You are on page 1of 82

Flooded Condenser Controls:

Principles and
Troubleshooting
Flooded condensers are the prime tower pressure-control methods for total condensers that
generate only liquid products, and although these control methods can be troublesome, a good
understanding of their principles will help achieve improved, trouble-free operations

FIGURE 1. Distillation columns


Henry Z. Kister
are crucial in many facilities, and Fluor Corp.
pressure control within the tower
is of the utmost importance in
ensuring steady operations IN BRIEF
COMMON CONTROL
ARRANGEMENTS

HYDRAULICS OF
FLOODED CONDENSERS

VAPOR PRESSURE
DIFFERENTIALS

OVERCOMING
CHALLENGES

VAPOR TO VAPOR AND


LIQUID TO LIQUID LINES

SURFACE AGITATION

INERT PADDING

DECANTING WATER

NON-CONDENSABLE
GASES

INSUFFICIENT

P
ressure is the most important denser. Another alternative for either vapor or
SUBCOOLING
variable for controlling distilla- liquid products is to manipulate the coolant
tion columns (Figure 1) because flowrate (or temperature) to control the tower AIR CONDENSERS
pressure affects every aspect of pressure. Coolant manipulation is popular in VALVE CONFIGURATIONS
a distillation system: vaporization, conden- refrigerated towers, but is usually avoided in
sation, temperature, volatility and so on. cooling-water condensers, as it can cause FLOODED DRUM
SCHEME
An unsteady pressure typically results in an accelerated fouling and corrosion.
unsteady column. Flooded condenser control is by far the FINAL REMARKS
There are several ways to control tower preferred pressure-control method used
pressure, depending on how the tower is with water-cooled total condensers (those
configured. If a tower has an overhead vapor generating liquid products only). It is also
product, manipulating the vapor flowrate common with air-cooled total condensers.
usually controls pressure. If the tower has no In this control method, the condenser area is
vapor product (it has a total condenser and partially flooded by condensate. The flooded
produces only liquid), tower pressure can be tubes do not contact the vapor and perform
controlled by partially flooding the condenser little condensation. The column pressure is
and manipulating the liquid level in the con- controlled by manipulating the flooded area.

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016 37


FIGURE 2. These common PC PC
flooded-condenser control
arrangements show two dif-
ferent control-valve configura-
Over-
head
from
~
~
P1 Over-
head
from
~
~
P1

Vent
tions. In Figure 2a, the control tower tower
valve is located in the conden- Vent
Pin
sate liquid line, and in Figure
2b, the control valve is placed Equalizing Equalizing
line line
in the vapor line
Pout

P1 Signal to P1 Signal to
LC product LC product
or reflux or reflux
valve valve

Product plus Product plus


reflux reflux
a b

Raising the liquid level in the condenser the condenser liquid outlet. The required
floods additional tubes, which reduces con- control valve is small, and should be lo-
densation area, thereby raising tower pres- cated as close to the reflux drum as pos-
sure. Conversely, lowering the liquid level in sible to maximize static head when the
the condenser exposes more tubes, which condensate enters at the top of the drum
increases the condensation area, and sub- [1]. For condensate entrance at the bottom
sequently lowers the column pressure. of the reflux drum (as seen in Figure 3a),
The principles of flooded condenser con- the valve should be located at the lowest
trols were described in literature more than horizontal leg. This method is simple and
60 years ago. Chin’s classic paper on dis- linear, and maintains the same pressure in
tillation pressure-control describes many of the column and in the drum. It is therefore
the principles and good practices [1]. Yet, often favored [1, 5].
these methods continue to be among the This control method requires that a pres-
most troublesome distillation controls. A sure-equalizing line is included [1, 5, 6, 7].
good understanding of the principles, as well Without this line, the pressure in the reflux
as learnings from past experiences, are key accumulator will be unsteady. A smaller
for avoiding many of the potential problems equalizing line is required when the sub-
[2]. This article provides an updated and de- cooled liquid is introduced near the bottom
tailed description of the principles of flooded of the drum, as shown in Figure 2a.
condenser control, and applies them to ad- Figure 2b shows a flooded condenser
dress many of the most common traps that scheme similar to that in Figure 2a, but with
can cause operational issues. the control valve located at the condenser
vapor inlet. Similar to the method in Figure
Common control arrangements 2a, the condenser liquid outlet line must
Although the flooded area performs little enter near the bottom of the reflux drum,
condensation, it serves the vital purpose and a pressure-equalizing line is required.
of subcooling the condensate. Subcooling Placing the control valve in the vapor inlet
is beneficial when pumping volatile liquids (Figure 2b) renders the condensation pres-
[3]. Although the subcooling consumes sure lower than when the valve is in the con-
some heat-transfer area, this area is not densate outlet (Figure 2a), resulting in the
always added in the exchanger design. requirement of additional condenser surface
Some designers are comfortable to as- area. If no additional area is provided, tower
sume that the subcooling area can come pressure must be raised, which increases
from the overage included in the exchanger energy consumption. The required vapor-
design [3]. Conversely, others prefer to control valve is large and may be expensive
oversize the condensers by as much as with large overhead lines.
25% to ensure subcooling, especially when Figure 3 shows three additional flooded-
the subcooling is critical, as in hot-vapor- condenser control schemes, all containing
bypass schemes [4]. a control valve in the condenser vapor by-
Figure 2 shows two common flooded- pass. Figures 3a and 3b are analogous to
condenser control arrangements, both with Figures 2a and 2b; the only difference being
the condenser mounted above the reflux the addition of the bypass control valve.
drum. Figure 2a has the control valve in This control valve helps overcome the pres-
38 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016
PT PT FIGURE 3. Three flooded-
Over-
head
from
P1 ~
~
Overhead
from tower
~
~
P1 condenser control schemes
with valves in the vapor by-
Vent Pin pass are shown: Figure 3a
tower Pbypass PC Pbypass
DPC DPC places the pressure-control
Vent
Pcond Pcond valve in the condensate liq-
uid line; Figure 3b places the
PC H PT PT pressure-control valve in the
Signal to H
Signal to
vapor line; and in Figure 3c,
P2 P2 the pressure-control valve is
LC product LC product
or reflux or reflux in the hot-vapor bypass
valve valve

Product plus Product plus


Pout reflux reflux
a b

sure drop in the condenser, especially when PT


the liquid head is small. P1
From
Figure 3c shows the hot-vapor-bypass tower
Pbypass PC
pressure-control method. Here, the location
of the pressure-control valve is switched Signal to
P2
from the condenser route in Figures 2, 3a LC product
or reflux
and 3b to the hot-vapor bypass. The con- valve
denser is at ground level, typically 10–20 ft Vent h
below the reflux drum (which may be hori- Pcond
zontal or vertical). The condensate must be
Product plus
subcooled so that the liquid surface in the reflux
drum is colder than in the condenser. While
c
the pressure in the condenser is equal to
the vapor pressure of the condensing vapor, Hydraulics of flooded condensers
the drum pressure is the vapor pressure of Figure 3a shows a very common arrange-
the cooler liquid surface in the drum. The ment. The condenser is elevated above the
difference in vapor pressures lifts conden- drum, with the condensate descending into
sate from the condenser into the drum. To the drum due to gravity. The column pressure-
reduce column pressure, the valve is throt- control valve is in the condensate line from the
tled, reducing the hot vapor supply to the condenser to the drum, which enters the drum
drum, and the drum’s liquid surface cools. below the liquid level. Up to this point, this
The colder surface has less vapor pressure. scheme is the same as Figure 2a. The differ-
This increases the pressure difference be- ence is that in Figure 3a, there is also a control
tween the condenser and the drum, which valve in the condenser bypass. The presence
in turn sucks liquid from the condenser into of this control valve renders the pressure in the
the drum. This exposes additional tubes in drum lower than at the condenser, which intro-
the condenser, and increases the conden- duces a vapor-pressure effect. Assuming neg-
sation rate, which lowers column pressure. ligible line pressure losses, a pressure balance
The hot-vapor-bypass arrangement per- on the condenser gives Equation (1) below.
mits the condensers to be mounted at
ground level instead of on a platform above P1 – P2 = –H + ∆Pcond + ∆Pout (1)
the reflux drum. Locating large cooling-wa-
ter condensers at ground level eliminates The variables in Equation (1) are defined
the requirement for a massive condenser- as follows:
support structure, and there is also no need • P1 is the pressure at the junction between
to pipe cooling water to high elevations. the vapor line to the condenser and the
This provides easy access for maintenance, condenser bypass in psia
the piping is simple, the control valve is • P2 is the pressure at the vapor space
small, and the response is fast [3, 8]. These inside the reflux drum in psia
advantages can translate into considerable • H is the head differential between the
savings in steelwork, platforms, trolleys and condenser liquid level and the reflux-drum
maintenance. These savings can be major liquid level in psi
in large installations, especially where a bat- • ∆Pcond is the condenser pressure drop in psi
tery of condensers rather than a single ex- • ∆Pout is the pressure drop across the
changer is used. However, this method suf- condensate outlet control valve in psi
fers from many potential issues, which are The density used to calculate the head dif-
described in detail in Ref. 9. ferential H is the difference between the liquid

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016 39


and vapor densities, due to the pres- Vapor pressure differentials
ence of a static leg of vapor in the by- As long as there is no hydraulic restric-
pass line. The vapor density is based on tion in the condenser bypass line (Figure
the drum pressure and the drum vapor- 2a), and the pressure drop of the con-
space temperature. The liquid density is denser inlet line and at the condenser
best approximated as the density of the entry is low, the pressure is the same at
subcooled liquid leaving the condenser. the condenser as at the reflux drum. In
Without a control valve in the bypass this case, the vapor-pressure differential
(Figure 2a), then P1 = P2, and Equation between the condenser surface and the
(1) becomes Equation (2). drum’s liquid surface is zero. In all other
situations, the vapor-pressure differential
H = ∆Pcond + ∆Pout (2) plays a role, often a major one.
The pressure differences between the
Equation (2) states that for the Fig- condenser and the drum in Figures 3a,
ure 2a configuration, the head required 3b and 3c introduce vapor-pressure ef-
to drain the condenser must be high fects. In Figures 3a and 3c, P1 – ∆Pcond
enough to overcome the condenser is the vapor pressure of the liquid sur-
pressure drop plus the pressure drop of face in the condenser, assuming most
the condenser outlet valve. This condi- of the condenser pressure drop is near
tion may not be satisfied when the con- the condenser inlet — usually a reason-
denser pressure drop (∆Pcond) is high, able assumption for total condensers. In
or the available liquid head H is low. Figures 2b and 3b, the vapor pressure
Adding the valve in the bypass (convert- of the liquid surface in the condenser is
ing the Figure 2a scheme to Figure 3a) P1 – ∆Pin – ∆Pcond. In all the schemes in
changes the difference between P1 and Figures 2 and 3, P2 is the vapor pressure
P2 to ∆Pbypass, giving Equation (3). at the reflux-drum surface.
In the schemes in Figures 2 and 3, the
P1 – P2 = ∆Pbypass (3) hot vapor provided by the bypass con-
denses onto the drum liquid surface,
Combining Equations (1) and (3) gives which keeps the surface hot. At steady
the scheme shown in Figure 3a, repre- state, the hot bypass introduces sufficient
sented by Equation (4). vapor to maintain the temperature of the
drum’s liquid surface at the value corre-
H + ∆Pbypass = ∆Pcond + ∆Pout (4) sponding to the desired vapor pressure
P2. Heat flows from the hot liquid surface
Therefore, the pressure drop across to the subcooled liquid underneath, and
the bypass valve helps the gravity head there are also atmospheric heat losses
push the liquid from the condenser into from the vapor space of the drum. These
the drum. For the arrangement in Figure heat flows must be matched by con-
3b, the pressure drop at the condenser densing the hot vapor from the bypass.
inlet ∆Pin (psi) replaces the pressure drop As long as the drum surface remains
at the condenser outlet ∆Pout, and Equa- steady, most of the heat flow from the
tion (4) becomes Equation (5) below. surface to the subcooled bulk liquid is
by conduction. Since process liquids are
H + ∆Pbypass = ∆Pcond + ∆Pin (5) good thermal insulators, the conduction
heat transfer from the hot surface to the
For the arrangement in Figure 3c, subcooled liquid is small. In reality, con-
there are no control valves at the con- vection and some bulk movement raise
denser inlet or outlet, and the liquid the heat transfer from the surface to the
head h (psi) is the difference between subcooled bulk liquid, but even account-
the reflux-drum liquid level and the liq- ing for these, the bypass vapor flowrate
uid level in the condenser, meaning that can easily match the heat demand at the
h = –H. The value of H in Equation (4) is drum liquid surface.
negative, as the liquid level in the reflux Ref. 9 details the heat balance for the
drum is at a higher elevation than that drum in relation to the scheme in Figure
of the condenser. Equation (4) then be- 3c. The heat-balance discussion pre-
comes Equation (6). sented there also fully applies to other
flooded-condenser control schemes
∆Pbypass = ∆Pcond + h (6) (Figures 2a, 2b, 3a and 3b).
40 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016
The vapor-pressure effects become of ut- any horizontal runs should drain into the re-
most importance in the hot-vapor-bypass flux drum. The author is familiar with cases
scheme with submerged condensers (Figure where a pocket of liquid in the hot-vapor-
3c). In this scheme, the vapor-pressure differ- bypass line in Figure 3c led to severe oscil-
ences directly determine the flooded height lations and column pressure swings. Most
in the condenser. In the elevated-condenser importantly, liquid from the condenser must
schemes (Figures 3a and 3b), the condenser enter the reflux drum near the bottom of the
inlet or outlet valve directly determines the drum, well below the liquid surface. This is
flooded height, with the bypass mainly used imperative with the Figure 3c configuration,
to provide sufficient pressure drop, per and also highly recommended with the other
Equations (4) and (5). schemes. The rule is “vapor to vapor, liquid
With the hot-vapor-bypass scheme (Figure to liquid.”
3c), the vapor-pressure difference provides If the liquid enters at the bottom of the
the driving head that pumps the conden- drum with an upward momentum (as shown
sate liquid from the condenser into the reflux in Figures 3a, 3b and 3c), a horizontal baffle
drum as described in Equation (6). Equation should be added above the inlet to spread
(3) can be combined with Equation (6) to the momentum of the incoming liquid jet. As
give Equation (7): reported in Refs. 9 and 10, liquid jets at ve-
locities of a few feet per second can easily
P1 – P2 – ∆Pcond = h (7) penetrate through several feet of drum liquid,
bringing a variable amount of subcooled liq-
Equation (7) shows that the vapor-pressure uid to the drum liquid surface, disturbing the
difference is balanced by the liquid head lift. If surface. In some cases, such disturbances
higher pressure is required in the tower, there have caused a massive amount of liquid to
is a need to flood more area in the condenser. be suddenly sucked from the condenser into
This requires reducing the liquid head lift h. the drum [9, 10].
To achieve this, the vapor-pressure differen- Figure 4a depicts a case in which viola-
tial P1 – P2 – ∆Pcond must be reduced. With tion of this practice led to severe pressure
P1 and ∆Pcond constant, this is achieved by fluctuations, an inability to maintain column
opening the hot-vapor bypass to raise P2. pressure and a capacity bottleneck [9, 11].
Opening the hot-vapor bypass heats up the In this scheme, subcooled liquid mixed
liquid surface in the drum, which raises the with vapor at its dewpoint, and vapor col-
vapor pressure P2. Conversely, to reduce col- lapse occurred at the site of mixing. The
umn pressure, there is a need to lower the rate of vapor collapse varied with changes
liquid level in the condenser, which raises the in subcooling, overhead temperature and

Most importantly, liquid from the condenser must enter the reflux drum
near the bottom of the drum, well below the liquid surface

liquid head lift. This is achieved by closing the condensation rate. Variation of this col-
bypass valve. This cools the surface in the lapse rate induced pressure fluctuations
drum and lowers P2. The larger P1 – P2 dif- and hammering.
ference sucks liquid from the condenser into The green piping in Figure 4b shows the
the drum, thus exposing more condenser piping modification that eliminated the prob-
area for condensation. These mechanisms lem. The liquid and vapor lines were sepa-
are described in detail in Ref. 9. rated, and the vapor line was altered so that
it introduced vapor into the top of the reflux
OVERCOMING CHALLENGES drum. After these changes were made, the
Correct configuration is mandatory for the tower pressure no longer fluctuated, and the
success of all flooded condenser schemes, problem was completely solved.
due to their challenging nature. This case is one example of a violation
of the “vapor to vapor, liquid to liquid” rule
Vapor to vapor and liquid to liquid lines described above, and is the most common
Bypass vapor must enter the vapor space of cause of poor performance with hot-vapor-
the reflux drum. The bypass should be free bypass schemes. A number of these cases
of pockets where liquid can accumulate, and have been reported in literature [5, 6, 11, 12].

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016 41


PC
Reprinted courtesy of AIChE decrease to as low as the vapor pressure of
the liquid at the subcooled temperature. The
author is familiar with situations where this
pressure loss pulled vacuum inside the reflux
drum. In other cases, drum pressure fluctu-
LC ated, sometimes wildly. In some other situa-
Tower tions where the bypass was large, the liquid
almost entirely lost its subcooling, causing
M

cavitation of the reflux pump. Splashing sub-


M

CW CW cooled liquid onto the drum surface can also


lead to the generation of static electricity.
Four
FC The higher the difference between the bub-
condensers
ble point and the subcooled temperature,
a
the more aggravated these issues become.
PC
Configurations where the liquid line enters
the drum liquid also have the advantage
of providing a better seal to the condenser
and preventing vapor from blowing through
the condenser [3].
LC A common design practice is to introduce
Tower the liquid from the top of the drum via a slot-
ted or perforated pipe, so that most of the
M

liquid is introduced below the drum liquid


M

CW CW level, but some is splashed onto the liquid


surface. This method is better than introduc-
FC ing all the liquid into the vapor space, but
is not as good as introducing all the liquid
b near the bottom of the drum, and has been
troublesome. The larger the opening that
FIGURE 4. These diagrams Any subcooled liquid streams entering the discharges liquid into the vapor space, the
show correct and incorrect drum must also enter at or near the bottom more troublesome this method is likely to be,
hot-vapor-bypass hookups.
Figure 4a illustrates a com- of the drum. In one case, subcooled liquid especially in situations with a high degree
mon mistake that leads to entered the drum vapor space (presum- of subcooling, such as during cold winter
pressure fluctuations. Figure ably due to unflooding of the liquid inlet) nights or low-rate operation. The issues are
4b shows modifications (in
green) that correct the issues
[6]. The vapor space was 100°F hotter, and identical to those described in the previous
in Figure 4a, and provide rapid condensation sucked the liquid leg paragraph. In the author’s experience, severe
sound pressure control [9] between the drum and condenser into the hammering has occurred when highly sub-
drum in seconds. cooled liquid was introduced from the top of
With the systems in Figures 2a, 3a and the drum with perforated or slotted dip pipes.
3b, there is some debate in the literature The hammering ceased after the slots in the
whether the liquid should be introduced vapor space were blocked.
into the vapor space or into the liquid at (or
at least near) the bottom of the drum. Ref. Surface agitation
1 recommends liquid entry above the liq- Operation may be troublesome if the drum’s
uid level so that drum level does not affect liquid surface is agitated. Surface agitation is a
the condenser level. particular concern with the hot-vapor-bypass
The author and others strongly prefer that scheme (Figure 3c), but the other schemes
the subcooled liquid enters at the bottom are not immune. Such agitation stirs up sub-
of the drum [8, 13]. Introducing subcooled cooled liquid and brings it to the hot liquid
liquid above the liquid level is likely to cause surface in the drum, causing fluctuations in
vapor collapse onto the cold liquid. This in the drum pressure. The source of agitation
turn may result in pressure fluctuations and may be from impingement of a high-velocity
possible hammering. Further, introducing the hot vapor jet on the liquid surface, due to up-
subcooled liquid onto the drum liquid sur- ward-directed subcooled liquid jets reaching
face drops the vapor pressure in the drum the liquid surface, as well as other causes.
by a large amount, raising the demand of Control instability has been reported when
hot vapor from the bypass tremendously, surface agitation occurred due to strong ex-
and often overwhelming the capacity of the ternal vibrations on the reflux drum platform
bypass. Unless a much larger bypass is [14]. Agitation of the liquid surface can often
available, the pressure inside the drum can be avoided by judicious baffling [9].
42 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016
Inert padding
PC
Instability due to surface disturbances or
agitation may be alleviated, even mitigated,
by padding the drum with non-condens-
Overhead
from tower ~
~
Vent
able inert gases. A source of inerts, such
as nitrogen or fuel gas, is connected to the
vapor space of the drum. The drum pres-
sure is controlled by adding or venting the
inerts. The drum pressure is no longer the
vapor pressure of the liquid, but now equals
the sum of the vapor pressure (VP) of the
Signal to
drum liquid and the inerts partial pressure, LC product
as shown in Equation (8). The box on p. 44 or reflux
valve
presents a practical calculation example of
the effects of inerts in a tower. ILC Interface

P2 = VPdrum liquid + Pinerts (8)

With total condensers, inert padding is


usually implemented during operation as Water Product plus
a temporary solution to alleviate instability, reflux

especially since the inerts can be quite ex-


pensive. The vented inerts contain vapor- which the liquid product and reflux are with- FIGURE 5. The flooded-
ized product. In the calculation example on drawn. The water-removal boot should be condenser control scheme
from Figure 2a is illustrated
p. 44, assuming ideality and equilibrium, just upstream of the point where the reflux here with a water decanting
10% (3.1 psia/30 psia) of the vent gas at and product streams are withdrawn [16], configuration
80°F on a molar basis will be hexane. On as illustrated in Figure 5 for the control sys-
a weight basis, the hexane fraction of the tem from Figure 2a. In many cases, a short
vent gas is even higher due to the low mo- standpipe (about 6 to 12 in. tall) or judicious
lecular weight of the inerts — 26% hexane baffling are used as additional measures to
on a weight basis for nitrogen padding. keep water out of the reflux and product
This vented product is likely to be lost, and draw [16], but these additional measures
may increase flaring or emissions. The in- may lead to water accumulation in the drum.
erts, even nitrogen and fuel gas, can be Also, corrosion is possible when the interface
absorbed into the product, and can later level controller in the boot malfunctions, and
increase pressure in downstream equip- potentially acidic water is not adequately re-
ment, resulting in more product loss and moved from the drum. Ref. 17 describes a
flaring downstream. To avoid inconsistent related experience.
transitions from the inert-addition mode to
the venting mode, there is often a pressure Non-condensable gases
range in which inerts are added simultane- Flooded condenser schemes are suitable
ously with venting, which compounds the only for total condensers, although some
previously described issues [15]. In order less satisfactory variations are also available
to maximize product recovery and minimize for partial condensers [5]. The schemes in
emissions and flaring, some experts rec- Figures 2 and 3 can handle small amounts
ommend against using inert padding with non-condensable gases, such as those in-
total condensers, other than as a temporary troduced during startups or upstream up-
solution [15]. Diagnosing the cause of, and sets. To handle these non-condensables,
eliminating the surface instability, is usually vents are required on the condenser and the
a preferred longterm solution, especially drum. The condenser vents can be directed
with volatile products. to the vapor space of the drum, to an up-
stream unit or elsewhere. The drum vents
Decanting water should be board-operated, and if frequent
If the reflux drum is used to decant small venting is anticipated, the condenser vents
quantities of free water from condensed should also be board-operated. In one case,
hydrocarbons or other water-insoluble or- a debutanizer flooded-condenser system
ganics, the entry point of the condensate experienced frequent high pressure, insta-
liquid (and other subcooled liquid streams bility and flaring due to the breakthrough of
that may contain free water) should be lo- non-condensables from an upstream tower
cated within the drum opposite to the end at that had control issues [18]. The problem

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016 43


THE IMPACT OF INERT PADDING ply an operator advisory to limit the pressure
minimization upon low subcooling, may also

C
onsider a tower making hexane top product at 35 psia and 210ºF. The over-
head vapor is totally condensed, and is subcooled to 80ºF before entering
be beneficial.
the reflux accumulator at 30 psia. With no inerts, the drum liquid surface will
be at about 200ºF to match the vapor pressure of hexane at 30 psia. A disturbance Air condensers
that lifts 5% of the subcooled liquid to the surface will cool the surface to 194ºF (0.05 Air condensers are elevated above the re-
× 80ºF + 0.95 × 200ºF), which will in turn drop the drum pressure by 3 psi — quite a flux drum, so the only compatible flooded
large pressure swing. In contrast, with inerts filling the drum vapor space, the drum condenser schemes are those for condens-
surface can be as cool as the subcooled temperature of 80ºF. At this temperature,
ers mounted above the drum (as seen in
the vapor pressure of hexane is 3.1 psia, with the partial pressure of the inerrts mak-
ing up the remaining drum pressure. A 6ºF drop in surface temperature will lower the
Figures 2, 3a and 3b, as well as Figure 7,
hexane vapor pressure to 2.7 psia, causing only a small change of 0.4 psia to the discussed further below). The hot-vapor-
drum pressure. ❏ bypass scheme (Figure 3c) requires mount-
ing the condenser below the drum, and is
was mitigated by adding a manual board- incompatible with air condensers. In one
operated condenser vent that was opened tower, overhead vapor was condensed in
upon high pressure and vented to an an elevated air condenser followed by a
upstream system. ground-level cooling water condenser. The
Figure 3c scheme worked well when the
Insufficient subcooling liquid level was in the water condenser, but
Flooded-condenser control methods pro- became unstable on cold days when the air
duce subcooled reflux and product. This condenser supplied the total condensation
subcooling is beneficial in avoiding net duty and the liquid level climbed into the air
positive suction head (NPSH) issues in the condenser. The solution was to reduce the
pump or flashing problems in the reflux or air condenser duty by shutting off fans and
product line. Such flashing can lead to in- closing louvers so the liquid level remained in
stability, poor reflux distribution at the tower the water condenser [9].
inlet, slug flow and even hammering [19]. An air condenser has a small ratio of
The instability may be particularly severe height to width. Any change in liquid level,
with the flooded drum method (discussed even as small as 1 in., may result in an en-
below), due to its potential interaction with tire tube row being covered or uncovered.
the column pressure control. However, Typically, an air condenser will have very few
other flooded condenser methods can also rows (well below 10), so covering or uncov-
exhibit such issues. ering one results in a bump in heat transfer.
Subcooling is diminished when the con- It is common to slightly slope several bottom
denser nears its maximum capacity. This tube rows, or all rows, towards the outlet so
may be the natural maximum limit, or can that the movement of liquid level up or down
be caused by fouling, non-condensable ac- the tubes is smoother [4].
cumulation, condenser drainage or other is-
sues. Subcooling is also diminished when Valve configurations
liquid is splashed onto the surface of the There are unique issues associated with the
drum, as discussed earlier. Finally, many various valve configurations shown in Fig-
advanced controls use pressure minimiza- ures 2 and 3. The following sections detail
tion strategies, such as Shinskey’s floating these issues and provide some guidance for
pressure control [19, 20]. These strategies avoiding them.
reduce tower pressure during periods of fa- Valve in the condenser vapor inlet line
vorable ambient temperatures to conserve (Figure 2b and 3b). As mentioned earlier,
energy, and in high-pressure towers (greater this method places a backpressure valve
than 150 psia), can also maximize capac- in the overhead vapor line, thereby re-
ity. The pressure reduction brings the con- ducing condenser temperature difference
denser closer to its limit, and by doing so, and capacity.
minimizes subcooling. To minimize pressure drop, the overhead
Issues with insufficient subcooling can valve is often designed for a small pressure
be avoided, as long as the condenser is drop when fully open. This often leads to
not near its capacity limit. The keys are to valve oversizing. When oversized, the valve
avoid splashing the condensate liquid onto operates barely open during winter and
the drum surface, minimize condenser foul- cold spells. In this situation, very small valve
ing, properly vent non-condensables from movements cause large fluctuations in tower
the condenser and adequately monitor the pressure. In one case, it was necessary to
subcooling. Some override control, or sim- throttle a manual valve upstream in the line
44 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016
PT
to force the control valve to operate close to
its half-open position [16].
This method is prone to liquid hammering
Overhead
from tower
~
~
Vent
if the valve closes excessively. In one case,
the valve closed fully under some startup
conditions [21]. Vapor downstream of the
valve rapidly condensed, causing liquid to be
PC PC
rapidly drawn from the reflux drum, which in
turn generated a liquid hammer that shook
the whole unit. The problem was solved
Signal to
by changing the valve so that it would not LC product
fully close [21]. or reflux
valve
Valves in both the condenser and bypass
lines (Figures 3a and 3b). The addition of Product plus
the second valve generates potential interac- reflux
a
tion between the loops controlling pressure
and differential pressure. There is also the PT
question of which variable should be used to
Over-
head
P1
~
control the bypass. Friedman’s work in Ref. from ~

