LUX LEVEL STANDARD CUM MONITORING SHEET Efft Date:

LUX LEVEL STANDARD

S.N AREA/LOCATION CONTROL SPECIFICATION METHOD FRQ. RESP. REMARKS

1 OFFICE 150 ~ 250

2 SHOP FLOOR 500 ~ 750

REWORK/RED BIN
3 500-750
TABLE

ONCE IN A QA HEAD
4 IPC INSPECTION TABLE TUBE LIGHT,CFL,LED,BULB 700 Min. LUX METER
MONTH MAINT.HEAD

5 INSPECTION TABLE 700 Min.

6 STANDARD ROOM 700 Min.

FINAL INSPECTION
7 700 Min.
AREA

Note : If the status of Light observed below the specified limits, please initiate action plan to improve the Light level.

SN AREA SPEC.

1 OFFICE 150 ~ 250

2 SHOP FLOOR 550 ~ 750

REWORK/RED BIN
3 500-750
TABLE

4 IPC INSPECTION TABLE 700 Min.


FINAL INSPECTION
5 700 Min.
AREA

6 STANADRD ROOM 700 Min.

7 INSPECTION TABLE-1 700 Min.

8 INSPECTION TABLE-2 700 Min.

300~500
9 CONFERENCE ROOM
Min.

10 STORE AREA 150 ~ 250

Checked By (QA Head/Maint.Head)


Doc No:-
Rev No:

LUX LEVEL STANDARD CUM MONITORING SHEET Efft. Date:

S.N AREA/LOCATION CONTROL SPECIFICATION METHOD FRQ. RESP. REMARKS

ONCE IN A QA HEAD
1 OFFICE TUBE LIGHT,CFL,LED,BULB 150 ~ 250 LUX METER
WEEK MAINT.HEAD

Note : If the status of Light observed below the specified limits, please initiate action plan to improve the Light level.
LUX MONITORING SHEET

SN AREA SPEC. MONTH Week-1 Week-2 Week-3 Week-4

1 OFFICE 150 ~ 250 Lux Observed


1 OFFICE 150 ~ 250 Lux Observed

Checked By (QA Head/Maint.Head)


Doc No:-
Rev No:

LUX LEVEL STANDARD CUM MONITORING SHEET Efft Date:

MACHINE NUMBER:

S.N AREA/LOCATION CONTROL SPECIFICATION METHOD FRQ. RESP. REMARKS

SHOP FLOOR (MACHINE ONCE IN A QA HEAD


1 TUBE LIGHT,CFL,LED,BULB 150 ~ 250 LUX METER
WISE) WEEK MAINT.HEAD

Note : If the status of Light observed below the specified limits, please initiate action plan to improve the Light level.
LUX MONITORING SHEET

SN AREA SPEC. MONTH Week-1 Week-2 Week-3 Week-4

SHOP FLOOR
1
(MACHINE WISE)
500~750 Lux Observed/DATE RECORDING
STARTED FROM

Checked By (QA Head/Maint.Head)


Doc No:-
Rev No:

LUX LEVEL STANDARD CUM MONITORING SHEET Efft Date:

S.N AREA/LOCATION CONTROL SPECIFICATION METHOD FRQ. RESP. REMARKS

ONCE IN A QA HEAD
1 REWORK TABLE TUBE LIGHT,CFL,LED,BULB 500~ 750 LUX METER
WEEK MAINT.HEAD

Note : If the status of Light observed below the specified limits, please initiate action plan to improve the Light level.
LUX MONITORING SHEET

SN AREA SPEC. MONTH Week-1 Week-2 Week-3 Week-4

1 REWORK TABLE 500~ 750 Lux Observed/Date RECORDING


STARTED FROM

Checked By (QA Head/Maint.Head)


Doc No:-
Rev No:

LUX LEVEL STANDARD CUM MONITORING SHEET Efft Date:

S.N AREA/LOCATION CONTROL SPECIFICATION METHOD FRQ. RESP. REMARKS

ONCE IN A QA HEAD
1 RED BIN AREA TUBE LIGHT,CFL,LED,BULB 500~ 750 LUX METER
WEEK MAINT.HEAD

Note : If the status of Light observed below the specified limits, please initiate action plan to improve the Light level.
LUX MONITORING SHEET

SN AREA SPEC. MONTH Week-1 Week-2 Week-3 Week-4

1 RED BIN AREA 500~ 750 Lux Observed/Date RECORDING


STARTED FROM

Checked By (QA Head/Maint.Head)


Doc No:-
Rev No:

LUX LEVEL STANDARD CUM MONITORING SHEET Efft Date:

IPC TABLE NUMBER-

S.N AREA/LOCATION CONTROL SPECIFICATION METHOD FRQ. RESP. REMARKS

ONCE IN A QA HEAD
1 IPC TABLE TUBE LIGHT,CFL,LED,BULB 700 MIN. LUX METER
WEEK MAINT.HEAD

Note : If the status of Light observed below the specified limits, please initiate action plan to improve the Light level.
LUX MONITORING SHEET

SN AREA SPEC. MONTH Week-1 Week-2 Week-3 Week-4

1 IPC TABLE 700 MIN. Lux Observed/Date RECORDING


STARTED FROM

Checked By (QA Head/Maint.Head)


Doc No:-
Rev No:

LUX LEVEL STANDARD CUM MONITORING SHEET Efft Date:

INSPECTION TABLE NUMBER-

S.N AREA/LOCATION CONTROL SPECIFICATION METHOD FRQ. RESP. REMARKS

ONCE IN A QA HEAD
1 INSPECTION TABLE TUBE LIGHT,CFL,LED,BULB 700 MIN. LUX METER
WEEK MAINT.HEAD

Note : If the status of Light observed below the specified limits, please initiate action plan to improve the Light level.
LUX MONITORING SHEET

SN AREA SPEC. MONTH Week-1 Week-2 Week-3 Week-4

1 INSPECTION TABLE 700 MIN. Lux Observed/Date RECORDING


STARTED FROM

Checked By (QA Head/Maint.Head)