Summary This manual provides instructions for the mechanical and electrical installation of the
inverter of type Biodyn and Yaskawa.
Page 1/45
Table of Contents
1 Safety Advice. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Safety Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Safety Warnings Used in this Manual . . . . . . . . . . . . . . . . . . 3
2 * Prerequisite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4 Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1 Inverter Biodyn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1.1 Connection to Biodyn 9/12 C BR . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1.2 Connection to Biodyn 25 C BR (EU) . . . . . . . . . . . . . . . . . . . . . 18
4.1.3 Connection to Biodyn 25 C BR (AP) . . . . . . . . . . . . . . . . . . . . . 22
4.1.4 Connection to Biodyn 42 C BR . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.2 Inverter Yaskawa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.2.1 AP/LA Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.2.2 NA Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5 Adjustments and Final Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
A1 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
y All people involved must know and follow the company and local safety regulations.
y Protective clothing and appropriate safety equipment must be worn.
The following types of safety warnings are used in the present manual.
DANGER
The safety warning with the signal word “Danger” is used to indicate a hazardous situation
which, if not avoided, will result in death or serious injury.
y To avoid any damage, keep the parts and components in the original packaging for as
long as possible before installation.
y Refer to the respective System Manual for specific details about prerequisites regarding
the building, electrical circuits or installed components.
Related
Documents Number Document
K 609826 Product Data Sheet Schindler 3100
K 609827 Product Data Sheet Schindler 3300
K 609759 Product Data Sheet Schindler 3300AP
K 609884 Product Data Sheet Schindler 3300IN
K 609828 Product Data Sheet Schindler 5300
K 609889 Product Data Sheet Schindler 5300IN
K 43401267 Product Data Sheet Schindler 6300 Rel. 2
EJ 604715 Technical Info and Configuration Schindler 6200 Hoistway Material
EJ 604720 Technical Info and Configuration Schindler 6200 (Rel. 02)
K 609741 Installation Machine FMB130/150
K 609744 Maintenance Machine FMB130/150
K 609704 Maintenance ACVF Biodyn and Yaskawa
K 609716 Installation Schindler 3100/3300/5300/6300 Hoistway Components
K 609778 Installation Schindler 3300AP Hoistway Components
EJ 609801 Installation Schindler 3100/3300/5300IN Hoistway Components
EJ 612040 Installation Schindler 3100/3300/5300LA Hoistway Components
EJ 44141711 Installation Schindler 3300/5300NA Hoistway Components
3.1 Overview
Overview Biodyn The Biodyn series features Schindler inverters designated for the commodity market in EU,
AP and IN and consists of a complete unit with all components integrated on one panel. The
following types are available:
Biodyn 25 C BR Version AP (with and without cover and side panel) [33140; 05.02.2010]
There is a variety of inverter brackets related to car weight and market area (EU, AP, LA
and IN).
For overview information and instructions about the inverter bracket installation refer to:
y K 609716 for EU installations
y K 609778 for AP installations
y EJ 609801 for IN installations
y EJ 612040 for LA installations
y EJ 44141711 for NA installations.
The bracket mounting method applies to all inverter types except Biodyn 42 C BR, which is
mounted on the hoistway wall.
Bracket Mounting
on Machine No Step
Support 300 Screw the three provided fixation screws (1) into the inverter bracket (2) but do
not screw them all the way in (see inset below).
301 Hang the inverter onto the three fixation screws of the inverter bracket.
302 Tighten the three fixation screws with a long shaft POZIDRIV screwdriver to
securely fasten the inverter to the inverter bracket.
50
3
2
1
Minimum Clearances Related to Wall-Mounted Biodyn 42 C BR [18851; 30.10.2006]
1 Biodyn 42 C BR
2 Machine support
3 Machine
When lifting and supporting the inverter unit during installation, consider that two people are
required for the type Biodyn 42 C BR.
Wall Mounting of
303 Mark the four positions (“A”, “B”) of the designated drill holes on the hoistway
Biodyn 42 C BR
wall. Make sure to observe the minimum distances indicated above.
If required to comply with earthquake safety requirements, two more fixation
positions (“C”) are available.
304 Drill four 8 mm holes 50 mm deep for the fixation points “A” and “B”.
305 Insert 40x8 mm plugs into the drill holes.
306 Fasten the support bracket (2) to the fixation points “A” on the hoistway wall with
the two provided 40x6 mm screws.
Make sure that the support bracket hangs flat against the hoistway wall. Refer to
the figure below.
307 Hang the inverter onto the support bracket (2) making sure that the base
plate (1) of the inverter fits into the notches (see detail in the figure below) of the
support bracket.