~
~
tower Vent
22 specifically addresses these questions.
DPC
Friedman advocates controlling the by- Pressure
setpoint
pass using a separate drum-pressure con-
troller (Figure 6a), rather than the differential
PC
pressure controller in Figures 3a and 3b. PT
Ref. 1 reports one successful case with the
system shown in Figure 6a where the liquid P2 Signal to
head was small and the valve in the bypass LC product
or reflux
line was needed. valve
The Figure 6a scheme is uncommon, but
Product plus
the author is familiar with troublesome inter- reflux
Pout
action between the pressure controllers in this b
scheme. This interaction is discussed in Refs.
8 and 22. Ref. 22 states that in this interaction, A widely preferred alternative to the dual FIGURE 6. These schemes
the two control loops help each other. Both pressure-controller scheme in Figure 6a is present alternatives to dif-
ferential pressure control
references also state that the key for success the differential-pressure (dP) control scheme on the vapor bypass. Figure
with this scheme is to tune the drum pres- in Figure 3a and 3b. Friedman notes that 6a shows a separate pres-
sure fast and the column pressure slow, much with this scheme, the two controllers tend sure controller on the reflux
drum, which is not favored
like a level controller. However, as previously to fight each other. Upon an increase in col- by the author. Figure 6b uses
stated, tower pressure is the most important umn pressure, the condenser outlet valve the pressure setpoint in the
column-control variable. It therefore needs to (Figure 3a) opens, lowering the liquid level in differential pressure control-
be tuned fast so it does not wander. Unlike the condenser, while the dP controller opens ler, and alleviates concerns
regarding negative controller
pressure, level does not affect many variables, the bypass valve, which raises the liquid level interactions
and as long as it stays within limits, it can move in the condenser. While there is some de-
slower and be allowed to drift. Therefore, bate in industry about the operability of this
the Figure 6a scheme is not recommended control scheme, it is accepted that if both
by the author. controllers are tuned fast, there may be an
Another issue with using a separate drum unfavorable interaction.
pressure controller is that every time the set- A simple solution, practiced by many of
point is changed on the tower pressure con- those that reported the scheme to be trou-
troller, the same change must be made on the blesome, is to tune the dP valve slow or to
reflux-drum pressure controller [8]. The reflux- place the dP valve in manual mode. These
drum pressure setpoint needs to be lower solutions have been implemented success-
than the tower pressure setpoint, making the fully to overcome the controller interactions.
scheme prone to major upsets if operator It is important to keep in mind that the main
error occurs. To overcome this issue, Ref. 8 objective of the dP valve is to provide a re-
proposes an advanced control that subtracts striction that will overcome the pressure
an appropriate bias from the tower setpoint drops on the righthand sides of Equations
to provide the setpoint for the reflux-drum (4) and (5), so there is no need for tight con-
pressure controller. trol of the bypass pressure drop. One must

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016 45


simply ensure that adequate resistance • There is a potential for interaction be-
is present. tween the drum and the condenser liquid
In Figure 6b, Friedman presents a more el- levels [5, 9, 10, 20, 24, 25]. To mitigate
egant, albeit less widely practiced, solution. the interaction, the pressure controller
Instead of controlling the actual dP, the dP is should be tuned much tighter than the
set as the difference between the setpoint on drum level controller [20, 24]. This can be
the pressure controller and the drum actual an issue if the reflux drum is small, and
pressure. This scheme has the strength of the level controller needs to be tuned fast
Figure 3a, which maintains a set dP, without to avoid overflow or loss of level. Al-
getting into the negative interactions. Also, though this scenario is quite uncommon,
this configuration permits fast tuning of the the author has experienced it, and Ref.
pressure controller, which is essential. As in 26 reports an additional case where
the Figures 3a and 3b schemes, the pres- this occurred
sure should be tuned fast and the dP slower. • Because of the liquid leg between the
Remember that the dP’s only purpose is to condenser and the drum, non-condens-
provide sufficient pressure drop across the ables accumulate in the condenser and
condensate valve. need venting from their accumulation

To mitigate potential interactions between the drum and the condenser


liquid levels, the pressure controller should be tuned much tighter than
the drum level controller

Hot-vapor-bypass controls (Figure 3c). points. If a vent line is absent, instability


In the hot-vapor-bypass configuration with and capacity bottlenecks may result [27]
submerged condensers, there are numer- • Leakage of vapor through the bypass
ous issues, which are covered in great detail valve at the closed position can sub-
in Ref. 9. The following are the key issues to stantially reduce condenser capacity. In
keep in mind with this scheme: one case, closing a manual valve in the
• Correct piping is mandatory for the suc- hot-vapor bypass increased condenser
cess of the hot-vapor-bypass control capacity by 50% [28]
method. As described earlier, the bypass • Undersizing the bypass control valve
vapor must enter the vapor space of the may lead to an inability to maintain the
reflux drum (Figure 3c or Figure 4b). The tower pressure during cold winter days
bypass should be free of pockets where when the drum is not insulated. In one
liquid can accumulate, and any horizontal situation, poor pressure control due to
runs should drain into the reflux drum. undersizing was improved by installing a
Most importantly, liquid from the con- throttling valve in the liquid line from the
denser, as well as any other subcooled condenser to the drum [29]
liquid streams, such as the reflux-pump • In some cases, the hot-vapor-bypass
minimum-flow recycle stream, must enter control valve is manipulated by the drum
near the bottom of the reflux drum. Many pressure instead of the tower pressure
experiences have been reported in which [29]. Dynamically, this control scheme is
incorrect piping led to instability, poor inferior because the vapor volume in the
control and hammering [4–6, 11, 12, 23] drum is much smaller than in the tower
• As previously described, operation may and more variable in response to
be troublesome and unstable if the drum’s ambient changes
liquid surface is agitated [1, 6, 9, 10] • The reflux-drum vapor space may require
• A sudden reduction in drum pressure insulation to minimize interference from
can rapidly suck the liquid out of the rain and snow [1, 5, 6, 9]. This issue is
condenser, causing a major upset [9,10]. reported to be more pronounced with
There is also the possibility of U-tube narrow boiling-range mixtures [1, 6],
oscillations [5, 24, 25]. Both issues can and at high pressure [6], where small
be mitigated by adding a throttling valve temperature changes have a large effect
in the liquid leg between the condenser on the split of overhead flow between
and the drum the condenser and the bypass. At the
46 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016
FIGURE 7. The flooded-drum
other extreme, the incidence of Rayleigh Over-
PC control method can offer cost
fractionation with wide-boiling mixtures head savings in some applications,
from Vent but also introduces some
(where heavy components condense tower unique issues
out without combining with the remain-
ing mixture), can also interfere with this
control system [3]
• The amount of subcooling and vapor
bypass rates can only be determined
Vent
empirically. Simplified sizing procedures
are available [6, 30], but these are based
on heating all of the subcooled liquid to Flooded
its bubble point, and therefore are grossly reflux drum
conservative. More reasonable sizing FC
Product
criteria can be inferred from the principles to
FC storage
discussed in Ref. 9
Reflux to
tower
Flooded drum scheme
Figure 7 illustrates the flooded reflux-drum
method. Here, the drum runs full of liquid, tem that has worked well in practice [5, 12,
and the level control of the reflux drum is 31]. A second pressure controller (PC 2),
eliminated. Sometimes, especially in grav- a level controller and a control valve in the
ity systems that have no reflux pump, the vent line are added. The setpoint of PC 2 is
reflux drum itself can be omitted. The pres- lower than that of the normal pressure con-
sure controller directly controls distillate troller (PC 1). When the drum is full, the level
flow. Due to the absence of vapor space, controller keeps PC 2 tripped off, and the
the flooded drum is smaller than a drum vent valve is closed. Drum unflooding (due to
with a vapor space, the piping is simpler, non-condensable accumulation) is sensed
and together with the elimination of the level by a drop in drum level. The lower level ac-
control, this method can offer significant tivates PC 2. Since the setpoint of PC 2 is
capital-cost savings. lower than PC 1, it opens the vent valve. As
Due to the tight pressure control that is the drum pressure falls, PC 1 closes, help-
usually required, distillate flowrate controlled ing to build up the drum level. As soon as
by this method is likely to fluctuate. These the drum refills, the level controller trips PC
fluctuations may destabilize downstream 2, and the vent valve closes.
units. This method should therefore only Since the venting required above is from
be used when the product goes to storage a liquid-full drum, leaks from the vent line
[1, 5, 20, 24], and should be avoided when are likely to be liquid, giving a product loss
the product goes directly to another unit. much greater than a leaking vapor valve.
This method has sometimes been used Flashing of liquid across the valve can chill
to control reflux flow, but this practice is not the vent line, sometimes resulting in icing or
recommended [5]. Here, reflux flow, rather “weeping” on the outside of the pipe due to
than product flow, is likely to fluctuate, and atmospheric moisture condensation, with
this can destabilize the tower. possible overchilling or corrosion of the vent
FIGURE 8. This flooded-drum
Besides the condenser venting issue pipe. Ref. 16 describes one case of icing automatic-vent system with
above, the flooded-drum method has an ad- due to such a leak from a flooded drum in a dual pressure control has op-
ditional venting issue. Accumulation of non- debutanizer unit. erated well in practice [31]
condensables in the drum may unflood the
drum and interrupt the control action. These
non-condensables must be vented from near
the top of a liquid-full drum, so they need to ~
~ Vent to
be vented to a facility that can handle liquids, fuel
such as a knock-out drum. If accumulation On/off
PC
2
of non-condensables is infrequent, manual
venting from the top of the drum is often Still PC
1
sufficient to maintain satisfactory operation. LC Flooded
reflux drum
If non-condensables accumulate frequently,
or the column is run unattended, automatic
venting is required. Product
Reprinted courtesy
Figure 8 illustrates an automatic vent sys- of AIChE

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016 47


PC
with a few minutes to take action before the
Over-
liquid fills the condenser. The author is familiar
head with one plant that replaced a flooded drum
from
tower with a new non-flooded drum that was over
twice the volume (to accommodate a vapor
space) just to prevent recurrence of such a
Relief valve elevated
above condenser relief scenario.
liquid level Any relief valve mounted on the flooded
drum (Figure 9) is most likely to discharge
liquid, which may not provide adequate
relief and may cause problems in the flare
system. Furthermore, when the drum relief
Vapor pocket valve is elevated above the liquid level in the
may form here
Vent condenser, a vapor pocket may form in the
valve inlet line during warm weather. Upon
cooling (for instance, at night), the vapor
pressure of the liquid in the small pocket
Flooded
reflux drum falls. The vapor pocket may collapse, forc-
FC
ing a liquid rush that will hit the relief valve
and cause chattering, as reported in two
Product cases in Ref. 19. The need for a relief valve
to
FC storage on the drum should be critically reviewed,
as the relief valve on the tower should usu-
Reflux ally be able to relieve the drum.
to
tower
Final remarks
FIGURE 9. This configura- Unless the product is subcooled and at a Despite their importance in tower pressure
tion illustrates a relief valve significantly higher pressure than the storage control, flooded condenser controls have
mounted on a flooded drum
facility, it is best to take the product to stor- been some of the most challenging distilla-
age from downstream of the reflux pump (as tion-control techniques. However, operat-
shown in Figure 7). If the product is taken ing experience indicates that they can be
directly from the drum, flashing may occur quite trouble-free when correctly designed
downstream of the control valve, or it may and applied. It is hoped that the principles
be difficult to get the product into storage and experiences described in this article
when the storage pressure is high. Either will pave the way for flooded-condenser
may cause instability or back excessive liq- controls’ successful application for tower
uid into the condenser, thereby reducing its pressure control. ■
capacity and possibly leading to a relief situ- Edited by Mary Page Bailey
ation. In one depropanizer process, pressure
variations in elevated propane storage bul- References
lets downstream induced intermittent flash- 1. Chin, T.G., Guide to Distillation Pressure Control Methods,
ing and slug flow in the product line even Hydrocarbon Processing, 58(10), p. 145, 1979.
though the product was pumped [19]. Col- 2. Kister, H.Z., What Caused Tower Malfunctions in the Last 50 Years?,
Trans. Inst. Chem. Eng., Vol. 81, Part A, p. 5, January 2003.
lapse of vapor due to elevation and pressure
3. Whistler, A.M., Locate Condensers at Ground Level, Pet. Refiner,
changes is believed to have caused transient 33(3), p. 173, 1954.
shockwaves and hammering, as well as 4. Schneider, D.F., and Hoover, M.C., Practical Process Hydraulic Con-
chattering of the relief valves, in the pump- siderations, Hydrocarbon Processing, p. 47, August 1999.
discharge circuit. The chattering was elimi- 5. Kister, H.Z., “Distillation Operation,” McGraw-Hill, New York,
nated by adding a backpressure controller N.Y., 1990.
that prevented the flashing. 6. Hollander, L., Pressure Control of Light-Ends Fractionators, ISA J.
4(5), p. 185,1957.
With the flooded drum method, a failure of 7. Sloley, A.W., Effectively Control Column Pressure, Chem. Eng. Prog.,
the reflux pump often produces a relief situ- p. 38, January 2001.
ation. The condensate has nowhere to go, 8. Smith, C.L., “Distillation Control – An Engineering Perspective,”
and quickly floods the condenser, ceasing Wiley, Hoboken, N.J., 2012.
condensation, causing the tower pressure to 9. Kister, H.Z., and Hanson, D.W., Control Column Pressure via Hot-
Vapor Bypass, Chem. Eng. Prog., p. 35, February 2015.
rise until the relief valve lifts. In other flooded
10. Kister, H.Z., and Hanson, D. W., Troubleshooting a Hot Vapor Bypass
condenser schemes (for instance, Figure 2a) Control Instability, 10th International Conference on Distillation and
where the reflux drum is not flooded, the Absorption, Friedrichshafen, Germany, September 14–17, 2014.
vapor space in the drum provides operators 11. Kister, H.Z., and Litchfield, J.F., Distillation: Diagnosing Instabilities in

48 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016


the Column Overhead, Chem. Eng., p. 56, September 2004. 26. Laird, D., and Cornelisen, J., Control-System Improvements Expand
12. Kister, H.Z. “Distillation Troubleshooting,” Wiley – Interscience, Refinery Processes, Oil & Gas J., p. 71, September 25, 2000.
Hoboken, N.J., 2006. 27. Sloley, A.W., Simple Methods Solve Exchanger Problems, Oil & Gas
13. Buckley, P.S., Luyben, W.L., and Shunta, J.P., “Design of Distillation J., p. 85, April 20, 1998.
Column Control Systems,” Instrument Society of America, Research 28. Lieberman, N.P., “Troubleshooting Process Operations,” 4th Ed.,
Triangle Park, N.C., 1985. PennWell Books, Tulsa, Okla., 2009
14. Hollowell, R.W., Private communication, May 2015. 29. Hartman, E.L., and Barletta, T., Reboiler and Condenser Operating
15. Lieberman, N.P., “Troubleshooting Process Plant Controls”, Wiley, Problems, PTQ, p. 47, Summer 2003.
Hoboken, N.J., 2009. 30. Durand, A.A., Sizing Hot Vapor Bypass Valves, Chem. Eng., August
16. Lieberman, N.P., “Process Equipment Malfunctions”, McGraw-Hill, 25, p. 111, 1980.
New York, N.Y., 2011. 31. Kister, H.Z., and Hower, T.C., Unusual Case Histories of Gas Pro-
17. Cardoso, R., and Kister, H.Z., Refinery Tower Inspections: Discov- cessing and Olefins Plant Columns, Plant/Operations Prog.,6(3),
ering Problems and Preventing Malfunctions, Proceedings of the p. 151, 1987.
Distillation Topical Conference presentation, AIChE Spring Meeting,
San Antonio, Tex., April, 2013.
18. Parsons, K., Private communication, March, 2015. Author
19. Mani, G., Avoid Condensation-Induced Transient Pressure Waves, Henry Z. Kister is a senior fellow and director
Hydrocarbon Processing, p. 41, January 2011. of fractionation technology at Fluor Corp. (3
Polaris Way, Aliso Viejo, CA 92625; Phone
20. Shinskey, F. G., “Distillation Control for Productivity and Energy Con-
+1-949-349-4679; Email: henry.kister@
servation”, 2d ed., McGraw-Hill, New York, N.Y., 1984.
fluor.com). He has over 30 years experience in
21. Steinmeyer, D.E., and Mueller, A.C., Why Condensers Don’t Oper- design, troubleshooting, revamping, field con-
ate as They Are Supposed To, Panel Discussion, Chem. Eng. Prog. sulting, control and startup of fractionation
70(7), p. 78, 1974. processes and equipment. He is the author of
22. Friedman, Y.Z., Condenser Hot Vapor Bypass Control, Hydrocarbon three books, the distillation equipment chap-
Processing, p.150, June 2008. ter in Perry’s Handbook, and more than 100
articles, and has taught the IChemE-sponsored “Practical Distilla-
23. Duguid, I., Take this Safety Database to Heart, Case MS16, Chem. tion Technology” course more than 450 times. A recipient of several
Eng., p. 80, July 2001. awards, Kister obtained his B.E. and M.E. degrees from the Univer-
24. Nisenfeld, A.E., and R.C. Seemann, “Distillation Columns”, Instru- sity of New South Wales in Australia. He is a Fellow of IChemE and
ment Society of America, Research Triangle Park, N.C., 1981. AIChE, member of the NAE, and serves on the FRI Technical Advi-
25. Lupfer, D.E., Distillation Control for Utility Economy, Proceedings of sory and Design Practices Committees.
the 53rd Annual Convention, Gas Processors Association, March
25–27, Denver, Colo., p. 159, 1974.

MONITOR VISCOSITY SIMPLY


SENSE MIXER MOTOR HORSEPOWER
WITH UNIVERSAL POWER CELL
EASY INSTALLATION PROFILING A PROCESS
•฀No฀holes฀in฀tanks฀or฀pipes฀ •฀฀Power฀changes฀refl฀ect฀viscosity฀changes
•฀Away฀from฀sensitive฀processes •฀฀Good฀batches฀will฀fi฀t฀the฀normal฀“profi฀le”฀for฀
that฀product
24
VERSATILE
POWER DECREASE
•฀฀One฀size฀adjusts฀to฀motors,฀from฀ 22
SHOWS BATCH
small฀up฀to฀150hp 20
IS DONE

•฀฀Works฀on฀3฀phase,฀fi฀xed฀or฀variable฀ 18

frequency,฀DC฀and฀single฀phase฀power 16
POWER
SENSOR
14
SENSITIVE
•฀฀10฀times฀more฀sensitive฀than฀ 12

just฀sensing฀amps 10 DRY MIX ADD LIQUID


HIGH SPEED LOW SPEED MIXER
CONVENIENT OUTPUTS 8 MOTOR

•฀฀For฀meters,฀controllers,฀computers฀ 6 BEGIN HIGH


SPEED MIX
4-20฀milliamps฀0-10฀volts 4

0
BATCH 1 BATCH 2 BATCH 3

CALL NOW FOR YOUR FREE 30-DAY TRIAL 888-600-3247


WWW.LOADCONTROLS.COM

Circle 7 on p. 66 or go to adlinks.chemengonline.com/61491-07

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016 49


Process Engineering
and Optimization
W. TANTHAPANICHAKOON and K. SURIYE,
SCG Chemicals, Thailand

Solve online analyzer time delays


by improving sampling system design
Process design engineers may occasionally become involved • Type and size of the sample tap nozzle chosen
in the design of online analyzers and their associated sampling • Sample conditioning (e.g., filtering, coalescing,
systems. Here are proven and practical strategies to signifi- vaporizing)
cantly reduce time delays without added or expensive invest- • Flow path components from the sample tap to analyzer
ment. Time delay is key in sampling loop design: to use analyzer (e.g., flowmeter, pressure gauge)
data to adjust process control, it should reflect the most recent • Analyzer response time and analysis time
process conditions. Specialist analyzer engineers are good at • Sample switching for multiple samples using the same
specifying components in analyzer systems based on experi- online analyzer
ence with previous analyzer systems. However, if they have This article provides proven and practical strategies to mini-
limited process engineering fundamental knowledge, analyzer mize time delays with low or no investment.
sampling loop design is often copied “as is” from prior designs Well-designed sample tap location, and tap nozzle type, can
without understanding that a seemingly reasonable design may significantly reduce time delay. For example, if a liquid sample
cause significant time delays. Too often, the time delay is not contains unwanted small particulates generated from a process,
calculated, but is blindly assumed as acceptable by the process then it is recommended to sample from an upward-flow verti-
engineers who design the main process system, causing unex- cal process line to ensure a liquid-full condition inside the pro-
pected process control problems in service. cess line. A 45° angle-cut probe, instead of a square-cut probe,
prevents unwanted particulates moving into the analyzer sam-
pling system. The right probe, properly installed, eliminates
WHAT ENGINEERING STANDARDS DO the need to install a particulate filter system—a cause of time
AND DO NOT TELL YOU delay and dead legs—in the analyzer sampling system.
Process design engineers who specify online analyzer sys- Components on the flow path from the sample tap to the
tems must define the maximum time delay that the process analyzer, such as flowmeter, pressure gauge and temperature
control can tolerate. The time delay should be designed as short gauge—used to monitor sample flowrate, pressure and tem-
enough for process operators to promptly use analyzer data to perature—are also crucial parameters increasing time delay. It
adjust process control, whenever analyzer readings are outside is technically smart to move these components from the main
of a normal range. flow path to the sample bypass line or the process return line to
Typical engineering standards require less than a 60-second minimize time delay and dead legs.
time delay between the sample tap and the analyzer inlet. The Analyzer analysis time can also be a main cause of time de-
distance of the analyzer house from the sample tap is critical in lay, especially on samples with a wide range of composition
meeting this time constraint. Use small sample lines and small (e.g., light gas to heavy liquid sample). Often, gas and liquid
volumes to minimize the residence time between the sample tap phases are pre-separated and then analyzed individually by two
and the analyzer. parallel analyzers to reduce the total time spent analyzing two
Note that engineering standards may not always provide de- phases sequentially.
tails about process engineering strategies to minimize time de- Therefore, the process design engineer must see the overall
lays. For example, they may state only the use of short distances, big picture of time delays when designing the analyzer sampling
small sample lines or fast loop to solve all time delay problems. loop system. Overall time delay of an analyzer system—includ-
Standards also may not state that time delays occur not only ing process delay, sample transport delay, sample conditioning
due to a time delay between the sample tap and analyzer inlet, delay and analyzer response time delay—should be consistent
but also due to other factors, such as: with the measurement and control requirements of a particular
• Location of the sample tap relative to the point of process. Limiting the “sample conditioning” time delay to no
process control more than 30 seconds is recommended.
Hydrocarbon Processing | JANUARY 2016 71
Process Engineering and Optimization

Two modes of sample transport from the sample tap to the 7. If calculated time delay < target time delay, the
analyzer are: calculation is finished; if not, then go back to Step 3.
1. Single-line transport A common mistake in calculating time delays is the failure to
2. Fast-loop transport. account for the following:
FIG. 1 shows single-line transport vs. fast-loop transport and 1. Gas (compressible fluid) velocity increase along the
how the fast loop can reduce time delay. The fast loop allows the gas sample line due to lower gas density when sampling
use of a higher flowrate and higher sampling line size up to the line pressure decreases as a result of pressure drop. This
analyzer inlet. There, a specified amount of the fast-loop flow is expansion results in higher pressure drop along the line
split and sent to the analyzer, while most of the fast-loop flow as gas flows. However, liquid (incompressible fluid)
bypasses the analyzer and returns to the process. density remains constant, despite a drop in pressure.
Therefore, liquid velocity stays constant, resulting in
constant pressure drop per length.
CALCULATING TRANSPORT TIME DELAY 2. Mixing volume time delay is at least three times the
OF AN ANALYZER SAMPLING LOOP average residence time. The mixing volume refers to
Steps to calculate transport time delay are as follows: components with low length-to-internal-diameter ratio
1. Specify components needed in analyzer sampling system (e.g., L/D < 10) such as filters, pumps and droplet
2. Specify a target transport time delay, such as 60 seconds coalescers. When inlet concentration suddenly changes
3. Identify sample’s flowrate required for analyzer + to a new value, it theoretically takes at least three times
analyzer bypass, used as basis for sizing sampling line the average residence time in that mixing volume
up to analyzer inlet (for single-line transport, analyzer for the outlet concentration to approach 95% of the
bypass flow = 0) required concentration change. Therefore, in a time
4. Identify available pressure drop for the sampling loop delay calculation, always multiply the mixing volume
5. Specify sampling line sizes for high velocity without residence time by three. Special designs of filters, pumps
exceeding available pressure drop, and calculate and coalescers may reduce this time delay effect.
sampling line volume. FIG. 2 shows an example of a high-pressure reactor pilot
6. Calculate transport time delay = (sampling line plant drawing a liquid sample from the inlet and a gas sample
volume) ÷ (analyzer flow + analyzer bypass flow) from the reactor effluent. The reactor operates at 30 barg at a
Single-line system:
temperature of 280°C. Single-line configuration is used with
flow and temperature monitors for both liquid and gas samples.
Both the liquid inlet and gas effluent’s flow into the analyzer
Field station Process analyzer sampling system can be controlled using needle valves. A buf-
Sample tap fer tank in the analyzer sampling system should be installed to
minimize fluctuation of sample flow and composition. Sample
pressure is regulated from 30 barg down to 5 barg with a pres-
Fast-loop system:
sure regulator before the sample switching system. It is also rec-
Sample tap ommended to use cascading double-block valve and bleed for
the sample switching system to eliminate dead leg problems.
Limit sample flows to the analyzer at not higher than 400 ml/
Sample tap min for liquid and 2,000 ml/min for gas (analyzer flowmeter
Fast-loop filter
Process analyzer condition = 25°C, 1 bara). TABLE 1 shows the total time delay in
this example calculated at 133.8 seconds for the liquid sample
FIG. 1. Single-line vs. fast-loop sample transport system. and 375.7 seconds for the gas sample.

PROCESS ENGINEERING STRATEGIES


Liquid PI
inlet
Vent Analyzer TO REDUCE TIME DELAYS
TI
Buffer
If the calculated time delay is too long, follow the strategies
FI below:
tank
1. Regulate gas sample pressure at the field station
Pilot right after the sample tap. Regulating gas pressure
reactor
30 barg PI at the field station after the sample tap with a pressure
280°C TI regulator allows the gas volume to expand (lower
FI Buffer gas density) and velocity to increase. It reduces time
tank delays, but at the expense of higher pressure drop at
the same mass flowrate. The velocity increases by the
Gas absolute pressure ratio defined by the gas law equation.
effluent
Single-line system Sample switching system Pressure regulation is generally not desirable in liquid
lines. Define flowrate at analyzer conditions: make a
FIG. 2. Non-optimized pilot plant analyzer sampling loop system design.
correction for temperature and pressure at transport
72 JANUARY 2016 | HydrocarbonProcessing.com
Process Engineering and Optimization

line condition. The temperature in the transport line composition to vary if the stagnant composition
can be assumed to be equal to ambient temperature in dead legs contaminate the main sample stream.
unless insulated or heat-traced, because the heat loss to Dead leg effects are more dominant on low-flow lines.
ambient is significant for small lines. Solutions are to:
[Time delay at Pline] = [Time delay at Panalyzer] × • Minimize dead legs in the flow path to analyzer
(Pline in bara ÷ Panalyzer in bara) × • Move dead leg components (e.g., pressure gauges,
(Tanalyzer in °K ÷ Tline in °K) pressure relief valves) to lines not flowing to the
To reduce time delay, move the pressure regulator after the analyzer, such as the sample bypass line.
sample tap point according to the design strategy in FIG. 3. TABLE 5. Heating or heat-tracing the sampling line. Gas
2 shows the time delay reduced below the non-optimized case in volume expands (lower gas density) with increasing
FIG. 2 by 20% for the liquid sample and by 64% for the gas sample. temperature, so velocity increases by the absolute
temperature ratio defined in the gas equation. Heating
Example 1. A fast-loop system requires 50 ml/min (1 bara, lines can sometimes eliminate the undesirable mixing
25°C) to the gas analyzer, and the sampling line volume from volume of a liquid knockout pot.
the sample tap to the analyzer is 300 ml. 6. Avoid adsorption on the tube inner surface.
• If the gas sample is tapped and transported close Measuring H2S at < a 10 mol ppm level can be
to analyzer conditions (1 bara, 25°C), what should inaccurate due to adsorption of H2S on the tube surface,
the analyzer bypass flowrate be to obtain a 60-second resulting in less or no H2S content making it to the
transport time delay? analyzer. Heating the tube to prevent adsorption or
[Answer: Analyzer bypass flowrate = 250 ml/min, coating the tube’s inner surface may help.
so that time delay at 1 bara = (sampling line volume)/ 7. Use process pressure to drive samples instead of a
(analyzer flow + analyzer bypass flow) = (300 ml)]/ sample pump. Whenever possible, first consider the
(50 ml/min + 250 ml/min) = 60 sec] use of process pressure by relocating the sample tap to
• If the gas sample is tapped and transported at average
4 barg and kept heated at 60°C until the analyzer inlet,
before dropping pressure across a needle valve into the Liquid PI Vent Analyzer
analyzer, then what would the time delay be? inlet TI
[Answer: Time delay at 4 barg = 60 sec × [(4 + 1) bara/ FI Buffer
1 bara] × [(273 + 25)°K/(273 + 60) °K] = 268.5 sec] tank
2. Change from single line to fast loop, if regulating
pressure is insufficient. Pilot
reactor
3. Avoid mixing volumes in the loop. The time delay 30 barg PI
effect of a mixing volume is three-fold, so it should be 280°C TI
avoided whenever possible. FI Buffer
tank
4. Avoid dead legs in the sampling line to analyzer.
Many components cause dead legs, such as pressure
gauges, pressure relief valves, lab sampling points, tee Gas
effluent
or purging connections, calibration or multi-stream Single-line system Sample switching system
manifolds. Dead legs not only increase sampling system
volume, causing time delays, but also cause sample FIG. 3. First optimized pilot plant analyzer sampling loop system design.

