REO-USA, Inc.
3250 E.
8450 North
47th Post
StreetRoad, Suite 132
Indianapolis, IN 46226
Phone (317) 899-1395 e-mail: info@reo-usa.com REOVIB MFS 268
Fax (317) 899-1396 www.reo-usa.com
web: www.reo-reo.com Frequency controllers for vibratory feeders
Operating instructions
Features
-Feeder operating frequency is adjustable and independent of mains frequency.
-Constant feed rate ensured by internal compensation, irrespective of mains
fluctuations.
-Integrated track control via backlog sensor.
-24 V DC output for operating an air valve (IP 54 version), and amplitude control
(sensor required).
-Independent resonant frequency search possible for feeder.
-Enable input (start / stop), status relay (output active / inactive).
-Stand-alone housings (IP 54) or panel-mounted units (IP 20).

Technical data:
Supply voltage 110 / 240 V, +/- 10%, 50/60 Hz
Output 0...100 / 0... 205 V, 3 A, 6 A, 8 A, 12A, 16A
Output frequency 5...300 Hz, (preset at 35... 140 Hz)
Enable input Contacts or 24 V, DC
MFS 268XXL 16A Track sensor 24 V, PNP (100 mA)
MFS 268XL 12A
ID# 626887 Solenoid air valve output 24 V, (150 mA)
ID# 626867
MFS 268 IP20 16A Status output relay (ON/OFF) Changeover contact (250 V, 1 A)
Operating temperature 0...+45 °C
ID# 621103
Storage temperature -10...+80 °C
Recommended fuse 3 A, 8 A, 16 A slow-blowing, Type 'D' MCB

Instructions: Operating displays


Menus are used for changing settings. The different parameters are
Enable OFF
Display and controls Increase value selected by entering a code.

Decrease value All adjustments are made by first pressing the P key, followed by Track full
selecting the menu code, using the cursor keys.
F Return Settings Setpoint in %
Programming mode Pressing the cursor key for a short time causes one digit Timer running
I P increase/decrease, holding down for a longer time gives changes in
F or Enter
Controller Output ten-digit steps. Stop using "0" key
I
P 0 ON Changed settings are saved when exiting the menu or automatically
Controller Output if a key is not pressed for 60 seconds.
0
OFF

Data is subject to change for the benefit of technical improvement.


1
Settings Range Code Factory Menu
settings code Error messages

Amplitude (feed rate) 0... 100 % A. 0% 000, 008


Maximum output voltage 5...100 % P 90 %. 096, 008 Overload (output current too high).
Vibrating frequency 5...300 Hz F. 100 Hz 096, 008 Possible cause: Feeder too large, frequency too low for
Soft start ramp up 0... 60 sec. /. 0.1 sec. 096 installed coils, air gap too large.
Soft stop ramp down 0... 60 sec. \. 0.1 sec. 096
External setpoint 0/I E.S.P. 0 003
Short-circuited output
Potentiometer setpoint 0/I POT. 0 003 Possible cause: Incorrect wiring, possibly a defective coil.
Setpoint 0(4)... 20 mA 0/I 4.20 0 003
Coarse / Fine control 0/I 2.SP. 0 003 Input voltage too high
Invert enable 0/I -En. 0 003 Cause: Mains voltage too high or induced voltage from coil
Switch on time delay 0... 60 sec. I. 1.0 sec. 007, 167
Switch off time delay 0... 60 sec. 0. 1.0 sec. 007, 167
Invert sensor PNP/PNP invers -SE. PNP 007, 167
Activate sensor timeout 0/I E.En. 0 015 Sensor timeout has elasped (material sensor)
Sensor timeout delay 1... 240 sec. E. 180 sec. 015
Switch off time air valve 0...60 sec. Ai. 4 sec. 015
Activate control mode 0/I ACC. 0 008
Sensor fault (only in regulation mode)
P characteristic 0...100 P.A. 40 008
I characteristic 0...100 I.A. 100 008 Accelerometer missing or faulty
Automatic frequency control ON 0/I A.F.C. 0 008
Automatic frequency search ON A.F.S. 008 Current spike limit
Display output current i. 040 Frequency set too low for installed coil or frequency
Display output frequency F. 040 altered too rapidly during setting up
Pulse feed 0/I HOP. 0 064
On time delay (only if HOP = I) 0..60 sec. H. 1.0 sec. 064
Off time delay (only if HOP = I) 0..60 sec. h. 1.0 sec. 064 Error messages must be cleared in Menu no. C 009 by means of 'Cl.err.'
Invert Hopper sensor (not active) 0/I -Ho. 0 064
Save user settings 0...3 PUSH. 0 143 Timeout can be cleared with the 'I' key or by means of enable
Restore factory settings FAC. 210
Restore user settings 0...3 US.PA. 0 210 Frequently appearing Errors, which are not described in this chapter,
Hide programming menus 0/I Hd.C. 0 117 should be reported to the manufacturer.
Hide setpoint adjustment 0/I di.S. 0 137
Display software version 001