308 Fasten the base plate (1) of the inverter to the hoistway wall with the two
provided 55x6 mm POZIDRIV screws at the fixation points “B”.
Optionally also use the fixation points “C”.
370
33 304
A A
2
C C
275 C
40 275 B
B B
DANGER
Hazardous Voltage
Contact with live parts will result in electric shock causing serious injury or death.
Take the following precautions:
y Do not touch live parts.
y Switch off the main switch and de-energize the installation completely before starting to
work on the installation.
Refer to the supplied electrical master schematic while carrying out the following
instructions.
Principal
Schematic
Biodyn xx C BR
Mains Cable
No Step
400 Insert and attach the flexible cable duct (4), which holds the mains cable (3) and
the mains ground wire PE (1), to the inverter casing.
401 Fasten the mains ground wire PE (1) to the mains ground point PE (2) with the
provided M6 POZIDRIV screw.
402 Plug in the connector X1 of the mains cable (3).
V
W SF1
X1 1
2
3
4
Biodyn 9/12 C BR - Mains Cable Connection and Grounding [33787; 10.02.2010]
1 Mains ground wire PE
2 Mains ground point PE
3 Mains cable
4 Flexible cable duct
2 SF
U
V
W SF1
X1
4
2 3+4
VF1 THMH MVE EF CAN
5 4 3 2 1 1 2 1 2 1 2 3 1 2 3
MGB VF2 KB TDIV
1 2 3 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 10
3
4
1 3
4
5
7
6
Biodyn 9/12 C BR - I/O Connections Between Inverter and Controller [33842; 08.03.2010]
1 Connector / cable VF2
2 Connector / cable VF1
3 Connector / cable EF
4 Connector / cable CAN (shielded)
5 Clamp bar (for grounding)
6 Tie-bar (for strain relief)
7 Grounding clamp (exemplary view)
2 4
VF1 THMH MVE EF CAN
5 4 3 2 1 1 2 1 2 1 2 3 1 2 3
MGB VF2 KB TDIV
1 2 3 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 10
3 1 5
2
4
1 5
6
8
7
Biodyn 9/12 C BR - I/O Connections Between Inverter and Motor [33843; 08.03.2010]
1 Connector / cable KB 5 Connector / cable TDIV (shielded)
2 Connector / cable THMH (shielded) 6 Clamp bar (for grounding)
3 Connector / cable MGB 7 Tie-bar (for strain relief)
4 Connector / cable MVE 8 Grounding clamp (exemplary view)
Mains Cable
No Step
415 Insert and attach the flexible cable duct (4), which holds the mains cable (3) and
the mains ground wire PE (1), to the inverter casing.
416 Fasten the mains ground wire PE (1) to the mains ground point PE (2) with the
provided M6 POZIDRIV screw.
417 Plug in the connector X1 of the mains cable (3).
X1
SF1
SF U V W
4
2 1
Biodyn 25 C BR - Mains Cable Connection and Grounding [33788; 10.02.2010]
1 Mains ground wire PE
2 Mains ground point PE
3 Mains cable
4 Flexible cable duct
2
A
4
A
X1
SF1
SF
5 U V W
3 2 1
Biodyn 25 C BR - Motor Cable Connection and Grounding [33785; 10.02.2010]
1 Motor ground point PE
2 Motor cable ground wire PE
3 Motor cable
4 Cable clamp
5 Phase wires (of motor cable)
6 Metal side plate (of inverter case)
2 3+4
VF1 THMH MVE EF CAN
5 4 3 2 1 1 2 1 2 1 2 3 1 2 3
MGB VF2 KB TDIV
1 2 3 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 10
3
4
3 4
1
2
1 2
4 3
Biodyn 25 C BR (EU) - I/O Connections Between Inverter and Controller [33739; 08.03.2010]
1 Connector / cable VF2
2 Connector / cable VF1
3 Connector / cable EF
4 Connector / cable CAN (shielded)
5 Grounding clamp (exemplary view)
4 2
VF1 THMH MVE EF CAN
5 4 3 2 1 1 2 1 2 1 2 3 1 2 3
MGB VF2 KB TDIV
1 2 3 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 10
5 3 1
3 2
4 1
6
7
5 4 1
3 2
Biodyn 25 C BR (EU) - I/O Connections Between Inverter and Motor [33757; 08.03.2010]
1 Connector / cable TDIV (shielded) 4 Connector / cable THMH (shielded)
2 Connector / cable MVE 5 Connector / cable MGB
3 Connector / cable KB 6 Grounding clamp (exemplary view)
Mains Cable
No Step
430 Insert and attach the flexible cable duct (4), which holds the mains cable (3) and
the mains ground wire PE (1), to the inverter casing.
