Professional Documents
Culture Documents
GFS 31.85.80.02-Gen.
November 2016
ECCN EAR99
This document contains information that is classified as EAR99 and, as a consequence, can neither be exported nor re-exported to any country which is under an
embargo of the U.S. government pursuant to Part 746 of the Export Administration Regulations (15 C.F R. Part 746) nor can be made available to any national of such
country. In addition, the information in this document cannot be exported nor re-exported to an end-user or for an end-use that is prohibited by Part 744 of the Export
Administration Regulations (15 C.F.R. Part 744).
PREFACE
GFS (General Functional Standard) publications reflect the views, at the time of publication, of Shell Global Solutions
International B.V. (Shell GSI) and, in some cases, of other Shell Companies. It is understood by Shell Company, any
company or other legal entity which, at the time in question, is being managed or operated by Royal Dutch Shell plc or a
company which at the time in question is directly or indirectly controlled by Royal Dutch Shell plc or a company being
provided services by Royal Dutch Shell plc under a construction, operation of technical services agreement on a cost
sharing basis.
These views are based on the experience acquired during involvement with the design, construction, operation and
maintenance of processing units and facilities. Where deemed appropriate GFSs are based on Shell DEPs, international,
and industry standards.
The objective is to set the standard for good design and engineering practice to be applied by Shell companies in oil and
gas production, oil refining, gas handling, gasification, chemical processing, or any other such facility, and thereby to help
achieve maximum technical and economic benefit from standardization.
The information set forth in these publications is provided to Shell companies for their consideration and decision to
implement. This is of particular importance where GFSs may not cover every requirement or diversity of condition at each
locality.
When Contractors or Manufacturers/Suppliers use GFSs, they shall be solely responsible for such use, including the
quality of their work and the attainment of the required designs and engineering standards. In particular, for those
requirements not specifically covered, the Principal will typically expect them to follow those design and engineering
practices that will achieve at least the same level of integrity as reflected in the GFSs. If in doubt, the Contractor or
Manufacturer/Supplier shall, without detracting from its own responsibility, consult the Principal.
The right to obtain and to use GFSs is restricted, and is typically granted by Shell GSI (and in some cases by other Shell
Companies) under a Service Agreement or a License Agreement. This right is granted primarily to Shell companies and
other companies receiving technical advice and services from Shell GSI or another Shell Company. Consequently, three
categories of users of GFSs can be distinguished:
1) Operating Units having a Service Agreement with Shell GSI or another Shell Company. The use of GFSs by these
Operating Units is subject in all respects to the terms and conditions of the relevant Service Agreement.
2) Other parties who are authorised to use GFSs subject to appropriate contractual arrangements (whether as part of
a Service Agreement or otherwise).
3) Contractors/subcontractors and Manufacturers/Suppliers under a contract with users referred to under 1) or 2)
which requires that tenders for projects, materials supplied or - generally - work performed on behalf of the said
users comply with the relevant standards.
Subject to any particular terms and conditions as may be set forth in specific agreements with users, Shell GSI disclaims
any liability of whatsoever nature for any damage (including injury or death) suffered by any company or person
whomsoever as a result of or in connection with the use, application or implementation of any GFS, or any part thereof,
even if it is wholly or partly caused by negligence on the part of Shell GSI.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual arrangements, GFSs shall
not, without the prior written consent of Shell GSI, be disclosed by users to any company or person whomsoever and the
GFSs shall be used exclusively for the purpose for which they have been provided to the user. They shall be returned after
use, including any copies which shall only be made by users with the express prior written consent of Shell GSI. The
copyright of GFSs vests in Shell Group of companies. Users shall arrange for GFSs to be held in safe custody and Shell
GSI may at any time require information satisfactory to them in order to ascertain how users implement this requirement.
All administrative queries should be directed to the Technical Standards Team in Shell GSI.
