Abstract:
Chnadubhai S. Patel Institute
The rapid growth of power sector and emergence to bulk power transfer over
of Technology, Charotar
University of Science and
long transmission line demand series compensation to ensuring stable
Technology, Changa, India operation of power system. The series compensation of transmission line by
xed series capacitors may potentially lead to subsynchronous-resonance
Received: 03/05/2017 (SSR) issues. This paper presents the detailed modeling of different power
Revised: 22/06/2017 system components which play an instrumental role in SSR phenomena. IEEE
Accepted: 27/06/2017 rst benchmark model (FBM) is used to simulate SSR phenomena and
eigenvalue analysis has been presented to identify potential modes that can
Correspondence to: lead to SSR. The modeling of Static Synchronous Series Capacitors (SSSC) is
*Nilaykumar A. Patel:
presented to mitigate SSR. The coordination of automatic voltage regulator
nilaypatel.cem@charusat.ac.in:
(AVR) and power system stabilizer (PSS) are explored to mitigate in accordance
with SSSC.
Keywords: Eigenvalues, IEEEFBM, SSR, Series Compensation, SSSC
37
TI Effect A. Modelling of Synchronous Machine
When the sub-synchronous torque induced in the Type 2.2 model of synchronous machine is used in
generator is electrically very close to one of the natural this work which has two windings on d- and q- axis of
modes of the generator shaft, it can set up the the rotor. The model of the synchronous machine has
conditions for the exchange of energy at a sub- three damper coils to capture accurate dynamics of the
synchronous frequency. Thus, it can cause the serious machine. Three phase armature winding on the stator
damage to the turbine-generator shaft. (a, b and c phase), one eld winding (fd) in d-axis of
(b) Transient SSR rotor along with the damper windings (g) and two
damper windings (h and k) on q-axis of the rotor are
The system disturbances such as sudden load
considered [12]. Fig. 1 shows the rotor model of
changes, faults or tripping of the lines can excite
synchronous machine along with different masses of
oscillatory torques on the generator rotor. The
turbine as per the IEEE FBM model.
setransient oscillatory electrical torques have many ω1
components such as unidirectional, exponentially Te
38
The state equations of electrical network in D–Q
components are given in (3)
(3)
(5)
where
39
A. Control of SSSC
The block diagram of SSSC control for SSR
mitigation is shown in Fig. 4 and its state space
modeling is given herewith.
40
IEEE FBM
IEEE FBM with 50% series IEEE FBM
50% series compensation is Modes of Oscillations
compensation SSSC+AVR-PSS
replaced by SSSC
-4.716 ± 623.63i -118.218 ± 547.17i -84.56 ± 733.75i Supersunchronous mode
-0.00000002 ± 297.97i -0.181 ± 297.97i -0.000002 ± 297.97i Torsional mechanical mode
-0.00021 ± 202.84i -0.025 ± 202.91i -0.008 ± 202.88i Torsional mechanical mode
-0.00036 ± 160.50i -0.151 ± 160.53i -0.0059 ± 160.51i Torsional mechanical mode
0.0004 ± 126.94i -0.65 ± 126.95i -0.0022 ± 126.95i Torsional mechanical mode
0.001 ± 98.70i -0.016 ± 98.77i -0.039 ± 98.71i Torsional mechanical mode
-2.636 ± 130.35i -10.00 ±47.06i -3.89 ± 39.58i Subsynchronous Mode
0.0013571638373 1.179 ± 12.12i -0.001 ± 12.13i Swing Mode
-0.0000000038616 -3.47 ± 0.77i -0.64 ± 0.77i Modes related to Damper and
Field winding
-0.998 -20.509 -2.763 ± 1.81i
-4.4399 -32.808 -20.470
-20.467 -24.055
-33.194 -35.690
-100.452
-494.272
41
of xed capacitors. In this case also, the torsional Inertia Inertia Shaft Spring Constant
modes still persist but the use of SSSC can successfully Constant (H) section (K) in pu
damped the unstable torsional modes and the real part torque/rad
of all the eigenvalues related to torsional oscillations HP turbine 0.092897 HP-IP 19.303
have turned to be negative, which is the indication that IP turbine 0.155589 IP-LPA 34.929
the system will not be unstable due to torsional LPA turbine 0.85867 LPA-LPB 52.038
oscillations. Thus, SSSC can be effective to mitigate the LPB turbine 0.884215 LPB-GEN 70.858
torsional oscillations but it leaves the system unstable Generator 0.868495 GEN-EXC 2.82
with network modes which are highlighted in Table 1. Exciter 0.034217
In order to mitigate the SSR as well as to prevent the
system to become unstable, the synchronous generator REFERENCES
has been considered to have AVR and PSS. The [1] IEEE Subsynchronous Resonance Task Force.
eigenvalues with this case are also shown in Table 1 First benchmark model for computer simulation
which show that the use of SSSC in transmission line of subsynchronous resonance. IEEE Trans Power
and AVR-PSS at synchronous generator can Apparatus System vol. 96, no. 5, pp. 1565–72,
successfully results in eigenvalues which have 1977
negative real part, thus it makes the system stable even [2] IEEE SSR Working Group. Terms, denitions,
with 50% of series compensation. and symbols for subsynchronous oscillations.
VI. CONCLUSION IEEE Trans Power Apparatus System, vol. 104,
The paper presents the state space modelling of no. 6, pp. 1326–33, 1985
different electrical components to study SSR of IEEE [3] I.C. Report. Readers guide to subsynchronous
FBM. The series compensation of transmission resonance. IEEE Trans. Power System, vol. 7, no.
network with certain degree of compensation may 1, pp. 150–157.
result in SSR. In this paper SSR phenomina is mitigated [4] Kundur P. Power system stability and control.
with the use of SSSC. The sub-synchronous, super- McGraw Hill; 1993.
synchronous and torsional modes have been identied
[5] Framer RG, Katz E, Schwalb AL. Navajo project
for IEEE FBM for 50% compensation. The torsional
on subsynchronous resonance analysis and
modes can be damped-out with the use of SSSC, but it
solutions. IEEE Trans PAS 1985:1057–66.
leaves the system unstable by making eigenvalues
[6] Edris A. Series compensation schemes reducing
positive corrosponding to swing mode. The use of PSS
the potential of resonance. IEEE Trans PAS
and AVR at synchronous generator in coordination
1990:219–26.
with SSSC in transmission line can make the system
stable and the torsional modes can be mitigated. [7] Rana RD, Huff SW, Hayes RM, Fromholtz EN,
Appendix Schulz RP. AEP's Kanawha river 345kV series
capacitor installations-subsynchronous
Synchronous Machine Parameters for IEEE-FBM: Values
are in pu resonance studies and torsional measurements.
XT=0.14 pu, RL=0.02, XL=0.50, XSYS=0.06, In: Proceedings of the American power
XC=0.371, Pg=0.9, VT=1 conference; 1991, p. 300–5.
[8] Zhu W, Spee R, Mohler RR, Alexander GG,
Reactance Value (pu) Time Constant Value (sec) Mittelstadt WA, Maratuhulam D. An EMTP
study of SSR mitigation using the thyristor
Xd 1.79 T'd0 4.3
controlled series capacitor. IEEE Trans Power
X'd 0.169 T”d0 0.032 Delivery 1995; 10:1479–85.
X”d 0.135 T'q0 0.85 [9] Dobson I, Chiang HD. Towards a theory of
voltage collapse in electric power systems. Syst
Xq 1.71 T”q0 0.05 Cont lett 1989; 13:253–62.
[10] Ajjarapu A, Lee B. Bifurcation theory and its
X'q 0.228
applications to nonlinear dynamical phenomena
X”q 0.2 in an electrical power system. IEEE Trans Power
Syst 1992; 7(1):424–31.
Xad 0.13
42
[11] Subsynchronous Resonance Working Group, [15] C. Yu, Z. Cai, Y. Ni, J. Zhong, Generalised
Reader's guide to subsynchronous resonance, eigenvalue and complex-torque-coefcient
IEEE Transactions on Power Systems 7 (1) (1992) analysis for SSR study based on LDAE Model,
150–157. IEE Proceedings-Generation, Transmission and
[12] R.Z. Davarani, R. Ghazi, N. Pariz, Nonlinear Distribution 153 (1) (2006) 25–34.
modal analysis of interaction between torsional [16] F.C. Jusan, S.G. Jr., G.N. Taranto, SSR results
modes and SVC controllers, Electric Power obtained with a dynamic phasor model of SVC
Systems Research91 (2012) 61–70. using modal analysis, International Journal of
[13] N. Kumar, M.P. Dave, Application of an auxiliary Electrical Powerand Energy Systems 32 (6) (2010)
controlled static var system for damping 571–582.
subsynchronous resonance in power systems, [17] M. Parniani, M.R. Iravani, Computer analysis of
Electric Power Systems Research 37 (3) (1996) small-signal stability of powersystems including
189–201. network dynamics, IEE Proceedings-Generation,
[14] C. Gross, C.F. Imparato, P.M. Look, A tool for the Transmis-sion and Distribution 142 (6) (1995)
comprehensive analysis of power system 613–617.
dynamic stability, IEEE Transactions on Power [18] P.M. Anderson, B.L. Agrawal, J.E. Vaness,
Apparatus and Systems 101 (1) (1982) 226–234. Subsynchronous Resonance in Power Systems,
Wiley-IEEE Press, New York, 1990.