TABLE 1. Time delay of the non-optimized sampling system


Main components on the flow path that contribute to time delay
Non-optimized sampling system: Single-line system Sample switching
Sample Components 20 m of ⁄4-in. tube
1
Flowmeter—mixing volume Buffer tank**—mixing volume 6 m of 1⁄8-in. tube Totals
Condition 30 barg, 30°C 30 barg, 30°C 5 barg, 30°C 5 barg, 30°C –

Liquid inlet, Actual volume 240 ml 16 ml 196 ml 15 ml 467 ml


400 ml/min Corrected volume* 240 ml 48 ml 588 ml 15 ml 891 ml
Time delay 36.0 sec 7.2 sec 88.4 sec 2.2 sec 133.8 sec
Condition 30 barg, 30°C 30 barg, 30°C 5 barg, 30°C 5 barg, 30°C –

Gas effluent, Actual volume 240 ml 18 ml 196 ml 15 ml 469 ml


2,000 ml/min Corrected volume* 7,323 ml 1,619 ml 3,477 ml 86 ml 12,505 ml
Time delay 220.3 sec 48.5 sec 104.3 sec 2.6 sec 375.7 sec
*Notes: Details of corrected volume used in calculating time delay (1 and 2):
1. Correction for mixing volume = 3 x actual volume for the flowmeter and the buffer tank
2. Correction for pressure and temperature = actual volume × (Pline in bara/Panalyzer in bara) × (Tanalyzer in °K/Tline in °K) only for gas (Panalyzer = 1 bara, Tanalyzer = 25°C)
** Located after regulator

Hydrocarbon Processing | JANUARY 2016 73


Process Engineering and Optimization

a higher pressure point and the analyzer effluent return With an extremely small available pressure drop, avoid high-
to a lower pressure location. Sample pumps tend to be pressure-drop needle valves and send the analyzer sample effluent
unreliable and create undesirable mixing volume. If a to a low-pressure location, such as a flare or vent to atmosphere—
pump is unavoidable, use a rugged high-quality standard if it is safe to do so. The process design engineer may also install
fast loop pump. For example, specify gear pumps or other a sample pump. However, simply relocating the sample tap and
positive displacement pumps for liquid samples. sample return locations may eliminate the low-availability-pres-
sure-drop problem. It is also important to prevent two-phase flow
formation—flashing liquid or condensing vapor—that leads to
VELOCITY LIMITATION VS. PRESSURE excessive pressure drop or undesirable flow regime inside the
DROP LIMITATION sampling line. Liquid slugs can also damage the analyzer.
Two extreme cases of analyzer sampling loop design are:
1. Extremely long distance from sample tap to analyzer BEWARE OF PHASE CHANGE
2. Extremely small available pressure drop. Sampling loop design is much more complicated when dealing
With extremely long distances, consider using a fast loop to al- with sampling line phase change. Some phase changes are inten-
low higher velocity with a larger sampling line size without exceed- tional, while some occur by design mistakes. Three major types
ing available pressure drop. If the available amount of the sample is of potential phase change that engineers should be aware of are:
too small for fast-loop configuration, choose to inject an inert dilu- 1. Gas sample close to or at the dewpoint. Reducing gas
ent, such as nitrogen, to accelerate the sample transport right after pressure right after the sample tap can make the gas move
the sample tap through the long line to the analyzer. Note: It is away from the dewpoint and reduce the possibility of
necessary to re-calibrate the analyzer for a nitrogen dilution case. condensation. Condensation can significantly change

TABLE 2. Time delay of the relocated pressure regulator case


Main components on the flow path that contribute to time delay
First optimized sampling system: Single-line system Sample switching
Flowmeter— Buffer tank—
Sample Components 1 m of 1⁄4-in. tube 19 m** of 1⁄8-in. tube mixing volume mixing volume 6 m of 1⁄8-in. tube Totals
Condition 30 barg, 30°C 5 barg, 30°C 5 barg, 30°C 5 barg, 30°C 5 barg, 30°C –

Liquid inlet, Actual volume 12 ml 46 ml 16 ml 196 ml 15 ml 467 ml


400 ml/min Corrected volume* 12 ml 46 ml 48 ml 588 ml 15 ml 891 ml
Time delay 1
1.8 sec 6.9 sec 7.2 sec 88.4 sec 2.2 sec 106.5 sec
Condition 30 barg, 30°C 5 barg, 30°C 5 barg, 30°C 5 barg, 30°C 5 barg, 30°C –

Gas effluent, Actual volume 12 ml 46 ml 18 ml 196 ml 15 ml 469 ml


2,000 ml/min Corrected volume* 317 ml 270 ml 313 ml 3,477 ml 86 ml 4,463 ml
Time delay1 9.5 sec 9.4 sec 104.3 sec 2.6 sec 133.9 sec
* Notes: Details of corrected volume used in calculating time delay
1
20% reduction in time delay for liquid inlet sample
2
64% reduction in time delay for gas effluent sample
** Located after regulator

TABLE 3. Time delay of the fast loop and new sample switching system
Main components on the flow path that contribute to time delay
Final optimized sampling system: Fast-loop system Sample switching
Sample Components 20 m of ⁄4-in. tube
1
5 m of 1⁄8-in. tube Totals
Condition 30 barg, 30°C at 600-ml/min flow 5 barg, 30°C at 400-ml/min flow –
Actual volume 240 ml 12 ml 252 ml
Liquid inlet
Corrected volume* 240 ml 12 ml 252 ml
Time delay1 24.0 sec 1.8 sec 25.8 sec
Condition 30 barg, 30°C at 8,000-ml/min flow 5 barg, 30°C at 2,000-ml/min flow –
Actual volume 240 ml 12 ml 469 ml
Gas effluent
Corrected volume* 7,323 ml 71 ml 7,394 ml
Time delay1 54.9 sec 2.1 sec 57.0 sec
* See notes in Tables 1 and 2
1
80% reduction in time delay for liquid inlet sample
2
85% reduction in time delay for gas effluent sample
** Located after regulator

74 JANUARY 2016 | HydrocarbonProcessing.com
Process Engineering and Optimization

the multi-component gas mixture composition to Other practices for the sample vaporizer are to:
the analyzer because heavy molecules are selectively • Keep liquid pressure as high as possible at the
condensed more than light molecules, changing vaporizer inlet to avoid pre-flashing.
gas composition. • Vaporize across a heated valve at the lowest pressure
2. Liquid sample close to or at the boiling point or and temperature possible for a given composition.
bubble point. Sub-cool the liquid before tapping the • Use electric heating with controlled temperature
sample to get below the bubble point and reduce the as low as possible.
possibility of flashing. Flashing alters liquid sample • Do not use steam heat due to the difficulty of
composition because of selective loss of light molecules temperature control.
into the vapor phase. • Do not overheat the vaporizer body because the
3. Liquid sample vaporization before entering the gas inlet tube may get hot and flash some liquid before
analyzer. The sample vaporizer is a major cause of time entering the vaporizer, causing sample phase
delays because vapor volumetric flow at the analyzer is separation and unexpected results.
typically > 300 times the liquid volumetric flow at the
vaporizer inlet. Therefore, significant time delay occurs CONCERNS OF SAMPLE SWITCHING DESIGN
on the liquid side upstream of the sample vaporizer. Typically, one analyzer is designed to analyze multiple sam-
Without proper measures, liquid-side time delay can ples from different sample taps, so sample switching is often
exceed 300 seconds. Recommended solutions are: required. Three conventional sample switching configurations
• Use small lines on the liquid side to minimize volume (FIG. 4) are:
and liquid residence time. The recommended practice 1. Conventional double block and bleed
is a maximum 300-mm length of 1⁄8-in. tubing. 2. Cascading double block and bleed
• Use the liquid bypass line to allow high liquid flowrate 3. Outlet flow loop double block and bleed.
up to the vaporizer inlet by splitting only small liquid Advantages of conventional double block and bleed are cost
flow to the vaporizer and most of the flow to the and ease of installment. A disadvantage is the presence of dead
liquid bypass line. legs, so cascading double block and bleed is preferred, even
• For clean and narrow-boiling-range liquid samples, with a higher installation cost. However, a much longer time
vaporize the liquid sample at the sample tap. delay becomes the next problem for cascading double block

HPI MARKET DATA


2016 WEBCAST
>>View on Demand Today!

Discover what’s in store for the global refining, petrochemical and natural gas/LNG industries
in 2016 and beyond. View on demand at HydrocarbonProcessing.com/Webcasts

Lee Nichols Ben DuBose


Editor/Associate Publisher, Digital Editor,
Hydrocarbon Processing Hydrocarbon Processing
“Global Construction and “Petrochemical Outlook
Investment and Updates on for 2016 and Beyond”
the Global Refining Industry”

Adrienne Blume Mike Rhodes


Executive Editor, Managing Editor,
Hydrocarbon Processing Hydrocarbon Processing
and Editor, Gas Processing
“Natural Gas/LNG Market
Status and Forecast”
Hydrocarbon Processing | JANUARY 2016 75
Process Engineering and Optimization

1) Conventional double block and bleed 2) Cascading double block and bleed 3) Outlet flow loop double block and bleed
Vent Vent Vent
Sample 1

Sample 1 Analyzer Analyzer Sample 1

Sample 2

Sample 2 Sample 2 Analyzer

Sample 3

Sample 3 Sample 3

FIG. 4. Sample switching configurations.

MANAGING TIME DELAYS IN A NUTSHELL


Vent Analyzer
Time delays can be managed by using process engineering
Liquid PI
fundamentals to analyze the problem and correct root-cause
inlet phenomena, not only the problem symptoms.
Process design engineers should never blindly believe that
analyzer engineers or other discipline engineers are doing ev-
TI PI erything right. It is the duty of competent process design engi-
FI neers to cross-check the design from other discipline engineers
by studying relevant engineering standards and utilizing sound
Pilot process engineering fundamental knowledge.
reactor PI
30 barg
280°C REFERENCES
1
T. Waters, Industrial Sampling Systems, Swagelok, 2013.
2
Instrument Engineers’ Handbook, 4th Edition, Chapter 8, ISA, 2003.
TI PI 3
Pichler, H. and O. Sauer, “Consider investing in a standard compliant process
FI analyzers,” Hydrocarbon Processing, July 2009.
4
Benton, A. and C. Valiz, “Use online analyzers for successful process monitoring,”
Gas Hydrocarbon Processing, January 2011.
effluent
Fast-loop system Sample switching system
WIROON TANTHAPANICHAKOON is a process technology
FIG. 5. Final optimized pilot plant analyzer sampling loop system design. leader for the Process Technology Center of SCG Chemicals Co.
Ltd. in Thailand. He has authored several international papers
and technical articles and holds technology patents. He is
and bleed. To overcome these limitations, it is recommended to now in charge of developing and implementing in-house and
external process technologies for SCG Chemicals. His expertise
use an outlet flow-loop double-block-and-bleed configuration also includes process and equipment design plus the
to significantly reduce both time delay and dead leg problems. conceptual, basic and detailed design of new processes. He has had experience
FIG. 5 shows the final optimized analyzer sampling loop sys- as a process engineer with an ExxonMobil subsidiary refinery in Thailand and as
tem with various strategies implemented. A fast-loop configura- an energy improvement engineer for SCG Chemicals. He obtained his BE and
ME degrees in chemical engineering from Kyoto University, Japan, and is a senior
tion is used with the removal of the original buffer tank. An out- licensed engineer in Thailand and a senior member of AIChE. He was also a
let flow-loop double-block-and-bleed configuration reduced member of the Elsevier Editorial Board in Process Plant Design during 2014–2015.
dead legs and time delay. It also helped minimize the fluctuation
of the sample’s flow and composition after the removal of the KONGKIAT SURIYE is a senior researcher for the Research and
Development Center of SCG Chemicals, Co. Ltd. in Thailand.
buffer tank. The pressure regulator was moved to the position He is now a group leader for the advanced catalytic process
right before the sample switching system to not limit fast-loop research team. He has authored more than 30 international
high flowrate. Components were also moved from the main papers and one book chapter in the fields of heterogeneous
flow path to the fast-loop return line. There were limited sample catalyst and catalytic processes, and has invented several
patents in these fields. One of his developed technologies has
flows to the analyzer at not higher than 400 ml/min for liquid been implemented on a commercial scale, and three are now at pilot scale. His
and 2,000 ml/min for gas. TABLE 3 shows that the time delay expertise also includes laboratory and pilot-scale reactor design and scale-up,
was reduced below the non-optimized case in FIG. 2 by 80% for and also a design of reaction online analysis with sampling loop systems. He
obtained his BE degree (1st ranking in class) in chemical engineering from King
the liquid sample and 85% for the gas sample, in which the final Mongkut’s University of Technology in Thonburi, Thailand, and also a PhD degree
time delays for both the liquid inlet and gas effluent are within in chemical engineering from a joint program between Chulalongkorn University
the typical engineering standards at 60 sec. in Thailand and the University of California–Davis, in the US.

76 JANUARY 2016 | HydrocarbonProcessing.com
Cover Story

Control Engineering
for Chemical Engineers
Chemical engineers who are aware of process control requirements and challenges are in a
position to improve process designs

C
Lou Heavner hemical engineers SODT vs INPUT
Emerson are ideal candidates (Non-integrating)
1.0
for control engineer-
ing jobs. They under- 0.9
IN BRIEF stand processes and process 0.8
Percent change in process output

A BRIEF HISTORY OF design. However, many have 0.7


PROCESS CONTROL never considered or studied
0.6
DESIGN BASIS AND
process dynamics. Process
engineers often provide the 0.5
PROCESS VARIABILITY
preliminary instrumentation and 0.4
CONTROL BASICS control requirements for new 0.3
ADVANCED PROCESS projects. Control engineering is
0.2
CONTROL just the next step. Control engi-
neers try to identify and under- 0.1
BATCH PROCESS
CONTROL
stand sources of process vari- 0
0 20 40 60 80 100 120 140 160 180 200 220 240
ability that can impact product Time, s
PROCESS SAFETY IN quality, and then reduce the FIGURE 1. Responses to process inputs in self-regulating processes can take the
CONTROL variability to mitigate its adverse form of first-order plus deadtime (FODT) or second-order plus deadtime (SODT)
PROCESS DATA economic effects.
There are many renowned chemical engi- Electronics gave the advantage of faster
CONCLUDING REMARKS
neers who have made careers and reputa- communications between field instruments
tions for themselves as control engineers, in- and controllers located in a central control
cluding the prolific author Greg Shinskey, the room, as well as space savings and some
father of model-predictive advanced control, improved features. They generally mimicked
Charles Cutler, and academics like Thomas pneumatic controls, but electrical engineers
Edgar, Thomas McAvoy and Dale Seborg. began to displace mechanical engineers as
Even if a process engineer never becomes control engineers. Relay systems were used
a control engineer, being aware of process to provide interlocks, logic control and se-
control requirements and challenges will lead quence control.
to better process designs. This article pro- Inevitably, analog single-loop controllers
vides information to aid chemical engineers in were replaced with multi-loop digital control
their understanding of how to reduce process systems — first, control computers and later,
variability by better controlling processes. distributed control systems (DCS). Also at this
time, programmable logic controllers (PLCs)
A brief history of process control began to displace systems of relays for logic
Early process controllers were mechani- and sequential control. Modern control sys-
cal devices using pneumatics and hydrau- tems are now leveraging the Internet, wireless
lics. Mechanical engineers were common technologies and bus technologies in new
in control engineering, especially since the and effective ways. Field instruments and
most common final control element — the final control devices are becoming increas-
control valve — is inherently a mechanical ingly more “intelligent,” providing for more
device. Pneumatic controllers were gradu- non-control information than control informa-
ally replaced with analog electronic systems. tion. Tools and user interfaces are becoming
42 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017
friendlier to use and more capable, offer- FODT vs INPUT
(Non-integrating)
ing tremendous productivity gains.
Electrical engineers continued to 1.0
dominate the field of automation and 0.9
control. But the additional computing

Percent change in process output


0.8
capability in microprocessor- and com-
0.7
puter-based systems led to an oppor-
tunity for more advanced control strat- 0.6
egies. Chemical engineers, with their 0.5
knowledge of process behavior and 0.4
process requirements, have been work-
0.3
ing for years in the field of automation
and control, and are often able to gain 0.2
more value out of control systems than 0.1
others with less process understanding 0
might achieve. 0 20 40 60 80 100 120 140
Time, s
160 180 200 220 240

Design basis and variability frequency (“fast”) variability (less than a FIGURE 2. Typical first-order plus deadtime
Process engineering focuses on process few seconds). (FODT) responses are characterized by a
rapid initial response to a process input,
design, and defines or assumes a de- Fortunately, process design can often followed by slowing response as a new
sign basis. That basis typically includes be used to attenuate fast variability. steady state is reached
normal, maximum and minimum pro- Surge vessels can be used to attenuate
duction rates, and the process engineer highly variable flows between units, for
tries to optimize the process design, first example, reducing the disruption to the
in terms of capital cost and second in downstream unit from variability in the
terms of operability. At this stage, project upstream unit.
cost considerations and the availability Control engineers need to understand
of standard process equipment may re- process dynamics, a topic area that is
quire design compromises that lead to a not always considered as part of the
process design with control challenges. core of process design. It is convenient
The design basis is a guideline, but to think of process dynamics in terms
operating conditions in a commissioned of process inputs and process observa-
plant may change over time. Equip- tions. Process inputs are material or en-
ment (especially control valves) wear, ergy flows, and they may be flows into,
feedstock qualities vary, catalysts age, out of, or intermediate within a given
processes are impacted by varying am- process. As flows are changed, the
bient conditions, and other sources of process is affected, as seen by process
variability impact production. Market observations. Process observations are
and regulatory conditions may also measured as variables like tempera-
vary, shifting demand for certain prod- tures, pressures, levels, compositions
ucts and byproducts or penalizing the and flowrates.
production of waste products. The con- As process designs are optimized
trol system of the plant is intended to for energy recovery and minimization
mitigate the effect of incoming sources of both capital cost and operating cost
of variability on product quality variabil- for a plant, they incorporate increasing
ity. As plants become increasingly com- integration between process streams.
plex, operators are faced with bigger If variability is not controlled in a highly
challenges, and simply operating the integrated process with a high degree
process manually is no longer an op- of process interactions, there are more
tion. A frequently cited analogy is the pathways for it to create quality issues.
pilot in an advanced meta-stable jet de- Therefore, it is increasingly important for
pendent on advanced avionics. design and control engineers to work
Perhaps the best way to look at au- together to ensure operability and strat-
tomation and control is as the business egize how to attenuate variability.
of managing process variability in real-
time. One important thing to understand Control basics
is that control systems are generally able Most process responses can be classi-
to attenuate low-frequency (“slow”) vari- fied into self-regulating and non-self-reg-
ability (on the order of seconds, minutes ulating (or integrating). Self-regulating pro-
or more), but cannot attenuate high- cesses respond to a change in process

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017 43


TUNING A PROPORTIONAL-INTEGRAL-DERIVATIVE (PID) LOOP

P
ID controllers are defined by the control algorithm, which gener- action is sensitive to noise in the error, which magnifies the rate of
ates an output based on the difference between setpoint and change, even when the error isn’t really changing. For that reason,
process variable (PV). That difference is called the error, and the derivative action is rarely used on noisy processes and if it is needed,
most basic controller would be a proportional controller. The error is then filtering of the PV is recommended. Since a setpoint change
multiplied by a proportional gain and that result is the new output. The can look to the controller like an infinite rate of change and pro-
proportional gain may be an actual gain in terms of percent change of cesses usually change more slowly, many controllers have an op-
output per percent change of error or in terms of proportional band. tion to disable derivative action on setpoint changes and instead of
Proportional band is the same as gain divided by 100, so the effect is multiplying the rate of change of the error, the rate of change of the
the same, even if the units and value are different. When tuning a control PV is multiplied by the derivative term.
system, it is important to know whether the proportional tuning param- There are two steps to tuning a controller. First the process dy-
eter used in the controller being tuned is gain or proportional band. namics must be identified. This can be done with an open-loop or
When the error does not change, there is no change in output. This closed-loop step test. In open loop, the controller is put in manual
results in an offset for any load beyond the original load for which the mode and the output is stepped. The PV is observed and the pro-
controller was tuned. A home heating system might be set to control cess deadtime, gain, and time constants are estimated. Several
the temperature at 68˚F. During a cold night, the output when the steps should be made to identify any nonlinearity and to ensure the
error is zero might be 70%. But during a sunny afternoon that is not response is not being affected by an unmeasured disturbance. In
as cold, the output would still be 70% at zero error. But since not closed loop, the controller is forced to oscillate in a fixed cycle by
as much heating is required, the temperature would rise above 68˚F. stepping the output, forcing it to oscillate with an amplitude that
This results in a permanent off-set. will be dependent on the process gain and step size. This can be
Integral action overcomes the off-set by calculating the integral of achieved with a controller by zeroing the integral and derivative
error or persistence of the error. This action drives the controller error terms and adjusting the proportional gain until the cycle is repeat-
to zero by continuing to adjust the controller output after the propor- ing, or by using logic that switches the output when the cycling PV
tional action is complete. (In reality, these two actions are working crosses the setpoint value.
in tandem.) The integral of the error is multiplied by a gain that is The second step is calculating the tuning parameters. There are
actually in terms of time. Again, different controllers have defined the different guidelines proposed by different authors and even software
integral parameter in different ways. One is directly in time and the that will calculate the tuning parameters for the tuner to achieve
other is the inverse of time or repeats of the error per unit of time. the desired response. One guideline that is wisely favored is the
They are functionally equivalent, but when calculating tuning param- “lambda” tuning method. Lambda refers to the closed loop time
eters, the correct units must be used. Adding further complication, constant in a controller response. The advantage of this kind of tun-
the time can be expressed in different units, although seconds or ing is that the tuner is free to choose the speed of response or the
minutes are usually the design choice. aggressiveness of the controller tuning. There is a tradeoff in loop
And finally, there is a derivative term that considers the rate of tuning. As noted earlier, faster response or more aggressive tuning
change of the error. It provides a “kick” to a process where the error may result in some overshoot or even cycling response that is un-
is changing quickly and has a gain that is almost always in terms of desirable and the loop could become completely unstable if there is
time. However, again the units of time may be seconds or minutes. any nonlinearity in the process. Therefore, robustness is the sacrifice
Derivative is not often required, but can be helpful in processes that for more aggressive control and lambda can be used to strike an
can be modelled as multiple capacities or second order. Derivative optimal balance between robustness and aggressiveness.

input by settling into a new steady-state more steam enters the heat exchanger.
value. For example, if steam is increased First, the steam pressure in the exchanger
to a heat exchanger, the material being rises and heat transfers to the tubes and
heated will rise to a new temperature. Re- finally to the colder stream. The tempera-
ponses often take the approximate form ture of the cold stream takes some time
of first order plus deadtime (FODT) or before it begins to rise. Then it rises grad-
FIGURE 3. Integrating, or non-self-regu-
lating process variables do not settle into
second order plus deadtime (SODT) (Fig- ually and increases its rate of change until
a new steady-state value within allowable ures 1 and 2). In a heat exchanger, for ex- it approaches the new steady-state tem-
operating limits ample, when the steam valve is opened, perature, where the temperature rise be-
gins to slow. The characteristic response
SODT vs INPUT
(Integrating) is a SODT.
0.24 The steam flow began increasing as
0.22 soon as the valve started moving. But if
0.20 a controller was telling the valve to open,
Percent change in process output

0.18 there might have been a short delay be-


0.16 fore the valve actually moved and the
0.14 steam flow changed. The steam flow
0.12 begins to increase quickly and begins to
0.10 increase more slowly as the new steady-
0.08 state flow is achieved. This is a typical
0.06 FODT response.
0.04 Self-regulating control loops can be
0.02 tuned for closed-loop control response
0.00 to assure that the process observation
0 20 40 60 80 100 120 140 160 180 200 220 240
Time, s (sometimes known as the process vari-
44 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017
able, or PV) is driven to and main- mon, and when it occurs, it tends to
tained at its target setpoint. The con- be minimal.
trol response can be tuned for faster Fortunately, controllers can also
or slower response, but as the speed be tuned on integrating processes
of response increases, so does the to achieve a first-order response.
risk of overshoot or oscillation. However, the response does not
Different measures of performance look exactly like the response of a
have been developed with tuning self-regulating process. Following a
rules to approximately achieve these setpoint change, the PV will move
objectives. Early performance objec- to the new setpoint and overshoot
tives focused on minimizing error,
square of the error, or absolute error
over time. Tuning to achieve quar-
ter-amplitude damping was often
described in early control literature.
Zeigler-Nichols tuning rules were
proposed to achieve this kind of re-
sponse. But this kind of aggressive
tuning results in some cycling.
Recent thought in automation
GEMÜ Quality Products...
prefers to attenuate variability, and GEMÜ Quality Service
that includes closed-loop oscilla-
4212 & 4242 Automation features:
tion, so most loops today should be
• Class 1 DIV 2, UL & CSA
tuned for a first-order response, with
• Multiple control options: 24 VDC, AS-I, DeviceNet
the response time being defined ac-
• Super bright LEDs indicate valve position
cording to process requirements.
The fastest-responding loops are Multiport Diaphragm Valve features:
limited by the point of critical damp- • Thousands of block designs to solve process challenges
ing. However, where loops inter- • Minimize dead leg and hold up volume for
act, one can be slowed relative to optimal process efficiency
another to prevent the interacting
loops from fighting with each other. Globe Valve features:
• High cycle life 550
Important time constants are the Globe valve
deadtime, which is the time before • Variety of end connections, materials with 1434
of construction and actuation positioner
the process observation is observed
to change, and a first-order time
constant, which is the time it takes
once the process begins moving to 4212
achieve approximately 63% of the Switch
way to the target setpoint. A first-
order process normally takes about
four time constants, plus the dead-
time, to reach steady-state at the
target setpoint.
Non-self-regulating process
variables do not settle into a new
steady-state value, at least not
within allowable operating limits 650 Diaphragm
Multiport valve with 4242
(Figure 3). Changing the rate of feed
into a vessel will change the rate at
which the level rises (or falls). In the
absence of some kind of control, the See us at Interphex Booth 2663i
level would continue to rise until the
tank overflowed. Usually integrat- 3800 Camp Creek Parkway • Building 2600 • Suite 120
ing process responses can be de- Atlanta, GA 30331 • info@gemu.com • Tel: 678-553-3400
scribed as deadtime and integrating www.gemu.com
gain or ramp rate. Sometimes, there
may be a lead or lag associated with
the ramp rate, but this is not com- Circle 22 on p. 90 or go to adlinks.chemengonline.com/66426-22

FKH(QJB*(08BLVOQGLQGG 30
45
CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017
robust and a good fit for the job as long
Elements of a feedback control loop
as the process response is not exces-
Load sively nonlinear or characterized by a
Set point Error Output Final control element or Fluid Product dominant deadtime dynamic. Propor-
∆ Controller 
slave loop process
tional, integral and derivative are the ac-
Sensor/ tions the controller can apply to drive the
Process value transmitter PV to setpoint. Every controller manufac-
turer may employ a slightly different form,
FIGURE 4. Most process control is accom- slightly before turning around and set- structure and options, but the functional-
plished by using a feedback control loop tling back at the target value. Following ity and results are the same. The propor-
a disturbance, the PV will deviate from tional, integral and derivative parameters
the target setpoint until finally being ar- can be adjusted by the control engineer
rested and returning to setpoint. Dead- to provide the best controller response.
time is the same as for a self-regulating In order to properly tune a control loop,
process. There is no open-loop time it is necessary to understand the things
constant by definition. However, the that influence loop performance and
closed-loop time constant for an inte- process profitability (Figure 5).
grating process is defined as the time Often, process inputs can impact
it takes to first cross the target setpoint more than one important process obser-
following a setpoint change or the arrest vation. If the heat exchanger was the re-
time for a disturbance. An integrating boiler of a distillation column, increasing
process normally takes about six time the steam could affect the levels in the
constants, plus the deadtime, to reach base of the column and the reflux accu-
steady-state at the target setpoint fol- mulator and compositions at the top and
lowing either a setpoint change or a load bottom of the column. It might also af-
disturbance. fect the column pressure and differential
pressure, and will affect temperatures up
Feedback controllers and down the column. Similarly, a pro-
Process control usually takes the form cess observation might be affected by
of a feedback controller (Figure 4). Some more than one process input. The dis-
process inputs can be manipulated in tillate composition may be affected by
order to drive important process obser- the steam flow to the reboiler, the reflux
vations to targets or setpoints. Other flow, the feed flow, the product flows
process observations may not be con- and other process inputs. An interac-
trolled to a target setpoint, but they are tive process requires that the controls
not allowed to exceed upper or lower be designed to minimize the detrimental
constraint limits. A control-loop includes impact of multivariable interaction, where
a measurement of the process obser- two or more loops could fight with each
vation to be controlled (the PV), a final other. One way to do this is with a de-
control element (usually a control valve) coupling strategy, which is something
that varies the process flow to be ma- easily understood by process engineers.
nipulated and a controller that makes a Feed-forward control and sometimes
move based on where the process ob- ratio-control strategies are used to de-
servation is relative to its setpoint. couple process interactions. The inter-
The workhorse controller in the pro- acting process inputs may be controlled
FIGURE 5. Several aspects of a process-
control loop can influence performance cess industry remains the PID (propor- or could be “wild” disturbances. Another
and profitability tional-integral-derivative) controller. It is way to decouple loop interactions is by
tuning one loop for a relatively faster
response and the other for a relatively
Feedback control: What in this loop limits profitability? slower response. This technique is very
Operator practices? Dead band? Vessel design? effective and is naturally applied when
Control strategy? Sizing?
Flow characteristic? tuning cascade loops.
Load
Set point