TABLE OF CONTENTS
1. INTRODUCTION ........................................................................................................ 5
1.1 SCOPE........................................................................................................................ 5
1.2 DISTRIBUTION, INTENDED USE AND REGULATORY CONSIDERATIONS ......... 5
1.3 DEFINITIONS ............................................................................................................. 6
1.4 CROSS-REFERENCES ............................................................................................. 8
1.5 SUMMARY OF MAIN CHANGES ............................................................................... 8
1.6 COMMENTS ON THIS GFS ....................................................................................... 9
1.7 DUAL UNITS ............................................................................................................... 9
1.8 NON NORMATIVE TEXT (COMMENTARY) .............................................................. 9
1.9 UPDATE POLICY ....................................................................................................... 9
2. BASIC REQUIREMENTS ......................................................................................... 10
2.1 GENERAL ................................................................................................................. 10
2.2 ORDER OF PRECEDENCE ..................................................................................... 10
2.3 SAFETY .................................................................................................................... 10
2.4 SERVICE CONDITIONS........................................................................................... 11
2.5 SCOPE OF SUPPLY ................................................................................................ 11
3. PERFORMANCE REQUIREMENTS ........................................................................ 12
3.1 RATING..................................................................................................................... 12
3.2 STARTING TIME ...................................................................................................... 12
3.3 NOISE ....................................................................................................................... 12
3.4 TORSIONAL VIBRATIONS ...................................................................................... 13
3.5 LATERAL VIBRATIONS ........................................................................................... 13
4. ENGINE REQUIREMENTS ...................................................................................... 13
4.1 BASIC REQUIREMENTS ......................................................................................... 13
4.2 ENGINE AND AUXILIARIES DESIGN ..................................................................... 15
5. GENERATOR REQUIREMENTS FOR APPLICATIONS OUTSIDE NORTH
AMERICA ................................................................................................................. 20
5.1 GENERAL ................................................................................................................. 20
5.2 GENERATOR IMPEDANCES .................................................................................. 20
5.3 EXCITATION SYSTEM............................................................................................. 21
5.4 OUTPUT VOLTAGE VARIATIONS .......................................................................... 22
5.5 EFFICIENCY ............................................................................................................. 22
5.6 GENERATOR COOLING.......................................................................................... 22
5.7 GENERATOR HOUSING ......................................................................................... 22
5.8 WINDINGS ................................................................................................................ 22
5.9 SPACE HEATER ...................................................................................................... 23
5.10 BUSHINGS AND TERMINALS ................................................................................. 23
5.11 BEARINGS................................................................................................................ 23
5.12 ELECTROMAGNETIC EMISSIONS AND IMMUNITY ............................................. 23
6. GENERATOR REQUIREMENTS FOR APPLICATIONS INSIDE NORTH
AMERICA ................................................................................................................. 24
6.1 GENERAL ................................................................................................................. 24
6.2 RATING..................................................................................................................... 24
6.3 GENERATOR IMPEDANCES .................................................................................. 24
6.4 EXITATION SYSTEM ............................................................................................... 24
6.5 VOLTAGE REGULATOR PERFORMANCE ............................................................ 26
6.6 WAVEFORM AND HARMONIC DISTORTION ........................................................ 26
6.7 EFFICIENCY ............................................................................................................. 26
6.8 GENERATOR HOUSING ......................................................................................... 26
6.9 WINDINGS ................................................................................................................ 27
6.10 RESTITIVE TEMPERATURE DEVICE (RTD) .......................................................... 27
6.11 INSULATION ............................................................................................................ 27
6.12 BUSHINGS AND TERMINALS ................................................................................. 27
6.13 BEARINGS................................................................................................................ 27
6.14 ELECTROMAGNETIC EMISSIONS AND IMMUNITY ............................................. 28
APPENDICES
APPENDIX A GENERATOR STATUS, ALARM, TRIP AND SHUTDOWN
REQUIREMENTS ............................................................................................ 52
APPENDIX B ENGINE MONITORING AND PROTECTION INSTRUMENTATION ............. 54
APPENDIX C TYPICAL BLOCK DIAGRAM FOR A PACKAGED UNIT AC
GENERATOR SET .......................................................................................... 56
APPENDIX D VENDOR DOCUMENT AND DATA REQUIREMENTS ................................. 57
1. INTRODUCTION
1.1 SCOPE
This GFS specifies requirements and provides recommendations for the design,
manufacturing, assembly, inspection, and testing of packaged unit emergency diesel
generator sets alternating current (AC), hereafter referred to as generator sets. Special
modes of operation (large non-linear loads, parallel operation and remote services) are
covered in this document. The generator set consists of a synchronous AC generator, a
diesel engine driving the generator, their control, protection and relay panels, auxiliary
equipment, a baseplate and an acoustic enclosure.
The intent of this GFS Specification is to specify requirements for generator sets that are
fully functional and self-contained with an air-cooled generator and a water-cooled engine
with conventional radiator (closed system). This specification for generator sets is globally
applicable.
Generators greater than 2000kW (2500HP) power ratings are considered to be for special
purpose applications. For these applications, the project team shall use this GFS together
with additional alternator requirements (to be included in the package requisition).
For generators less than 250kW (350HP), vendor standard product for petrochemical
applications should be considered by the Principal depending on criticality.
If the generator is used for both base load and emergency applications, the engine rating
shall be for continuous operation and the generator shall be suitable for 6 years
uninterrupted operation (routine maintenance excepted).
This GFS was developed with direct engagement and input from major global
manufacturers/ suppliers to use industry standards as the basis of design with needed
features to design and fabricate packages for both offshore and onshore facilities.
References to DEPs in this document are minimized. References to subsequent DEPs in
the referred DEPs can be ignored.
This GFS is classified as a TIER 1 document. See section (1.3) for definitions of
TIER 1/TIER 2.