431 Fasten the mains ground wire PE (1) to the mains ground point PE (2) with the
provided M6 POZIDRIV screw.
432 Plug in the connector X1 of the mains cable (3).
X1
SF1
SF U V W
4
2 1
Biodyn 25 C BR - Mains Cable Connection and Grounding [33788; 10.02.2010]
1 Mains ground wire PE
2 Mains ground point PE
3 Mains cable
4 Flexible cable duct
2
A
4
A
X1
SF1
SF
5 U V W
3 2 1
Biodyn 25 C BR - Motor Cable Connection and Grounding [33785; 10.02.2010]
1 Motor ground point PE
2 Motor cable ground wire PE
3 Motor cable
4 Cable clamp
5 Phase wires (of motor cable)
6 Metal side plate (of inverter case)
2 3+4
VF1 THMH MVE EF CAN
5 4 3 2 1 1 2 1 2 1 2 3 1 2 3
MGB VF2 KB TDIV
1 2 3 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 10
3
4
2 1
3 4
1 2
4 3
Biodyn 25 C BR (AP) - I/O Connections Between Inverter and Controller [33961; 08.03.2010]
1 Connector / cable VF2
2 Connector / cable VF1
3 Connector / cable EF
4 Connector / cable CAN (shielded)
5 Grounding clamp (exemplary view)
4 2
VF1 THMH MVE EF CAN
5 4 3 2 1 1 2 1 2 1 2 3 1 2 3
MGB VF2 KB TDIV
1 2 3 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 10
5 3 1
1
4 3 2
1
5 4 1
3 2
Biodyn 25 C BR (AP) - I/O Connections Between Inverter and Motor [33962; 08.03.2010]
1 Connector / cable TDIV (shielded) 4 Connector / cable THMH (shielded)
2 Connector / cable MVE 5 Connector / cable MGB
3 Connector / cable KB 6 Grounding clamp (exemplary view)
Mains Cable
No Step
445 Insert and attach the flexible cable duct (4), which holds the mains cable (3) and
the mains ground wire PE (1), to the inverter casing.
446 Fasten the mains ground wire PE (1) to the mains ground point PE (2) with the
provided M6 POZIDRIV screw.
447 Connect the phase wires of the mains cable (3) to the terminal block X1, which is
located on the left side in the inverter box.
X1
X1
X2
1
3
4
Biodyn 42 C BR - Mains Cable Connection and Grounding [33790; 05.03.2010]
1 Mains ground wire PE
2 Mains ground point PE
3 Mains cable
4 Flexible cable duct
3
A
5
4
A
X2
X1
X2
3
1
4
9 3 2 7+6
VF1 THMH MVE EF CAN
5 4 3 2 1 1 2 1 2 1 2 3 1 2 3
MGB VF2 KB TDIV
1 2 3 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 10
5 8 4 1
6
7
X1
10
9
8
7
6
11
5 4 3 2 1
Biodyn 42 C BR - I/O Connections Between Inverter and Controller or Motor [33969; 05.03.2010]
1 Connector / cable TDIV (shielded) 7 Connector / cable EF
2 Connector / cable MVE 8 Connector / cable VF2
3 Connector / cable THMH (shielded) 9 Connector / cable VF1
4 Connector / cable KB 10 Clamp bar (for grounding)
5 Connector / cable MGB 11 Tie-bar (for strain relief)
6 Connector / cable CAN (shielded)
9 3 2 7 6
VF1 THMH MVE EF CAN
5 4 3 2 1 1 2 1 2 1 2 3 1 2 3
MGB VF2 KB TDIV
1 2 3 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 10
5 8 4 1
Biodyn 42 C BR - Connectors on the OPTAG I/O Board [33971; 24.02.2010]
Mains The Yaskawa inverter features different means for the connecting of the mains depending
Connection on the mains voltage:
Variants
1) Screw terminal X1 (1)
for 200 V mains with Yaskawa FCL2.
The screw terminal is suitable to
carry higher currents.
2) Socket X1 (2) 1 2
for 400 V mains with Yaskawa FCL4.
[22960; 19.07.2007]
Overview
SF
U
3 X1
V
W
2
00015203
1
Mains Cable (AP/LA installation) [19046; 19.07.2007]
1 Flexible cable duct
2 Mains ground point (PE)
3 Mains ground wire PE
4 Mains cable
Check for the correct supply phase sequence before terminating the motor cable.
