Professional Documents
Culture Documents
B
∆I
I
2
I n = 1A 5A ( I o ) f n = 50Hz I o ∆I o IRF
5
I n = 1A 5A (∆I o ) 60Hz
SPAJ 115 C
STEP 2.5
80...265V –
~ ∆I o>
U aux [%]
18...80V – In STEP
0.5 5.0
SPCJ 2C30
20
REGISTERS I o>
[%] SG1
0 0 0 0 In 1
5.0 40 2
3
1 ∆ I o /I n [ % ] 4
5
2 I o /I n [ % ] 0.6 6
3 n (∆ I o> ) SGR 7
t o>[s] 8
4 n (I o> ) 1
k 0 1
2 0.1 1.0
5 t / t o> [ % ] 3
4
5 RESET
6
7
8
0 1
∆I o> I o>
1411
1304
Restricted earth-fault and residual earth-fault relay SPAJ 115 C 1MRS 750658-MUM EN
Combined restricted earth-fault and residual earth-fault
relay module SPCJ 2C30 1MRS 750659-MUM EN
General characteristics of C type relay modules 1MRS 750328-MUM EN
Features Sensitive restricted earth-fault protection stage Serial interface for two-way data communica-
for fast, selective earth-fault protection tion over fibre-optic bus between relay level and
superior system levels
Sensitive definite time or inverse time earth-
fault stage for back-up residual earth-fault pro- High immunity to electrical interference and
tection robust aluminium case to class IP54
Output relay functions freely configurable for Continuous self-supervision of hardware and
desired relay operations software, including auto-diagnostics
Flexible adaptation of the relay to a certain Powerful optional software support for setting,
application reading, copying and recording relay parame-
ters
Accurate settings and stable functions due to
fully digital relay design The relay is a member of the SPACOM product
family, which is compatible with PYRAMID™,
Local numerical display of setting values, meas- the coordinated protection and control concept
ured values and recorded fault values of ABB.
Application The combined restricted earth-fault and re- relay contains two energizing input circuits, that
sidual earth-fault relay SPAJ 115 C is intended is a differential earth-fault current circuit and a
to be used for the earth-fault protection of residual earth-fault current circuit.
power generators, motors and transformers. The
2
Principle of The combined restricted earth-fault and re- The start current of the restricted earth-fault
function sidual earth-fault relay SPAJ 115 C is a second- stage is set so high, that the stage cannot operate
ary relay which measures two energizing cur- on currents caused by external faults into the
rents; the differential current ∆I0 and the re- differential current circuit.
sidual current I0. When an earth-fault is de-
tected the relay operates, alarms and trips the When an earth-fault appears inside the area of
circuit breaker, according to the settings and protection, both transformers tend to feed cur-
configuration of the relay. rent into the differential current circuit and the
stage operates. To keep the resistance of the
The differential current is formed with an exter- secondary circuit as low as possible, the sum-
nal circuit, for instance the one shown in Fig. 2. ming point for the currents should be located as
close to the current transformers as possible.
The main earth-fault protection is formed by
the restricted earth-fault current stage ∆I0, which The back-up earth-fault protection is formed by
operates instantaneously, when the differential the residual current stage I0>, which can be
current exceeds the set start value of the re- given definite time or inverse time characteris-
stricted earth-fault stage. The restricted earth- tic.
fault stage operates exclusively on earth-faults
inside the area of protection. The area of protec- When the residual current exceeds the set star
tion is the area limited by the phase current value of the residual current stage I0>, the re-
transformers and the current transformer of the sidual current stage starts. After the set operate
neutral earthing circuit. The operation of the time t0> at definite time operation or the calcu-
restricted earth-fault stage on faults outside the lated operate time at inverse time operation the
area of protection is prevented with a stabilizing stage operates delivering a trip signal.
resistor, which is connected in series with the
matching transformer of the relay, see Fig. 2. When inverse time characteristic has been se-
lected four time/current curve sets according to
The operation of the restricted earth-fault stage IEC 255 and BS 142 are available. The curve
exclusively on faults inside the area of protection sets are referred to as "Normal inverse", "Very
is based on the fact, that the impedance of a inverse", "Extremely inverse" and "Long-time
transformer decreases as the transformer is satu- inverse".