All equipment and services are to be provided in accordance with this GFS which excludes
the supply of the following items which are outside of the package boundary:
a. civil engineering such as buildings, cable floors, trenches, foundations and protective
fences;
b. cabling between skids/packages;
c. outside cable tray systems, except as fitted within the package;
d. switchboards, including the generator circuit breaker, which are installed outside in
the electrical rooms.
The detailed scope of supply is given in section (2.5).
If national and/or local regulations exist in which some of the requirements could be more
stringent than in this GFS, the Contractor shall determine by careful scrutiny which of the
requirements are the more stringent and, which combination of requirements will be
acceptable with regards to safety, environmental, economic and legal aspects. In all cases,
the Contractor shall inform the Principal of any deviation from the requirements of GFS
which is considered to be necessary in order to comply with national and/or local
regulations. The Principal may then negotiate with the Authorities concerned the objective
being to obtain agreement to follow this GFS as closely as possible.
1.3 DEFINITIONS
1.3.1 General Definitions
The Contractor is the party that carries out all or part of the design, engineering,
procurement, construction, commissioning or management of a project or operation of a
facility. The Principal may undertake all or part of the duties of the Contractor.
The Manufacturer/Supplier is the party that manufactures or supplies equipment and
services to perform the duties specified by the Contractor.
The Packager is the party that designs, manufactures, assembles, inspects and tests the
complete generator set.
TIER 1 packaged equipment solutions are kept evergreen and have a revision cycle.
TIER 2 packaged equipment solutions do not have a revision cycle and updated when
needed.
The Principal is the party that initiates the project and ultimately pays for it. The Principal
may also include an agent or consultant authorised to act for, and on behalf of, the
Principal.
The Buyer is the party authorized by the Principal to specify and procure the package.
The word shall indicates a requirement.
1
If deviating from a requirement represented as shall , refer to the Principal for the
appropriate deviation process.
The word should indicates a recommendation.
Term Definition
air-to-air Closed machine with an integral or machine mounted heat exchanger,
cooled using air as the primary and secondary coolant
machine
air-to-water Closed machine with a heat exchanger using air as primary coolant and
cooled water as secondary coolant
machine
alarm Audible and/or visible means of indicating to the operator an equipment
malfunction, process deviation, or abnormal condition requiring a
response.
aluminium Copper-free aluminium that contains less than 0.40 % copper.
Certificate Document issued by a recognised authority certifying that it has examined
a certain type of apparatus and, if necessary, has tested it and concluded
that the apparatus complies with the relevant standard for such apparatus
Certificate of Certificate stating that the electrical apparatus complies with the relevant
Conformity standards for apparatus for potentially explosive atmospheres
Declaration of Document issued by the Manufacturer stating that the electrical apparatus
Compliance complies with the requirements of IEC 60079-15
Term Definition
Generator Sets Generator sets with an ability to operate without permanent supervision in
for Parallel parallel with the main grid system, in parallel with other generators, or
Operation both.
Generator Sets Generator sets with an ability to supply large non-linear loads, e.g.,
Supplying rectifiers, while operating within their temperature limits.
Large Non-
Linear Loads
hazardous Area in which an explosive gas mixture is or may be expected to be
area present in a quantity such as to require special precautions for the
construction, installation and use of electrical apparatus
lifetime Time during which the generator set remains for the application for which
it was made, provided it is regularly inspected, examined and serviced in
accordance with the Manufacturer's instructions, with replacement of
lubricants and of parts subject to wear
low voltage Set of voltage levels used for the distribution of electricity and whose
upper limit is 1000 V AC
marking Data put on the electrical apparatus by the Manufacturer giving
information for the safe use of the apparatus
site conditions External factors, e.g., altitude, air temperature, wind velocity, vibration,
earthquake, black body temperature and relative humidity, which may
influence the operation of a machine or apparatus
test report Document prepared by the Manufacturer indicating in detail the tests and
verifications to which the apparatus has been subjected, and their results
trip Automatic shutdown of a machine upon reaching a pre-set trip value.
vital service Service which, when failing in operation or when failing if called upon, can
cause an unsafe condition of the process and/or electrical installation,
jeopardize life, or cause major damage to the installation
Zone 2 (in the Area in which an explosive gas atmosphere is not likely to occur in normal
classification operation and if it does occurs it will exist for a short period only
of hazardous
gas areas)
1.3.3 Abbreviations
Term Definition
AC Alternating Current
AHJ Authority Having Jurisdiction
AISI American Iron and Steel Institute
AVR Automatic Voltage Regulator
CoG Centre of Gravity
CT current transformer
CVA Certification Verification Authority
DC Direct Current
ECM Engine Control Module
EGR Exhaust Gas Recirculation
EMC Electromagnetic Emissions
1.4 CROSS-REFERENCES
Where cross-references to other parts of this GFS are made, the referenced section or
clause number is shown in brackets ( ). Other documents referenced by this GFS are listed
in (14).
Feedback that has been registered in the Feedback System by using one of the above
options will be reviewed by the GFS Custodian for potential improvements to the GFS.
2. BASIC REQUIREMENTS
2.1 GENERAL
1. Manufacturer/Supplier shall confirm that the selected generator set consists of
equipment that is proven.
Proven equipment is defined as equipment of which at least three units of similar
type, size and specific loading have together accumulated a minimum of 24,000
hours of comparable satisfactory service.
2. When a new design or component is offered that has not been proven in service for at
least two years, proposals shall indicate which components are affected and the extent
of experience with such components.
3. Any deviations from industry standards as defined in this GFS shall be included in the
vendor’s proposal.
2.3 SAFETY
1. The generator set shall be designed to withstand the thermal and dynamic stresses
and transient mechanical torques such as those resulting from a short circuit and
circuit switching operations.
2. All exposed rotating or moving parts of the generator set shall be protected by guards.
3. Rotating or moving part guards shall prevent contact with personnel and their clothing.
4. The rotating or moving part guards shall be readily removable for plant maintenance
purposes and meet local regulatory requirements.
5. The rotating or moving part guards shall be of non-spark material.
6. All flexible drive belts shall be of anti-static material in accordance with ISO 1813.
7. Equipment or piping, that in normal operations exposes personnel to surface
temperatures greater or less than those shown in Table 1 for momentary contact and
accessible from normal working areas and access ways, shall be provided with
personnel protection to a height of 2000 mm (80 in) above the walking level.
3. PERFORMANCE REQUIREMENTS
3.1 RATING
1. The generator set rating shall be the total net output rating at the generator terminals.
2. Unless otherwise specified in the requisition, the generator set output rating shall be
based on Emergency Prime Power (EPP) according ISO 8528.
3.3 NOISE
1. The noise attenuated enclosure (8.8) shall reduce sound pressure levels outside of the
enclosure.
2. The maximum guaranteed noise level shall not exceed 85 dB on 1 m distance and
1.5 m height.
3. Noise control requirements in accordance with ISO 15664 shall be adhered to.
4. The Packager shall submit guaranteed sound power levels and sound pressure levels
of the packaged unit.
5. The Packager shall indicate what special silencing measures, if any, are proposed.
4. ENGINE REQUIREMENTS
5. The Manufacturer/Supplier shall provide a statement of the engine emissions and the
method of achieving guaranteed "”Not To Exceed” (NTE) levels.
6. Any installation, maintenance requirements or best practices to maintain emission
levels shall be clearly documented in the operating manual.
7. Unless otherwise required by local regulation or specified in the requisition, the
Manufacture/Supplier shall design, fabricate and test the complete package to fully
comply with EPA Tier 2 emission requirements.
3. Unless vendor can demonstrate proven experience with different heater sizing, the
heater shall be rated to achieve a minimum temperature of 45 °C (113 °F) in the
engine block during the lowest ambient temperature as defined in the requisition.
4. The integral thermostat shall cut off the heater when the coolant temperature reaches
75 °C (167 °F).
5. The engine shall be equipped with a thermostatically-controlled electrical heater for
maintaining lubricating oil temperature at 20 °C (68 °F) or higher as defined by NFPA
110.
6. The thermostatically-controlled electrical heater shall be sized to keep the value of
watts per square inch at the surface of the immersion heater elements to a minimum to
prevent local lube oil carbonization on the elements.
7. Heat dissipation from the immersion heating element shall not exceed 2.3 W/cm2
(50 Btu/hr/in2) on heaters in hydrocarbon heating duty.
8. Power circuits supplying the heater shall be protected by miniature circuit breakers
incorporating overload, short circuit and earth leakage protection, in accordance with
respective regional electrical standards as specified in the requisition.
4.2.5.4 Radiator
1. Unless otherwise specified in the requisition, the entire engine cooling system
(radiator, fan and all ducting, interconnecting piping and wiring) shall be supplied by
Manufacturer/Supplier and integrated into the generator skid.
2. The radiator shall be designed for 110 % of the engine heat rejection at the engine
service power at site conditions with the absolute maximum ambient temperature
given in the requisition.
3. The air flow through the radiator shall be away from the engine or towards the outside
of the enclosure or vertically upwards as appropriate for the location of the radiator.
4. For engines installed in enclosures, the radiator and all cooling and ventilation fan
system shall be designed to meet required cooling and ventilation to comply with
specified area classification as defined in the requisition.
5. The blades of forced draft fans shall be non-sparking.
6. The forced draft fan blades shall be designed to withstand an operating temperature of
120 °C (248 °F).
7. The forced draft fan ring for aluminum alloy blades shall be of a spark reducing
material such as reinforced plastic or of brass.
On engines packaged with the Manufacturer's/Supplier’s standard integral
radiators, the Manufacturer's/Supplier’s standard engine driven steel bladed fans
are acceptable.
4.2.5.5 Remotely located cooler
1. If the cooler location is remote from the engine, e.g., not in the wall of an enclosure or
free standing adjacent to the baseplate, the interconnecting piping shall be installed by
the Buyer.
2. The orientation of the air flow from the cooling fan shall be away from the package.
3. The Packager shall ensure continued adequate cooler performance when the wind is
blowing directly against the cooler with a maximum wind velocity of 93 km/hrs
(50 knots).
4. If a remotely located cooler has a fan that is mechanically driven from the engine, the
Packager shall provide line shafting and belt drive as necessary.
5. The cooling system shall include a design feature (e.g., deaeration tank and high point
vents into deaeration tank) for proper deaeration of the entire cooling system (e.g.,
radiator, interconnection piping).
6. The cooling system deaeration tank shall be located at the highest point in the system,
or on the top of the remote radiator.
7. The deaeration tank shall be fitted with a pressure relief cap of the same working
pressure of the engine.
8. A non-pressurised cooling system shall not be used.
9. The deaeration tanks should be sized for more than 15 % of the total volume of the
cooling system (engine, pipework and radiator).
10. The deaeration tank shall be provided with a sight glass for visual check on coolant
level.
4.2.5.6 Fan drives
1. Flexible couplings in the fan drives shall be of the dry type.
4.2.5.7 Belt drives
1. Either toothed belts or V-belts shall be used for fan drives.
2. All belt drives shall be in accordance with ISO 155, ISO 254, ISO 4183, ISO 4184 or
ISO 5292.
3. Driving belts shall be anti-static in accordance with ISO 1813.
4.2.6 Engine electrical system
1. The engine electrical system shall comply with the requirements for electric systems
on the package (8.2).
4.2.7 Starting systems
1. Each engine generator set shall be designed for black start using either, hydraulic or
electric starting system, which will be defined in the requisition.
2. The electric starting system shall be autonomous for each machine.
3. Generator starting shall not be dependent on equipment external to the provided
generator set.
4. Starting batteries shall be rated for six consecutive starts at the lowest stated
generator operating temperature.
5. A charging system shall be provided to ensure the generator batteries are fully
charged after each starting operation.
6. The charging system shall be a DC battery charger powered from the site main power
distribution system.
A requirement for duplicate batteries and charger will be stated in the Requisition
if applicable.
7. For pneumatic and hydraulic systems, the size and arrangement of accumulators (i.e.,
common or individual for each set) shall be agreed with the Buyer.
8. Accumulator(s) shall offer sufficient capacity to allow six attempts to start each diesel
engine generator set without replenishment at lowest ambient temperature.
9. Unless otherwise specified in the requisition, the air accumulator(s) shall be kept
topped up automatically by air compressors on the starting skid provided as part of the
generator set.
Normally, the electric motor driven air compressor will operate ‘on demand’,
supplied and controlled from the generator control panel.
10. The hydraulic starting systems shall include hydraulic pumps as part of a self-
contained system to charge the accumulator(s).
5.1 GENERAL
1. The generator shall be designed, manufactured and tested in accordance with IEC
60034-1 and IEC 60034-14.
2. Generators greater than 2000kW power ratings are considered to be for special
purpose applications. For these applications, the project team shall use this GFS
together with additional generator requirements (to be included in the package
requisition).
1if deviating from this requirement please refer to the Principal for the appropriate deviation
process
a. Subtransient reactance
b. Transient reactance
c. Synchronous reactance
d. Zero sequence reactance
e. Negative sequence reactance
5.5 EFFICIENCY
1. The generator efficiency at nominal load and a power factor of 0.8 shall be not less
than the following:
Table 2 Generator efficiency
5.8 WINDINGS
1. The windings of the generator, and if installed, of the exciter and the pilot exciter, shall
be designed in accordance with IEC 60034-1 and IEC 60034-14.
2. For high voltage generators the winding star point shall be brought out and terminated
in a separate terminal box on the opposite side of the machine to the main terminal
box.
3. A set of star point current transformers shall be provided for fitting in the separate
terminal box together with a matching set for fitting in the switchgear to provide
differential protection.
5.11 BEARINGS
1. The bearing design shall be in accordance with IEC 60034-1 and IEC 60034-14.
2. If bearings are of the grease-lubricated rolling element type, grease nipples and
grease relief devices shall be fitted.
3. Bearings shall have a minimum greasing interval of 4,000 operating hours, but a
greasing interval of greater than 8,000 operating hours is preferred.
4. The required greasing intervals shall be indicated on the rating plate.
5. If sleeve bearings are fitted, a lubricating oil overflow shall be provided which prevents
the bearing from holding an excess of oil while still permitting efficient lubrication when
the machine is running.
6. Measures shall be taken to prevent lubricant from creeping along the shaft or
otherwise gaining access to the insulation of the machine or to any live part thereof.
7. Insulation shall be provided on all bearings unless the generator Manufacturer/Supplier
can demonstrate that rotor stray currents are too low to damage the bearings.
6.1 GENERAL
1. The generator shall be designed to perform in accordance with NEMA Standards
Publication MG1.
2. Medium voltage generator test shall be in accordance with IEEE-115 and NEMA MG1.
3. Generators greater than 2500HP power ratings are considered to be for special
purpose applications. For these applications, the project team shall use this GFS
together with additional generator requirements (to be included in the package
requisition).
6.2 RATING
6.2.1 General
1. The generator shall be capable of supplying full load kilowatts at the frequency and
voltage required by the generator requisition sheet, at 40 °C (104 °F) ambient with a
maximum temperature rise (by resistance) at full load of 80 °C (176 °F).
6.2.2 Fault rating
1. The generator shall be capable of withstanding a maximum bolted single line-to-
ground fault at its terminals without damage, with the neutral solidly grounded.
2. The generator rotor short-time thermal requirements for unbalanced faults shall be as
specified in IEEE/ANSI C50.13 as will limitations for continuous current imbalance.
3. The short time current overload capability shall be 300 % of rated current for ten
seconds and 150 % of rated current for one minute.
d. Voltage adjuster;
e. AVR voltage failure relay (alarm).
4. The AVR shall be of the electronic type provided with a precision voltage adjuster.
5. The AVR shall include frequency-sensing circuitry to limit the ceiling voltage and to
prevent damage to components when the generator is driven at reduced speeds, such
as when starting or when the engine is at idling speed.
6. The AVR shall be equipped with frequency dependent constant voltage (U = constant
down to 90 % rated frequency) and adjustable slope (U/f) facilities.
7. The AVR shall be installed in the generator control panel.
6.4.2 Excitation – Rated current
1. The rated excitation current shall be at least 110 % of the excitation current at the
rated output of the generator under the most stringent operating conditions stated in
the requisition.
2. The excitation system shall be able to cope with any field forcing conditions that the
generator shall experience, e.g., starting large motors.
3. The field forcing capability shall be sufficient to enable graded relay settings to be
made for system fault current protection.
4. Unless otherwise specified on the requisition sheet, an excitation support feature shall
be provided to enable the alternator to support 300 % rated current for ten seconds.
6.4.3 Excitation – Rated voltage
1. The rated voltage of the excitation system shall be at least 110 % of the rotor voltage
at the rated output of the generator under the most stringent conditions stated in the
requisition.
2. The ceiling voltage shall be not less than 120 % of the rated voltage of the exciter.
6.4.4 AHJ regulations
1. When the requisition sheet indicates USCG regulatory jurisdiction, the generator
excitation system shall conform to Section 35.23 of the ABS Rules for Building and
Classing Steel Vessels.
6.4.5 Exciter requirements
1. The exciter shall be a brushless type using a rotating rectifier bridge circuit.
2. The exciter shall be capable of supplying the field excitation current requirements for
the generator and delivering 150% of its rated current for one minute without being
subject to damage.
3. The complete exciter shall be enclosed and protected by a removable cover.
6.4.6 Permanent magnet generator
1. A permanent magnet generator (PMG) pilot exciter shall be provided.
2. The PMG exciter shall provide constant input power to the automatic voltage regulator
to maintain generator voltage and at least 300 % generator short circuit current for
2 seconds.
3. The PMG voltage shall be constant and of such a value that the voltage regulator
output can drive the generator exciter to its saturation voltage.
6.7 EFFICIENCY
1. The generator shall be a standard performance electrical design unless specified
otherwise on the requisition sheet.
2. Guaranteed efficiency values shall be provided for 50 %, 75 % and 100 % of rated
output.
5. The space heater leads shall be securely fastened to the interior of the generator
frame between the external terminal box and the heaters.
6. When indicated on the requisition sheet, space heaters shall be strip heater type
designed for Class 1, Division 2, or Zone 2, Group D, with a T3 temperature code,
rated at voltage and frequency specified on the requisition sheet.
6.8.3 Jacking bolts
1. Jacking bolts shall be provided on all four corners of the generator to accommodate
vertical and horizontal alignment.
6.9 WINDINGS
1. All windings and winding terminations shall be copper.
2. Stator coils shall be form wound.
3. All insulation materials shall be Class F, as defined in IEC 60034-18.
4. The rating of the generator offered by the Manufacturer/Supplier shall be based on a
Class B temperature rise for all parts of the machine windings (stator, rotor and
exciter).
6.11 INSULATION
1. The generator insulation shall conform to NEMA Class F requirements with a Class B,
80 °C (144 °F) rise by resistance over 40 °C (72 °F) ambient.
2. The generator insulation shall be suitable for use under the variety of conditions
specified on the requisition sheet.
3. A sealed, Vacuum Pressure Impregnation (VPI) insulation system shall be used.
6.13 BEARINGS
1. The generator shall be a single or double bearing design, coupled to the engine.
2. Bearing type shall be as indicated on the requisition sheets.
3. Anti-friction bearings shall be grease lubricated, insulated, and sized for radial and
axial thrust load of the rotor at rated speed.
4. Lubricant shall be a synthetic oil based high temperature compound rated for the
maximum temperature rise of the generator nameplate.