Error Output Final control element or Fluid Product Advanced process control
Controller
slave loop  process There are different definitions of ad-
Sensor/ vanced process control (APC). Some
Process value transmitter people consider ratio control and over-
Tuning? ride control to be advanced control.
Algorithm?
Nonlinearity?
Control strategies that use feed-for-
Sampling, filtering?
ward, override-control, cascade and
46 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017
ratio loops and other complexities are
often referred to as advanced regulatory $$$
Limit or spec
control (ARC). Another type of control-
ler is the multivariable, model-predictive Setpoint
controller (MPC). The response models
Before APC After APC
of all process outputs to changes in any
process inputs are modelled and incor-
porated into the controller. dustries. It is an excellent platform for FIGURE 6. Advanced process control (APC)
The controller attempts to maintain constraint optimization. Many process- techniques help allow processes to oper-
ate closer to the limit through constraint
the controlled variables at targets and control problems benefit from constraint optimization
constraint variables within limits while optimization. Optimization objectives,
minimizing the moves of process inputs. such as maximizing production and
It does this with an algorithm that con- yield, and minimizing give-away and
trols a prediction sometime in the future energy consumption are examples of
rather than the current process value. It where constraint optimization can gen-
is an ideal approach for interactive prob- erate substantial benefits over single-
lems, since instead of decoupling the loop control. Maximizing or minimizing
interactions, it coordinates the moves some variables can drive the process to
to compensate for or accommodate the constraint limits and the models allow
known interactions. Those interactions for tight control at constraint limits with-
are identified in the embedded models. out violating them (Figure 6).
It is also the only truly effective means of
handling deadtime-dominant processes Batch process control
because the deadtime is inherently de- Up to this point, the discussion has cov-
fined in the controller models. ered continuous processing. Continu-
APC has been widely applied in the ous processes dominate the chemical
petroleum refining industry and is gain- process industries (CPI), but some sec-
ing greater acceptance in other in- tors of the CPI, including pharmaceuti-

■ Universal corrosion resistance in extremely


high temperatures.
■ Custom complex shapes in any size with tight

tolerances.
Eliminate Downtime & Minimize Maintenance Costs
Reduce Energy Consumption & Emissions Visit our NEW website: http://hexoloy.com
For more information, technical data & case studies contact:
Maximize Productivity
SCD.sales@saint-gobain.com ■ 716-278-6233

Circle 34 on p. 90 or go to adlinks.chemengonline.com/66426-34

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017 47


GLOSSARY OF CONTROL TERMINOLOGY
APC Advanced process control. A general term for types of con- to plan moves in the future to provide control over a future
trols more elaborate than the basic loops. MPC is a type of time interval. This technology is helpful with processes that
APC, and MPC is often used interchangeably with APC. Other have long process delays or a high degree of interaction be-
examples of APC include fuzzy logic and expert systems tween multiple process inputs and outputs. It is the ideal
ARC Advanced regulatory control. A complex control strategy platform for constraint optimization
often involving more than one PID controller (examples in- (2) Multivariable process control. Means controlling more
clude cascade control, ratio control, feed-forward control, than one measurement or variable at a time from the same
override control and inferential control) calculation. Since most model-predictive controllers are also
CV Control variable. A process observation that has a setpoint multivariable controllers, the definitions are often used inter-
that may be provided by the operator or by a supervisory changeably
controller MV Manipulated Variable. A process input that is an output of
DCS Distributed control system. A digital process control plat- a controller
form in which various controllers are distributed throughout PID Proportional, integral, derivative. The name used for the
the system most common control loop algorithm seen in the process
DV Disturbance variable. Measured process inputs that are industries. PID controllers are SISO feedback controllers
not manipulated by the controller (also known as feed-for- PLC Programmable logic controller. Computer for industrial
ward inputs) control
HC Hand control. Used to indicate a manually positioned valve PV Process value. The term commonly used for the CV of a
LV Limit variable. A constraint variable or process observation PID control loop
without a setpoint SIMO Single-input, multi-output. A term describing an uncom-
MIMO Multi-input, multi-output. A term describing a multivariable mon multivariable controller with one process output (an ex-
controller ample would be split-range control)
MISO Multi-input, single output. A term describing a multivari- SISO Single-input, single-output controller. A term describing
able controller with one output typical PID controller or any controller with one input and one
MPC (1) Model predictive controller. A controller that controls output
future error rather than current error. To do this, it incorpo- SP Set point. The target value for the control variable
rates process response models that describe the dynamic TSS Time to steady state. The time required for a self-regulating
behavior of process observations (CVs and LVs) to changes process to come to a new stable steady state after a change to
in process inputs (MVs and DVs). This allows the controller a process input

cals and specialty chemicals, rely heavily batch quality. There is a standard de-
on batch processing. Some engineers fined (ANSI/ISA S88) for batch process
muse that all processes are batch pro- control that standardizes the concepts
cesses, but some batches are longer of control, equipment and unit modules
than others. A batch control engineer in a batch process.
might suggest that a batch process is And batch processes are often de-
just a continuous process that never signed to make a variety of products or
gets the chance to reach steady-state. product grades. Furthermore, there may
Both are valid points of view. Designing be multiple trains of equipment with some
batch process sequences and recipes common process equipment or utilities.
fall right in the comfort zone for chemi- These plants may involve special recipes.
cal engineers. But the more interesting Recently in batch control, the focus has
part of batch control is not defining the been on managing multiple recipes and
normal sequence of steps. Rather, it is optimizing equipment selection for maxi-
defining what should happen when an mum or optimum production.
abnormal event occurs. Can a batch be Because product flaws in the phar-
“saved” following an upset or must it be maceutical industry can be devastating,
scrapped? What is required to rework a traceability is a major concern. This in-
batch that suffered an abnormal upset? cludes traceability of the materials con-
Thinking through the possible problems sumed in the production of pharmaceu-
that could disrupt a batch process and ticals, and traceability of the equipment
defining safe sequences to abort or re- and processes used to produce the
cover a batch are classic chemical engi- pharmaceuticals. Regulatory involve-
neering exercises. ment is high, and validation is an inte-
Another opportunity for batch optimi- gral part of pharmaceutical processes.
zation involves trying to minimize transi- This requires more data collection and
tion times between steps. This can be more rigorous adherence to manage-
done with equipment selection, but also ment of change (MOC) procedures than
with logic in the batch sequence. Ramp most other processes, whether batch
rates and dwell times can be minimized or continuous.
to the extent practical without impacting
48 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017
Process safety in control pact is data management and analysis.
Another area of process control deals Control systems have access to a great
with safety instrumented systems (SIS). deal of data other than control data. His-
Up to this point, the discussion has torization and archiving of process data
centered on control requirements to enables process engineers to identify
keep the process running in the face of and prioritize continuous improvement
variability. Safety systems have a single opportunities and allows management
function, which is to safely shut down to make more effective decisions regard-
a process if a catastrophe is imminent. ing operation and future investment.
Process engineers may be better pre- Business systems that manage main-
pared to consider process safety than tenance processes, quality processes,
most disciplines, at least with regard to planning processes and other work pro-
the CPI. The general concept is to evalu- cesses can be integrated with process
ate the risks, in terms of probability, and control. This has been enabled by modern
the magnitude of the consequences. technology for networking, databases,
Layers of protection are defined and operator interfaces and enterprise-man-
deployed to reduce the risk of a serious agement software all working together.
safety or environmental exposure. High- While the nature of integration of these
risk possibilities need to employ engineer- various systems requires more knowledge
ing solutions to reduce the risk. Some in computer programming, database ad-
solutions will include process design, ministration and networking than chemical
such as dikes around tanks and pressure- engineers might learn in their academic
relief equipment. Controls will also be em- programs, the process management re-
ployed to reduce the risk, including safety quirements require an understanding of
interlocks. The requirement for high on- the process plant and its economic sen-
demand availability of the safety-protec- sitivities. Chemical engineers are likely to
tion systems leads to specialized safety have a better understanding than most
systems with redundancy (including triple of the information required by company
redundancy) and pro-active diagnostics managers at both the local and corpo-
to monitor the health of the safety sys- rate level in order to make best use of the
tems. One of the first layers of protec- data and systems in place. The increasing
tion is alarm management, although it is wealth and richness of data makes analy-
limited by the presence of the human el- sis of that data with evolving “big data”
ement to respond to an alarm (for more tools a real opportunity. Networking, data
on alarm management, see Chem. Eng. sharing, and collaboration between the
March 2016, pp. 50–60). Designing plant and specialized resources located
safety-instrumented control systems is a far away is the promise of the Industrial
specialized area that is critical in managing Internet of Things (IIOT).
the risk of hazards in the process. There is
a growing trend to design safety systems Concluding remarks
to be integrated into — but still separate Often the greatest knowledge gap for
from — the basic control systems. Care a chemical engineer who wants to be-
is taken during design to ensure the inte- come a process automation engineer
gration does not create a vulnerability or is deep knowledge of instrument and
common point of failure of the safety sys- control hardware. This is not an insur-
tem function and reliability. mountable problem, however, because
Along with this trend is the increasing vendors are happy to share the infor-
use of diagnostics and capabilities of mation you need. A good salesperson,
“smart” instruments and field devices to perhaps contrary to popular opinion,
reduce the probability of failure on de- can be a valuable and trusted advisor.
mand. This is a critical consideration for The best salespeople know that exag-
safety systems, because they may not gerating the benefits of one offering for
be employed for long periods of time, immediate sale may win the order, but
if ever, but then must work when called will lose the confidence and trust of the
upon to shut a process down safely. customer for future opportunities.
In most cases, vendors truly do want
Process data to recommend the most economical so-
A final area of process control where pro- lution. To do that, they need to under-
cess engineers can have a significant im- stand the process and control require-

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017 49


ments and the expected life cycle of the ested in process control can find many
unit where the offering will be deployed. resources to gain a deeper understand-
They can recommend the best mea- ing in the further reading section. Q
surement technology or valve selection Edited by Scott Jenkins
and help size the instrument as well.
They can help evaluate the value and Further reading
return of additional options or choices. 1. Shinskey, F.G., “Process Control Systems: Application, Design
So leverage their special knowledge and and Tuning,” 4th ed., McGraw Hill, 1996.
expertise. Often on a larger project, an 2. McMillan, G., “Handbook of Control Engineering,” McGraw Hill,
1999.
engineering firm with its own subject-
3. Blevins, T. and Nixon, M., “Control Loop Foundation – Batch
matter experts may help with selection and Continuous Control,” International Society for Automation
and procurement, or selection may be (ISA), 2011.
defined by corporate guidelines or pro-
cess licensing requirements. Author
In the final analysis, the control engi- Lou Heavner is a control engineer at
neer is trying to identify and understand Emerson (1100 West Henna Boulevard,
Round Rock, TX 78681; Phone: +1
the sources of variability that can impact (512) 834-7262; Email: Lou.Heavner@
product quality, production throughput, Emerson.com). Heavner has been with
yields, utility consumption and other Emerson for over 30 years, with respon-
sibility for project engineering, sales and
economic impacts, and tries to design consulting with customers across all of
controls to attenuate the variability or the process industries and all over the
world. His current role is to scope and
move it to a part of the process where lead advanced control and optimization projects, primarily in
it has less economic impact. By simply the oil-and-gas industry. Prior to joining Emerson, Heavner
reducing variability, it is possible to op- worked for Olin Corp. as a process automation and control
engineer. Heavner earned a B.S.Ch.E. degree from the Mas-
erate nearer to constraints and hence sachusetts Institute of Technology (MIT) in 1978. When he
maximize the processing capability of isn’t helping customers control their processes, Heavner en-
the existing plant. joys controlling his own home brewery operation. He may be
contacted on LinkedIn at www.linkedin.com/in/louheavner.
Chemical engineers who are inter-

WHERE THE INDUSTRY TURNS


FOR PRECISE CONTROL
Achieve precise control over every aspect of your chemical operation.

MODEL 521 MODEL 1049


The Model 521 is a sliding The Model 1049 Secure-Gard
stem, globe style, bellows is a pilot-operated vent valve
intended for installation
MODEL 1078 sealed, pneumatically
on atmospheric and low-
The Model 1078 actuated control valve
designed for maximum pressure storage tanks,
Vacu-Gard is a pilot- vapor recovery systems,
operated valve, corrosion resistance in pure
chemical service. and process systems.
specifically designed to
reduce blanketing gas
losses on low-pressure
storage tanks.
MODEL 3100
The Model 3100 is a
MODEL 987 pressure/vacuum vent
The Model 987 is a pneumatic control designed to vent the tank
valve designed to control moderate vapor away to atmosphere
to severe corrosive applications but and to relieve vacuum
may be applied in general service pressure within the tank.
applications also. The 3100 is a weight
loaded style.

www.cashco com
Cashco, Inc. Innovative Solutions

P.O. Box 6, Ellsworth, KS 67439-0006


Ph. (785) 472-4461, Fax: (785) 472-3539 www.cashco com
Innovative Solutions

Circle 11 on p. 90 or go to adlinks.chemengonline.com/66426-11
50 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017
Environment
and Safety
V. CHADHA, S. BHANDARI and P. VIRDI,
Bechtel, Haryana, India

Control design for steam vent noise in refineries


Noise pollution in oil refineries has a direct effect on worker • Depressurization of steam lines for system maintenance
health. Noise is the unwanted or undesirable sound produced • Steam ejector discharge and exhaust.
by process control equipment, which includes valves. Sound is
produced by fluctuating pressure waves that arise from the flow NOISE ABATEMENT METHODS
of fluid through the valve. The specific sources are either me- Source treatments. Not only do source treatments re-
chanical or of fluid structure in nature. These pressure waves duce the strength of the noise source, but they also shift
are characterized by both amplitude (volume) and frequency. the frequencies to a higher, non-problematic range. Source
Amplitude is measured in decibels (dB). Industrial noise levels treatments prevent noise at its source, which can involve the
are often expressed in a form that takes into account human valve. Common source treatments include noise attenuation
sensitivity to frequency. This is known as “A-weighting” and is valve trims, and inline and external diffusers that minimize
measured in units called A-weighted decibels (dBA). turbulence. TABLE 1 provides a list of valve and diffuser de-
Many refineries have a specification for noise levels within signs that can be used, depending on their noise-reduction
the plant environment and, in some cases, they are subject capabilities.
to fence line noise requirements to protect the refinery’s sur- Path treatments. In addition to eliminating noise at its
rounding environment. As populated areas are moving closer source, path treatments can impede the propagation and trans-
to processing refineries, noise attenuation is crucial to adhere to mission of sound waves. Path treatments help eliminate noise
compliance requirements and avoid potential regulatory action. heard outside of the pipe wall by increasing the resistance of
Per ISA 75.171 or IEC 60534-8-3/60534-8-42,3, the maxi- the noise path. Typical path treatments include increasing the
mum permitted noise level, measured at 1 m from the valve, pipe thickness, adding acoustical or thermal insulation, or
must be less than 85 dBA. For all gas, vapor, steam and flashing adding inline pipe silencers.
liquid valves that have a typical pressure drop of 0.4 × upstream
pressure, a noise calculation must be supplied. If the predicted TABLE 1. Typical source treatment noise attenuations
noise level is found to exceed 85 dBA, then the valve will be Treatment Typical noise attenuation Typical application
treated for noise.
Single-stage cage trim Up to 18 dBA Steam letdown
The venting of high-pressure steam to the atmosphere dur-
ing plant operations often leads to unacceptably high noise lev- Multiple-stage cage trim Up to 30 dBA Gland steam
els. This can be a result of: External diffusers Up to 40 dBA Sky vent
• Steam safety relief valve discharge Inline diffusers Up to 50 dBA Steam letdown
• Dumping of steam during steam generator startup

Silencer Vent to atmosphere


Vent to atmosphere

Valve with diffuser assembly


Valve

Steam generator Steam generator

FIG. 1. Valve with a silencer assembly (path treatment). FIG. 2. Valve with a diffuser assembly.

Hydrocarbon Processing | DECEMBER 2016 73


Environment and Safety

Silencers offer noise attenuation up to 45 dBA, depending is difficult. This means that attenuation is only effective for the
on treatment and application. The weakness of path treatments area where the treatment is applied.
is that both the fluid stream and the piping itself are very effec-
tive at transmitting noise; therefore, complete noise attenuation CASE STUDY
Atmosphere
Initial design. A common design on various projects con-
sists of a steam generator with a valve and silencer assembly
for noise reduction (FIG. 1). When operated, the large pressure
differential across the sky vent valve can cause high noise lev-
els. To reduce the noise potential, the pressure drop is split be-
tween the valve and a downstream silencer. The pressure split
Tube also serves to optimize the size of each component. Other key
Baffle
Shell challenges include:
• Valve leakage due to an inadequate seat load,
which could lead to reduced plant load and
efficiency, as well as damage to the valve
• Fast opening in case of a plant upset condition
• Properly addressing noise for two separate noise
sources (valve and silencer).
This design requires additional support requirements, an in-
crease of weight/size, and the need for a larger platform. This
type of design is more capital intensive.
Proposed design. All of these limitations were overcome by
using a combined assembly consisting of a valve with a diffuser
Intermediate pressure (FIG. 2). A diffuser is a pressure-reducing device that is installed
Atmospheric pressure downstream from the valve. When installed, total pressure drop
Inlet pressure of the system is divided across the valve and the diffuser. This
enables the valve to operate at a lower pressure drop ratio, there-
FIG. 3. Valve with a diffuser assembly.
by lowering the noise level generated from the process flowing
through the valve.
At this location, the vent diffuser was used, which helped
reduce the noise generated by steam being vented to the at-
NEW VERSION
mosphere. The valve can be used during startup and abnormal
conditions. A diffuser valve combination can result in a noise re-
InstruCalc duction of up to 40 dBA, and retains the pressure/flow control
associated with a standard valve.
CONTROL VALVES • FLOW ELEMENTS • RELIEF DEVICES • PROCESS DATA In the initial design valve and silencer proposed by the licen-
sor to attenuate noise, the valve and silencer are procured and
designed by different disciplines, which can lead to overdesign
InstruCalc 9.0 calculates the size of control valves, and result in a higher cost. In the design proposed here, noise
flow elements and relief devices and calculates fluid measurement is considered in its entirety for the venting of
properties, pipe pressure loss and liquid waterhammer steam to the atmosphere. Different treatments are worked out
flow. Easy to use and accurate, it is the only sizing to reduce noise, which helps to achieve an optimized and cost-
program you need, enabling you to: Size more than 50 effective design.
different instruments; Calculate process data at flow
conditions for 54 fluids in either mixtures or single RECOMMENDATION
components and 66 gases, and; Calculate the orifice The assembly shown in FIG. 3 is a better and more cost-effec-
size, flowrate or differential range, which enables the tive assembly than that shown in FIG. 1 to fulfill the requirements
user to select the flow rate with optimum accuracy.
of ISA 75.17 or IEC 60534-8-3/60534-8-4 maximum permit-
ted noise level. The valve diffuser assembly in FIG. 3 requires no
Updates include Engineering Standard
maintenance after installation. These features combine to offer
Upgrades and Operational Improvements increased noise control at a minimum investment.
in InstruCalc Version 9.0 Although the case study discussed here comes from a refin-
ery application, this design may be implemented in any steam
Order Direct from the Publisher. service application.
GulfPub.com/InstruCalc or call +1 (713) 520-4426.
LITERATURE CITED
1
ISA 75.17: Control valve aerodynamic noise prediction.
2
IEC 60534-8-3/60534-8-4: Noise considerations–Control valve aerodynamic
noise reduction method.
3
IEC 60534-8-4: Noise considerations–Prediction of noise generated by hydrody-
namic flow.

74 DECEMBER 2016 | HydrocarbonProcessing.com
LNG Technology
I. NEMOV, Sakhalin LNG, Sakhalin Energy
Investment Co. Ltd., Yuzhno-Sakhalinsk, Russia

Optimal control of mixed refrigerant


composition at Sakhalin LNG plant
A technique for the optimization of • The Carnot factor was used as on calculated component
mixed refrigerant (MR) composition was an invariant parameter to assess inventories rather than on
developed and successfully applied at the refrigeration cycle performance. component concentrations.
Sakhalin LNG plant on Sakhalin Island, The invariance is a crucial feature This transformation effectively
Russia. Indirect control of the MR com- of the factor that enables the linearizes and decouples the
position was implemented via calculated comparison of cycle performances system of controlled variables,
inventories, replacing direct control of in different plant operation cases. contributing to higher control
component concentrations and maximiz- • Clear correlations were observed performance and, thereby, more
ing the LNG plant’s performance. between the Carnot factor and the efficient plant operation.
MCHE temperature approaches,
Introduction. The MR cycle is used for as well as between the temperature Process description. The Shell DMR
liquefaction and subcooling of natural approaches and the concentrations process applied at the Sakhalin LNG
gas in most large LNG trains based on of MR components. From these plant uses a PMR cycle and an MR cycle
technologies such as AP-C3MR, AP-X correlations, functions of optimal to liquefy natural gas.1 The MR cooling
and Shell DMR. The varying composi- MR composition setpoints were cycle—in which the refrigerant is a mix-
tion of MR cycle technology is its ma- derived and implemented in the ture of nitrogen, methane, ethane, pro-
jor advantage over the Cascade process. plant’s control system. pane and traces of butane—provides the
This advantage comes from the fact that • To maximize control effectiveness, cooling duty for the liquefaction of gas
MR composition can be adjusted to fit a new MR composition control within a temperature range of –40°C to
the natural gas condensation curve and strategy was applied. It is based –150°C (FIG. 1).
maintain an optimum temperature ap-
proach between cold and warm streams
inside the main cryogenic heat exchanger
(MCHE) for a wide range of NG inlet
temperatures, depending on propane or
precooling MR (PMR) cycle duty. Addi-
tional degrees of freedom related to MR
composition help increase the efficiency
of the refrigerant cycle. The correct setup
of MR composition setpoints, as well as
their robust control, are key problems
that must be solved to maximize the ef-
ficiency of any MR cycle.
The MR composition optimization and
process control solutions described in this
article were developed and implemented
in-house at the Sakhalin LNG plant oper-
ated by Sakhalin Energy Investment Co.
Ltd. The research results were success-
fully applied on the MR circuit of the Shell
DMR process, but they are generally valid
for any MR cycle, irrespective of specific
LNG technology details. The results are
FIG. 1. MR cycle of Shell double mixed refrigerant process.
summarized in the following points:
Hydrocarbon Processing | JANUARY 2019 61
LNG Technology

MR vapor exiting the shell side of the ing is defined by three parameters: circuit affect the MR holdup in those
MCHE’s E-07A/B section is compressed • The MR temperature in the E-06 parts, while the total inventory is fixed
in MR compressors K-01 and K-02. Inter- outlet, which depends on PMR and the HMR liquid level in V-02 serves
cooling and initial discharge cooling are cooling duty as a buffer for those fluctuations.
achieved by air coolers E-01, E-02, E-03 • The LMR to HMR mass ratio
and E-04, while further cooling and par- (LMR/HMR), which is maintained Optimization of MR composition
tial condensation are achieved by cooling by the control system setpoints. Most MR composition opti-
against PMR at two different pressure • The MR composition, which mization techniques deal with an offline
levels—the E-05 high-pressure PMR pre- depends on the V-02 separation process model, rather than with a running
cooler and the E-06 low-pressure PMR temperature and LMR/HMR, plant.2,3 Usually, such techniques repre-
precooler. Cooled and partially con- as well as on component sent a combination of a relatively simple
densed MR is separated into light mixed inventories in the MR system. model of a liquefaction unit and a fully or
refrigerant (LMR) vapor and heavy mixed The pressure in V-02 results from partially automated optimization routine.
refrigerant (HMR) liquid in MR sepa- vapor-liquid equilibrium. A two-phase However, at Sakhalin LNG, this meth-
rator vessel V-02. The HMR and LMR mixture with a given composition at a od was found not to work well for the opti-
high-pressure streams are subcooled sepa- given temperature splits the vapor and mization of a running plant. Any mismatch
rately inside the MCHE and returned to liquid phases with a given ratio between between process equipment models and
the shell side after expansion, providing them, but only at a certain pressure. In actual plant operation resulted in a sub-
cooling duty for gas liquefaction. this system of mutually dependent pa- optimal solution where the actual plant
The separation of MR in V-02 creates rameters, the MR component concentra- performance did not reach the predicted
two cycles with different compositions tions are subject to the influence of many level, or even decreased. The adoption of
and circulation rates. The composition factors, and the component inventories a rigorous, model-based MR optimization
of refrigerant in different sections of the are the only invariants. In general, the of a running LNG plant has potential, but
MR cycle is far from uniform, which is a inventory of an MR component in the this depends on the further development
challenge for tight control. system can be changed in a controlled of modeling techniques.
Changing process conditions for way by adding a certain component and Statistical treatment of past operational
two-phase MR mixture flashing in V-02 removing either the HMR mixture or the data is the most prevailing method adopt-
are the main source of variability in MR LMR mixture. Changes in pressure and ed by the LNG industry for the optimiza-
composition measurements. The flash- temperature in different parts of the MR tion of MR composition at running plants.
It provides credible results if the data
population is large enough to represent
the variations of MR composition and
cycle efficiency. The method is based on
the extraction of top efficiency data from
the total data population, as well as the de-
velopment of correlations between PMR
or propane cycle cooling temperature and
optimum MR component concentrations.
The main challenge of this method is de-
riving an invariant performance indicator
that is sufficient to describe cycle efficien-
cy. The estimation and application of the
Carnot factor for MR composition opti-
FIG. 2. Real (A) and ideal (B) refrigeration cycle diagrams showing compression with mization at Sakhalin LNG is described in
inter-cooling and after-cooling in air coolers (points 1–2); MR cooling in the PMR cycle the following paragraphs.
(points 2–3); MR self-cooling in the MCHE (points 3–4); Joule–Thomson expansion (points 4–5); If PMR cycle capacity is given and
and MR boiling in the MCHE (points 5–1).
fixed, the total flowrate of LNG measured

FIG. 3. Correlations between the Carnot factor of the MR cycle and the MCHE temperature approaches (Tcp slice from –47°C to –48°C).

62 JANUARY 2019 | HydrocarbonProcessing.com
LNG Technology

just downstream of the MCHE’s E-07A/B • The hot reservoir temperature verted into an analytical form as a func-
unit depends on several factors: and the gas inlet temperature tion of temperature (Eq. 7):
• Gas temperature on the E-07A/B are the same. dqNG = λ(T) × dT (7)
inlet (i.e., cutpoint temperature, The minimum specific work of the where:
or Tcp) as defined by PMR cycle ideal cycle can be derived from the basic λ(T) = Natural gas specific heat func-
operating conditions principles of the Carnot cycle3 (Eqs. 3, tion of absolute temperature.
• LNG temperature on the E-07 4 and 5): Finally, after integration of Eq. 6, mini-
A/B outlet (i.e., LNG rundown dwid = dqPMR − dqNG (3) mum specific work Wid can be expressed
temperature, or Trd) as defined as a function of Tcp and Trd and then used
by the control system dqPMR = Tcp × dS (4) for Carnot factor estimation (Eq. 2), as
• The available power of MR shown in Eq. 8:
dqNG = T × dS (5)
compressor drivers (KT-01 λ(T)
and KM-01) where: Wid = ∫dwid = Tcp × ∫ TTrdcp (8)
T
• MR cycle coefficient of NG = Natural gas
performance, which is the ratio of dqNG, dqPMR = Amount of heat removed × dT − ∫ TTrdcp λ(T) × dT
cooling duty provided to the gas from the gas stream and transferred to a
stream over the compressor drivers’ high-temperature reservoir (PMR cycle)
total power. It can vary depending dS = Entropy change corresponding to
on MR cycle process conditions, as dqNG heat removed from the gas stream at
well as on equipment availability. absolute temperature T.
The actual performance coefficient of Combining Eqs. 3, 4 and 5, Eq. 6 can
the MR cycle can be calculated as shown be obtained in differential form for ideal
in Eq. 1: specific work:
FLNG × ∆H LNG dq
COPact = (1) dwid = (Tcp − T) NG =
PMR T
(6)
where: dqNG
Tcp × − dqNG
FLNG = LNG flowrate T
∆HLNG = NG enthalpy change over the Condensation heat removed from the FIG. 4. MCHE temperature approaches
temperature range from Tcp to Trd gas can be obtained in numeric form from corresponding to top 15% efficient operation
PMR = Power of MR drivers delivered a thermodynamic package and then con- vs. historical operation data variance.
to MR compressors.
The MR cycle coefficient of perfor-
mance is a value invariant to the changes
of available power, since the LNG pro-
duction rate is a function of the power
(1). The ratio of actual COP to ideal
COP (Carnot factor) was used to obtain
a value that is also invariant to Tcp and Trd,
as shown in Eq. 2:
COPact FLNG × ∆H LNG
ψ= = ×
COPid PMR (2)
Wid FLNG × Wid
=
∆H LNG PMR
where:
Wid = Minimum specific work/1 kg of
gas required to cool it from Tcp to Trd in an
ideal refrigeration cycle.
Two assumptions were made when de-
fining an ideal refrigeration cycle for gas
liquefaction (FIG. 2):
• The ideal cycle can be represented
as the number of Carnot cycles,
each operating between a specific
cold reservoir temperature
(gas condensation curve) and
a hot reservoir temperature, FIG. 5. MR composition corresponding to the optimum MCHE temperature approaches (error
which is common for all the cycles bars correspond to standard deviations of the correlations) vs. historical operation data variance.

Hydrocarbon Processing | JANUARY 2019 63


LNG Technology

A major advantage of the Carnot fac- natural variance from suboptimal Clear correlations were found only
tor is its invariance, which allows for the plant operation, were estimated between the MCHE temperature ap-
comparison of MR cycle performance • The maximum possible increase in proaches and the Carnot factor, and
based on a single scale, irrespective of the MR cycle efficiency was estimated between the MR component concentra-
PMR cycle capacity, the available power • Data was checked for correlation tions and the MCHE temperature ap-
of MR compressor drivers and varia- between several process parameters proaches. This observation is important,
tions in LNG rundown temperature. and the Carnot factor since it confirms the theoretical conclu-
Therefore, the yearly probability dis- • Functions of optimal MR sion that MR cycle efficiency strongly
tribution of the Carnot factor can help composition setpoints were depends on MCHE temperature ap-
estimate the available room for cycle derived based on top-performance proaches (FIG. 3). At the same time, real
efficiency increases, as well as confirm operational data plant data indicate that the minimum
positive effects after the implementation • Derived optimum functions were possible temperature approach does not
of optimization-related changes. Several validated by applying them to all correspond to the highest efficiency,
operations were performed on historical data populations and estimating an likely because of limited heat transfer
operation data, including Carnot factor expected economic impact. area and developing temperature pinch.
values array: The list of process parameters checked Moreover, it was found that MR compo-
• Instrumentation bad data and for correlation with the Carnot factor in- nent inventories do not correlate with
periods of turndown or transient cluded the MCHE’s superheat margins the cycle efficiency. This is the reason
operation were filtered out, along and temperature approaches, the MR why the inventories cannot be used in
with equipment unavailability and compressor pressure ratio, the LMR/ an MR composition control strategy as
malfunctions HMR mass flow ratio, the LMR and self-sufficient optimization targets. In
• Carnot factor inaccuracies due to HMR compositions, the MR component other words, a wide range of component
instrumentation noise, as well as concentrations and inventories. concentrations (including optimum and
sub-optimum sets) can correspond to a
single set of component inventories.
Operational data was sliced by Tcp val-
ues with a 1°C interval, and the slices were
treated to extract cases with a high Car-
not factor (top 15%) with corresponding
MCHE temperature approaches. The av-
erage values of extracted temperature ap-
proaches were used to derive optimal ΔT
functions (FIG. 4). Finally, the functions
of optimum temperature approaches
were used to extract the corresponding
MR component concentrations data and
build correlations between Tcp and opti-
mum MR composition (FIG. 5). Those
correlations could then be used for con-
tinuous scheduling of MR composition
setpoints in a control system.

Indirect MR composition control


via component inventories. Statis-
FIG. 6. Schematics of MR direct concentrations control. tical treatment of operational data and
MR cycle efficiency provides valuable
information about minimum MR com-
TABLE 1. Multiple input/multiple output (MIMO) model structure for direct position control compliance required to
concentration control achieve the expected increase in perfor-
Controlled variables mance. Standard deviations of MR com-
C1 C2 C3 N2 L V-02 P V-02
ponent concentrations corresponding to
the top-performance operation from the
C1 makeup ++ – – – + +
Manipulated variables

derived functions of MR optimum com-


C2 makeup – ++ – – ++ – position were used as control compli-
C3 makeup – – ++ – ++ – ance benchmarks (see error bars on the
N2 makeup – – – ++ + ++
trends in FIG. 5). This makes sense, since
composition control tightness must be at
HMR drain – –– –– – – 0
least as good as the correlations between
LMR vent –– – – –– 0 – MR composition and cycle efficiency.

64 JANUARY 2019 | HydrocarbonProcessing.com
LNG Technology

Maintaining MR component concentra- MR component concentrations into actual form refrigerant composition across the
tions within a ±0.3% target window is a and target inventories involves the input circuit (varying gas compressibility and
challenge, since measured MR composi- of V-02 level measurement and the level liquid density), as well as the presence of
tion continuously experiences disturbance setpoint. It results in the indirect control two-phase mixtures in some sections of
effects from several factors: of not only MR composition, but also the the MR circuit.
• Adjustment of LMR/HMR by V-02 level. V-02 temperature changes are
control system realized in smaller variances in V-02 pres- m Pi × Vi
n j = R × ∑i=1 Cij × (9)
• Variation of PMR capacity resulting sure, due to the higher performance of the Zi × Ti
in Tcp changes inventory control scheme; therefore, the where:
• Adjustment of MR compressor use of a V-02 pressure protective control nj = Amount of substance of j compo-
suction pressure by control system loop can be avoided. nent in mixture
• Variation of MR circulation rate While refrigerant composition control
• Possible MR composition drift is traditionally implemented with the use
due to passing valves and leaking of multivariable predictive control tech- TABLE 2. Multiple input/single output
MCHE tubes. niques, the decoupling of the controlled (MISO) model structure for inventory
control
The most straightforward method of variables provides more freedom in the se-
MR composition control relies on the di- lection of control technology. An example Controlled variables
rect use of component concentrations in of a simplified control scheme for the two- C1_i C2_i C3_i N2_i
the control scheme (FIG. 6). The V-02 level component system is shown in FIG. 7.
C1 makeup + 0 0 0

Manipulated variables
and pressure protective controls must be While pressure and temperature condi-
involved in that scheme, since the level tions and volumes are known for most of C2 makeup 0 + 0 0
does not depend on concentrations but the MR circuit sections, the continuous C3 makeup 0 0 + 0
rather on a measure of component inven- online estimation of component invento- N2 makeup 0 0 0 +
tories and must be controlled separately. ries accumulated in the refrigerant loop is
HMR drain – –– –– –
At the same time, variations in the pressure still not a straightforward operation (Eq.
allowed by that control scheme must be 9). Complexity comes from the non-uni- LMR vent – – – ––
moderated by protective control.
A general analysis indicates that no con-
trollability issues are anticipated, since the
numbers of controlled and manipulated
variables are equal and each component is
independently controlled (TABLE 1). How-
ever, several crucial features still limit the
control performance of this scheme:
• The ramp character of process
models between all manipulated
and controlled variables
• Strong mutual dependency of
the controlled variables
• Non-linear gains, depending on
LMR and HMR composition
• N-1 degrees of freedom in the system
of N component concentrations,
which make independent control FIG. 7. Simplified example of base-layer inventory control scheme for a two-component system.
impossible.
The combination of listed features
makes tight control impossible with the de-
scribed scheme.
From a process control point of view, the
inventory of each component is more suit-
able for control than its concentration in
the MR mixture. The inventories are invari-
ant to process changes (Tcp, LMR/HMR,
etc.) and completely decoupled from one
another, which simplifies the model struc-
ture from multiple input/multiple output
(MIMO) to multiple input/single output
(MISO) (TABLE 2).
FIG. 8. Schematics of MR inventory control.
The transformation of actual and target

Hydrocarbon Processing | JANUARY 2019 65


LNG Technology

same time and will correspond to the


same process parameters. This point is
crucial for minimizing the effect of mea-
surement noise on parallel actual and
target inventory estimates.
The implementation of MR inventory
control has delivered excellent results in
terms of MR composition compliance
with optimum targets. An analysis of one
month of post-commissioning opera-
tional data showed that MR composition
had been maintained inside the specified
target windows for approximately 98.5%
FIG. 9. Calculation schematics for gas-liquid equilibrium in V-02 for actual and target MR
of controller uptime, while the windows
concentrations. were specified at ±0.3 mol%, on average
(the correlation error bars in FIG. 5 refer to
the specified target windows).
The average offset between MR com-
ponent concentrations and dynamically
set targets was reduced to zero, and the
variance of the error was decreased by sev-
eral times (FIG. 10). The inventory control
scheme was also found to be sufficiently
robust to work autonomously, without
any adjustments by the control room op-
erator, as opposed to the previously used
direct-concentration control scheme that
required 8–10 manual operator actions
per day. These results show that inventory
FIG. 10. MR composition offset and variation before and after the implementation of an control is the correct strategy for improv-
inventory control scheme based on plant operational data. ing MR composition control, resulting in
increased LNG plant efficiency.
R = Universal gas constant calculations based on volume holdups The methods of MR composition opti-
Cij = j component concentration in i of equipment and pipelines. The calcu- mization and control described here have
section of MR system lations provided estimates of actual and been patented in Russia (RU 2640976
Pi, Ti = Pressure and temperature in target inventories across the MR circuit, C1). Similar patent applications have been
the i section which are used for control (FIG. 8). submitted in six other countries (Austra-
Vi = Volume holdup of the i section V-02 temperature is assumed to be lia, Indonesia, Malaysia, Nigeria, Qatar
Zi = Compressibility of real gas in the the same for the actual and target con- and the US) and are under review. GP
i section. ditions, since the temperature is an ex-
A common solution for the outlined ternal parameter depending only on the LITERATURE CITED
problems is to use the equation of state PMR cycle cooling capacity. Pressure 1
Dam, W. and S.-M. Ho, “Unusual design consider-
ations drive selection of Sakhalin LNG plant facili-
(EOS) solver for the continuous estima- and flash rate, in combination with tem- ties,” Oil & Gas Journal, Vol. 40, 2001.
tion of gas, liquid or two-phase mixture perature and mixture composition, com- 2
Khan, M. S., et al., “Knowledge-based decision-mak-
properties in all MR cycle sections. This pletely define two-phase equilibrium. In ing method for the selection of mixed-refrigerant
approach was successfully applied at the the inventory control of MR separation, systems for energy-efficient LNG processes,” Applied
Energy, Vol. 111, 2013.
Sakhalin LNG plant to estimate MR com- flash rate is a fixed variable since it is
Complete literature cited available online at
ponent inventories corresponding to ac- directly related to the controlled LMR/ GasProcessingNews.com.
tual and target concentrations. HMR; therefore, the calculation of EOS
The Peng-Robinson EOS solving algo- for target conditions is supplied with an IVAN NEMOV is a Senior Process
rithm4 was implemented at the distribut- LMR/HMR target value that matches Control Engineer who worked at
ed control system (DCS) as a structured the operating conditions, and the pres- Sakhalin Energy Investment
text program developed in-house. It is ro- sure is adjusted to match the ratio. Note: Company Ltd. from 2012–2017,
mainly supporting Sakhalin LNG
bust against abnormal process conditions, The calculation of gas-liquid equilib- plant operation. In 2017, he joined
like quick changes of parameters or trips, rium in the V-02 vessel must be time- Shell Australia Pty. Ltd. for
as well as instrument signal abnormalities. synchronized for actual and target MR commissioning and startup of the Prelude FLNG vessel.
He earned his ME degree from Gubkin Russian State
Several estimators were implemented compositions, as shown in FIG. 9. This University of Oil and Gas in Moscow, Russia in 2012 and
for different sections of the MR circuit, ensures that calculation outputs will be teaches as an Assistant Professor at Astrakhan State
linked with corresponding inventory delivered to inventory estimates at the Technical University in Astrakhan, Russia.

66 JANUARY 2019 | HydrocarbonProcessing.com
Cover Story
Part 1

Implementing an
‘Integrity Operating
Window’ Program
An effective Integrity Operating Window (IOW) program — which establishes safe operating
limits and acceptable limits of process variation before an asset begins to degrade — can help
operators stay ahead of potential repairs and reduce risk
Russ Davis System Description Color API 570 Corrosion Damage Limits
MISTRAS Group Pipe Class rate, mil/yr mechanism
100 Ammonia vapor 1  O.5 NH3 SCC* Carbon steel in aqueous
ammonia non-PWHT*
IN BRIEF 101 Ammonia liquid 2  1 Ammonium Concentration of ammonium
DEFINING INTEGRITY chloride cor- salts and temperature
rosion
OPERATING WINDOWS
102 Ammonia, CO2, H2O 2 3  NH3 SCC Carbon steel in aqueous
IOW PROGRAM- vapor, ammonia recycle ammonia non-PWHT
DEVELOPMENT High-pressure streams
OVERVIEW 300 Tail gas 2 3  CO2 corrosion <300°F
DAMAGE OR CORROSION Liquid phase where CO2
ANALYSIS condenses from vapor
phase
RISK RANKING
500 Natural gas 2  O.5 CO2 corrosion <300°F
EVALUATING ALARMS Liquid phase where CO2
condenses from vapor
DEFINING THE IOW
phase
CRITICALITY
501 Fuel gas 2 O.5  CO2 corrosion <300°F
DOCUMENTATION AND
Liquid phase where CO2
TRAINING condenses from vapor
phase
IOW INTEGRATION
502 Hydrogen line 2 O.5  CO2 corrosion <300°F
Liquid phase where CO2
condenses from vapor
phase

A
comprehensive asset-integrity FIGURE 1. Damage mechanisms are established to identify
the key controllable monitoring parameters, or variables that
management (AIM) program is es- can be effectively adjusted to bring the process back within
sential to ensuring process integ- safe operating limits (*SCC = stress corrosion cracking;
rity and reducing risk of operations PWHT = post-weld heat treatment)
to as low a level as practicable. Historically,
these programs are based on a given set tegrity (MI) subject matter experts (SMEs).
of operational parameters that were es- These experts identify the potential damage
tablished during the implementation of mechanisms associated with anticipated
the program. To develop these programs, operating conditions, and help to establish
process conditions — such as the various inspection methods and testing frequen-
chemical components present in the pro- cies. In the subsequent management of the
cess streams, temperature, pressure, and AIM program, reliability and MI groups rely
flowrates — are analyzed by mechanical in- on these parameters and testing method-
42 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MAY 2017
ologies that were established during the requires a multi-disciplinary team of engi-
program’s development. neering SMEs, with advanced knowledge of
But over time in a process facility, op- mechanical, corrosion, reliability and mate-
erational parameters change, and the rate rials engineering disciplines; a multitude of
of equipment degradation may change as inspection and maintenance services; and
well, causing the asset-integrity program to plant data-management software to store
become ineffective. This can shorten equip- and trend data over the program’s lifetime.
ment lifespans, raise costs, and greatly en- With such a wide range of SMEs and com-
hance potential risk to personnel, assets and petencies required, operating companies
the environment. may partner with an experienced third-party
To maintain the integrity of process equip- service provider with expertise in the full
ment in petroleum refining and petrochemi- scope of asset-protection solutions, includ-
cal facilities, a comprehensive process safety ing inspection, engineering, maintenance,
management (PSM) system is required. Cur- condition-monitoring, and mechanical in-
rently, most of these systems are oriented tegrity data management software. Through
toward a rigorous mechanical integrity pro- such a partnership, the stakeholders can
gram that predicts or prevents failures of develop, implement and manage an effec-
pressure equipment. Beyond this, however, tive program.
the optimal PSM support systems include
implementation of so-called integrity oper- Defining integrity operating windows
ating windows (IOWs; defined below) and As defined by the American Petroleum Insti-
management-of-change (MOC) programs, tute’s (API) RP 584, integrity operating win-
which are designed to monitor and control dows are established limits for process vari-
process variables that can impact the likeli- ables (parameters) that can affect the integrity
hood of failure. of the equipment if the process operation
The implementation and management deviates from the established limits for a pre-
of an effective IOW program is complex. It determined length of time [1]. In short, IOWs

T +49 2961 7405-0 | info@rembe.de

Your Specialist for


PRESSURE RELIEF SYSTEMS
and
© REMBE | All rights reserved

EXPLOSION SAFETY

Consulting. Engineering. Products. Service.

Gallbergweg 21 | 59929 Brilon, Germany


F +49 2961 50714 | www.rembe.de

Inc.
3809 Beam Road Suite K Charlotte, NC 28217, USA
T +1 704 716 7022 | F +1 704 716 7025
info@rembe.us | www.rembe.us

Circle 35 on p. 90 or go to adlinks.chemengonline.com/66428-35 Circle 05 on p. 90 or go to adlinks.chemengonline.com/66428-05


CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MAY 2017 43
Cover Story

FIGURE 2. As shown in this establish acceptable limits of process varia- is an integrity parameter, which, if exceeded
sample process flow dia- tions before an asset begins to incur damage. over a specific time frame, could cause in-
gram, process flow streams
and control groups are often The purpose of defining an IOW is to es- creased corrosion rates or eventually lead
color-coded in accordance tablish, implement and maintain a program to to cracking or other damage to materials
with the colors assigned to identify any potential damage mechanisms of construction. Standard limits are typically
them on the damage-mecha-
nism analysis table shown in
that may adversely affect the process, and very time-based, in that the time required for
Figure 1 then use that information to create a system equipment to be adversely impacted gener-
where parameters can be modified as pro- ally defines the response to a standard limit
cesses evolve over time. IOWs identify safe IOW. The consequence of damage to the
operating limits with the express purpose of equipment associated with the IOW will also
avoiding equipment degradation that could influence an SME’s response to the param-
lead to a loss of containment. The ultimate eter being exceeded. An example of a stan-
goal of IOWs is to lower the risk of operating dard limit IOW could be an elevated temper-
plant process equipment. ature on a heater tube skin, which could lead
Integrity operating windows are typically to tube failure over time.
defined by their criticality. API RP 584 divides IOW critical limit. IOW informational lim-
IOWs into three categories: its are generally used by SMEs to predict
1. IOW critical limit the long-term integrity of equipment, or to
2. IOW standard limit analyze impact on the asset-integrity pro-
3. IOW informational limit gram. Informational IOWs are parameters
IOW critical limit. An IOW critical limit would that may or may not be affected by opera-
be one that, if exceeded, could lead to rapid tions. These IOWs do not typically require
deterioration of process equipment. A criti- operational responses but may be utilized
cal limit requires immediate operator action to assess future repairs of turnaround and
to return the process variable to a predeter- shutdown frequencies. Informational IOWs
mined parameter in order to prevent poten- can be used to evaluate the process as-
tial equipment damage in a short time frame. sumptions used to establish risk-based in-
An example of a critical limit could be a pH spection (RBI) programs. An example of an
excursion in a process stream, as an ex- informational limit would a temperature rise
tremely low pH could quickly damage pres- due to process creep, which could indicate
sure equipment and could reasonably lead to facility operators that the parameters that
to loss of containment in a short time. were defined during the AIM program
IOW standard limit. An IOW standard limit development are misaligned with current
44 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MAY 2017
operating processes. ably safe state, or to further assess plant operations, maintenance and
These terms vary across compa- the response to limit exceedance, reliability programs, and plant data-
nies and industries. Critical limit IOWs depending on criticality. management software. This is an es-
may also be referred to as safe oper- Step 6. After IOWs and procedures sential step, to ensure that IOW pro-
ating or safety critical limits. Standard have been properly documented, all gram procedures are being uniformly
limit IOWs have been referred to as personnel involved in the process practiced throughout a facility, and
key operating limits or reliability limits, operation must be trained in IOW im- that any change to a process param-
and informational limit IOWs may also plementation and timely responses eter is being catalogued alongside
be referred to as corrosion control to IOW indicators and alarms. the rest of the facility’s integrity data.
limits, depending on the industry in Step 7. Step seven is integrating Step 8. Finally, the last step to an
which they are used. the IOW program into the rest of the IOW program is the revalidation of

IOW program-development
overview
Step 1. The first step to developing
an IOW program is to identify all po-
tential damage or corrosion mecha-
nisms that may adversely impact the YOUR COMPETITIVE EDGE IN
process equipment. A diverse team
of engineers will evaluate the oper-
ating parameters of each process PROCESS HEAT TRANSFER TECHNOLOGY
condition to understand their po-
tential corrosivities, and will evaluate
their impacts on equipment materi-
als of construction. The SME team Do you need accurate heat exchanger technology for real-world situations?
will develop a damage or corrosion Software and services to help you design equipment that performs under the
map, which will be used again later
broadest range of operating conditions? IF SO, YOU CAN RELY ON US.
to evaluate what indicators are cur-
rently provided to detect exceed-
ance of an IOW limit. SMEs can then
HTRI is a leading provider of
define the IOW limits for each dam-
age mechanism. products and services that help
Step 2. After all damage mecha- engineers around the world rate, RESEARCH
nisms have been identified, the con- simulate, design, and enhance the
sequence of failure and the likelihood performance of heat exchangers.
of failure need to be analyzed and SOFTWARE
understood. Consequence of failure Our extensive expertise is the result
data can be gathered from process of more than 50 years of applied
hazard analysis (PHA) data or by research conducted in our
consequence modeling. The equip- industrially relevant testing facilities. TECHNICAL
ment failures are then risk-ranked. SUPPORT
We deliver research, proprietary
Step 3. The third step in IOW pro-
gram development is typically an contract services, training, support,
evaluation of alarms, indications, and and software, including our
procedures necessary to recognize acclaimed Xchanger Suite®, to PROPRIETARY
exceedance of the IOW limit.
Step 4. Step four is to define the crit-
assure our customers the highest CONTRACTS
icality of the operating limit and de- operating confidence in equipment
fine the priority of the IOW limit. This designed using our technology.
is where SMEs determine whether TRAINING
the IOW is critical, standard or
informational.
Step 5. The next step is the docu-
mentation of each IOW, and the de-
velopment of proper responses to Visit www.htri.net
IOW alarms and notifications. Pro- to learn more.
cedures or work instructions should
define the roles and responses nec-
essary to return the process to a reli- Circle 21 on p. 90 or go to adlinks.chemengonline.com/66428-21

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MAY 2017 45


Cover Story
Consequence category ure for the equipment within each system.
A B C D E
Consequence-of-failure data may come
< $10K $10K to $100K $100K to $1M $1M to $10M > $10M from process-hazard analysis (PHA) data
5 or consequence modeling, and analysis
0 0 0 2 0 may be performed as an element of the
1E to 1
4 risk assessment. Once a risk analysis is
0 0 0 2 0 completed, ranking can be performed and
1E-2 to 1E-1
3 the risk rank associated with each system
0 0 0 0 0 or subsystem can be documented.
1E-3 to 1E-2
1 The risk-ranking data will be used to cat-
0 0 0 1 0
0 to 1E-4 egorize the IOW limits, as shown in Figure 3.
Target risk 4 4 3 2 2 High-risk events will require a Critical IOW.
Events with medium risk may require a Stan-
dard IOW, and low-risk events may be cat-
Risk rank Low Medium Medium high High
egorized as requiring an Informational IOW
Bold line indicates target risk only.

FIGURE 3. Risk-ranking data the IOWs, which consists of reviewing each Evaluating alarms
can be used to categorize the IOW for effectiveness and avoidance of spu- By understanding the limits associated with
IOW limits, as shown here. rious alarms and notifications. potential damage mechanisms that may af-
High-risk events will require
a Critical IOW. Events with fect the equipment, SMEs can perform an
medium risk may require a Damage or corrosion analysis evaluation of what alarms, alerts and notifi-
Standard IOW, and low-risk A comprehensive analysis must be per- cations will be required for operations, reli-
events may be categorized
as requiring an Informational
formed by an engineering team with knowl- ability and mechanical integrity groups to
IOW only edge of the relevant processes, operating recognize exceedance of an IOW limit.
parameters, corrosion analysis and damage Alarms are the typical indicators for criti-
mechanisms. This team assesses poten- cal limit IOWs, usually coming in the form of
tial damages that can adversely affect the horns and flashing lights in the control room
equipment based on the material of con- to denote that immediate action must be
struction. They will also assess the operating taken. Alerts and notifications can span from
parameters of process conditions, such as visual or audio signals to simple emails to
temperature, stream constituents, pressure, operations and technical personnel, inform-
vibration, abrasiveness and more. Once ing them that an IOW has been exceeded
the team has identified potential corrosive but without any urgent need for time-sensi-
streams and the equipment materials of con- tive action to be taken.
struction, the limits associated with the dam- The engineering team typically assesses
age mechanism are identified. The team may process parameters such as the following:
have an output report such as that shown in • Temperature
Figure 1. • Pressure
Once the potential damage mechanisms • Flow
associated with the various process systems • Stream constituents
and limits have been identified, these data • Water content
can be depicted on plant process flow dia- • Chlorides
grams (PFDs), such as the one shown in Fig- • Sulfur
ure 2. Process flow diagrams typically con- • pH
tain all major pieces of process equipment,
identified by a unique number; all process Defining the IOW criticality
flow streams, identified by a number and At this step, operators must determine IOW
their chemical compositions; and control criticality limits and priorities, depending on
loops, or groups of equipment and piping potential damage severity and the expected
with similar materials, operating conditions time constraints before serious damage oc-
and degradation mechanisms. curs.
• Critical IOW — An alarm requiring a timely
Risk ranking response by a facility operator or SME
Risk profiles should be developed for each to bring the process back within IOW
equipment item that has a potential influ- parameters
ence on process safety. The risk-ranking • Standard IOW — Typically includes an
process consists of analysis of the conse- alert to operations personnel and to the
quence of failure, and the probability of fail- reliability SME. Standard IOWs usually
46 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MAY 2017
The ultimate for
small tanks!
The future is 80 GHz: a new generation
of radar level sensors

When it comes to contactless level measurement of liquids in


small containers, smaller is better. With the smallest antenna of
its kind, VEGAPULS 64 is simply the greatest! With its excellent
focusing and insensitivity to condensation or buildup, this new
radar sensor is truly exceptional. Simply world-class!

www.vega.com/radar

Wireless adjustment via Bluetooth with


smartphone, tablet or PC. Compatible retrofit to
all plics® sensors manufactured since 2002.

Circle 45 on p. 90 or go to adlinks.chemengonline.com/66428-45
Cover Story
have a timeframe associated with them. tiveness, an IOW program must be as in-
If an integrity limit is exceeded for a set tegrated into plant operations as possible.
time, equipment will suffer damage Utilizing a comprehensive mechanical-
• Informational IOW — Information con- integrity data-management software pro-
veyed from field-gathered data to the gram, in which inspection, corrosion, and
reliability SME. This information may integrity data, MOC activities, RBI man-
require changes to the RBI assumptions, agement and more are stored, organized,
frequency of inspection, or nondestructive trended and analyzed — helps to ensure
evaluation (NDE) methodology that IOW program data are centrally located
considerations and consistently updated.