rated. The reactance of the excitation circuit of
a fully saturated transformer is zero and in these The start signal of the relay, obtainable as a
cases the impedance is composed purely of the contact function, can, for example, be used as a
resistance of the coil. Under the influence of the blocking signal for other protection relays.
stabilizing resistor in the differential current
circuit the secondary current of the non-satu- The relay is provided with one optically isolated
rated transformer is forced to flow through the control input, which can be used as a blocking
secondary circuit of the saturated transformer. input.
TRIP 1
∆ Io
INSTANTANEOUS RESTRICTED
87N
EARTH-FAULT PROTECTION STAGE
TRIP 2
Io
DEFINITE TIME OR INVERSE TIME
51N SIGNAL 1
NEUTRAL EARTH-FAULT STAGE
START 1
BLOCKING OF EITHER ONE OR BOTH
EARTH-FAULT PROTECTION STAGES
IRF
Fig. 1. Protection functions of the combined restricted earth-fault and residual earth-fault relay
SPAJ 115 C. The encircled numbers refer to the ANSI (=American National Standards Institute)
number of the concerned protection function.
3
Connections
L1
L2
0 -
L3
- Ι
I
+
0
+
Rx Tx
SPA-ZC_
+ (~)
Ru Uaux
- (~)
≅_ E D C B A
U3
+ - 1 1 1 1
SGR/1
U3
IRF SGR 2 4 7 5 8 6
∆Io> TS1
35 ms
SGB
4
5 SS2
t>,k TS2
Io>
U1 I/O
SPAJ 115 C U2
Fig. 2. Connection diagram for the combined restricted earth-fault and residual earth-fault relay
SPAJ 115 C
4
25 61
Serial Port
26 62
SPA
27 65
37 66
38 68
39 69
Made in Finland
80
81
77
70 78
71 10
72 11
B470703
Fig.3. Rear view of the restricted earth-fault and residual earth-fault relay SPAJ 115 C.
Contacts Function
The combined restricted earth-fault and re- on the rear panel of the relay. The opto-con-
sidual earth-fault relay SPAJ 115 C connects to nectors of the fibre-optic cables are plugged into
the fibre-optic data communication bus by means the counter connectors Rx and Tx on the bus
of the bus connection module SPA-ZC 17 or connection module. The selector switch for the
SPA-ZC 21. The bus connection module is mode of operation of the bus connection mod-
fitted to the D-type connector (SERIAL PORT) ule is to be set in position "SPA".
5
Configuration of The trip signal of the ∆I0> stage is firmly wired addition, the following functions can be se-
output relays to output relay A and the trip signal of the I0> lected with the switches of the SGR switchgroup
stage is firmly wired to output relay B. In on the front panel:
SGR/2 Routes the start signal of the I0> stage to output relay D 1
SGR/4 Routes the operate signal of the I0> stage to output relay D 1
SGR/5 Routes the operate signal of the I0> stage to output relay C 1
SGR/6 Routes the operate signal of the I0> stage to output relay A 1
SGR/7 Routes the operate signal of the ∆I0> stage to output relay C 1
SGR/8 Routes the operate signal of the ∆I0> stage to output relay B 1
The circuit breakers can be directly controlled output relay and two separate circuit breakers
with output relay A or output relay B. Thus can be controlled with the same earth-fault
either operation stage may have its own trip relay.
6
Start and B
with the RESET push-button. An unreset
∆I
operation 2
I indicator does not affect the operation of the
indicators I n = 1A 5A ( I o ) f n = 50Hz
5
I o ∆I o IRF relay.
I n = 1A 5A (∆I o ) 60Hz
SPAJ 115 C 2. The yellow LEDs (∆I0 and I0) on the upper
80...265V –
~ ∆I o>
STEP 2.5 black part of the front plate indicate, when lit,
18...80V – U aux In
[%]
0.5 5.0
STEP
that the value of the energizing current of the
SPCJ 2C30
concerned protection stage is being dis- played.
