THE SIZING CALCULATION OF CCCW

EXPANSION TANK

膨胀水箱选型计算

Plant: IL&FS Cuddalore Power Project

Owner IL&FS Tamil Nadu Power Company Limited

Owner’s Engineer Fichtner Consulting Engineers (India) Private Ltd. CHENNAI

Contractor
SHANDONG TIEJUN Electric Power EngineeringCo.,Ltd

Contractor’s Engineer SHANDONG Electric Power Engineering Consulting Institute CORP.,Ltd

Document Code: Rev. No . 0


文件编码

Date: APR .2 012

REV DATE REVISION REVD CHKD RVWD APPRD


1. Philosophy for sizing
The volume of CCCW expansion tank should be considered asper
listed following condition:
1) The volume of CCCW side in CCCW system
2) Temperature difference from initial filling to normal operation
2. sizing cal.
1) The volume of CCCW side in CCCW system
Unit No. No.
name data remark
(cu. m) (installed) (operating)
total volume in piping 37.2466+12.64 1 1 49.8866
steam and water
1 1 1 1
sample cooler
cccw pump's motor
0.35 3 2 0.7
bearing cooler
occw pump's motor
1 2 1 1
bearing cooler
hydrogen cooler 0.18 4 4 0.72

generator stator water 0.2 2 1 0.2

cooler

BFPT oil cooler 0.0687 4 2 0.1374

MDP motor air cooler 0.2 1 1 0.2

MDP working oil cooler 0.085 2 1 0.085

MDP lube oil cooler 0.045 2 1 0.045

MDP cooler 0.02 1 1 0.02

TFBP cooler 0.005 2 2 0.01

CEP's motor bearing 0.0026 3 2 0.0052

cooler
condensate water
0.02 2 2 0.04
transfer pump's motor
bearing cooler
generator sealing oil
0.01 1 1 0.01
vacuum pump cooler
fire-resistant oil cooler 0.01 2 1 0.01

TDFP cooling cooler 0.02 2 2 0.04


hydrogen drier cooler 0.01 1 1 0.01

MDBP cooler 0.005 1 1 0.005

mill lube oil cooler 0.1 7 6 0.6

forced-draft fan oil 0.001 2 2 0.002

cooler
primary air fan oil cooler
0.01 2 2 0.02
air preheater's motor
0.12 2 2 0.24
bearing cooler
sealing air fan's motor
0.01 2 1 0.01
bearing cooler
induced draft fan oil
0.01 2 2 0.02
cooler
Volume of cooling water
0.032 1 1 0.032
for ash disposal
boiler recirculation
0.1 3 3 0.3
pump system cooler
Total volume 55.3482

2) Expansion volume
Vexp=VtotalXΔTX F
Where
Vexp----- expansion volume
Vtotal----- total volume of CCCW side
ΔT----- Temperature difference from initial filling to normal operation
F------- expansion coefficient for water
Vexp=55.3482x5x0.00984=2.723
CCCW expansion tank in this project is considered as 20 , so
meeting requirement.