Documentation and training Closing thoughts


Just like every other aspect of a process Getting the longest, safest reliable life from
safety program, documentation is critical. each equipment component in the plant is
The IOW program must include documenta- critical to the profitability of any chemical
tion of each IOW and the proper response process operation. Process safety is an ev-
to IOW alarms, alerts and notifications. This ergreen management program, and changes
information should be incorporated into the that affect the program design must be mon-
facility’s operating procedures as well as reli- itored and properly responded to in order to
ability program documentation. maintain a risk rate that is as low as practi-
cable.
When process changes occur, the asset-
integrity group may not always be informed,
When process changes occur, the asset-integrity or may be using an outdated frame of ref-
erence from the program’s original develop-
group may not always be informed, or may be using ment. For example, a slight temperature ele-
an outdated frame of reference from the program’s vation can raise a corrosion rate significantly.
Changes in sulfur content in a crude stream
original development. can lead to sulfidation damage in areas the
MI group had not anticipated.
The key for any facility is to control these
variables before they start harming equipment
Once all necessary IOW information has and people. An effective IOW program — one
been documented, the facility must properly that is fully integrated into plant processes,
define the roles and responsibilities for op- and implemented and managed by properly
erations, engineering, reliability and mechani- trained personnel — helps facilities to be in-
cal integrity personnel. All of this information formed when variables become unsafe, and
should be proceduralized, and all responsible lets them know the actions that must be taken
personnel should be trained in IOW imple- to quickly reduce risk. An integrated IOW pro-
mentation and the proper, timely response to gram is an essential component of any me-
IOW alarms, alerts and notifications. chanical integrity program. Q
Edited by Suzanne Shelley
IOW integration
The IOW program must be fully integrated References
into the plant’s operations and maintenance, 1. American Petroleum Institute, Integrity Operation Windows, RP 584,
reliability and mechanical integrity programs, 1st Ed. May 2014.
2. Center for Chemical Process Safety (CCPS), Guidelines for Asset
/
and engineering processes. Changes in feed-
Integrity Management, John Wiley & Sons, Inc., Hoboken, New
stock, temperatures and flow characteristics Jersey, 2017.
that impact individual assets can have an im-
pact on the entire asset-integrity program. It Author
is critically important for a facility to fully un- Russ Davis, CSP, is the National Asset Integrity Management Ser-
derstand the information returned from the vices (AIMS) & Mechanical Integrity (MI) Center of Excellence Man-
ager for MISTRAS Group, Inc. (4000 Underwood Rd., La Porte, TX
IOW program and to recognize the effects 77571; Phone: 281-478-1636; Email: russ.davis@mistrasgroup.
that changes in one process parameter can com). Davis has several decades of experience in program design
have on other equipment, as this information and implementation in the mechanical-integrity and asset-reliability
industries. He has extensive experience in process safety manage-
should inform operations from purchasing all ment (PSM) and hazard assessment and consequence analysis.
the way through post-production. Davis has also served as both an internal and external consul-
tant, directing the implementation of MI programs for companies
This step can be time-consuming and throughout the global CPI.
meticulous. In order to maximize its effec-
48 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MAY 2017
Engineering Practice

Key Considerations in Specifying Control Valves


Follow this guidance to specify a control valve accurately during the design phase
Satyendra Kumar Singh at maximum flow may be greater P = y
Simon India Limited than 90% of the rated travel — both
scenarios mean poor controllability

C
ontrol valves are one of of the valve. In that case, pressure
the most common and im- drop across the control valve should P1
A B
P2
portant instruments used be increased so that the target ratio
in the chemical process can be lowered, as shown in Equa-
industries (CPI). They help to en- tion (1). For incompressible fluids, P = x
sure smooth and efficient operation the ratio of maximum Cv to minimum
of process plants, by achieving the Cv is given by Equation (1): FIGURE 1. Shown here is a typical control valve
desired operating parameters by circuit, which is used illustratively in the descrip-
tions provided in the main text
means of regulating the fluid flow in
connected pipes. The need to prop-
erly specify control valves during the (1)
design phase of a plant cannot be (2)
overemphasized. Figure 1 shows a typical control
The size of a control valve is de- valve circuit. The following notes add From Equation (1) and Equation (2),
rived from a parameter called the further explanation: (Cv)max/(Cv)min is approximately:
flow coefficient (Cv), which is defined i. The segments represented by
as volumetric flowrate (in gal/min) P1A and BP2 represent items con-
of water through the valve at 60°F nected to the valve (such as pipes,
when pressure drop across the valve fittings, heat exchangers, flow el-
is 1 psi (Cv is calculated using the ements, and more), whereas the (3)
formula given in the standard ISA- segment represented by AB rep-
75.01.01-2007). Process engineers resents the control valve in the
should take the following aspects complete circuit P1ABP2. The ar- The following conclusions can be
into consideration when specifying rows in this circuit represent flow drawn from Equation (3):
control valves, to ensure that the direction. iv. As r>1 and z≥x, any increase in
valves that are manufactured by the ii. ∆P denotes pressure drop. y leads to decrease in the ratio
vendors function according to the iii. Indicated pressure drops are for (Cv)max/(Cv)min. That is, better
requirements. maximum flow. controllability can be achieved by
1. Controllability. While specifying Referring to Figure 1, if x is the increasing pressure drop across
a control valve during the design pressure drop across the control the control valve at maximum flow.
phase, the process engineer should valve circuit P1ABP2, and y is the (Note: z = x if P1 and P2 are fixed
ensure that the valve’s controllability pressure drop across the control pressure points, and in general z>x
must be good over the entire range valve AB for maximum flow, then the if the control valve is located at the
between minimum and maximum pressure drop in the remaining part discharge of a centrifugal pump
flowrates. This can be done by es- of the circuit (consisting of the pipes, v. If r increases, y also increases
timating the maximum Cv and mini- fittings, heat exchangers, flow ele- for the same ratio of (Cv)max to
mum Cv that correspond to maxi- ments and more; as represented by (Cv)min. This means that pressure
mum flowrate and minimum flowrate, the segments P1A and BP2) is x–y drop across the control valve at
respectively. In general, the control- for maximum flow. maximum flow should increase
lability of a control valve is deemed If r is the ratio of maximum to with an increase in the ratio of
acceptable if its travel at maximum minimum flow, and z is the pressure maximum to minimum flow, if
flowrate does not exceed 90% of the drop across the circuit P1ABP2 at the same controllability has to
rated travel, and if travel at minimum minimum flow, then — ignoring the be achieved.
flowrate is in the range of 10–20% elevation difference between P1 and vi. In most common cases,
of the rated travel. This means the P2 — pressure drop in the part of the maximum flow is 110%, and mini-
ratio of estimated maximum Cv to circuit other than the control valve mum flow is 50%, of normal flow.
estimated minimum Cv should pref- (that is, P1A and BP2) at minimum In such cases, if pressure drop
erably not be more than 15. If the flow is approximately = (x–y)/r2. across the circuit P1ABP2 remains
ratio far exceeds this value, travel Pressure drop across the con- same for maximum and minimum
at minimum flow may be less than trol valve AB at minimum flow is flows, then Equation (3) becomes
10% of the rated travel, or the travel approximately: the following:
84 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017
Recognize and honor the most noteworthy
chemical-engineering technology by
nominating it for the Kirkpatrick Chemical
Engineering Achievement Award

Winner is selected by a Board of Judges


comprised of current chairs of chemical-
engineering departments at accredited U.S. and
E.U. universities. It is this unbiased selection
process, combined with a more than 80-year
tradition that makes the Kirkpatrick Chemical
Engineering Achievement Award one of the most
prestigious honors that a CPI company can The aim of the Kirkpatrick Chemical Engineering
receive. The Kirkpatrick Chemical Engineering Achievement Award is to recognize and honor the
most noteworthy chemical-engineering technology
Achievement Award will be bestowed in
commercialized anywhere in the world during the
November at the Chem Show in New York. two years prior to a given award year.
Chemical Engineering magazine has awarded this
For the full list of winners and biennial prize continuously since 1933.
submission details, please visit:
chemengonline.com/kirkpatrick

DEADLINE FOR NOMINATIONS:


MARCH 15, 2017

chemengonline.com/kirkpatrick
CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017 85
(Cv)max/(Cv)min is approximately = TABLE 1: COMPARISON OF VARIOUS TYPES OF CONTROL VALVES [1 ]
[1 + (3.84x/y)]0.5, which implies that Parameter Type of the control valve
(Cv)max/(Cv)min is approximately Butterfly valve Ball valve Globe valve
3.5, for an x/y value of 3.0. A (Cv) Cost Low Low High
max/(Cv)min value close to 3.5 cor- Pressure drop Low Low High
responds to reasonably good con- Flow capacity High High Low
trollability. Hence, it can be said
Flow characteristic Fixed (approximately Fixed. For V-notch ball Any of the three (linear,
that for good controllability, pres- equal percentage) valve, flow characteristic equal percentage, quick
sure drop across the control valve is equal percentage opening), depending on
should be approximately one third plug or cage design
of total dynamic pressure drop Liquid pressure recovery Low Low High
across the circuit at maximum flow, factor (FL)
if maximum and minimum flow are Cavitation potential High (due to low FL) High (due to low FL) Low (due to high FL)
110% and 50%, respectively, of Noise potential High High Low. Can be reduced
normal flow. further by using cage
guided plug
Although Equation (3) is true for
incompressible fluid, the above re- Control range Low In-between for V-notch High
ball valve
sults in general are reasonably true
Control type Throttling and on-off On-off. However, V-notch Throttling
for compressible fluid, as well. ball valves have good
2. Cavitation. When fluid is flowing throttling capability, too
through a control valve, the mini- Rangeability Low V-notch ball valves have High
mum pressure occurs at the vena very high rangeability
contracta, and then pressure in-
creases along the path of flow until P2 = Absolute pressure at the outlet in an exchanger in the control
the fluid reaches the outlet of the of the control valve valve circuit, the control valve
control valve. The vena contracta is FL = Liquid pressure-recovery factor, should be located upstream of
the point in the flow path where the as defined by: the exchanger — not down-
flow area is minimum, the veloc- 0.5 stream — so that vapor pressure
ity is maximum and, hence, pres- FL = [(P P2 ) /(P1 PVC )] of the liquid is sufficiently less
sure is minimum [1]. For liquids, if than the operating pressure at
the pressure at the vena contracta Pvc = Absolute pressure at the vena the vena contracta of the control
is less than the vapor pressure of contracta valve. This will eliminate flashing
the liquid, vapor bubbles will form. FF = Liquid critical pressure ratio fac- through the control valve.
Downstream of the vena contracta, tor iii. Locate the control valve in the
pressure recovery takes place, re- FF = 0.96–0.28 (Pv / Pc)0.5 circuit where the elevation is mini-
sulting in higher pressure at the Pc = Absolute thermodynamic criti- mum so that static head is maxi-
valve outlet than at the vena con- cal pressure of the liquid mum. This will maximize P1 as well
tracta. If pressure at the outlet of Pv = Absolute vapor pressure of the as P2 without impacting (P1–P2).
the control valve exceeds the vapor liquid at inlet temperature That can make the left-hand term
pressure, the vapor condenses The exact value of FL for a particu- in Equation (4) less than the right-
and bubbles collapse. As bubbles lar valve can only be available in the hand term and, hence, prevent
collapse, it causes impact on the valve vendor’s specifiction sheet, but cavitation.
valve body and creates noise. This an indicative value can be obtained iv.Select a control valve body type
phenomenon is called cavitation. from the vendor catalog, from ISA- with higher pressure-recovery
Full cavitation occurs when pres- 75.01.01-2007, or from other con- factor (FL), which makes critical
sure drop across the control valve trol valve literature during the design pressure drop for cavitation —
is more than or equal to certain phase. that is, FL2(P1—FF PV) — higher.
minimum pressure drop (or critical Process engineers should try to For example, a globe valve has
pressure drop), and the pressure minimize the possibility of cavitation a higher FL than that of butterfly
at the outlet of the control valve is when specifying control valves. This and ball valves. Thus, the use of
more than the vapor pressure of can be done in the following ways: a globe valve (instead of a butter-
the liquid. Thus, full cavitation oc- i. Alter the hydraulics of the control fly or ball valve) might prevent the
curs if the following conditions are valve circuit and reduce the pres- cavitation.
met [2]: sure drop across the control valve It is absolutely necessary to specify
to less than FL2(P1—FFPV), where the thermodynamic critical pressure
P FL 2 ( P1 FF PV ) (4) possible (as explained above), and vapor pressure of the liquid in
without compromising the control- the process datasheet of a control
lability of the valve. valve handling a liquid, so that the
P = P1 P2 ii. Try to change the location of the occurrence of the cavitation can
control valve such that the possi- be assessed. Full cavitation re-
Where: bility of flashing through the con- sults in choked flow and hap-
P1 = Absolute pressure at the inlet of trol valve can be avoided. For ex- pens if ∆P ≥ FL2 (P1–FFPv). How-
the control valve ample, if a liquid is being heated ever, partial cavitation can occur
86 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017
without causing choked flow, if excessive noise. Noise can be mini- The type of flow characteristic
pressure drop is less than criti- mized with a globe valve with the should be specified in the process
cal pressure drop but greater than use of cage-guided trim. However, datasheet, considering the param-
∆Pincipient cavitation [2],where: if the available pressure drop across eter to be controlled, or the pres-
the valve is low, then a butterfly sure drop scenario in the system.
∆Pincipient cavitation = valve may be the preferred choice. For flow or level control, linear char-
Meanwhile, V-notch ball valves acteristic should generally be speci-
KC ( P1 FF PV ) can be preferred where high range- fied. In general, linear characteristic
ability is required. Standard, round- should also be specified if most of
Where: ported ball valves are generally used the pressure drop (as a proportion of
Kc = The coefficient of incipient cavi- for on-off applications. Table 1 pro- total pressure drop in the system) is
tation, which is less than FL [2]. vides valve-selection guidelines. across the valve itself so that pres-
3. Multiple operating cases. 5. Leakage class. The allowable sure drop across the valve remains
Whereas a control valve is gen- control valve seat leakage is spec- nearly constant for varying flow-
erally specified for three cases ified in terms of ANSI/FCI 70-02- rates. Equal-percentage character-
— minimum, normal and maxi- 2006 leakage class. This standard istic should be specified for pressure
mum flowrates, with correspond- recognizes six classes of allow- control, or where a high proportion
ing pressure drop — there may be able seat leakage (Class I, II, III, IV, of the total pressure drop occurs
more than three operating cases. V and VI). Class I means highest in the system other than the valve
In such situations, normal flowrate allowable leakage; Class VI means (that is, in pipes, fittings, equipment
and corresponding pressure drop least allowable leakage [3]. Gener- and so on). It should also be speci-
should be specified in accordance ally, control valves for CPI applica- fied where pressure drop across
with the normal operating case, tions are specified with leakage the valve varies with varying flow-
whereas other operating cases (if Class IV. However, in situations rate. A quick-opening characteristic
there are more than two) should where tight shutoff is required, at should be specified for on-off appli-
be narrowed down to two cases. least Class V should be specified. cations. As in most of the common
When narrowing down the operat- If a control valve is discharging to systems, pressure drop across the
ing cases, Cv should be estimated a flare, or is controlling (on-off) fuel control valve varies significantly with
for each case. Then, minimum and flow to the burner of a fired heater flowrate, so equal-percentage flow
maximum flowrates (and corre- or furnace, it should be specified characteristics are most commonly
sponding pressure drops) should with Class VI leakage. specified [1]. Q
be specified in such a way that 6. Flow characteristics. The most Edited by Suzanne Shelley
they correspond to the minimum common types of inherent flow char-
and maximum Cv of the control acteristics are the following [1]: References
valve, and the Cv corresponding to • Linear — A valve with an ideal 1. Emerson Process Management, “Control Valve Hand-
all other cases should lie between linear inherent flow characteris- book,” 4th Ed., p. 18, pp. 33–36, p. 46, pp. 59–60, pp.
109–110, p. 136.
minimum Cv and maximum Cv. As tic produces a flowrate that is di-
2. “Masoneilan Handbook for Control Valve Sizing,” 7th Ed.,
actual Cv is not available when a rectly proportional to the amount pp. 7–8, p. 10, 1987.
control valve is specified, the esti- of valve plug travel, throughout the 3. American National Standard, Control Valve Seat Leakage,
mated Cv should be used. travel range. ANSI/FCI 70-2-2006, Cleveland, Fluid Controls Institute,
4. Selection of type of valve. But- • Equal percentage — Ideally, for Inc., p. 2, 2006.
terfly valves, which are compact and equal increments of valve plug
generally have a relatively low cost, travel, the change in flowrate re- Author
are often the first choice. However, garding travel may be expressed Satyendra Kumar Singh is the
constraints may dictate otherwise. as a constant percent of the flow- general manager (Head of Depart-
For instance, if high pressure drop rate at the time of the change. ment) – Process for Simon India
across the valve is required, a globe • Quick opening — A valve with Limited (Mehtab House, A-36,
Ground Floor, Mohan Co-operative
valve may be the better choice. quick-opening flow characteris- Industrial Estate, New Delhi-
Because the resistance of a globe tic provides a maximum change 110044, India; Email: sty_singh@
valve is higher than that of a butterfly in flowrate at low travel rates. A yahoo.com; satyendra.singh@
adventz.simonindia.com). He has
valve, higher pressure drop can be quick-opening characteristic is more than 24 years of experience
obtained across a globe valve with basically linear through the first in engineering consultancy and engineering procure-
reasonable size. 40% of valve plug travel (corre- ment construction in the fields of petroleum refining,
petrochemicals, chemicals, oil-and-gas, and ammonia.
In liquid applications, high pres- sponding to 70% of maximum Singh holds a Bachelor of Technology (Honors) degree
sure drop could lead to cavitation. flowrate), and there is little in- in chemical technology from Harcourt Butler Techno-
As the pressure-recovery factor of crease in flowrate with further in- logical Institute (Kanpur, India), and an Masters of Busi-
globe valves tends to be higher than crease in plug travel. ness Administration from Indira Gandhi National Open
University (New Delhi, India). He is a Chartered Engineer
that of other valve styles, cavitation The flow characteristic of a valve de- (India), and a Fellow of The Institution of Engineers
can often be avoided with the use of pends on its trim design. While ball (India); and has published numerous papers on man-
globe valves. valves and butterfly valves have fixed agement and engineering subjects.
In the case of gases, high pres- characteristics, globe valves can
sure drop could lead to choking have any of the three characteristics,
flow conditions, which can generate depending on plug or cage design.

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM MARCH 2017 87


12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/29 6/15
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/29 7/15
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/29 8/15
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/29 9/15
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/29 10/15
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/29 11/15
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/29 12/15
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/29 13/15
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/29 14/15
SAFETY

Keys to successful
alarm management
Here are the features you want in alarm management software
J. GOOCH, Consultant, Houston, Texas

O
ver the past few years, alarm • Description considered to be chattering. A listing of chat-
management has become a very • Alarm [e.g., process variable high tering alarms can be used by the maintenance
important topic within a number (PVHI), process variable low (PVLO), and engineering groups to target resources on
of articles, technical papers and books. change of state, etc.] instrument and process problems.
Most of the discussions have been centered • Value at time of alarm. Additional, very useful alarm analyses are:
on the importance of alarm management For certain advanced features, it is use- • Duplicate alarms—A listing of alarms
and how to implement and maintain an ful if the connectivity solution provides the where one alarm always follows another.
alarm-management process. However, not ability to write information back to the Effectively, the alarms are duplicates and
much has been written on the tools to sup- DCS. However, keep in mind that it is fun- the removal of one should be considered.
port alarm management and, in particular, damental that the ALMS had good data • Stale alarms—A listing of alarms that
alarm-management software. This article is with which to work. Therefore, if the ALMS have been in the alarm state for more than
intended to meet that need. you are considering does not have rock-solid 24 hrs. A stale alarm is not available to the
A number of alarm-management soft- connectivity, find another ALMS. Period. operator and may be considered disabled.
ware systems are on the market. As you Such an alarm should be reviewed and
might expect, each has its own strengths Alarm analysis. Another fundamental repaired or removed.
and weaknesses. This article will provide a feature is a suite of alarm analyses. Infor- • Dynamic alarm priority distribu-
vendor-neutral listing of key features, along mation from alarm analysis will be used tion—A distribution of alarms by prior-
with a brief discussion of each. to drive alarm monitoring and reduction ity. This can be an indication of a problem
efforts, as well as to provide information for with alarm priorities.
Connectivity. Although alarms can be reporting mechanisms. The bare minimum • Operator changes—A listing of
generated on many systems such as dis- analyses to be included are: changes initiated by an operator, such as
tributed control system (DCS), emergency • Alarm frequency—A listing of alarms changes to alarm, controller state or con-
shut-down (ESD), tank-gauging or flow- in order of frequency. The analysis should troller setpoints. A high change rate is
measurement systems, most companies be able to show what percentage of total indicative of problems with the alarm sys-
bring alarms to the DCS since it is used as alarms comes from each alarm reported. tem or control loops. The more time an
the primary device for presenting informa- • Alarm rates—A listing of alarm rates operator spends adjusting the system, the
tion to the operator. Therefore, it is abso- per unit of time over an extended period, less time is spent managing the unit.
lutely vital that the alarm-management for a selected operator position. Typical The alarm analysis system should sup-
software has good connectivity to the DCS. time units are per day, hour and 10 mins. port a very flexible set of alarm system
Numerous ways to connect an alarm-man- The analysis must be able to distinguish parameters. This is generally accomplished
agement system (ALMS) to a DCS include: between annunciated alarms and recorded by the use of filters that allow selecting such
• Object linking and embedding for alarms. This type of analysis can be used things as:
process control (OPC) data access (DA) to give an estimate of operator and system • A specific operating area or set of
• OPC alarms and events (AE) alarm loading. areas
• Printer intercept • Alarm floods—Alarm floods can be • Time periods such as past seven days,
• Open database connectivity (ODBC) the bane of an operator’s life. Alarm floods complete week, 30 days or complete month
• Event files. are generally considered to occur when the • Alarm type
The method does not matter much as alarm rate exceeds 10 alarms per 10-mins. • Alarm priority.
long as the connectivity scheme is stable, It is commonly considered that an alarm If a site can get control of the most fre-
collects information on all alarms and can flood is a time when the system generates quent and chattering alarms and the major
collect at least a minimum set of parameters more alarms than the operator can process. alarms during alarm floods, the average
for each alarm. A suggested minimum list It represents a time when the alarm system alarm rates will come down. Lowered alarm
of parameters is: is of no value. rates during an abnormal situation give the
• Alarm time/date • Chattering alarms—An alarm that operator time to respond to the alarm. This
• Tag name occurs three or more times in a minute is means the operator is thinking rather than

I
HYDROCARBON PROCESSING APRIL 2011 85
SAFETY

reacting. However, lowered alarm rates do of the best ways to determine an effective selection criteria are much too complex to
not solve the entire problem. The alarm alarm set for a control system. Typically, a be discussed here. Please see the references
system must be reviewed to ensure that the site will develop a formal document, often included at the end. The ability to docu-
optimum collection of alarms and priorities called an alarm philosophy, that details for ment the alarm rationalization results is
are included. alarm selection and priority determina- crucial. This will allow others to determine
tion criteria. The ALMS must support the the thought process later. Also, the alarm
Alarm rationalization support. alarm selection and priority determination system is essentially part of the unit system.
An alarm rationalization (also known as criteria. Most sites use a selection mecha- Being able to show how and why an alarm
an alarm objective analysis, or AOA) is the nism based on the maximum severity of has been set may be of importance during
systematic review of all potential alarms the consequences if there is no response a thorough review of such systems.
within an operating area, applying a rig- to the alarm and the time available for the Every alarmable parameter for each tag
orous set of selection criteria. This is one operator to react. The details of developing in the system must be presented for review.
This implies some knowledge of the sys-
tem configuration by the ALMS which,
in turn, implies that some mechanism for
importing configuration information into
Compression… the ALMS. This is not trivial. The vendor
must be able to demonstrate a reliable con-
figuration import method for all applicable
Without Exception control systems.
Other desirable features of an alarm
rationalization support package are:
• Filtering/selection capabilities—it is
often good practice to look at a group of tags
together. For example, it might be prudent
to look at all of the tags related to a distilla-
tion column to create a consistent column
alarm strategy for the column, as opposed to
looking at individual tags in isolation.
• Copy/paste capabilities—once an
alarm strategy is determined for one piece
of equipment, it may be possible to use it
for other similar pieces of equipment. This
has the advantage of enforcing consistent
Howden Burton Corblin Process Compressors strategies.
from Gas and Air Systems • Export of results—This can ease
developing management of change (MOC)
When you specify a compressor • Two-compartment, documentation.
to API 618, you expect the high full-stroke distance pieces. • Results implementation—Results
reliability achieved by compliance of an alarm rationalization are only useful
• Buffer-purged packing cases.
with the Standard. if actually implemented. There are often
• Conservative design hundreds, if not thousands, of changes that
Gas and Air Systems’ Howden
and ratings. must be made to the alarm system. ALMS
Burton Corblin Compressor
packages include the following support is convenient and a reliable method
API 618 demands it…you
important features required by to transfer the results to the control system.
expect it, and we provide it...
API 618...without exception. without exception.
Reporting. Reports often form the heart
• Water-cooled, horizontal Contact Gas and Air Systems of an alarm-system improvement process.
cylinders. for the process compressor built It has been said that if you cannot measure
• Replaceable dry cylinder liners. to your standard. an activity, you cannot improve it. Most
ALMS reporting packages are based on the
If you require low-volume and/or high-pressure compression analysis package. Reports should be:
of hazardous gas with zero leakage and zero contamination,
• Configurable to meet site needs
Gas and Air Systems’ Howden Burton Corblin Diaphragm Compressors
• Able to run automatically
will meet your specification…without exception.
• Available in multiple formats such as
HTML, spreadsheets such as XML or flat
Gas and Air Systems, Inc.
1304 Whitaker St. • Hellertown, PA 18055
files.
Toll free: 1 (888) 8 GASAIR • Ph: (610) 838 9625 Most companies separate the control sys-
Fax: (610) 838 9650 • info@gasair.net tem from the IT business LAN by a firewall
www.gasair.net of some type. Most ALMS packages will be
on the control-system side of the firewall.
Select 174 at www.HydrocarbonProcessing.com/RS
86
Select 78 at www.HydrocarbonProcessing.com/RS
AD: www.graficadueprint.com
© 2010 Costacurta S.p.A.-VICO

SINCE 1921...
AND WE
STILL LOVE IT

For more than eighty years, we at Costacurta have been


constantly and resolutely committed to the development
and manufacture of special steel wire and plate
components used in many different industrial processes.
Every day at Costacurta, we work to improve the quality
of our products and services and the safety of all our
collaborators, paying ever-greater attention to the
protection of the environment.
Within the wide range of Costacurta products you will
also find some, described below, that are used specifically
in the oil, petrochemical and chemical industries:
- RADIAL FLOW AND DOWN FLOW REACTOR INTERNALS;
- GAS-LIQUID AND LIQUID-LIQUID SEPARATORS;
- ARMOURING OF REFRACTORY, ANTI-ABRASIVE AND
ANTI-CORROSIVE LININGS.
For more information visit our website or contact the
division 'C' components for the oil, petrochemical
and chemical industries at tcrc@costacurta.it.
Radial Flow and Down Flow reactor internals

Costacurta S.p.A.-VICO Management systems


www.costacurta.it
via Grazioli, 30 certified by LRQA:
20161 Milano, Italy ISO 9001:2008
tel. +39 02.66.20.20.66 ISO 14001:2004
fax: +39 02.66.20.20.99 OHSAS 18001:2007
Select 84 at www.HydrocarbonProcessing.com/RS
SAFETY

BORSIG
Reports are likely to be required on the busi- been identified, alarms for the affected tags
ness LAN for ease of reporting to manage- will be rationalized for each state. The state-
ment. Some method for transporting reports based alarm package will implement the
across the firewall will be beneficial. different alarms as the different states occur.
Many companies use key performance This can be triggered by a change in a tag
indicators (KPIs) to measure performance. value, an operator action or a calculation. A
KPIs for the alarm system will likely be good state-based alarm package will incor-
developed as a part of the alarm philosophy. porate a method of performing a calculation
The reporting package should have some to control the transitions between states.
means of generating reports that match the • Alarm flood suppression—despite all
KPI requirements; otherwise, the site will efforts to create an optimum alarm param-
need to process data to generate the required eter set, alarm floods may still happen,
KPI. For example, import XML files into especially during an upset. An alarm-flood
Excel and calculate the KPI data there. suppression package can help in this situ-
ation by detecting an abnormal situation
Advanced features. The basic features and adjusting the alarm system by either
listed previously can be used to improve modifying alarm priorities/settings or by
alarm-system performance by focusing on suppressing the alarms. The flood trigger
remedial activities, developing an optimal must be detectable and the alarms to be
set of alarms, and providing reporting facil- included must be known. The package
ities to support ongoing improvement pro- must also be able to reverse the changes
cesses. These features assume that the alarm appropriately. It should be noted that it
system is static. There are features that are takes time for the event to be detected and
more real-time, where the alarm system is the alarm changes made. There may well
modified based on input from the system, be an initial alarm burst, but the alarm rate
or on predefined operator input. This is a will fall away very quickly, which reduces
broad field so only a few concepts can be demands for operator attention.
briefly discussed. These packages must be aware of each
• Audit and enforcement—Without
attention, alarm systems will degrade and
other and work together. For example,
the audit and enforcement package must
Leading
drift from the settings determined during
alarm rationalization and implemented
be aware of changes made by the alarm-
shelving package and the state-based alarm
Technology for
by MOC processes. Inappropriate change package to prevent errors in reporting and Innovative
comes from many sources and is, unfor- potentially enforcing the wrong alarm val-
tunately, common. An alarm audit is the ues. And there you have it—a brief discus- Solutions
periodic comparison of the alarm-system sion of features that, in my opinion, are in
settings with the values implemented. Lists an ALMS. Hopefully this will provide some Quench Coolers
of discrepancies can be reported as needed. food for thought if the need should arise to Process Gas Waste Heat
Also, the ALMS can correct discrepancies evaluate an ALMS. HP Recovery Systems
for ammonia, methanol, hydrogen, gas-to-liquid,
by implementing the correct value in the coal gasification and direct reduction plants in
BIBLIOGRAPHY
control system. iron metallurgy, waste heat boilers downstream
The Equipment and Materials Users’ Association of the partial oxidation of oil and natural gas
• Alarm shelving—Alarm-system mal- Publication No. 191, Alarm Systems: A Guide to
functions will occur at the most incon- Design, Management and Procurement, Scraped Surface Exchangers
venient times. Alarm shelving allows for www.eemua.org. Reciprocating Compressors
the temporary alarm suppression in a con- ANSI/ISA—18.2-2009, Management of Alarm for Process Gases
Systems for the Process Industries, www.isa.org.
trolled fashion. Care must be used with this Hollifield and Habibi, The Alarm Management Centrifugal Compressors
feature since an alarm that is shelved forever Handbook, www.pas.com. for Process Gases
is no alarm. To prevent this, alarm shelving
Compressor Valves
should have the following characteristics:
o Allow shelving of only one alarm Jerry Gooch has over 30 years of
experience in the oil and gas industry. Other BORSIG Products:
at a time, not all alarms for a tag. The majority of this experience has Membrane Technology, Boiler and Power Plant
o Provide security for access. been in process control in refineries Technology, Industrial and Power Plant Services
o Provide control over the maxi- in the US and the Middle East with a
mum shelving time allowed. notable exception as the controls coordinator for the new
o Record the identity of the person build liquefied natural gas ships in Japan. Mr. Gooch was BORSIG GROUP
employed as an alarm management consultant for several
shelving the alarm. Egellsstrasse 21
years, executing alarm management projects at refining,
• State-based alarms— Since some D-13507 Berlin/Germany
petrochemical and power plants in the US, Europe and
the Middle East. He worked closely with plant managers,
Phone: +49 (30) 4301-01
equipment can exist in multiple states (such Fax: +49 (30) 4301-2236
engineers and operators and was a strong proponent of
as out-of-service, half rate or alternative feed a comprehensive operator effectiveness program’s value E-mail: info@borsig.de
stock), different alarms may apply at dif- and alarm management’s key role in this program. Mr. www.borsig.de
ferent times. Once the different states have Gooch is currently employed at KBR in Houston.
Select 175 at www.HydrocarbonProcessing.com/RS
LOOP CONTROL

Best practices for PID


by Gregory K. McMillan and P. Hunter Vegas

PROPORTIONAL-INTEGRAL-DERIVATIVE (PID) control is used in more than 99% of the


loops for chemical, pharmaceutical, and food and beverage production. PID has proven
to be capable of the best load rejection by using the best tuning and the extensive flex-
ibility of functionality offered by the PID structure and options, most notably external-
reset feedback. Bohl and McAvoy enlightened us about it in a 1976 landmark paper,
“Linear Feedback vs. Time Optimal Control, II. The Regulator Problem” (Industrial & En-
gineering Chemistry, Process Design and Development, Vol. 15, No. 1, 1976, p. 30-33).
The opening challenge with PID control is recognizing the effect of PID form, struc-
ture and tuning units. Going from proportional band in percent to a dimensionless PID
gain, and from a reset in repeats per minute to seconds, are recognizable factors to
address, but are sometimes overlooked. Less understood is how to convert tuning set-
tings to the ISA Standard Form from the Series (Real) Form in analog control and early
DCS systems, and from the Parallel (Independent) Form in the control literature, con-
verting integral and derivative gains to reset and rate times.

