Professional Documents
Culture Documents
Introduction to substations
Electrical power systems nowadays are generated, transmitted, and distributed in the
form of alternating current. The electric power is produced at the power stations which are
located in suitable places, generally quite away from the consumers.
The Essentials Of Substations, Electrical Equipment and Busbar Arrangements (on photo: Little yellow
bird and big transformer in substation behind; credit: Tomislav Bicanic via Flickr)
For that, in between the power station and ultimate consumer, a number of
transformations and switching stations have to be created. These are generally known as
substation.
Contents:
1/23
1. What is the substation?
The assembly of apparatus used to change some characteristic (e.g., voltage, AC to DC,
frequency, pf, etc.) of electric supply is called a substation. Substations are important part
of power system. The continuity of supply depends to a considerable extent upon the
successful operation of substations.
It is, therefore, essential to exercise utmost care while designing and building a
substation.
The following are the important points which must be kept in view while laying out
a substation:
Go back to contents ↑
2. Classification of substations
2/23
There are several ways of classifying substations. However, the two most important ways
of classifying them are according to (1) service requirement and (2) constructional
features.
A substation may be called upon to change voltage level or improve power factor or
convert AC power into DC power, etc.
Obviously, transformer will be the main component in such substations. Most of the
substations in the power system are of this type.
3/23
Those substations which improve the power factor of the system are called power factor
correction substations. Such substations are generally located at the receiving end of
transmission lines.
4/23
Figure 3 – Frequency converter substation (on photo: SEPTA Wayne Rail Substation &
Static Frequency Converter – Philadelphia, Pennsylvania; credit: wikimapia.org)
5/23
Figure 4 – Industrial substation, LV and switchgears displayed
A substation has many components (e.g., circuit breakers, switches, fuses, instruments,
etc.) which must be housed properly to ensure continuous and reliable service.
For voltages up to 11 kV, the equipment of the substation is installed indoors because of
economic considerations. However, when the atmosphere is contaminated with
impurities, these substations can be erected for voltages up to 66 kV.
The components of substations take the form of metal cabinets or enclosures, each of
which contains the equipment of one main connection cell. Within such cabinets or
enclosures an oil circuit breaker, a load interrupter switch, and one or more voltage
transformers may be mounted.
6/23
Figure 5 – Compact substation
7/23
Watch Video At: https://youtu.be/l53NrBvlorQ
In thickly populated cities, there is scarcity of land as well as the prices of land are very
high. This has led to the development of underground substation. In such substations, the
equipment is placed underground.
8/23
2.2.4. Pole-mounted substation
It is a distribution substation placed overhead on a pole. It is the cheapest form of
substation as it does not involve any building work. Figure 7a shows the layout of pole-
mounted substation, whereas Figure 7b shows the schematic connections.
The transformer and other equipment are mounted on H-type pole (or four-pole
structure).
The transformer steps down the voltage to 400-V, three-phase, four-wire supply. The
voltage between any two lines is 400 V, whereas the voltage between any line and neutral
is 230 V. The oil circuit breaker (OCB) installed on the low-tension side automatically
isolates the transformer from the consumers in the event of any fault.
The pole-mounted substations are generally used for transformer capacity up to 200
kVA.
There should be periodical checkup of the dielectric strength of oil in the transformer
and OCB.
9/23
In case of repair of transformer or OCB, both gang isolator and OCB should be shut
off.
Go back to contents ↑
Go back to contents ↑
10/23
4. Transformer substations
The majority of the substations in the power system are concerned with the changing of
voltage level of electric supply. These are known as transformer substations because
transformer is the main component employed to change the voltage level.
1. Step-up substation
2. Primary grid substation
3. Secondary substation
4. Distribution substation
Figure 8 shows the block diagram of a typical electric supply system, indicating the
position of above types of substations. It may be noted that it is not necessary that all
electric supply schemes include all the stages shown in the figure.
For example, in a certain supply scheme there may not be secondary substations and in
another case, the scheme may be so small that there are only distribution substations.
11/23
4.1. Step-up substation
The generation voltage (11 kV in this case) is stepped up to high voltage (220 kV) to
affect economy in transmission of electric power. The substations which accomplish this
job are called step-up substations.
These are generally located in the power houses and are of outdoor type.
Here, electric power is received by the primary grid substation which reduces the
voltage level to 66 kV for secondary transmission. The primary grid substation is
generally of outdoor type.
The voltage between any two phases is 400 V and between any phase and neutral it
is 230 V. The single-phase residential lighting load is connected between any one phase
and neutral, whereas three-phase, 400-V motor load is connected across three-phase
lines directly.
It may be worthwhile to mention here that in some countries majority of the distribution
substations are of pole-mounted type.
12/23
Figure 9 – Single line diagram of major components of power system from generation to consumption
(click to expand)
Go back to contents ↑
5.1. Busbars
13/23
3. Double busbar arrangement
5.2. Insulators
The insulators serve two purposes. They support the conductors (or busbars) and confine
the current to the conductors.
The most commonly used material for the manufacture of insulators is porcelain. There
are several types of insulators (e.g., pin type, suspension type, postinsulator, etc.), and
their use in the substation will depend upon the service requirement.
For example, post-insulator is used for busbars. A post-insulator consists of a porcelain
body, cast iron cap, and flanged cast iron base. The hole in the cap is threaded so that
busbars can be directly bolted to the cap.