No code number is required to change the feed rate: pressing the P key twice will call the setpoint display.

Feed rate setting


Code 000 Feed rate set point a [mm]
100 %
Amplitude

P Feed rate 0...100 %


Feed rate

Operating mode 0 Setpoint 100 %

2
Safety instructions
This description contains the necessary information for the correct application of the product described below. It is intended for use by technically qualified personnel.
Qualified personnel are persons who, because of their training, experience and position, as well as their knowledge of appropriate standards, regulations, health and
safety requirements and working conditions, are authorised to be responsible for the safety of the equipment, at all times, whilst carrying out their normal duties and are
therefore aware of, and can report possible hazards (definition of qualified employees according to IEC 364).

WARNING! Declaration of conformity


Hazardous voltage!
We declare that these products conform with the following standards and
Failure to observe can kill, cause serious injury or damage. directives:
Isolate from mains before installation or dismantling work, as well as for fuse changes or EN 50081-2 and EN 50082-2 in accordance with directive 89/336/EEC.
post installation modifications.
REO ELEKTRONIK AG, D-42657 Solingen
Observe the prescribed accident prevention and safety rules for the specific application.
Before putting into operation, check if the rated voltage for the unit conforms with the
local supply voltage.
Emergency stop devices must be provided for all applications. Operation of the
emergency stop must inhibit any further uncontrolled operation.
Electrical connections must be covered. Specified use
The units described herein are electrical controllers for installation in
Earth connections must be checked for correct function, after installation. industrial plants.They are designed for power adjustment on vibratory
feed equipment.

Installation
Do supply voltage, operating voltage of the conveyor and controller input voltage match ?
Is the controller adequately rated for the rated power of the feeder ?
What is the vibrating frequency of the feeder ?
During switch-on, internal capacitors cause a high inrush current. Especially if several controllers are switched on simultaneously, the
external fuse can blow or the circuit breaker can trip. Therefore, we recommend fitting slow-acting fuses or circuit breakers, e.g. with type 'D'
characteristic.

Connect the unit in accordance with the wiring instructions and ensure that earthing is correct !

New units are factory set (see table with settings).


Attention! For units with unknown settings, first recall the factory settings using Menu C 210 'FAC'.

If an external setpoint source is used, select "E.S.P." = I in Menu C003. If a potentiometer is used, select also 'Pot.' = I.
To set the minimum vibration level, select E.S.P. = 0, adjust the vibration level with the cursor keys and then set E.S.P. = I.

The specific settings for a system can be saved by selecting 'US.PA.' in Menu C143 (recall settings via Menu C 210 'US.PA').
Menu access can be hidden by selecting 'Hd.C.' = I in Menu C117.

3
Code 003 Function settings Display 0...+10 V 0(4)...20mA Potentiometer .

Set point input


Internal using keys in
touch panel
External setpoint
-

7 8 9
-

7 8 9
7 8 9
P 0...+10 V,
+ 10 kR
+ 0(4)...20 mA
+5 V Potentiometer 10 KW
0 = Setpoint using display 500R
P
I = external setpoint 0...+10 V ON Sensor input
+24 V Sensor +24 V Track control
0 = external setpoint 0...+10 V or
P 0 0

Sensor input
I = external setpoint 4...20 mA Coarse / fine control with
a [mm] Feed rate two feed rates
a [mm]
0 = 0...10 V/ 0(4)...20 mA
P Feed rate
I = Potentiometer
0 = Track control via backlog sensor t t
P I = Coarse/fine control with second setpoint t-on t-off
Track control / backlog Coarse / fine control

P
0 = Enable
I = Invert enable Enable Enable
+24 V signal or
+24 V +24 V
closed contact will

Enable input
Operating mode enable the output.
0 t 0 t
+24 V signal or
a [mm] a [mm]
Feed rate Feed rate closed contact will inhibit
the output.
0 t 0 t

Code 096 / 020 Feeder a [mm]


Feed rate Maximum
Limiting the maximum
100 %
feed rate
Amplitude

P. 100%

Maximum feed rate


a [mm] P. 80%
P

100 %
The set point will still

Amplitude
Feed rate display 0... 100 %, even
P Feed rate 0...100 % 0 Setpoint though it is limited
100 % internally.

P Maximum limit 100...5 % 0 Setpoint 100 % 100 %

Vibrating frequency
Vibrating frequency [Hz] The frequency setting
P
depends on the feeder
type.
Important!
P Soft start time 0...5 sec.
The wrong frequency
setting can damage the
coil.
P Soft stop time 0...5 sec.
a [mm]

Soft start / soft stop


100%
Feed rate
Operating mode
Time ramp for starting
and stopping the feeder.
0
t

4
Code 008 Control mode
a [mm] Limiting of output voltage
P. 80% P. 100% Maximum
100 % a [mm]
or feed rate, e.g. to

Amplitude
P prevent hammering. The
100 %
displayed setpoint range

Amplitude
Feed rate Feed rate
remains at 0...100%.
P Feed rate 0...100 % 0 Setpoint 100 % t
0 Setpoint 100 % 100 % t
P Maximum limit 100...5 %
Frequency setting
depends upon the feeder
P Vibrating frequency [Hz] type.

Switch to control mode


P 0 = Regulation (without sensor)
I = Control (with sensor) Activates the control mode
to ensure a constant
P Proportional characteristic + MFS vibration amplitude, even
(gain) with large load variations.
Integral characteristic - The control mode requires
P an acceleration sensor.
(damping)

P Automatic frequency control


P Influences the regulation
0 = Off I = On 10= behaviour: Lineout time
a [mm] U, I, P and vibration behaviour
Start frequency search I 100= (pumping) of feeder.

Operating mode t
Automatic frequency
f = fixed f = f resonant change in case of
resonance.

key will start automatic frequency search Start automatic


frequency search

* An acceleration sensor, type SW-70, has to be fitted to the feeder for constant amplitude control. Care must be taken in the method of mounting to ensure
that the fixtures are solid, provide the correct orientation and do not flex under vibration.

Manual setting of the vibrating frequency:


It is important to have a low set point setting (e.g. 30 %) because upon reaching resonance it is possible that a high amplitude will be induced, even with a low output
voltage, thus increasing the risk of the coil "hammering". To determine the resonant frequency you must connect to the output. Resonant frequency has been reached
when there is maximum amplitude and minimum output current .

Automatic frequency search (regulation mode only).


* Put set point at zero.
* Select regulation mode ( Menu C 008, Parameter ACC = I ).
* The optimum, vibrating frequency of the feeder is determined by initiating the frequency search (Menu C 008, Parameter, select A.F.S. and press any cursor key).
Return the controller back to normal running mode after the resonant frequency has been found.
5
Code C 007 / C 167 Track control / Backlog sensor Sensor Sensor
24V 24V Adjustment of the ON
and OFF delays

Time delays
0 0
P
Feeder
a [mm] a [mm]
ON Feeder OFF
P Switch on time delay
0...60 sec.
t t
Switch off time delay t-on t-off
P
0...60 sec.

