 8.42 - -
19 32B Pipe 8" 8.59 7.15 8.56 8.88 7.15 - -
20 32C Pipe 8" 8.92 8.54 8.52 8.60 8.52 - -

Remarks: 01). 100% Scanning of fittings &100% Scanning at HAZ area of pipe lengths done of above items.
02). For thickness Monitoring Location kindly refer to attached drawing

Prepared By Reviewed By Approved By


Name: Waleed Ahmed & M.Danish Zia Name: Irfan Ahmed Khan Name: Muhammad Kamran Ibrahim

Designation: NDT Inspector Designation: Technical Manager Designation: Operations Manager

Signature: Signature: Signature: