Tamrock Turku/AMF 1 (5)
T007 has a PLC controlled manual/automatic gearshifting, central lubrication timing and engine start
inhibit system.
For gear selection there are five buttons in the left joystick:
+ (plus), - (minus), F(forward), R(reverce) and neutral.
+ PLUS - MINUS
NEUTRAL
F R
STEERING
(LEFT)
Direction:
+ forward
- reverce Gear in use
On remote control gearshifting is allways on manual mode, only 1. forward and reverce are used.
-With PLUS and MINUS buttons you can select biggest gear allowed. Normally all 4. gears are used.
-With F and R buttons you can select the driving direction. The PLC changes the gear automatically
according driving speed.
-Upshifting is possible only if engine rpm is high, over 1800rpm. This is to ensure that you can use
engine braking at down hill driving.
-If converter slip is high when you are driving at 1st gear forward, machine goes to manual mode.
Normally this happens during loading and it prevents unneccessary up-shiftings if wheels are slipping.
Automatic mode returns when driving direction buttons F or R or neutral button N is pressed.
-Engine torque control is always used during shiftings and when driving direction is changed.
-During downshifting torque control is used until converter slip is low. After that gear is shifted down
directly from high to low, f.ex from 4th to 1st. Downshifting is quicker if brake pedal is pressed.
Biggest gear
Direction:
+ forward
- reverce Gear used
-When you are pushing the DISPLAY SELECT button you can see the driving speed (=km/h*10, alias
4km/h => 40).
At programming mode gearshifting works exactly as on automatic mode. Parameters can be adjusted
according separate instructions.
Central lubrication time interval can be adjusted by using a trimmer under a lid in a lower right corner of
the logic controller. You need a little screwdriver to do that. After the adjustment you have to take the
power off and on once. You can see the time value as a parameter nr. 8 but it can’t be adjusted as
other parameters.
Lubrication time
adjustment
-full right for a
max.time = 10min
CONTROLLER
01.06.06
Tamrock Turku/AMF 5 (5)
Programming
If you have to restore the program or factory settings you can do that by using a separate memory
module. When the power is off place the module to it’s place under a lid in a upper right corner of the
logic controller. Switch the power on and wait about ten seconds until the amber STOP led turns off and
green RUN led turns on. After that turn the power off and remove the memory module. The program
and factory settings are now restored.