You are on page 1of 27

密级:公司秘密

Confidential Class: Internal

东 方 汽 轮 机 有 限 公 司
DONGFANG TURBINE Co., Ltd.

THERMODYNAMIC CORRECTION CURVES FOR


MODEL N600-16.7/538/538
STEAM TURBINE
FICHTNER Consulting Engineers (India)
Private Limited, (FI) Chennai.
VENDOR DRAWING REVIEW STATUS

o Action - 1 Approved
o Action - 2 Approved except as noted on drawing. Revise
drawing and resubmit for records.
o Action - 3 Returned with Comments. Resubmit for approval.
o Action - 4 Not Approved. Resubmit for review
Action - 5 Information noted. Retained for reference
o` and records.
This document has been reviewed as noted with regard to general
conformity with the Contract specifications and requirements. The
Vendor / Contractor is responsible for correctness of design calculation
and details. Approval of this document does not relieve the Vendor /
Contractor of his responsibility in carrying out the work correctly and
fulfilling the complete requirements of the contract nor does it limit the
purchasr's rights under the contract.

FI Letter Ref. No. Date:


1110233/ME/VDT/2050/0509 29/10/2014

Signature Initials: PS 2014 年 9 月


September ,2014
Contents

NO. Chapter-Section Description


1 Preface
2 1 Correction curves for TMCR condition
3 1-1 Correction curves for throttle pressure
4 1-2 Correction curves for throttle temperature
5 1-3 Correction curves for reheat temperature
6 1-4 Correction curves for reheat pressure drop
7 1-5 Correction curves for exhaust pressure
8 1-6 Correction curves for superheater spray water flow
9 1-7 Correction curves for reheater spray water flow
10 1-8 Correction curve for Strainers pressure drop
11 1-9 Correction curve for valve position
12 1-10 heat rate correction curve for speed
13 1-11 Correction curve for unit aging
14 1-12 No.1 extraction line pressure drop correction curve
15 1-13 No.1 HP heater TD correction curve
16 1-14 No.1 HP heater DC correction curve
17 1-15 Correction curve for condenser depression
18 1-16 Correction curve for feed water pump turbine flow
Preface
This thermodynamic correction curves is provided for 2X600MW steam turbines of
ITPCL Power Station in INDIA .
By DTC proprietary heat balance software which is the same software to get TMCR,
we get the data sheet. The following correction curves is came from the data sheet.

1 Correction curves for TMCR condition


The following correction curves is provided for TMCR condition.
1-1 Correction curves for throttle pressure
THROTTLE PRESSURE CHANGE IN OUTPUT CHANGE IN HEAT RATE
Mpa % %
15.20 -8.61 1.11
16.67 0 0
17.65 5.59 -0.58
1-2 Correction curves for throttle temperature
THROTTLE TEMPERATURE CHANGE IN OUTPUT CHANGE IN HEAT RATE
℃ % %
520 0.33 0.51
538 0 0
550 -0.24 -0.28
1-3 Correction curves for reheat temperature
REHEAT TEMPERATURE CHANGE IN OUTPUT CHANGE IN HEAT RATE
℃ % %
520 -1.67 0.52
538 0 0
550 1.08 -0.30
1-4 Correction curves for reheat pressure drop
REHEAT PRESSURE DROP CHANGE IN OUTPUT CHANGE IN HEAT RATE
% % %
6 0.95 -0.37
10 0 0
14 -1.04 0.43
1-5 Correction curves for exhaust pressure
CONDENSER PRESSURE CHANGE IN OUTPUT CHANGE IN HEAT RATE
kPa % %
4 2.76 -2.76
6 2.32 -2.32
8 1.33 -1.33
10.13 0 0
12 -1.37 1.37
15 -3.77 3.77
1-6 Correction curves for superheater spray water flow

SUPERHEATER SPRAY WATER


CHANGE IN OUTPUT CHANGE IN HEAT RATE
FLOW RATIO
% % %
0 0 0
5 0.66 0.15
8.05 1.075 0.22
1-7 Correction curves for reheater spray water flow