20
REGISTERS I o>
[%] SG1
0 0 0 0 In
5.0 40
1
2
3
3. The red IRF indicator of the self-supervision
∆ I o /I n [ % ]
1
2 I o /I n [ % ] 0.6
4
5
6
system indicates, when lit, that a permanent
3
4
n (∆ I o> )
n (I o> )
SGR
1
t o>[s]
7
8 internal relay fault has been detected. The
k 0 1
5 t / t o> [ % ]
2
3
4
0.1 1.0
fault code appearing on the display once a
RESET
5
6
7
fault has been detected should be recorded
0 1
8
and notified when service is ordered.
∆I o> I o>
1411
1304
Power supply The combined power supply and I/O module The power supply and I/O module is available
and I/O module (U2) is located behind the system front panel of in two versions which have different input volt-
the protection relay and can be withdrawn from age ranges:
the relay case after removal of the system front
panel. The power supply and I/O module incor- - type SPTU 240S1 Uaux = 80...265 V ac/dc
porates a power unit, four output relays, the - type SPTU 48S1 Uaux = 18...80 V dc
control circuits of the output relays and the
electronic circuitry of the external control in- The input voltage range of the power supply and
put. I/O module incorporated in the relay on deliv-
ery is marked on the system front panel of the
The power unit is transformer connected, that relay.
is, the primary circuit and the secondary circuits
are galvanically isolated. The primary circuit is
protected by a slow 1 A fuse F1, placed on the
PC board of the module. When the power
source operates properly, the green Uaux LED
on the front panel is lit.
7
Technical data Energizing inputs 1A 5A
Terminals 25–27, 37–39 25–26, 37–38
Rated current In 1A 5A
Thermal withstand capability
Continuous carry 4A 20 A
Make and carry for 10 s 25 A 100 A
Make and carry for 1 s 100 A 500 A
Dynamic current withstand capability,
half-wave value 250 A 1250 A
Input impedance <100 mΩ <20 mΩ
Rated frequency fn acc. to order 50 Hz or 60 Hz
Signalling contacts
Terminals 70-71-72, 77-78, 80-81
Rated voltage 250 V ac/dc
Carry continuously 5A
Make and carry for 0.5 s 10 A
Make and carry for 3 s 8A
Breaking capacity for dc, when the signalling
circuit time constant L/R ≤ 40 ms,
at the signalling voltages
- 220 V dc 0.15 A
- 110 V dc 0.25 A
- 48 V dc 1A
Contact material AgCdO2
8
Combined restricted earth-fault and residual earth-fault relay module SPCJ 2C30
Restricted earth-fault current stage ∆I0>
Start current ∆I0>, setting range 0.5...5% x In
Operate time 35 ms
Residual earth-fault current stage I0>
Start current I0>, setting range 5…40% x In
Selectable operation characteristic
- definite time characteristic
- operate time t0> 0.1…100 s
- inverse definite minimum time (IDMT) characteristic
- curve sets acc. to IEC 255-4 and BS 142 Normal inverse
Very inverse
Extremely inverse
Long-time inverse
- time multiplier k 0.05...1.00
Data communication
Transmission mode Fibre-optic serial bus
Data code ASCII
Selectable data transfer rates 300, 1200, 2400, 4800 or 9600 Bd
Fibre-optic bus connection module,
powered from the host relay
- for plastic fibre cables SPA-ZC 21 BB
- for glass fibre cables SPA-ZC 21 MM
Fibre-optic bus connection module,
powered from external power source
- for plastic fibre cables SPA-ZC 17 BB
- for glass fibre cables SPA-ZC 17 MM
Test voltages *)
Dielectric test voltage (IEC 255-5) 2 kV, 50 Hz, 1 min
Impulse test voltage (IEC 255-5) 5 kV, 1.2/50 µs, 0.5 J
Insulation resistance (IEC 255-5) >100 MΩ, 500 V dc
Disturbance tests *)
High-frequency (1 MHz) disturbance test
(IEC 255-22-1)
- common mode 2.5 kV
- differential mode 1.0 kV
Electrostatic discharge test (IEC 255-22-2
and IEC 801-2), class III
- air discharge 8 kV
- contact discharge 6 kV
Fast (5/50 ns) transients
- IEC 255-22-4, class III
- IEC 801-4, level IV:
power supply inputs 4 kV
other inputs 2 kV
Environmental conditions
Specified ambient service temperature range -10...+55°C
Long term damp heat withstand acc. to IEC 68-2-3 <95%, +40°C, 56 d/a
Relative humidity acc. to IEC 68-2-30 93...95%, +55°C, 6 cycles
Transport and storage temperature range -40...+70°C
Degree of protection by enclosure
for panel mounted relay IP 54
Weight of relay including flush mounting case 3.0 kg
*) The tests do not apply to the serial port, which is used for the bus connection module only.