PID BASICS
1. Measure each flow, inventory (e.g., level or weight and pressure), every process variable for safe
operation and environmental protection, and each indicator of process efficiency and capacity
(e.g., composition, quality, pH, and temperature) with sufficient accuracy (particularly least drift
and best repeatability), speed and rangeability.
2. Manipulate each flow by a control valve or variable-frequency drive (VFD) with the least dead-
band (e.g., < 0.4% backlash) and sufficient linearity (e.g., < 5:1 gain change), resolution (e.g.,
< 0.2% stiction), speed (e.g., < 2-sec., 86% response time) and rangeability (e.g., > 40:1).
3. Make sure every component in the process, whether a reactant, inert, byproduct or product, is
accounted for by field or scheduled lab measurements, and is controlled to ensure exit or con-
sumption by reaction with no continual accumulation.
4. Pair controlled variables (e.g., composition and temperature) with manipulated variables (e.g.,
flows) that have the largest effect as seen in Relative Gain Array (RGA).
5. If the RGA assessment of choices doesn't clearly favor a particular pairing, choose the manipu-
lated and controlled variable pair with the smallest deadtime-to-time constant ratio.
6. Use flow feedforward for gas pressure control with linearization of valve characteristics.
7. Use flow ratio control for composition, level and pH control, where there's a secondary flow con-
troller and a ratio controller (RC) with a setpoint and bias that both can both be remotely set or
manually adjusted by the operator. If the RC block doesn't have a remotely settable bias, the RC
output becomes the input to a bias and gain block.
continued on p.26

22 • DECEMBER 2018 www.controlglobal.com DECEMBER 2018 • 23


Measurably drive
Measurably drive

Safely
Safely

Turn industrial automation into the profit engine of your business.


Turn industrial automation into the profit engine of your business.

A
A control
control system
system that
that measurably
measurably improves
improves operational
operational profitability?
profitability? Now
Now that
that is
is aa bold
bold idea.
idea.
Only the
Only the EcoStruxure
EcoStruxure Foxboro
Foxboro DCS
DCS provides
provides measurable
measurable operational
operational profitability
profitability improvements
improvements
and a
and a future-proof
future-proof architecture
architecture to
to enable
enable 100%
100% ROI
ROI in
in less
less than
than one
one year.
year. Together
Together with
with our
our
IIoT-ready apps, analytics,and services; edge control; and connected products – Schneider
Electric can optimize every asset in your enterprise and empower you to control operational
efficiency, reliability, safety, and profitability together – in real time.

#WhatsYourBoldIdea
#WhatsYourBoldIdea

schneider-electric.com/foxboro
schneider-electric.com/foxboro

Ignite your profit engine today by downloading our whitepaper.


Ignite your profit engine today by downloading our whitepaper.

© 2018 Schneider Electric. All Rights Reserved. Schneider Electric | Life Is On is a trademark
and the property of Schneider Electric SE, its subsidiaries, and affiliated companies. • 998-20278420_GMA-US
© 2018 Schneider Electric. All Rights Reserved. Schneider Electric | Life Is On is a trademark
and the property of Schneider Electric SE, its subsidiaries, and affiliated companies. • 998-20278420_GMA-US
Your Global Automation Partner
Delay Lag Gain
θd τL Кd
∆DV
Load upset
Secondary Secondary Primary Primary
Delay Lag Gain delay lag delay lag
θV τV КV θS τS θP τP КP
∆FV
Valve or VFD Process ∆PV

Local
% ∆%CO setpoint Кm = 100%/span
%SP
PID КC Ti Td ½ of wireless default update rate
% ∆%PV (∆CV)
Delay Lag Gain Lag Delay Lag
τC2 θC τC1 Кm τm2 θm2 τm1 θm1
Lag
Controller Measurement Delay

MAJOR SOURCES OF LOOP DYNAMICS


Figure 1: For a first-order approximation, the total loop deadtime θ0 ≈ θV + θS + θP + θm1 +
θm2 + θC + Y*τV + Y*τS + Y*τm1 + Y*τm2 + Y*τC1 + Y*τC2. The Y fraction of small lag that is
equivalent to deadtime is a logarithmic function of the ratio of the smallest to largest lag (Y =
0.28, 0.88 for ratios of 1.0 and 0.01, respectively). КV is the slope of the installed flow charac-
teristic, and τ0 is the largest lag in the loop, hopefully τP. For self-regulating processes, К0 =
КV * Кd * Кm; for near-integrating processes, Кi = КV * (КP/τP) * Кm.

Especially noteworthy is that in the Series open-loop gain is the product of the valve or Reduce Costs – One
Form, the derivative time (rate time) could be variable-frequency drive (VFD) gain, process
Sensor Detects
set as large as the integral time (reset time). gain and measurement gain. The result-
Some older tuning methods even suggested ing gain is dimensionless for self-regulating all Metals
this. Interaction between these modes in processes and has units of 1/sec for integrat-
the time domain by Series Form would in- ing processes. The open-loop time constant Detect all metals at the same
herently prevent oscillations by effectively is the largest time constant in the loop, and range with inductive sensors
reducing integral and proportional action hopefully in the process to slow down distur- from Turck – no position
thru interaction factors. When using the ISA bances on the process input. Unfortunately adjustment required. These
Standard Form, the rate time has to be set for flow, liquid pressure and surge control, non-contact, durable inductive
less than one-fourth the reset time to prevent the largest time constant is in the automation sensors help you reduce the
oscillations. Many users have made mistakes system, slowing down the ability to see and number of sensors needed
in system upgrades by not paying attention correct for disturbances. for detecting the position or
to the changes in form and units by the even The secondary time constant is the sec-
presence of metal parts. Plus,
the same system supplier. ond largest time constant in the system,
our IP68-rated versions stand
often in either heat transfer surfaces or the
up to challenging washdown
Literature can’t always automation system. The total loop deadtime
environments.
be taken literally is the sum of all the deadtimes and the frac-
The literature is also misleading by nearly tion of all the small time constants creating
always citing a process deadtime, process equivalent deadtime. To better communi-
time constant and process gain when the ac- cate, realize the implications of dynamics,
tual dynamics depend on what's in the auto- and achieve the best PID, see the Control
mation system (Figure 1). PID tuning needs Talk blog post, “Understanding terminol-
β Gain
to use the open-loop gain, open-loop time ogy to advance yourself and the automation
constant (primary time
+ constant), secondary profession” (www.controlglobal.com/blogs/
*P = (β – 1) * Gain * %SP
* total∆loop deadtime.
time constant and * The controltalkblog/understanding-terminology- 1-800-544-7769
-
www.turck.us
%SP
www.controlglobal.com
For reverse action, For zero error,
error = %SP - %PV Out1 = 0
LOOP CONTROL

to-advance-yourself-and-the-automation-
PID BASICS, continued from p.22
profession)
8. Ratio control (RC) details: Another major point of confusion is lack of
a. Connect BKCAL_OUT from a manipulated RC setpoint or bias to BKCAL_IN recognition that nearly all disturbances are on
of the PID, correcting the RC to ensure a bumpless transfer to the remote the process input and not the process output,
setting of the RC setpoint or bias. as is commonly depicted in the control litera-
b. The RC input is the leader flow (e.g., largest feed). The RC output is the cas- ture. Also, except for flow and liquid pressure
cade setpoint of the secondary flow controller, or is the input to a bias and control, the response is near-integrating or true
gain station whose output becomes the cascade setpoint of the secondary integrating, requiring integrating process tun-
flow controller. ing rules and an overshoot by PID output of its
c. F or vessels and columns, the primary controller corrects the RC bias. final resting value that's the output after com-
d. For inline plug flow systems, the primary controller corrects the RC setpoint. pletion of the response to a load or setpoint
e. For reactants, there may be several flow loops ratioed to the leader flow (e.g., change. What's in the literature are self-regulat-
primary reactant flow). To eliminate temporary stoichiometric imbalances ing processes with a process time constant-to-
from changes in production rate, put a setpoint filter with a filter time on each deadtime ratio for dynamics that rarely gets be-
flow loop just large enough for a smooth response, so reactant feed flows low 0.25 or above 4, leading to Internal Model
move in concert. Control. While these dynamics are infrequent
9. For override control of constraints (e.g., maximum pressure, temperature, or in chemical plants except for flow loops, they're
throttle valve position), use external-reset feedback to intelligently prevent applicable to pulp and paper and mining plants
unwanted integral action; tune each PID gain to provide the correct point of due to a lack of back mixing.
takeover (selection) of the override PID relative to its setpoint; historize the You can convert back and forth between
total time each PID is selected; and capture the overshoot of the setpoint. self-regulating and integrating process dynam-
10. Use cascade control to: ics by realizing that open-loop, near integrating
a. Provide rapid correction of secondary upsets and nonlinearities (e.g., secondary process gain is simply the open-loop self-reg-
flow loop correction for pressure changes and installed flow characteristic). ulating process gain divided by the open-loop
b. Enable flow ratio control by manipulating a flow PID setpoint instead of a valve. time constant (Figure 1).
c. Give a relatively constant and easily estimated open-loop process gain from Integrating process tuning rules are de-
controller output (CO) scale needed to prevent violating the low PID gain limit for signed to provide the best disturbance re-
processes with a near-integrating, true integrating or runaway response. jection. This can be tested by momentarily
d. Convert the secondary time constant from a detrimental term in the pri- putting the PID in manual and making the
mary loop creating deadtime to a beneficial term as the largest time con- largest step change in PID output that the
stant in the secondary loop, thus decreasing the deadtime-to-time constant operator is comfortable with (e.g., 5-10%).
ratio of both loops, and offering tighter control. Changes less than 1% typically show a much
e. Reduce the deadtime and hence the ultimate period of the primary PID, slower and possibly no response due to ac-
enabling better handling of disturbances originating in the primary loop by tuator and positioner sensitivity limit, as well
more aggressive tuning. as valve backlash and stiction.
11. Match the PID output limits and engineering units to the setpoint limits and
engineering units of the secondary loop. Set any anti-reset windup (ARW) Feedforward and ratio control
limits to match the output limits, except for special cases where you set the are underused
ARW limits inside the output limits when the PID must move quickly through Nearly all control loops end up manipulat-
stiction at a low limit, or quickly recover from a high limit that's an adverse ing a flow either directly by cascade control,
operating condition. where a primary process controller manipu-
12. Use valve position control (VPC) to maximize feed rate, waste fuel and waste lates a secondary controller setpoint, or by
reagent use, and minimize energy usage by minimizing compressor pressure directly positioning a control valve. Here,
and maximizing the refrigeration unit or cooling tower temperature by forcing we consider changes in speed as effectively
affected control valves (e.g., feed, waster fuel or reagent, coolant, steam and causing changes in flow even in sheet lines.
vent valves) to the maximum throttle position. Nearly all fast disturbances are changes in
13. Use positive-feedback implementation of integral action (Figure 2) for the ISA flow, and decoupling signals from interacting
Standard Form to provide true external-reset feedback (e.g., dynamic reset loops are changes in manipulated flow. The
limit). needed end result is a ratio of the manipu-
continued on p.28 lated flow or speed to a leader flow or speed
that is a disturbance from an uncontrolled

26 • DECEMBER 2018 www.controlglobal.com


Your Global Automation Partner

MORE RESOURCES
To really dig into what PID can do, get the book, Tuning and Control Loop Performance,
Fourth Edition (www.momentumpress.net/books/tuning-and-control-loop-performance-
fourth-edition). See the following for a greater appreciation of what you should know
about PID control:
• www.controlglobal.com/articles/2017/the-greatest-source-of-process-control-knowledge
• www.controlglobal.com/articles/2017/common-automation-myths-debunked
• www.controlglobal.com/blogs/controltalkblog/solutions-to-prevent-harmful-feedforwards
• www.controlglobal.com/blogs/controltalkblog/uncommon-knowledge-for-achieving-
best-feedforward-and-ratio-control
• www.controlglobal.com/blogs/controltalkblog/deadtime-dominance-sources-conse-
quences-and-solutions
• www.controlglobal.com/blogs/controltalkblog/pid-options-and-solutions-part-1
• www.controlglobal.com/blogs/controltalkblog/pid-options-and-solutions-parts-2-and-3

(wild) flow, a manipulated flow by another cesses, particularly distillation columns, are Reduce PLC Costs
loop, or a deliberate change in production started up on ratio control. The ratio is cor-
with Multi-protocol
rate or composition. rected by a bias to the secondary controller
If there's no secondary controller, flow setpoint for volumes with some mixing, such On-Machine I/O
feedforward is used primarily via a feedfor- as crystallizers, columns, evaporators, neu-
ward summer. The most common example tralizers and reactors. For sheet lines and Expand your communication
is steam header letdown pressure control, extruders, the ratio setpoint is corrected. capabilities and reduce costs
where feedforward signals from steam users Dynamic compensation must be applied with innovative multi-protocol
and suppliers and decoupling signals from to a leader flow before it becomes a feed- on-machine I/O. Whether you
other header letdown valves are summed forward signal or ratio controller input flow. are using one communication
together in a feedforward summer. Signal To make sure a change in manipulated flow protocol or several, Turck
characterization is used where there are arrives in the process at the same place at ensures you get flexible,
not flow measurements to convert a per- the same time as a change in leader flow, a future-proof fieldbus solutions.
cent valve signal to a percent valve flow per deadtime and lead/lag (L/L) block is used. Our vast range of rugged on-
installed flow characteristics. For compres- If the correction arrives too soon or too late, machine I/O streamlines your
sor surge and pressure control, feedforward inverse response and sequel disturbance processes and is ideal for out of
summers are used for decoupling between are created, respectively. Unfortunately, tun- the cabinet applications.
headers and disturbances from downstream ing software packages may not identify the
users, since the controller outputs go directly deadtime and L/L settings. The block dead-
to valves and vanes. Secondary flow control- time for dynamic compensation is the dead-
lers would be too slow in these cases. time in the disturbance variable path minus
Most process equipment involving liquids the deadtime in the manipulated variable
can benefit from secondary flow controllers. path. The L/L block lead time is the lag time
Here, ratio control is used to achieve and in the manipulated variable path, and the
correct as needed the ratios of flows seen L/L lag time is the lag time in the disturbance
on a process flow diagram (PFD). Many pro- path. The lag time should be at least one- 1-800-544-7769
www.turck.us
www.controlglobal.com DECEMBER 2018 • 27
LOOP CONTROL

fourth the lead time to prevent noise. Model


PID BASICS, continued from p.26 predictive control (MPC) does this identifica-
14. U se external-reset feedback with setpoint rate limits to provide directional move sup- tion and correction for the user, which, along
pression to enable a VPC to provide a gradual, smooth optimization and fast getaway for with ability to avoid tuning override control-
abnormal conditions, and to prevent unnecessary crossings of the split-range point. lers, are the principal reasons why MPC
15. Use external-reset feedback to stop oscillations from deadband and stiction, a slow replaces PID for even a small applications
secondary loop, or slow control valve, and to provide enhanced PID action to prevent where a PID could suffice (e.g., one decou-
oscillations for increases in analyzer cycle time. pler, one feedforward and one constraint).
16. Use signal characterization of the controlled variable for pH titration curves and of the After good load disturbance rejection is
manipulated variable for installed flow characteristics, where the changes in process achieved, good setpoint response is possible
gain or valve gain, respectively, from changes in slope are greater than a factor of five. by using a filter lag equal to the reset time, or
17. Minimize total loop deadtime by faster and more precise measurements and valves, a structure with proportional and derivative
shorter transportation delays, faster fluid velocity and better mixing. action on the process variable and Integral
18. M inimize process noise by a sensor location that's less affected by cross-sectional action on error (PD on PV and I on E). If you
changes in velocity, phases, temperature and concentration. want a faster approach to setpoint, you can
19. Use middle-signal selection to prevent adverse reactions to a single sensor failure use a L/L instead of a filter on the setpoint
of any type, decrease reaction to noise or a slow sensor, reduce unnecessary main- with the L/L lag time equal to reset time, and
tenance, increase reliability and accuracy, improve diagnostics minimize lifecycle the L/L lead time equal to one fourth the lag
costs, and maximize onstream time and product quality. time, or a two-degrees-of-freedom (2DOF)
20. Choose loop objectives and choose the PID structure in the ISA Standard Form by structure with the setpoint weights for propor-
turning off modes and by setting setpoint weights and tuning the PID accordingly. tional and derivative action set equal to 0.5
Since there's is no interaction in the time domain like there is in the Series Form to and 0.25, respectively. Most of the literature
prevent derivative action from exceeding integral action, the rate time must not ex- concentrates on setpoint response, ignoring
ceed one-fourth the reset time. load response and advantages of lead/lag
21. Employ procedure automation and state-based control to utilize the best operator and and structure options.
process knowledge to eliminate any operator manual actions during startup, transi-
tions and recovery from abnormal situations, such as equipment and instrument fail- Remember external-reset feedback
ures or unusually bad disturbances. The other thing most users are not aware
22. Compute a future value of PV by passing the PV through a deadtime block and adding of is the incredible capability offered by
to the block input the change in PV during the block deadtime, that is, the block in- external-reset feedback (e.g., dynamic re-
put minus the block output. Block deadtime is greater than loop deadtime for a good set limit) to:
signal-to-noise ratio. Use the future PV value for a faster startup and batch cycle • Suppress oscillations from a slow sec-
time, where the manipulated flow is initially maximized and then set to its final rest- ondary loop, slow control valve or VFD,
ing value when the future value is projected to reach a setpoint or batch endpoint. and deadband and resolution limits.
23. To prevent snowballing buildup of recovered and recycled component concentration, • Provide directional move suppression
ensure there's a flow controller with a fixed setpoint for a given production rate some- to prevent unnecessary crossings of
where in the flow path from the discharge back as a feed input of the affected equip- split-range points; enable gradual opti-
ment (e.g., centrifuge, column, crystallizer, evaporator, reactor). mization and fast getaway by a VPC, a
24. Performance metrics should be put online and historized for key unit operations and fast-opening and slow-closing vent, or
the production unit. The ratio of total raw material or utility used to total product pro- recycle valve for surge control; and mini-
duced over a representative time (e.g., last 12 hours or last batch) gives a measure mization of upsets to other loops.
of process efficiency. The total product produced over this time gives a measure of • Achieve deadtime compensation as
process capacity. The total value of product in dollars in this time frame minus the good as a Smith Predictor or MPC with-
total cost of raw materials (e.g., reactants, reagents, additives and feeds from other out having to know the open-loop gain
units), utilities (e.g., steam, coolant and electricity) and fixed costs (e.g., staff and or time constant, or needing to provide
depreciation) is the profit in dollars. Most important is the trend and not the accuracy a special operator interface. Deadtime
of prices and costs. compensation is achieved by simply in-
25. Use a virtual plant (digital twin) for flexible and fast exploring, discovering, prototyp- serting a deadtime block in the external-
ing, testing, justifying, deploying, testing, training, commissioning, maintaining, trou- reset feedback path and tuning the PID
bleshooting, auditing and continuous improvement, showing the “before” and “after” much more aggressively (e.g., reset time
benefits of solutions from online metrics. can be decreased by an order of magni-
tude if deadtime is accurately updated).

28 • DECEMBER 2018 www.controlglobal.com


Your Global Automation Partner

β Gain
+ *P = (β – 1) * Gain * %SP
* ∆ *
-

%SP
For reverse action, For zero error,
error = %SP - %PV Out1 = 0
+ P Out1 PI
Filter ∆ * Σ
Filter time =
Σ %CO
- Positive I Out2 reset time D
feedback Bias
*P
γ Rate Switch position
time Filter ∆ for external-reset
feedback
+
* ∆ * * Filter Derivative
- ERF
%PV Filter Filter time =
α * rate time

ISA STANDARD FORM WITH TRUE EXTERNAL-RESET FEEDBACK


Figure 2: All signals are percent-of-scale in the PID algorithm but inputs and outputs are in
engineering units. For structures with no P action, gain is zero for the proportional mode. Gain
is one for the integral mode, and equal to the PID block gain setting for derivative mode. Bias
is used as input to the reset time filter block when there is no integral action. Bias is the PID
output when the error is zero, and is filtered by the reset time whose best setting is reduced to
be about the deadtime. External-reset feedback (ERF) is, for example, secondary loop process
variable (%PVs) or fast valve readback.

Figure 2 shows the only known time close to one or slightly higher. Negative
domain block diagram that details the ISA relative gains are disastrous. Often, the rela-
Standard Form with the ability to achieve tive gain array can be simplified to show Industrial Ethernet
eight different structures and true external- the relative gains for the four pairs possible Cables – Your Path to
reset feedback with the positive feedback between two controlled variables and two
implementation of integral action. manipulated variables (2 x 2). Smart Manufacturing
Relative gain analysis is a powerful tech- If you want a comprehensive, concise
Smart machines need higher
nique for accessing the type and degree of view of how to achieve the best PID con-
bandwidth to process the
interaction. The relative gain for a given loop trol, and gain an excellent understanding of
real-time data that optimizes
is its open-loop steady state gain with the everything else needed for a successful au-
your manufacturing processes.
other loops open divided by its open-loop tomation project, look for the McGraw-Hill
Turck’s industrial Ethernet
steady state gain with the other loops closed. handbook Process/Industrial Instruments
cables meet those needs with
The given loop is open for the tests with the and Controls, Sixth Edition, due out early
rugged, flexible, and multi-
other loops open and then closed, to show in 2019. The handbook covers the design,
protocol solutions. With many
response without and with interaction, re- installation, calibration, commissioning and
options for customization and
spectively. A loop is considered open if the maintenance of every part of an automa-
short lead times, Turck is your
mode is manual or remote output. tion system, concluding with a list of best
ideal partner for more cost-
For integrating processes, the process practices for each of its 100 sections.
effective networks.
variable is translated to a rate of change, Meanwhile, the sidebar provides best
so a steady ramp rate gives a steady state. practices excerpted from the handbook’s
The relative gain is dimensionless, and thus PID Basics section.
doesn't depend on the engineering units of
the loops involved. The relative gain doesn't Gregory K. McMillan, Control columnist and
change when a flow ratio rather than a flow Hall of Fame member, can be reached at Greg.
is manipulated. Operating point nonlineari- McMillan@emerson.com, and P. Hunter Ve-
ties will affect the analysis but not changes gas, engineering manager, Wunderlich-Malec
in time constants and deadtimes. Ideally, Engineering, can be reached at hunter.vegas@
pairing of loops should have a relative gain wmeng.com. 1-800-544-7769
www.turck.us
www.controlglobal.com DECEMBER 2018 • 29
Focus

Temperature measurement
United Electric Controls
HART-compatible transmitter closed-loop (PID) and simple on-off
eases temperature monitoring temperature control, in both heating
Industrial sensors monitor tempera- and cooling applications. This unit
ture or pressure abnormalities by has a thermoelectric heating and
comparing the process conditions cooling element that is capable of
with pre-programmed setpoints in 5–50°C setpoint, and a Type K ther-
a PLC or DCS controller. The HART- mocouple for temperature readings.
compatible One Series 1XTXSW The unit comes with panel-mounted
transmitter line (photo) is said to be USB and Ethernet connectivity, an
the first to integrate 4–20-mA out- alarm indicator, a 4–20-mA remote
put and two solid-state program- setpoint potentiometer, a push-
mable relays (compatible with HART button digital input, and more. Its
7) for monitoring temperature or 32-bit, 120-MHz ARM processor
pressure in safety, alarm and emer- provides full PID control process
gency-shutdown applications. Typi- with auto-tuning and a fuzzy-logic-
cal electromechanical switches are based, adaptive control algorithm.
blind and cannot alert workers that According to the company, the unit
something is amiss with the device, automatically adjusts and optimizes
says the company. With this device, the control-loop parameters based
however, users deploying a HART on external environmental or control-
communications networks can add system deviations. A comprehensive
switches to the field assets used in set of alarm functions may be used
their predictive-maintenance strat- to trigger output signals, or modify
egy and reduce routine inspections the display colors for conditions
and unplanned shutdowns. Combin- that are above or below a thresh-
ing HART and smart diagnostics in old value, or in or out of the accept-
one device, workers can manage all able range. Setup is easy, says the
of their instrumentation assets, in- company, thanks to an integrated
cluding switches, using a centralized four-button keypad and a structured
asset-management solution. A large, menu system that eases naviga-
back-lit display provides process val- tion to only those parameters appli-
ues and setpoint programming. The cable to the selected configuration
One Series 1XTXSW hybrid transmit- step. — Omega Engineering, Inc.,
ter switch effectively replaces a gage, Stamford, Conn.
switch and transmitter, requiring only www.omega.com
one connection to the process. This
helps to improve reliability while re- Measure temperature reliably
ducing lifecycle costs, and allows for in high-voltage systems
health and switch-status notifications To ensure optimal operational safety
at about half the cost of a traditional for power plants and grids, critical
process-control transmitter, says the factors, such as hot spots inside
manufacturer. The new One Series iX high-voltage transformers, power-
line has worldwide hazardous loca- factor-correction capacitors and al-
tion approvals for Class I, Divisions 1 ternators are monitored. Similarly,
Omega Engineering and 2 (Zones 0, 1 and 2). — United temperature is routinely measured on
Electric Controls, Watertown, Mass. high-voltage distribution power lines,
www.ueonline.com and in gas-isolated power breakers
and power-factor-adjusted capaci-
PID control simulator supports tors. The FotempTrafo is a fiber-op-
temperature tracking tic thermometer that is available with
The Platinum Series controller dem- one to eight measurement channels.
onstration and training kit provides a Its compact design and height-ad-
PID control simulator (photo) that is a justable DIN-rail clip allow for easy
fully integrated temperature-control installation in a cabinet. A wide selec-
system. It is suitable for use in both tion of interfaces (RS-232, RS-485,

Note: For more information, circle the 3-digit number on p. 66, or use the website designation.
26 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016
Milwaukee Tool
Profibus and Modbus) makes com- up to 20 measured values per sec-
munication easy. A fast measurement ond. At the same time, the T15 fulfills
speed of 250 ms per channel allows high standards of safety, for example,
the direct detection of overloads. Its in accordance with NAMUR recom-
measurement range is from –200 to mendations for EMC protection, sig-
300°C, with an accuracy of ±0.2K, nalling and sensor-break monitoring.
says the company, which notes that It is said to be the first transmitter
its use of gallium arsenide (GaAs) in to be certified to the new EMC pro-
the sensor tip eliminates the need for tection standard, DIN EN 61326-2-
recalibration throughout the product 3:2013. The T15 also has ATEX and
life. The probe sensor is completely IECEx approvals for use in hazardous
non-conductive, and the fiber-optic areas. When used with the WIKA-
sensors offer complete immunity soft-TT software, the transmitter can
against radio-frequency interference be programmed intuitively. Both
(RFI), electromagnetic interference head-mounted and rail-mounted ver-
(EMI), nuclear magnetic resonance sions are available. — WIKA Alexan-
(NMR) and microwave radiation— der Wiegand SE & Co. KG, Klingen-
Optocon AG, Dresden, Germany berg, Germany
www.optocon.de www.wika.com