5. If bearings are of the grease-lubricated rolling element type, grease nipples and
grease relief devices shall be fitted.
6. Bearings shall have a minimum greasing interval of 4,000 operating hours, but a
greasing interval of greater than 8,000 operating hours is preferred.
7. The required greasing intervals of bearings shall be indicated on the rating plate.
8. If sleeve bearings are fitted, a lubricating oil overflow shall be provided which prevents
the bearing from holding an excess of oil while still permitting efficient lubrication when
the generator is running.
9. Measures shall be taken to prevent lubricant from creeping along the shaft or
otherwise gaining access to the insulation of the generator or to any live part thereof.
7.1 GENERAL
1. Unless otherwise specified in the requisition, the generator set shall be provided with
the following monitoring, control and protection equipment:
a. engine control panel;
b. generator control panel.
Appendix C shows a typical example of a block diagram for a generator set.
2. Unless otherwise specified in the requisition, the engine control panel shall be
combined with the generator control panel in one freestanding cubicle.
3. If the engine control panel is to be installed adjacent to the engine, it shall be
supported with suitable anti-vibration hardware provided by the Packager.
4. Clear physical segregation between engine and generator controls shall be provided.
11. Partitioning between AC power and control sections shall be provided where
necessary to allow adjustment and inspection to be carried out safely.
12. All live terminals of door-mounted equipment having a maximum voltage greater than
24 V shall be shrouded or otherwise protected by barriers to a degree of ingress
protection of at least equal to IP 2X, to prevent inadvertent contact by personnel when
the control equipment enclosure door is open.
13. Barriers in the control equipment enclosure shall be of rigid transparent insulating
material to enable the screened components to be identified.
14. Any relays that can cause tripping of the unit shall not be installed on the control
equipment enclosure door.
15. To prevent inadvertent contact or short circuit by personnel performing control circuit
adjustments or resetting/replacing protective devices, all bare busbars and live
terminals of equipment and components located within the enclosure shall be similarly
protected by barriers or shrouds to a degree of ingress protection of at least IP 20,
unless adequately recessed within the enclosure.
7.4.2 Sub-distribution
1. Each incoming supply to the control panel shall have an appropriate padlockable type
disconnecting device.
2. Any sub-distribution shall be via miniature circuit breakers, manufactured in
accordance with IEC 60898.
3. Switches, including miniature circuit breakers, shall simultaneously de-energize and
isolate all phases and the neutral.
7.4.3 Anti-condensation heaters
1. Adequate provisions shall be made to avoid deterioration of the control panel interior
caused by condensation.
2. Anti-condensation heaters shall be arranged to provide uniform heating of the control
panel.
3. Anti-condensation heaters shall maintain the control panel interior at approximately
5 °C above ambient temperature.
4. The surface temperature of the heater elements shall not exceed the limiting
temperature specified by the Packager.
5. The heater elements shall be protected against accidental touching by personnel
performing tasks in the control panel.
7.4.4 Internal wiring and terminations
1. Insulated stranded copper conductors shall be used for secondary wiring.
2. The size and type of wiring shall be selected according to current carrying capacity,
voltage and mechanical strength.
3. Wiring between terminals shall be continuous and without joints.
4. Wires shall be held in position by means of insulated tubes, channels, cleats or plastic
strips.
5. Wires shall be routed so as to avoid mechanical damage.
6. Channels and tubes shall not be filled to more than 75 % capacity during manufacture.
7. Wiring between fixed portions and hinged doors shall, in addition to the electrical
insulation, have protection against abrasion or entrapment.
8. Wiring between fixed portions and hinged doors shall not cross or be routed along
sharp edges.
earth rail and the earth stud shall be such as to maintain effective continuity of earth
circuits.
8. The minimum size of earth conductors shall be 2.5 mm2 for internal earth connections.
9. Earth connections shall be yellow/green coloured insulated copper flexible wires.
10. Removable metal parts, including doors, shall be earthed.
11. All electrical connections made for earthing shall be accessible to allow checking of
tightness and electrical contact.
7.4.7 Marking
1. All external operating, measuring and indicating components shall be clearly identified
with permanent descriptive labels that facilitate easy recognition by the operator.
2. Descriptive labels shall be white with black lettering.
3. All components shall be identified by labels inscribed in accordance with the system of
identification as used on the Manufacturer's/Supplier’s reference drawings and
documents.
4. All labels shall be of corrosion resistant material with indelible inscriptions in English
unless otherwise specified in the requisition.
5. Rail-mounted terminals of equipment and components shall be identified by numerical
or alphabetical markings in accordance with the Manufacturer's/Supplier’s drawings.
6. Terminals of input and output supply cables shall be clearly marked to indicate the
nominal system voltage and the phase/polarity of the supply.
7. The identification of terminals shall be in accordance with IEC 60445.
8. Wiring between fixed portions and hinged doors shall not cross or be routed along
sharp edges.