REHEATER SPRAY WATER


CHANGE IN OUTPUT CHANGE IN HEAT RATE
FLOW RATIO
% % %
0 0 0
5 3.54 0.88
8.05 5.70 1.36
1-8 Correction curve for Strainers pressure drop

STRAINERS CHANGE IN OUTPUT CHANGE IN HEAT RATE


PRESSURE DROP THROTTLE VALVE REHEAT VALVE THROTTLE VALVE REHEAT VALVE
% % % % %
0 0 0 0 0
3 -0.40 -0.76 0.38 0.34
5 -0.66 -1.24 0.63 0.56
1-9 Correction curve for valve position

HP control #1and #2 valve loop

CHANGE IN HEAT RATE %


1.0

0.9

0.8

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0.0
0 20 40 60 80 100

HPGV#1 AND HPGV#2 OPENING %

1# and 2# valve
% 30 37.5 50 62.5 80 90 100
position
CHANGE IN HEAT RATE % 0.449 0.482 0.496 0.446 0.306 0.166 0.000
HP contro3 #1and #4 valve loop

CHANGE IN HEATRATE %
1.0

0.9

0.8

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0.0
00 20
20 40
40 60
60 80
80 100(0)
100 12020 40
140 60
160 80 100
180 200
4# VALVE POSITION %
3# VALVE POSITION %

3# valve position % 30 37.5 50 62.500 80 90.000 100


CHANGE IN HEAT RATE % 0.390 0.419 0.431 0.388 0.266 0.144 0.000

4# valve position % 0 12.5 25 37.5 50


CHANGE IN HEAT RATE % 0.000 0.113 0.225 0.285 0.295
1-10 heat rate correction curve for speed

CHANGE IN HEAT RATE %


3.5

3.0

2.5

2.0

1.5

1.0

0.5

0.0
2900 2950 3000 3050 3100
ROTATING SPEED R/MIN
Output correction curve for speed

CHANGE IN OUTPUT %
0.0

-0.5

-1.0

-1.5

-2.0

-2.5

-3.0

-3.5
2900 2950 3000 3050 3100
ROTATING SPEED R/MIN

ROTATING SPEED CHANGE IN OUTPUT CHANGE IN HEAT RATE

R/MIN % %
2910 -0.7 0.7
2950 -0.3 0.3
3000 0 0
3050 -0.3 0.3
3090 -0.7 0.7
1-11 Correction curve for unit aging

CHANGE IN HEAT RATE %


0.7

0.6

0.5

0.4

0.3

0.2

0.1

0.0
0 2 4 6 8 10 12 14
TIME BETWEEN FIRST SYNCHRONIZATION AND TEST MONTH

MONTH CHANGE IN HEAT RATE


%
2 0.0
4 0.1
6 0.2
8 0.3
10 0.4
12 0.5
14 0.6
1-12 No.1 extraction line pressure drop correction curve

NO.1 EXTRACTION
CHANGE IN OUTPUT CHANGE IN HEAT RATE
PRESSURE DROP
% % %
0 -0.30 -0.02
3 0 0
7 0.44 0.03
1-13 No.1 HP heater TD correction curve

NO.1 HP HEATER TD CHANGE IN OUTPUT CHANGE IN HEAT RATE


℃ % %
-3 -0.21 -0.02
-1.7 0 0
2 0.59 0.07
1-14 No.1 HP heater DC correction curve

NO.1 HP HEATER DC CHANGE IN OUTPUT CHANGE IN HEAT RATE

℃ % %
2 -0.001 -0.007
5.6 0 0
10 0.002 0.009
1-15 Correction curve for condenser depression

CHANGE %
0.15

HEAT RATE

0.10

0.05

0.00

-0.05

-0.10
OUTPUT

-0.15
0 1 2 3 4 5
CONDENSER DEPRESSION ℃

CONDENSER DEPRESSION CHANGE IN OUTPUT CHANGE IN HEAT RATE

℃ % %
0 0 0
2 0.062 -0.063
4.28 0.132 -0.133
1-16 Correction curve for feed water pump turbine flow
CHANGE IN FEED WATER
CHANGE IN OUTPUT CHANGE IN HEAT RATE
PUMP TURBINE FLOW
t/h % %
-6.8 0.23 -0.25
0 0 0
8.9 -0.33 0.34