9
Current The sensitivity and reliability of a resistor-stabi- Ikmax = Maximum through-fault current, for
transformer lized restricted earth-fault protection depends which the relay must not operate
requirements to a great extent on the current transformers to Rin = Resistance of the CT secondary circuit
be used. The number of turns of all the current Rm = Total resistance of the longest measur-
transformers of the same differential circuit ing circuit (to and from)
must be equal. n = CT transforming ration
10
Examples of
L1
application L2
L3
Example 1. TRIPPING OF EXCITATION
Generator earth- CIRCUIT BREAKER AND
SHUT DOWN OF PRIME
fault protection MOVER
TRIPPING OF
GENERATOR
CIRCUIT
BREAKER
Rx Tx
SPA-ZC_
Ru
Ir + (~)
Iu Uaux
- (~)
5A
1A
≅_ E D C B A
U3
+ - 1 1 1 1
SGR/1
U3
IRF SGR 2 4 7 5 8 6
TS1
∆Io>
35 ms
SGB
4
5 SS2
t>,k TS2
Io>
U1 I/O
SPAJ 115 C U2
Fig. 5. Generator earth-fault protection using the restricted earth-fault and residual earth-fault relay
SPAJ 115 C. The selector switch positions are shown in the table on the following page.
The restricted earth-fault stage ∆I0> acts as main ers, the current flows through the current trans-
earth-fault protection. The residual earth-fault formers and causes no relay operation. When
stage I0> acts as busbar earth-fault protection the earth-fault arises inside the area of protec-
and back-up earth-fault protection for the net- tion the current transformers feed current
work. through the differential current circuit and the
relay operates.
The stability of the restricted earth-fault protec-
tion stage is based on the fact that the impedance An external stabilizing resistor Rs is needed in
of a current transformer decreases when the the differential current measuring circuit. The
transformer saturates. The reactance of the exci- purpose of the stabilizing resistor is to prevent
tation circuit of a fully saturated current trans- the relay from operating on faults outside the
former is zero and thus the impedance is purely area of protection. The short time power with-
composed of the winding resistance. The stabi- stand capability of the stabilizing resistor must
lizing resistor in the differential current circuit be high enough to stand for the power appearing
forces the secondary current of the unsaturated in the differential current circuit. The most
current transformer to flow through the second- suitable resistor type is an open wire-wound
ary circuit of the saturated current transformer. resistor.
The start current of the restricted earth-fault
stage is set so high, that the protection does not The purpose of the voltage dependent resistor is
operate on currents induced in the circuit dur- to prevent the voltage from exceeding the insu-
ing faults outside the zone of protection. lation voltage level during in-zone faults. The
voltage dependent resistor must be so selected
When the earth-fault appears outside the zone that the current through the resistor at the
of protection limited by the current transform- stabilizing voltage level is as low as possible.
11
Current transformers with the same transform- The excitation current Ie corresponding to the
ing ratios and equal numbers of winding turns stabilizing voltage Us is determined either from
are selected. In order to minimize the length of the excitation curves provided by the CT manu-
the CT secondary circuits the summing point of facturer or by assuming a linear excitation curve
the secondary currents is to be located as close for voltage values below the knee-point voltage.
to the CT terminals as possible.