Sensor Invert sensor input

Sensor
P Invert sensor function 24V Sensor 24V
I = inverted 0 0
t t

Operating mode

Code 015 Special functions


Sensor Sensor control active.
P 24V If no components are

Sensor control
0 detected during the
inactive Feeder ON
0 = Feeder doesn't switch off during timeout a [mm] timeout period, the
P
I =Feeder switches off during timeout active t-on feeder switches off.

t
P E. = Sensor timeout [sec]

P Run-on-time for air valve output Setting the run-on-


24V
time for the air valve

Air valve output


0 output.
a [mm]
Operating mode

Code 064 Pulse feed t

P Feeder Air valve


OFF OFF

P
0 = Pulse feed Off
I = Pulse feed On

P Feeder on time On and Off time for


a [mm] Hopper pulse feed

Pulse feed
P Feeder off time
0 t

P Sensor invert (not active)

Operating mode
6
Code 117 Inhibit access

P P

Parameter menus cannot be accessed, except for the feed rate setpoint Hide programming
I= Hidden menus menus.
P P
Parameter menus can be accessed

P Operating mode

Code 137 Inhibit setpoint access

P P

0 = Setpoint access ON Setpoint can be adjusted Setpoint access


P P
I = Setpoint access OFF Setpoint cannot be adjusted

P Operating mode

Code 143 Save parameter settings

Service
P P

Select parameters 0 to 3 Save parameter


P Saves up to 4 different parameters (no. 0 - 3).
settings

P P
Save parameter settings All previously set parameters are saved.

P Operating mode

Code 210 Restore parameters

P P

Restore factory settings Restore


P P Restore factory settings. factory settings

P Select parameters 0 to 3 Saves up to 4 different parameters (no. 0 - 3).


Restore parameter
settings previously
P P Restore user settings Restore settings saved under C143. stored under C143

P Operating mode
7
Code 127 Enable service menu
Code 008

P P

Enables access to the adjustment of Imax,

Service
Extended
P P
0 = Service mode OFF Fmin / Fmax, and Output voltage limiting. settings
I = Service mode ON

P Service mode

Code 040 Service


Code 008
Conversion
P Monotoring
P Display x Inom 38,5 x 6 the output current.
Display shows the actual coil current = = 2,31 A
Actual value in % (display only) in % of the nominal current (Inom). 100 100
P P of the nominal coil current
Conversion: e.g. 4,8 A coil:

Current limit
Current limit in % of Imax. Adjusting output current
P P
llimit depending on coil.
Adjustment of the current limit I-limit x 100 4,8 x 100
= = 80 %
in & of the nominal current (Inom). Inom 6
P P Lower frequency limit
5 Hz 300 Hz
Setting the limits of the
Adjustable frequency range F.L. F.H.

Frequency range
frequency adjustment
P P Upper frequency limit Parameters 'F.L.' and 'F.H.'
range accessible for the
in Menu C 040.
user.
Actual frequency value max. 1 : 4 A narrow adjustment
P P
Effective frequency range range is preferable for
(display only) Parameter 'F' in the automatic frequency
Menus C 008, C 096, and C 020. search function.
Output voltage F.L. F.H.
P P limiting 100 V
0 = Off, I = On
Monitoring the
Display shows the actual vibration frequency. vibration frequency
P Operating mode

When operated with 230 / 240 V mains supply, the output voltage is limited to 100 V.