Figure 10 – Porcelain post insulators for disconnectors (photo credit: PPC Insulators)
In other words, isolator switches are operated only when the lines in which
they are connected carry no current.
14/23
Figure 11 – Use of isolators in a typical substation
Figure 11 shows the use of isolators in a typical substation. The entire substation has
been divided into five sections. Each section can be disconnected with the help of
isolators for repair and maintenance.
For instance, if it is desired to repair section II, the procedure of disconnecting this
section will be as follows. First of all open the circuit breaker in this section and then open
the isolators 1 and 2. This procedure will disconnect section II for repairs.
After the repairs has been done, close the isolators 1 and 2 first and then the circuit
breaker.
A circuit breaker is equipment which can open or close a circuit under normal as well
as fault conditions. It is so designed that it can be operated manually (or by remote
control) under normal conditions and automatically under fault conditions.
15/23
Figure 12 – High voltage transformer
Therefore, they will not work satisfactorily if mounted directly on the power lines. Tis
difficulty is overcome by installing instrument transformers on the power lines.
The secondary consists of a large number of turns of fine wire and provides for the
measuring instruments and relays a current which is a constant fraction of the current in
the line. Suppose a CT rated at 100/5 A is connected in the line to measure current. If the
current in the line is 100 A, then current in the secondary will be 5 A. Similarly, if current
in the line is 50 A, then secondary of CT will have a current of 2.5 A.
Thus the CT under consideration will step down the line current by a factor of 20.
16/23
Figure 13 – High voltage current transformers (CTs) – photo credit: PFIFFNER
Instrument Transformers Ltd
b. Potential transformer
It is essentially a step down transformer and steps down the voltage to a known ratio. The
primary of this transformer consists of a large number of turns of fine wire connected
across the line.
The secondary winding consists of a few turns and provides for measuring instruments
and relays a voltage which is a known fraction of the line voltage.
17/23
Figure 14 – Coupling Capacitor Voltage Transformers
More information and guide about HV instrument transformers you can find here.
8. Miscellaneous equipment
18/23
1. Fuses
2. Carrier-current equipment
3. Substation auxiliary supplies
Go back to contents ↑
As the name suggests, it consists of a single busbar, and all the incoming and outgoing
lines are connected to it. The chief advantages of this type of arrangement are low initial
cost, less maintenance, and simple operation.
19/23
Figure 15 shows single busbar arrangement in a substation. There are two 11 kV
incoming lines are connected to the busbar through circuit breakers and isolators. The
two 400 V outgoing lines are connected to the busbars through transformers (11 kV/400
V) and circuit breakers.
In this arrangement, the single busbar is divided into sections, and load is equally
distributed on all the sections. Any two sections of the busbar are connected by a circuit
breaker and isolators. Two principal advantages are claimed for this arrangement.
Firstly, if a fault occurs on any section of the bus, that section can be isolated without
affecting the supply from other sections. Secondly, repairs and maintenance of any
section of the busbar can be carried out by de-energizing that section only, eliminating the
possibility of complete shutdown.
This arrangement is used for voltages up to 33 kV. Busbar with sectionalization where
the bus has been divided into two sections.
Figure 16 shows busbar with sectionalization where the bus has been divided into two
sections. There are two 33 kV incoming lines connected to sections I and II as shown
through circuit breaker and isolators.
20/23
Figure 16 – Busbar with sectionalization
This system consists of two busbars, a “main” busbar and a “spare” busbar. Each
busbar has the capacity to take up the entire substation load.
The incoming and outgoing lines can be connected to either busbar with the help of a
busbar coupler that consists of a circuit breaker and isolators. Ordinarily, the incoming
and outgoing lines remain connected to the main busbar.
However, in case of repair of main busbar or fault occurring on it, the continuity of
supply to the circuit can be maintained by transferring it to the spare busbar.
For voltages exceeding 33 kV, duplicate busbar system is frequently used. Figure
17 shows the arrangement of duplicate busbar system in a typical substation.
The two 66 kV incoming lines can be connected to either busbar by a busbar coupler. The
two 11 kV outgoing lines are connected to the busbars through transformers (66/11 kV)
and circuit breakers.
21/23
Figure 17 – Duplicate busbar system
Go back to contents ↑
Figure 18 shows the key diagram of a typical 11 kV/400 V indoor substation. The key
diagram of this substation can be explained as follows:
22/23
Figure 18 – Key diagram of a typical 11 kV/400 V indoor substation
Diagram explanation:
1. The three-phase, three-wire 11-kV line is tapped and brought to the gang operating
switch installed near the substation. The GO switch consists of isolators connected
in each phase of the three-phase line.
2. From the GO switch, the 11 kV line is brought to the indoor substation as
underground cable. It is fed to the HT side of the transformer (11 kV/400 V) via the
11 kV OCB the transformer steps down the voltage to 400 V, three phases, four
wires.
3. The secondary transformer supplies to the busbars via the main OCB. From the
busbars, 400-V, three-phase, four-wire supply is given to the various consumers via
400 V OCB. The voltage between any two phases 400 V and between any phase
and neutral it is 230 V.
Go back to contents ↑
Reference // Elements of Power Systems by Pradip Kumar Sadhu and Soumya Das
23/23