The value of the stabilizing resistor can be
The calculations for the restricted earth-fault calculated from the expression:
protection are performed using an iteration
Us
method. First the current transformers are de- Rs =
fined and then their suitability for the intended Ir
application is checked. The start current Ir can be changed, if needed,
by changing the value of Rs. It is recommended
The stabilizing voltage Us required by the pro- that the start current Ir is greater than the sum of
tection in through-fault situations is determined the excitation currents of the CTs. That is, the
according to the following expression: start current is to be Ir ≥ m x Ie, where m is the
number of CTs in the differential current cir-
I x (Rin + Rm)
Us = kmax cuit.
n
Ikmax = Maximum through-fault current, for The primary current value corresponding to the
which the relay must not operate. If the start current Ir is obtained from the expression:
current is unknown the generator is
given the value Ikmax ≈ 6 x In Iprim = n x (Ir + m x Ie + Iu)
Rin = Resistance of the CT secondary circuit
Rm = Total resistance of the longest measur- Iu = current through the varistor at Us,
ing circuit, i.e. from the summing point see Fig. 5.
to the current transformer
n = CT transforming ration, for example The selector switches of the relay SPAJ 115 C
n = 2000/5 A = 400 can be given the following settings:
Contact Function
65-66 Trip signal from the restricted earth-fault stage; opens the excitation CB and
stops the prime mover of the generator
68-69 Trip signal from the restricted earth-fault stage or the residual earth-fault stage;
opens the generator CB
80-81 Signal on operation of the restricted earth-fault stage
77-78 Signal on operation of the residual earth-fault stage
70-71-72 Self-supervision alarm signal
12
Example 2.
Earth-fault
L1
protection of the L2 TRIPPING OF THE
HIGH-VOLTAGE SIDE
high-voltage side of L3 CIRCUIT BREAKER
a power transformer
TRIPPING OF THE
LOW-VOLTAGE SIDE
CIRCUIT BREAKER
Rx Tx
Ru
SPA-ZC_
Iu Ir
+ (~)
Rs Uaux
- (~)
5A
1A ≅_ E D C B A
U3
+ - 1 1 1 1
SGR/1
U3
IRF SGR 2 4 7 5 8 6
TS1
∆Io>
35 ms
SGB
4
5 SS2
t>,k TS2
Io>
U1 I/O
SPAJ 115 C U2
Fig. 6. Transformer earth-fault protection using the restricted earth-fault and residual earth-fault
relay SPAJ 115 C. The selector switch positions are shown in the table on the next page.
13
The calculations are performed in the same way The selector switches of the relay SPAJ 115 C
as in the previous example. If the maximum can be given the following settings:
through-fault current Ikmax is not known, the
value 16 x In can be used when the settings for
the transformer protection are calculated.
∑ 172
Contact Function
65-66 Trip signal from the restricted earth-fault stage; opens the low-voltage side CB
68-69 Trip signal from the restricted earth-fault stage or the residual earth-fault stage;
opens the high-voltage side CB
80-81 Signal on operation of the restricted earth-fault stage
77-78 Signal on operation of the residual earth-fault stage
70-71-72 Self-supervision alarm signal
14
Example 3.
Earth-fault L1
protection of the L2
low-voltage side of L3
a power transformer
TRIPPING OF THE
HIGH-VOLTAGE SIDE
CIRCUIT BREAKER
TRIPPING OF THE
LOW-VOLTAGE SIDE
CIRCUIT BREAKER
Rx Tx
Ru
SPA-ZC_
Iu Ir
+ (~)
Uaux
Rs - (~)
5A
1A
≅_ E D C B A
U3
+ - 1 1 1 1
SGR/1
U3
IRF SGR 2 4 7 5 8 6
∆Io> TS1
35 ms
SGB
4
5 SS2
t>,k TS2
Io>
U1 I/O
SPAJ 115 C U2
Fig. 7. Transformer earth-fault protection using the restricted earth-fault and residual earth-fault
relay SPAJ 115 C. The selector switch positions are shown in the table on the next page.