Motor Cable
462 Remove and discard the protective plastic foil.
463 Use the cable clamp (2) to securely ground the motor cable shield.
464 Connect the phase wires of the motor cable (1) to the motor contactor SF on the
inverter.
Connect the wires according to the labeling.
465 Connect the PE wire (4) of the motor cable to the designated motor ground
point (3) on the inverter.
3 4
SF
U
X1
V
W
00015204
2 1
Motor Cable (AP/LA installation) [19051; 14.11.2006]
1 Motor cable
2 Cable clamp
3 Motor ground point PE
4 Motor cable ground wire PE
I/O Connections Between Inverter and Controller (AP/LA installation) [19052; 14.11.2006]
1 Flexible cable duct
2 Connector VF2
3 Connector VF1
4 Tie-down slots
5 Connector EF
6 Connector CAN
I/O Connections Between Inverter and Motor (AP/LA installation) [19101; 14.11.2006]
1 Tie-down slots
2 Connector MGB
3 Connector KB
4 Connector TDIV
5 Connector THMH
6 Connector MVE
Overview
L1 POW-IN
L2 MVE FAN
L3 X1
POW-OUT THMH THMH
PE PE
MGB MGB
CAN
WDPNA KB KB
VF2 U U
SF V V MH
VF1 W W
SEM
EF TDIV TDIV
U
X1
V
3
W
2
00016080
1 4
Mains Cable (NA installation, left-hand cable entry) [22953; 19.07.2007]
SF
U
X1
V
3 W
2
00016081
1 4
Mains Cable (NA installation, right-hand cable entry) [22955; 18.07.2007]
1 Termination box
2 Mains ground wire PE
3 Mains ground point PE
4 Mains cable
3
2
SF
U
X1
V
W
1 5 4
Motor Cable (NA installation, left-hand cable entry) [34106; 08.03.2010]
3
2
SF
U
X1
V
W
1 5
Motor Cable (NA installation, right-hand cable entry) [34107; 08.03.2010]
I/O Connections
between Inverter 2
and Controller 1
3
VF
1
4
6
3
2
SF
U
V
W
00016082
8
I/O Connections between Inverter and Controller (NA installation, left-hand cable entry) [22956;
20.07.2007]
6 Tie-down slots
7 CANIVF board
8 Terminal box
3
2
SF
U
V
W
00016083
8
I/O Connections between Inverter and Controller (NA installation, right-hand cable entry) [22957;
20.07.2007]
6
4
3
2
SF
U
V
W
1 8
I/O Connections between Inverter and Motor (NA installation, left-hand cable entry) [34108;
08.03.2010]
6
4
3
2
SF
U
WV
1 8
I/O Connections between Inverter and Motor (NA installation, right-hand cable entry) [34109;
08.03.2010]
1 Terminal box
2 Connector MGB
3 Connector KB
4 Connector TDIV
5 CANIVF board
6 Connector THMH
7 Connector MVE
8 Tie-down slots
Adjustments and
No Step
Final Checks
500 Check that the inverter is securely mounted.
501 Check that all screws are tight.
502 Check that all cabling is secure and clear from moving mechanical parts.
503 Check that:
y All connectors are securely located
y The wiring is securely terminated
y The wiring insulation and all cables are free of damage.
504 Inverter Biodyn only: on the OPTAG I/O board, check that:
y The jumper XTSF is inserted between pins 1 and 2 of the TSF socket.
y The jumper XTSF1 is inserted between pins 1 and 2 of the TSF1 socket.
3 3 3
2
TSF
TSF1
2 2
1 1 1
TSF TSF1
OPTAG Rev
3 3
TSF1
TSF
2 2
1 1
TSF TSF1
1
CANIVF Board of Yaskawa Inverter [22962; 20.07.2007]
1 CANIVF board
2 Termination switch
3 Boot switch
506 Finally, check that no material or tools remain on top of the brake resistor
module.
Abbreviations
Abbreviation Description
ACVF Inverter (frequency converter) with variable frequency output for the
powering of AC motors
CAN Controlled area network (bus system)
CBD Car blocking device
CL Closed loop (control)
CLC Car load cell
HCU Hoistway control unit (for automatic evacuation)
HMI Human machine interface
IG Incremental encoder
JH Main power switch
KTHMH Thermal switch hoisting motor
LDU Landing door unit
MGB Magnetic brake
MH Hoisting motor
MVE Motor fan
OL Open loop (control)
SCIC Cabinet interface controller
SEM Automatic evacuation module
SF, SF1 Travel contactor
SMIC Main interface controller
SNGL Elevator power supply
STM Suspension and traction media
TDIV Motor encoder
THMH Thermal element hoisting motor
VF Inverter (frequency converter)