GENERAL CONDITION FOR CONNECTION DESIGN

 RCC column below ground 304.8 MM X 304.8 MM size


( 6-12 mm dia. bar)for Column
 All truss member is detailed above.
 Type of foundation: CENTRALLY LOCATED
ISOLATED FOOTING
 Total height including truss 4.65 m.
 All size of footing as 0.6m * 0.6m with 12 mm dia bar
150mm c/c in both direction and thickness of footing is 350
mm mm. For detail ref. str. Drawing
 The column section should be properly connected to top of
RCC footing by 20mm base plate for column with 4 no. of
anchored M20 high friction grip of length 200 mm at least.
 Base plate and column are so connected by 10mm thick
fillet welding. For detail connection ref. str. Drawing
 For TRUSS and column connection should be provided
both welding and bolting concept and Should be connected
with at least 10mm bearing plate. The size of fillet weld
should be no less than 5 mm.
 Column and truss should be connected with 4-12M bolt and
bearing plate thickness 6mm
.