15
In this example the residual earth-fault stage is the residual earth-fault stage operates. An in-
used as a fast feeder cubicle and busbar earth- coming blocking signal is routed to the residual
fault protection. Should the fault appear on the earth-fault stage by means of switch SGB/5 in
feeder, the feeder earth-fault relay transmits a the relay module SPCJ 2C30.
blocking signal to the residual earth-fault stage
of the infeeder cubicle. Should the earth-fault, The selector switches of the protection relay
however, appear in the infeeder cubicle or on the module SPAJ 115 C can be set as follows:
busbars, no blocking signal will be obtained and
∑ 12
Contact Function
65-66 Trip signal from the restricted earth-fault stage; opens the high-voltage side CB
68-69 Trip signal from the restricted earth-fault stage or the residual earth-fault stage;
opens the low-voltage side CB
80-81 Signal on operation of the restricted earth-fault stage
77-78 Signal on operation of the residual earth-fault stage
70-71-72 Self-supervision alarm signal
16
Recorded The data registered by the relay can be used to values can be compared with the residual cur-
information analyze the faults and the behaviour of the rent values measured by the relay under normal
protection. operation conditions.
Register 1 contains the maximum value of the Register 3 records the number of operations of
differential current as a percentage of the rated the differential current stage ∆I0>.
current of the used energizing input. The regis-
ter is updated, if The number of starts of the the residual earth-
- the value of the measured current exceeds the fault stage, register 4, provides information about
value already in the register how frequently earth-faults appear in the net-
- the relay operates. At relay operation the value work. Frequent starts may indicate an imminent
of the current at operation is recorded. earth-fault caused, for instance, by a broken
isolator or some kind of disturbance apt to cause
The value of the differential current measured an earth-fault. The reason may also be too low
during a fault shows the magnitude of the earth- a start current setting. The residual earth-fault
fault current. When the earth-fault current of stage, unlike the restricted earth-fault stage, also
the total network is known, the probable loca- detects faults outside the zone of protection.
tion of the fault inside tha transformer can be
judged. The value in register 1 shows how close The values recorded in register 5 shows the
the set relay start current value is to the real fault duration of the latest start of the residual earth-
current value. Correspondingly, the set start fault stage, expressed as a percentage of the set
current values can be compared with the differ- operate time. Any new start resets the counter,
ential current values measured by the relay un- which always starts counting from zero. If the
der normal operation conditions. stage operates, the value of the register will be
100 [%].
Register 2 contains the maximum value of the
residual current as a percentage of the rated Register 5 provides information on the duration
current of the used energizing input. The regis- of the earth-fault and the safety margins of the
ter is updated, if grading times of the protection. Should, for
- the value of the measured current exceeds the instance, the duration recorded by the earth-
value already in the register fault relay, functioning as a back-up relay for the
- the relay operates. At relay operation the value feeder earth-fault relay show the value 75 [%]
of the current at operation is recorded. after that the feeder earth-fault relay has tripped,
the safety margin of the selective protection has
The value of the residual current measured been 25% counted on the operate time of the
during a fault shows the magnitude of the earth- residual earth-fault relay.
fault current. When the earth-fault current of
the total network is known, the degree of devel- The registers 1…5 are reset, either by pressing
opment of the earth-fault can be judged. The the STEP and RESET push-buttons simultane-
value in register 2 shows how close the set relay ously or with a command, V102, over the SPA
start current value is to the real fault current bus.
value. Correspondingly, the set start current
17
Secondary The secondary testing should always be per- DANGER!
injection testing formed in accordance with national regulations Do not open the secondary circuit of a cur-
and instructions. rent transformer during testing, if the pri-
mary circuit is live. The high voltage pro-
The protection relay incorporates an IRF func- duced by an open CT secondary circuit could
tion that continuously monitors the internal be lethal and may damage measuring instru-
condition of the relay and produces an alarm ments and insulation.