8
MFS 268, 621605, 3Amp, IP 20

F I
P O

REOVIB
MFS

9
MFS 268, 626848, 8Amp, IP 20

REO - USA

F I
P O

10
MFS 268, 621103, 15Amp, IP 20

REO - USA

F I
P O

11
MFS 268, 3Amp & 8Amp, IP 20, Electrical

1
Track Sensor E

2
3
+24V
- USA

4
4
Enable +
5

5
12...24V, DC

6
- E A
7 - 7

7
0(4)...20mA 0...10V S
Set point + 8 + 8 10k

8
9 10
+10V
F I
black GND

31 32 33 34
Accelerometer SW... orange E
+ 24V
P 0
red

SPEED
P P P

21
Status Relay

22
23
24
Feeder

25
26
L

27
N
Main Input PE
28
29

PE

12
MFS 268, 15Amp, IP 20, Electrical

USA

26
L
Main Input

27
N

28
PE

29
PE

F I

1
Track Sensor E

2
3
+24V
-
P 0

4
4
Enable +
5

5
12...24V, DC SPEED

6
- E A
7 - 7 P P P

7
0(4)...20mA 0...10V S
Set point + 8 10k

8
+ 9

9 10 31 32 33 21 22 23
+10V
black
GND
Accelerometer SW... orange
E
red
+ 24V

! Only use screened


control cables!

Screen clamb
for cable from
acceleration sensor

Feeder
Output
24
25
29

PE REOVIB MFS 268 Screen clamb for


Only use screened output cable
! power output cables.

13
MFS 268, 626848, 8Amp, IP 54

14
MFS 268, 626867, 12Amp, IP 54

6.314 8.200

REO - USA
REOVIB MFS 268

F I
P O
7.598 8.071

Key Functions:
F = Former Menu
P = Pass/Accept
= Increase DISCONNECT MAIN SUPPLY
= Decrease BEFORE REMOVING COVER
I = Run
O = Stop

www.reo-usa.com

15
MFS 268, 626887, 16Amp, IP 54

7.125 8.000

REOVIB MFS 268

F I
P O
7.563 8.062

Key Functions:
F = Former Menu
P = Pass/Accept
= Increase DISCONNECT MAIN SUPPLY
= Decrease BEFORE REMOVING COVER
I = Run
O = Stop

www.reo-usa.com

7.875

16
1
MFS 268, IP 54, 8A, Electrical

PNP-Sensor track control Track control 2 1 1 + 24 V, DC


2

2 2 1
+24V PNP-sensor
3

4
-
X4 3 4 3 GND
4

+ Enable 4 Input
3 4
5
5

12...24V, DC
6

10k
- - 0(4)...20mA
7

7 7
A S E + + R=500 ohm
+10V 8 8
8

0...10V extern Acceleration 2 1 1 + 24 V 2 1


9

sensor 2 Input
External set point 3
X 40 3 4 GND 3 4
4

5pol.Flanschdose
31 32 33 34

Acceleration
SW...
+24 V sensor +Schwingweite

Output
A1 brown / A1
blue A2
21

Internal status relay / A2 Buchsenein-


22 23

ye/gn satz 4+PE


screen Buchsenein-
satz 4+PE
A2 A1
24 25

Output Feeder
26

Main Input 110 / 240 V Input


27

Buchsenein-
satz 4+PE L brown / A1
PE PE
28

blue N
PE
/ A2
29

ye/gn

17
MFS 268, IP 54, 12A & 16A, Electrical
Acceleration 2 1 1 + 24 V Track control 2 1 1 + 24 V, DC
sensor 2 Input 2
3
PNP-sensor
X 40 3 4 GND
X4 3 4 3 GND
4 4 Input

2 1 2 1

3 4 3 4
Internal status relay
22 23

5pol.Flanschdose
+Schwingweite
21

PE PE PE PE PE
Time out +24V
35 36 37

51
Valve + 24V

54 53 52
GND

55
31 32 33 34

Buchsenein-
satz 4+PE Buchsenein-
+24 V Acceleration satz 4+PE
SW...
sensor
PE PE

28

+10V External set point


PE
9

29

0...10V + + 0(4)...20mA
8

S 10k 8 8 R=500 ohm


- -
7 extern
7

7
24
A2 A1

A E Output
6

12...24V, DC
25

5
+ feeder
5

- Enable
4
4

Main
26
N
3

+24V
input
27

PNP-Sensor track control


L
2

110 / 240 V
1

Input Output
L Buchsenein-
brown / A1 satz 4+PE A1 brown / A1
blue N
blue A2
/ A2
/ A2
ye/gn ye/gn
screen

18