Compact thermal imager Distributed temperature sensor


provides sharp images keeps a watchful eye
The M12 7.8KP Thermal Imager The DTSX 3000 Distributed Tem-
(photo) is said to have the highest perature Sensor is a single device
pixel density in its class, and its ex- that is capable of detecting minute
clusive Dual Sense pixel technology temperature changes, and monitor- WIKA Alexander Wiegand SE

provides sharp definition of hot and ing the temperature distribution over
cold details within any given image. a long distance or across a wide
It is designed to support trouble- area. It can measure the temperature
shooting and predictive maintenance along fiber-optic cables up to 50 km
activities. It is particularly useful for in length (eight times the distance
determining thermal conditions asso- possible with the company’s previ-
ciated with hard-to-access systems. ous model), with a spatial resolution
Its Dual Sense technology allows the of one meter. It is well suited for plant
imager to individually optimize pixels, and infrastructure maintenance ap-
which helps to reduce or eliminate plications that require the monitoring
the blurring of hot and cold details in of temperatures over long distances
complex scenes, says the manufac- or wide areas. Specific applications
turer. When the device is integrated include temperature monitoring of
with the company’s Thermal Imager the outer walls of high-temperature
Report Software, users can analyze industrial furnaces, the detection
images and generate reports quickly of gas and liquid leaks in tanks and
and easily. Users can download im- other large production facilities, and
ages from the thermal imager with the detection of abnormal heat levels
its included 8-GB SD card or micro- in power lines and natural-gas-recov-
USB connection port. Every image ery processes. — Yokogawa Corp. of
capture also generates an image with America, Newnan, Ga.
the .png file format, allowing images www.yokogawa.com
to be emailed for convenience. —
Milwaukee Tool, Milwaukee, Wisc. Thermocouple wire resists
www.milwaukeetool.com oxidation at high temperatures
This company’s Type N thermocou-
This temperature transmitter is ple wire provides excellent repeat-
accurate and EMC-resistant ability and resistance to oxidation
The Model T15 is a new digital trans- at high temperatures (1,500°F and
mitter (photo) with analog output. De- above) and in applications where sul-
signed to process signals from resis- fur is present. The nickel-based ther-
tance sensors and potentiometers, it mocouple alloy resists oxidation at
is ready for operation in less than three higher temperatures, and is designed
seconds, according to the company, for applications with temperatures
and offers a high basic accuracy of from 200 to 2,000°F, such as high-
0.1% of span, at a measuring rate of temperature heat-treating applica-

CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016 27


Quintex GmbH

tions. — Watlow Electric Manufac- the SFRSS can be used to build a


turing Co., St. Louis, Mo. full wireless network using the best
www.watlow.com sensors for each sensing application
point. — Signal Fire Wireless Telem-
This electronic thermostat has etry, Hudson, Mass.
a flameproof enclosure www.signal-fire.com
A common challenge for many elec-
tronic controllers located in hazard- Device manages high-precision
ous areas is setting the temperature thermocouple measurements
and alarm setpoints. Adjustments The TC-32 high-precision, thermo-
normally require the power supply couple-measurement device (photo)
to be switched off before opening offers 32 thermocouple channels
the flameproof enclosure housing, plus 8 digital inputs and 32 digi-
which makes accurate, onsite set- tal outputs/alarms. For larger sys-
ting challenging, says the company. tems, users can add the TC-32-ESP
By contrast, the EXTC 100 (photo) module to double the number of
is a fully adjustable, remote-con- TC inputs (to 64), digital inputs (to
trolled, electronic controller that is 16), and digital outputs/alarms (to
housed in a flameproof (Ex-d type) 64). The TC-32 and TE-32-EXP are
enclosure. It can be fully controlled 19-in.-rack-mountable and feature
by means of an intrinsically safe, easy-to-connect, mini-jack connec-
remote-control infrared beam — tors for all thermocouple channels.
without having to open or turn off The device features USB and Eth-
the unit. All settings are stored and ernet interfaces, 24-bit resolution for
accessed securely, using a four- high-accuracy measurements, and
digit password. This hazardous-area includes a wide range of software
Signal Fire Wireless Telemetry
thermostat is available for electric support. It can provide digital alarm
trace heating circuits and other pro- notifications when a temperature
cesses. — Quintex GmbH, Lauda- exceeds programmed limits. —
Königshofen, Germany Measurement Computing Corp.,
www.quintex.eu Norton, Mass.
www.mccdaq.com
Device supports wireless
monitoring of field assets Multi-function loop calibrator
The Sentinal-RTD (photo) is the lat- uncovers hidden problems
est interface option that can be The portable PIE 850 Multifunction
added to this company’s Wireless Calibrator (photo) is a handheld instru-
Measurement Computing
Remote Sensing System, to sup- ment that combines eight single-func-
port two-, three- or four-wire RTD tion calibrators (including a milliamp
sensors. As part of the company’s current calibrator, a voltage calibra-
Class 1, Division 1 Sentinel node tor, a thermocouple calibrator, and
family, the Sentinel-RTD provides a more), legacy 10–50-mA capabilities,
direct connection to P100 2-, 3- or and advanced troubleshooting tools.
4-wire RTD sensors (and other types The PIE 850 is capable of diagnosing
are available upon request). The de- common loop-control problems that
vice has a long life with an intrinsi- are hard to find, says the company.
cally safe battery pack, making it Loop-diagnostic technology and the
especially well-suited to function reli- LoopScope feature show key loop
ably in demanding outdoor industrial parameters — such as current, volt-
environments (such as oil-and-gas age and resistance — at a glance. It
operations). The Signal Fire Remote is compatible with all common instru-
Sensing System (SFRSS) uses long- ments, smart transmitters and PLCs
range, mesh-networking technology, with 14 types of thermocouples and 9
and uses Sentinal (and other types types of RTD tempearature sensors,
of) battery-powered wireless notes to says the company. This lightweight
interface with the sensors. The nodes tool includes a backlit display for
extract and then communicate data use in dark environments, a protec-
to control devices via a gateway. The tive rubber boot and built-in stand, a
system has an open architecture, hands-free carrying case and all test
which allows users to integrate many leads.— Saelig Co., Fairport, N.Y.
types of sensors, including RTDs, to www.saelig.com n
Saelig monitor remote assets. In this way, Suzanne Shelley

28 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM JANUARY 2016


12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/19 1/5
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/19 2/5
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/19 3/5
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/19 4/5
12/28/2018 January 2019

https://view.imirus.com/8rLRGj2mK8G/document/13064/page/19 5/5
ANSWERS
INSTRUMENTATION, TUNING
Allan Kern, APC Performance LLC

Top 10 tuning tips


for control engineers
Best practices to follow to increase loop tuning performance and
reliability in a facility include increased efficiency, controller gain,
and being aware of loop interactions.

C
ontrol engineers often face ques- is usually much faster than the rest of the process.
tions and concerns about loop tuning. This is often the most salient consideration when
Often, there are no readily available tuning any loop—being timely in the context of the
answers, unless time is available for process, while minimizing the potential for con-
a step test or to research a loop’s past trol instability. Large, slow valves may need a lon-
performance record. ger reset; occasional loops may need an even smaller
By applying the following guidelines, a control gain, especially if they’re operating at very low valve
engineer can tell whether a loop is tuned appro- opening.
priately or if it may be a source of performance

2.
problems, and then make or recommend the Don’t waste time on level loops. Set the
appropriate changes. tuning to 1.0/response time/0.0 – and move
Note: Tuning is given in the format “gain/integral/ on. Response time, in level control context,
derivative,” where gain (or proportional control) is on is the approximate time it would take for the ves-
a percentage-of-span basis, integral (or reset) is in min- sel, beginning at setpoint (typically 50%), to com-
utes per repeat, and derivative is in minutes. The term pletely fill (or empty), in response to an average
“valve” may refer to any final control device. disturbance, in the absence of any control response.
Typical refining process response times are 1 to 3


minutes for boots, 5 to 15 minutes for drums, and
30 to 60 minutes (or longer) for tanks.
Level is an integrator and is often Where severe disturbances are possible, or
where potential consequences of overfill or under-
nonlinear, so that proportional control fill are severe, use a larger gain instead of a shorter
integral (excessive integral action on level loops is
the most common source of process oscillations).
provides the most reliable overall The level loop gain should rarely be more than 2.0.
This level tuning guideline applies whether or not


the level is cascaded to flow.
long-term performance. Level is an integrator and is often nonlinear, so
that proportional control provides the most reliable
overall long-term performance. There are several

1.
Don’t waste time on flow loops. Set the tun- common alternative strategies, such as gap gain, surge
ing to 0.25/0.25/0.0 and move on. Spending control tuning, and dynamic optimization of vessel
more time is usually pointless because process inventory under model-based control. However, none
gain will normally vary with valve position itself. of these approaches add value or are more reliable.
The relatively small gain—overall ideal flow control-

3.
ler gain is 1.0—reflects operation at low valve open- Don’t waste time on temperature, pres-
ing, where actual flow response is usually greatest. sure, composition, etc., unless they are
At higher valve openings, the short integral time will already cascaded to flow (or sometimes
make up the difference, typically bringing flow to pressure). If not cascaded, implementing a cascade
setpoint in a matter of minutes if not seconds, which is the next best step to take. The cascade will lin-

22 • November 2018 CONTROL ENGINEERING www.controleng.com


ANSWERS
INSTRUMENTATION, TUNING

earize the process response, thereby allowing opti- potentially changing process conditions, which
mal reliable tuning across the full operating range. can be expected to occur in most loops for many
Where a flow meter is not available, it may be pos- reasons. Set the integral equal to the process
sible to characterize the controller output based on response time that is determined by using a step
the valve characteristic; however, this technique test, process experience, or historical data—erring
carries several uncertainties and vulnerabilities on the long side. There is a significant long-term
and is a distant second-best practice. performance benefit to a slightly smaller gain and
longer integral than traditional error-minimiza-

4.
Invest time on pressure, tempera- tion or quarter-amplitude decay criteria—such as
ture and composition loops that are Zeigler-Nichols—will recommend, up to the point
cascaded to flow (or sometimes pres- of exceeding the process timeliness consideration.
sure). The cascade structure, in addition to lin-

6.
earizing the process response, allows loop Do not use derivative action. Deriva-
gain to be accurately determined from pro- tive is a way to reduce total error by using
cess data at two or more operating points. more aggressive gain and reset, and then
Exercise: Try this calculation on a common heater relying on derivative to put on the brakes. This
temperature/fuel gas flow cascade. (See link online.) is like speeding up and then braking hard as you
approach a stop sign, to get there slightly sooner.

5.
Set gain to roughly ½ to ¾ of the Derivative action is inappropriate in most indus-
observed gain to maintain long-term trial process control applications when observing
stable and reliable performance due to process speed limits, minimizing overshoot and
oscillation, and safeguarding process stability at all
times are paramount. Many modern tuning soft-
Loop tuning cycle of rework ware packages that routinely recommend non-zero
derivative settings are inexperienced. Model-based
multivariable control algorithms do the same thing
to achieve “error minimization” or “profit maximi-
zation,” but the resulting aggressive behavior, as in
single-loop control, usually needs to be backed out
to provide long-term reliable performance. This
caveat is in addition to the traditional concern
about large derivative bumps due to transmitter
noise or instability.

7.
Controller gain is heavily dependent on
span. For example, a pressure controller
with a span of 0 to 1,000 per square inch
gauge (PSIG) (using a modern smart transmit-
ter) will need a gain that is 10 times larger than
the same controller spanned for 900 to 1,000 PSIG
(as such loops were often designed in the past, to
have greater accuracy within the actual operating
region) to provide the same control response to
a given error. Without understanding this differ-
ence, there is reluctance to accept the larger, but
functionally equivalent, gain values. As a loose
Sites frequently raise the priority of loop tun- guideline, gain is typically 1.0 for every 100 to 200
ing efforts, and allocate significant financial units of span for large-span temperature and pres-
and human resources, to remedy conditions sure controllers.
such as loops in manual, frequent citing of

8.
loop tuning as a contributor to process upsets Be aware of loop interactions. When the
or trips, to take advantage of the latest most action of one loop strongly impacts other
promising tools and technologies, to “re-engi- loop(s), the user will need to decide which
neer” degraded multivariable controllers, etc. loop should be tuned normally and which one(s)
Unfortunately, important considerations from a reducing gain and increasing reset time. There is
process operation perspective are often over- often no practical reliable option to tune all loops
looked. Courtesy: APC Performance LLC in a set of interacting loops for timely response,

24 • November 2018 CONTROL ENGINEERING www.controleng.com


ANSWERS
INSTRUMENTATION, TUNING

due to the technical demands of doing so, using disturbance is well understood, when its model
techniques such as “decoupling,” and the reality (gain, response time, and deadtime) does not
of changing process gains, which undermines any change significantly in time for any reason, and
such schemes. The speed guideline for interacting where it is warranted to avoid hitting a hard pro-
loops has a similar basis to the traditional cascade cess limit or to capture large earnings or avoid
rule, except in reverse. large losses. When these criteria are not met,
For example, the secondary loop(s) should be especially if model dynamics (response time and
detuned to be at least three to five times slower deadtime) are not reliably known, feedforward
than the primary (high priority) loop. This funda- should be avoided. Every feedforward model
comes with engineering, reliability, and mainte-


nance costs, which the wholesale use of feedfor-
ward in model-based multivariable control has
Model-based control remains subject emphasized.
Successful loop tuning—defined as mini-
to most of the same tuning caveats as mizing rework, detuning, retuning, remodeling,
etc.—relies as much on an understanding of pro-
cess operation performance criteria as knowing
traditional loop tuning, such as the effects traditional single-loop tuning tools and methods
such as Ziegler-Nichols. When the process oper-
of variable process gains, the implications ation perspective is neglected, loop tuning often
is caught in a cycle of rework (See Figure), rather
than behaving as it should.
of interactions, discretion regarding Another important takeaway is that mod-
el-based control remains subject to most of the
same tuning caveats as traditional loop tuning,
feed forward, and leaving level controls such as the effects of variable process gains, the
implications of interactions, discretion regard-
in the base-layer with robust tuning to ing feedforward, and leaving level controls in the
base-layer with robust tuning to maximize pro-
cess reliability.


maximize process reliability. Originally, it was thought that model-based
control transcended most of these concerns, but
experience such as degraded performance, model
mental rule has been historically overlooked and maintenance, and short lifecycle, has revealed
ignored in multivariable control. This frequent- how these principles still apply.
ly results in unstable performance and ultimately Using these guidelines can help break the
contributes to a degraded performance unless all rework cycle, increase success rate, and lead to
the involved models remain highly accurate, which years of reliable maintenance-free process control
is rarely realistic. performance for most loops. ce

9.
Be bold with gain and cautious with reset Allan Kern is an APC consultant with APC Per-
when tight control is necessary. There is a formance LLC. Edited by Emily Guenther, associate
perception that too much gain may cause content manager, Control Engineering, CFE Media,
cycling, and that since reset is in units of time, eguenther@cfemedia.com.
a shorter setting might bring faster control. In
reality, proportional control action is instanta-
neous and too much reset, especially in combi-
nation with too little gain, is the most common
cause of process oscillations. So where tight-
M More
ANSWERS
KEYWORDS: Loop tuning, process optimization
er control is necessary, use more gain (up to the
Guidelines for loop tuning
limit of actual average process gain) and tune
Tips for loop tuning to avoid process issues.
integral more accurately (being careful not to
make it less than actual process response time). CONSIDER THIS
What issues have you come across with loop tuning?

10.
Understand when to use, and when ONLINE
not to use, feedforward. Feedforward Read more about tuning online at
can be advantageous when a major www.controleng.com.

26 • November 2018 CONTROL ENGINEERING www.controleng.com


Special Report Process/Plant Optimization
W. SCRIVEN and A. MARTIN, Valero Energy Corp.,
Pembroke refinery, Wales; and D. SEIVER, Valero
Energy Corp., Houston, Texas

Utilize an optimizer to blend gasoline directly to ships


A new control system and single-blend optimization system This method required the refinery to maintain considerable
make it possible to blend gasoline directly into tanker ships for tank capacity. Tanks are costly, they require maintenance, and
delivery, rather than only into tanks, thereby saving millions in safety and environmental regulations require instrumentation
capital and reducing product giveaway. to prevent leaking, overfilling, etc. Additionally, the tanks are
The 550-acre Pembroke refinery (FIG. 1) has been operating never completely emptied, which represents essentially frozen
since 1964. In addition to its terminal equipment, the facility has assets—inventory that is never shipped but stays on the books
eight berths for ships and more than 100 tanks of various sizes and is taxed every year. The average tank inventory is generally
with total capacity of 10.5 MMbbl. The complex can facilitate 10 considered to be captured cashflow that is not realizable until
crude ships per month. the tank is emptied or the assets sold.
Touchups, even if they result in shipped product that meets
Gasoline blending system. The refinery’s gasoline blending specifications exactly, are also expensive. They result in poor
system has a capacity of 2,000 m3/hr. The blending situation utilization of both equipment and human assets; they put an
for the refinery is very complex, if for no other reason than the
number of different components and grades of finished gaso-
line it produces. The produced gasoline must meet the differ-
ent specifications for multiple markets (US, Europe, etc.). Most
outgoing products go by tanker ship, with a smaller amount go-
ing by road tanker.
Refining is a highly competitive commodity industry that
yields fungible products with low margins, and a refinery’s blend-
ing operation can be considered its “cash register.” This is the last
chance to optimize the final saleable product, as well as the fi-
nal opportunity to achieve as close to product specifications as
possible. Any giveaway at blending—caused by shipping better-
than-grade specification product—is lost revenue and cancels
out the benefits from optimizing upstream unit process areas.
As illustrated in FIG. 2, a small reduction in giveaway yields
impressive results; for a typical refinery, blend optimization FIG. 1. The Pembroke refinery in Wales has eight berths for ships and
could deliver millions of dollars per year in bottom-line savings. more than 100 tanks of various sizes with total capacity of 10.5 MMbbl.
It is estimated that the industry-wide total costs of Reid vapor
pressure (RVP) and octane giveaway exceed $2 B/yr in the US Crude Unfinished/components Product blends Finished product
and several times that total worldwide. Capturing even a fraction
of that opportunity can offer a strategic refining advantage. 1.2
Refinery margin, price factor × crude

Optimum
blending $$$$
Traditional gasoline blending methods. The original blend-
ing system in the Pembroke refinery combined set volumes of 1.1
multiple gasoline component streams in a header to produce Crude mixing
penalty Suboptimum
each batch of finished gasoline, which was then routed into a set blending
of tanks. A sample was taken to the laboratory for analysis. Af- 1.0
ter the results were determined, the mixture would be “touched
up” to meet requirements, if necessary, and a certificate of qual-
Crude receiving Process units Blending Product shipping
ity/analysis would be issued. Often, the touchup of an off-spec offsites
blend caused giveaway by adding a buffer to avoid carrying out
a second touchup. When the ship arrived, the blended gasoline FIG. 2. Capturing even a fraction of blend optimization opportunity
can present a strategic refining advantage.
would be pumped aboard from multiple tanks.
Hydrocarbon Processing | JUNE 2016 45
Process/Plant Optimization

extra load/cost on the lab due to the retesting required; and, flows, etc., and calculates a recipe that is optimal for the blend at
if there is a problem and the blend testing comes out off-spec, any given moment to meet the optimization objectives. The op-
then shipments are delayed and incur potential demurrage timized recipe from the BOSS is then fed to the regulatory soft-
charges for holding up the ship. ware package, which calculates the appropriate flow setpoints
In 2011, a study was undertaken to find ways to improve the for the individual blend component control loops. For example,
blending process: a project to replace the existing blending ar- it takes a 41% alkylate recipe and translates that into a setpoint
rangement with one that would allow the blending of gasoline for the alkylate flow control loop. It performs other regulatory
directly to ship rather than solely to tankage. Such a system had level functions as well, such as starting and stopping pumps, etc.
the potential to save millions of dollars each year by reducing FIG. 3 shows schematically how the different parts fit together.
the number of tanks needed in gasoline service, as well as satisfy
the key performance indicators of lower average blend giveaway Consistent data helps obtain operator acceptance.
and the minimization of touchup blends. A critical success factor of the new system is the presentation of
consistent views to the operator. The design and implementa-
Upgrading the blending system. The refinery was already tion of such a system must revolve around a single-screen inte-
scheduled for a control system update, which would ultimately grated approach to minimize the different operator system inter-
include replacing the existing, and obsolete, distributed con- actions. All the blend regulatory controls—start/stop, routes,
trol system (DCS). The gasoline blending optimization proj- ramp, ratio and pacing—are handled in the DCS via commands
ect was approved, and the project teams realized that it would from the blend optimizer, akin to a master/slave control rela-
integrate well with a new DCS system upgrade in the blending tionship. The operator displays are kept to a minimum and are
and shipping areas. integrated with the DCS graphic, which helps considerably in
Each batch of finished gasoline is made by simultaneously obtaining operator acceptance of the new system.
blending up to 21 different component streams in a header— The optimizer screen is the interface that the operators use to
typically 10 or fewer streams at a time, with mid-blend pump start and monitor the blends. This screen is typically provided on
and tank changes. Each component has a flowmeter, a propor- a separate interface screen, but using RDP from the DCS made
tional integral derivative (PID) controller and a target ratio set it possible to display this screen within the DCS system, simpli-
by the control system. A set of online analyzers provide feed- fying it for the operators and demonstrating the “single-screen
back for optimization and certification using state-of-the-art integrated” approach the project team and operators wanted.
redundant sample compositors. The system can achieve up to
20 quality limits simultaneously, although the number is usu- Challenges encountered. As expected, designing and imple-
ally closer to five. The output of the blending system (finished menting the new system was not without its challenges, many
gasoline) can go into tanks or directly onto a ship. of which coincided with systems not always being available
The blend optimization system used at Pembroke is com- when needed. At the front-end engineering and design (FEED)
prised of a highly standardized mix of both hardware and phase, there were gaps in the system knowledge, which is often
software components. The system is built of several layers: At the case in projects where very old systems are in place and little
the bottom (just above the field devices) is the DCS; on top or no good documentation still exists.
of the DCS is an advanced regulatory software package, which To in-line blend directly to a ship, a composite sampler that
handles the ratio control functions. Above this layer is a blend can take samples at required rates for the size of the blend and
optimization supervisory system (BOSS) software package. Sit- provide a composite of exactly what went onto the ship (it is
ting at the top of the pyramid, it processes data from analyzers, very difficult to test the separate tanks on a ship) is required. The
sample compositor takes a cross-section of
Refinery blending unit DCS Blend optimizer the final product exiting the blend header.
SBO blend SBO blend
This can be tested in the lab and a certifi-
FT
Tank AE M recipe ratio property M
cate of quality/analysis can be produced.
component A
M control control These custom-built, redundant-sam-
ple compositors, which are a proxy for the
Multi-blend
FT planning M blend tender going to the final destination
Tank AE
M
M software (i.e. ship), must be very robust and very
component B accurate. The reliability of such a system
M is critical, as any failure would result in
Pipeline uncertain specifications of the gasoline
FT
M VGBOP product loaded onto the ship. Note:
Tank AE
M Redundant FTIR and M
component C vapor pressure online Backup procedures are in place that allow
field analyzers for additional testing and sample collec-
FT tion, should the compositors fail to avoid
M
Tank AE
M Multi-blend PT
M Finished any off-spec loading to the ship. Establish-
component D planning product tank
Coriolis software ing the reliability of this system was a mi-
meter nor challenge, but in the end it proved to
be extraordinarily valuable to the overall
FIG. 3. A schematic drawing of the various parts that comprise a blend optimization system.
success of the project.
46 JUNE 2016 | HydrocarbonProcessing.com
Process/Plant Optimization

Another challenge came from the limited time available for


the factory acceptance test (FAT). There were delays in getting
all parts of the project approved due to the compressed tim-
escales needed to take advantage of the earlier-than-planned
DCS upgrade. Consequently, this reduced the time available
for the FAT. To make things worse, the system was being mi-
grated from one that had been in place for decades. Many pages
of leftover custom code needed to be identified and stripped
out before the new system could be fully programmed.
Hardware problems also had to be overcome. Communi-
cations with some of the antiquated and poorly documented
serial devices in the facility proved difficult. Some of the flow-
meters on the blend header had little or no parts availability FIG. 4. A blend analyzer screen shows an overview of all running
and documentation was sparse, making installation and tun- pumps, control valve positions and flowrates, providing an expedited
ing impossible. It was decided to replace a number of these view of gasoline blend property values.
instruments on the blender to improve long-term reliability.
Custom modifications to the DCS input modules were in- It is much easier to see the sequential function charts execut-
stalled to integrate these into the DCS so that future updates, ing the sequencing of the startup and shutdown with the new
tuning and maintenance would be simplified and could be car- displays; if there is a problem, the operators can detect its ori-
ried out in-house. gins and how to correct it. It is also useful when calibrating new
turbine meters, making it possible to see exactly what K-factors
Results. The new system was first used to produce optimized have been installed and the changes needed for calibration.
blends to tankage, and within weeks optimized blends were be- Additional benefits may be considered, such as the reduc-
ing successfully loaded directly to ship in parallel to loading from tion of approximately 70 Mbbl of gasoline, which reduces the
existing tanks. Several months later, the site completed its first onsite storage of hazardous materials, the need for operators
100% full blend to ship, a parcel of 46 Mm3 taking over 50 hours and maintenance to work around a commissioned tank, and the
for an export cargo. All direct-to-ship blends tested to spec on environmental risks of hazardous material storage. Overall, the
shipping, and again when received at their final destination. project team identified process improvement opportunities, de-
As discussed, one of the eight gasoline storage tanks (used livered one-time capital benefits of several million dollars, and
previously for final product containment prior to ship loading) provided a sustainable blending optimization solution that has
was removed from gasoline blending service and reallocated to already contributed significant ongoing annual operational sav-
another component system. This move freed up several mil- ings and is expected to continue for many years forward.
lion dollars of gasoline inventory, mitigating required upgrades
and allowing tank scheduling decisions to be made on decom- WILL SCRIVEN is a senior control system specialist for the
missioning or changing of service. Far fewer reblends are seen, blending and shipping area at Valero Energy Corp.’s
Pembroke refinery. He has six years of experience in the
and the blends are closer to spec than before, which reduces control systems department. Prior to this role, Mr. Scriven
giveaway costs. completed an apprenticeship in instrumentation and was
To maximize the system and manage assets effectively, a an instrument technician at the site for two years.
multi-discipline team was developed to monitor, maintain
and improve the gasoline blender and its peripheral systems. ANDREW MARTIN is a senior process engineer with Valero
A series of key performance indicators (KPIs) was set up, and Energy Corp. He has five years of experience as an engineer
in the Pembroke refinery as part of the process engineering
the site began monthly tracking of the optimizer savings and and advanced control teams. He also spent three years in the
performance. To date, the results have shown excellent per- power generation sector, where he was a performance and
formance, and the new system provides more flexibility for commercial engineer as part of the operation and
product planning and scheduling. The site has been able to commissioning team for the Pembroke combined-cycle gas
turbine (CCGT) power station. Mr. Martin has developed advanced control
maximize the value of the gasoline blender by reducing the applications for steam and utility plants and led process optimization for
time it takes to fill, test, certify and load multiple tanks to ship, gasoline blender and CCGT power station operation. He has experience in power
resulting in increased system throughput and, at the same time, station commissioning, energy markets and multiple DCS platforms. He holds
an MS degree in chemical engineering from Cambridge University, where he
minimizing the cost of finished product by blending the least attended Queens’ College.
costly components required to make on-spec gasoline.
System troubleshooting has also become much easier. For DAVID S. SEIVER is the director of blending APC technology
example, the old system had four graphics for the operators to for Valero Energy Corp., managing the rollout of the
monitor pumps and controllers, whereas the new system con- company’s single-blend optimization (SBO) program at its
refineries. Mr. Seiver has over 25 years of experience in the
densed that down to one graphic. Operators can now quickly petrochemical and industrial gas industries. Prior to coming
view the blend header graphics, which are more of a graphical to Valero, he specialized in gasoline and diesel SBO for
representation of the system, and provide an overview of all ConocoPhillips at its Wood River refinery, as well as provided
technical blending assistance to other sites. He has extensive expertise in APC,
running pumps, control valve positions and flowrates. A blend SBO and NIR modeling, and has two US patents in the APC field and one US
analyzer screen (FIG. 4) provides an expedited way of checking patent for gasoline optimization. Mr. Seiver holds an MS degree
gasoline blend property value. in chemical engineering from the University of Houston.

Hydrocarbon Processing | JUNE 2016 47

You might also like