signal on detection of a fault. According to the
manufacturer’s recommendations the relay When the auxiliary voltage is connected to the
should be submitted to secondary injection test- protection relay, the relay performs a self-testing
ing at five years’ intervals. These tests should program. The self-testing does not include the
include the entire protection chain from the matching transformers and the contacts of the
instrument transformers to the circuit breakers. output relays. The operational condition of the
relay is tested by means of ordinary relay test
The secondary testing described in this manual equipment and such a test also includes the
is based on the relay’s setting values in the matching transformers, the output relays and
concerned application. If necessary, the second- the accuracy of the operate values.
ary testing can be extended by testing the protec-
tion stages throughout their setting ranges. Equipment required for testing:
- adjustable voltage transformer 0...260 V, 1 A
As switch positions and setting values may have - current transformer
to be altered during the test the correct positions - ammeter, accuracy ±0.5%
of switches and the setting values of the relay - stop watch or counter for time measurement
during normal operation conditions have to be - dc voltage source for auxiliary supply
recorded, for instance, on the reference card - switches and indicator lamps
accompanying the relay. - supply and pilot wires
- calibrated multimeter
To enable secondary injection testing the relay
has to be disconnected, either through dis- The secondary current of the current trans-
connectable terminal blocks or a test plug fitted former is to be selected on the basis of the rated
on the relay. current, 1 A or 5 A, of the relay energizing input
to be tested. The energizing inputs are specified
under the heading "Technical data, Energizing
inputs".
18
Uaux
U2
+ (~)
- (~)
6
A
1
TRIP1
65 66
TIMER STOP
8
TRIP2
68 69
5
C
SIGNAL1
7
80 81
L3
4
D
1
START1
SGR 2
77 78
TS1
L2
SS2
TS2
I/O
E
IRF
35 ms
70 71 72
t>,k
IRF
U3
L1
∆Io>
Io>
≅_
61 62
+ -
SGB
U1
4
5
SGR/1
S2
11
BS
10
TIMER START
25 26 27 37 38 39
1A
5A
1A
SPAJ 115 C
5A
A
U3
S1
L1 N
Fig. 8. Secondary test circuit for the earth-fault relay SPAJ 115 C.
The auxiliary voltage can be connected to the The correctness of the test connection can be
relay, as the test connection has been finished verified by using a multimeter.
and the selector switches properly set.
19
Checking the Pure sinusoidal energizing current is fed to the The measurement can be made at the rated
matching relay. Compare the current value shown in the current of the relay. The matching transformers
transformers display with the current reading of the ammeter. are tested separately.
Checking the The switches of switchgroup SGR should be set Start function
restricted earth- as follows:
fault stage ∆I0> Close switch S1 and slowly increase the test
Switch Position current until the relay operates, indicator L3 is
lit. Read the start current value from the am-
1 1 meter.
2 0
3 - Operate time
4 0
5 0 The operate time of the restricted earth-fault
6 0 stage is measured at a test current equal to 2
7 1 times the set start value of stage ∆I0>. The timer
8 0 is started when switch S1 is closed and stopped
by contact 65-66 on operation of output relay A.
The output relays have the following functions: The operation of output relay C is indicated by
LED L3.
Output Function
(terminals) When the relay operates, the indicator ∆I0> in
the right bottom corner of the front panel of the
A (65-66) Trip signal of stage ∆I0> relay module turns red.
B (68-69) Not in use
C (80-81) Signal on tripping of stage ∆I0> Blocking
(L3)
D (77-78) Not in use Switch 4 and 5 of switchgroup SGB on the PC
E (71-72) Self-supervision alarm signal (L1) board of the relay module and switch SGR/1 on
the front panel are to be set in position 1 (ON).
20
Checking the The switches of switchgroup SGR should be set Start function
restricted earth- as follows:
fault stage I0> The measuring current is slowly increased until
Switch Position the stage starts and indicator L2 is lit. The start
current is read from the ammeter.
1 1
2 1 Operate time
3 0
4 0 Definite time characteristic
5 1
6 0 The operate time of the residual earth-fault
7 0 stage is measured at a test current equal to 2
8 0 times the set start value of I0> stage. The timer
is started by closing switch S1 and stopped by
contact 68-69 on operation of output relay B.
