KKS:
Name: Stator water pump B suction valve.
Location: Valve Located in stator water skid, TG 0 meter.
Purpose: stator water A Isolation.
Normal Condition: open.
Operation method: MIV
Name: Stator water cooler A inlet valve
Location: Valves Located in stator water skid , TG 0
meter
Purpose: Stator water inlet to cooler A Isolation.
Normal Condition: open when cooler in service
Operation method: MIV
When outlet pressure of the operating stator cooling water pump is LOW (L1) value
(110kPa), after 1s delay, the standby pump will start by interlock.
When outlet pressure of the operating stator cooling water pump is low low (L2) value
(89kPa), the standby pump will be started by interlocking.
If the generator unit stator cooling water inlet pressure gives LOW-LOW value (<89kPa) and
the flow is extremely low (≤34T/h). After 3s delay, water break protection device will act.
When the generator unit stator cooling water inlet conductivity is >9.9μs/cm, manually shut
down the unit.
Stator cooling water tank water level alarm
Alkayzer:
Dosing pump
Dosing point
Inlet valve
Alkalyzer parameter monitor:
Water chemistry parameter:
PH-7
Conductivity-0.4ms