The output relays have the following functions:
Inverse time characteristic
Output Function
(terminals) At inverse time characteristic the operate time of
the stage is measured at two current values (2 x
A (65-66) Not in use I0> and 10 x I0>). The operate times thus
B (68-69) Trip signal of stage I0> received are compared with the operate times
C (80-81) Signal on tripping of stage I0> shown in the current/time curves for the corre-
(L3) sponding inverse time characteristic.
D (77-78) Start signal of stage I 0> (L2)
E (71-72) Self-supervision alarm signal (L1)
Checking the self- The self-supervision system and its operation "General characteristics of C-type relay mod-
supervision system indicator IRF and output relay E can be tested ules" of this manual. The operation of output
in the Trip-Test mode described in section relay E is indicated by the LED indicator L1.
21
Maintenance When used under the conditions specified in the relay specifications, the relay should be given
and repair the section "Technical data", the relay requires a proper overhaul. Minor measures, such as
practically no maintenance. The relay includes exchange of a faulty module, can be undertaken
no parts or components that are liable to abnor- by personnel from the customer’s instrument
mal physical or electrical wear under normal work-shop, but major measures involving meas-
operating conditions. ures in the electronic circuitry are to be taken by
the manufacturer. Please contact the manufac-
If the environmental conditions on site differ turer or his nearest representative for further
from those specified, as to temperature and information about checking, overhaul and
humidity, or if the atmosphere around the relay recalibration of the relay.
contains chemically active gases or dust, the
relay should be visually inspected during the Note!
relay secondary testing. The visual inspection The protection relays contain electronic circuits
should focus on: which are liable to serious damage due to elec-
- Signs of mechanical damage on relay case and trostatic discharge. Before withdrawing a mod-
terminals ule from the relay case, ensure that you are at the
- Dust accumulated inside the relay cover or same electrostatic potential as the equipment by
case; remove carefully with compressed air or touching the case.
a soft brush
- Signs of corrosion on terminals, case or com- Note!
ponents inside the relay Static protection relays are measuring instru-
ments and should be handled with care and
If the relay fails to operation or if the operation protected against damp and mechanical stress,
values considerably differ from those stated in especially during transport and storage.
Ordering Combined restricted earth-fault and residual earth-fault relay SPAJ 115 C
numbers
SPAJ 115 C RS 421 012 -AA, CA, DA, FA
Combined restricted earth-fault and residual earth-fault relay SPAJ 115 C with
test adapter RTXP 18
The two last letters of the ordering number designate the rated frequency fn and
the Uaux voltage range of the relay as follows:
22
Dimensions and The relay case is basically designed for flush- by 80 mm and type SPA-ZX 112 reduces the
instructions for mounting. The mounting depth can be reduced depth by 120 mm. The relay can also be mounted
mounting by the use of a raising frame: type SPA-ZX 111 in a case for surface mounting, type designation
reduces the depth behind the mounting panel SPA-ZX 115.
by 40 mm, type SPA-ZX 112 reduces the depth
250
142
216 34
30 186
136
162
129 ±1 a b
139 ±1
Panel cut-out
Raising frame a b
SPA-ZX 111 176 74
SPA-ZX 112 136 114
SPA-ZX 113 96 154
Fig. 9. Dimensions of the restricted earth-fault and residual earth-fault relay SPAJ 115 C.
The relay case is made of profile aluminium and along the edge of the cover provides an IP54
finished in beige. degree of protection between the case and the
cover.
A rubber gasket fitted on the mounting collar
provides an IP54 degree of protection between All input and output wires are connected to the
relay case and mounting panel, when the relay is screw terminal blocks on the rear panel. Each
flush mounted. terminal is dimensioned for one max. 6 mm2
wire or two max. 2.5 mm2 wires. The D-type
The hinged cover of the relay case is made of a connector connects to the serial communica-
clear, UV stabilized polycarbonate, and pro- tion bus.
vided with a sealable fastening screw. A gasket