9. Individual wires or cables terminating at fixed (not plug-in) components shall be
identified by means of ferrules of insulating material marked in accordance with the
Manufacturer's/Supplier’s drawings.
10. Wrap-around adhesive type markers shall not be used.
11. Terminals shall be of the non-loosening type and only accept one wire, unless the
terminals are specially designed to accept more than one wire.
12. Terminals shall be constructed in such a way that direct contact between screws, bolts
or nuts and the conductor is prevented.
13. Partitions shall be placed between terminals of different voltages.
14. Stranded wiring ends that are to be connected into butt-type contacts and terminals
shall be provided with compression type pre-insulated wire pins with insulation
support.
7.5.6 General wiring, grounding and marking
1. Vendor standard general wiring, grounding and marking shall be in accordance with
vendor standard.
2. All internal cables shall be numbered each end by cable printing or wire markers to
permit fault finding.
8. PACKAGE REQUIREMENTS
8.1 BASEPLATE
1. The generator/engine combination shall be mounted on a common baseplate, made of
structural steel beams and with flat top plates designed for stationary installation.
2. The baseplate shall be designed to withstand transport and lift conditions.
3. A horizontal force equal to the total transport weight shall be assumed for transport
forces in the design of the package.
4. The design should include accommodations for lifting shock forces, in particular for
offshore installation.
5. Welding of main component shall comply with AWS D1.1/D1.1 M or the relevant local
code.
Intermittent welds or stitch welds are not allowed on any structural part of the
skid.
6. The baseplate shall be designed to support the mass of the components and resist the
torque reaction imposed by any operating condition.
7. The baseplate shall be capable of withstanding the shock loads defined in (2.4.2).
8. The baseplate shall be constructed so that it does not interfere with maintenance or
routine servicing of the engine and the generator.
9. No fuel piping shall be contained within the baseplate.
10. The baseplate shall have a drip pan and rim with DN 50-Class/ 150 ASME B16.5
flanged drain connections in strategic locations.
11. Unless specified otherwise in the requisition, the Packager shall supply anti-vibration
mounts to limit the engine vibrations transmitted to the foundations or surroundings.
12. Anti-vibration mounts shall be located between the baseplate and the supporting
structure.
13. Anti-vibration mounts shall be of a totally enclosed type that are designed for the
environment and possess an isolation efficiency of at least 90 % in respect of all
induced vibrations.
14. Full details, including drawings, of the anti-vibration mounts shall be submitted
together with the frequency and magnitude of any unbalanced forces and moments
that will be transmitted through the mounts into the Principal's supporting structure.
15. The baseplate shall be designed to withstand any dynamic forces arising from action
of the anti-vibration mounts.
16. Design of the complete baseplate with the mounted equipment shall be such that
stresses in the rotating components arising from motion of the complete assembly on
the anti-vibration mounts are minimised.
17. The Packager shall furnish the Principal with calculations of resonant frequencies and
the stresses arising on the rotating components.
18. At least two accelerometers shall be mounted on the baseplate to give an alarm on
high vibrations.
19. Lifting lugs shall be attached to the baseplate.
20. The positioning of the lifting lugs shall be positioned according to the centre of gravity
of the complete assembly and be such that lifting slings do not interfere with any
equipment mounted on the baseplate.
21. If a spreader bar is required for lifting, the Packager shall supply it.
22. Lifting lugs shall be designed for a load equal to twice the complete assembly.
23. Lifting lugs shall comply with AWS D1.1/D1.1M or the relevant local code.
24. The area of material where lifting lugs are to be welded shall be clean from any dirt,
paint or grease and tested ultrasonically for laminations prior to welding.
25. Finished welds shall be inspected visually and by magnetic particle testing.
2. Electrical equipment supplied by the Packager other than trays and supports and
requiring external connections shall be wired by the Packager to terminal blocks in
junction boxes located at the edge of the baseplate or to terminals in the control panel.
3. For applications outside North America the following applies:
a. Cabling on the baseplate and the engine cooler assembly shall be flame
retardant and oil resistant, complete with galvanized steel wire braiding and
interwoven copper earth wires.
b. The wire insulation level shall be 600/1000 V.
c. All cabling shall be mounted on AISI 316L stainless steel cable trays.
d. The stainless steel cable trays shall be insulated from the steel structure to
prevent corrosion caused by dissimilar materials.
e. The cable trays shall have equipotential bonding with the baseplate.
f. Cable extensions from cable trays to equipment shall be supported and
protected against mechanical damage.
g. The cables shall be fastened to the cable tray with UV-resistant ties.
h. Cables shall be marked by stainless steel tags or by Critchley 'K' type cable
markers mounted on a carrier strip with ties.
i. Cable markers shall be installed at each gland at both sides of the gland plate.
j. All junction boxes shall have a minimum degree of ingress protection of IP 55.
k. Junction box wire identification, terminal partitions, terminal execution, wire pin
requirements, and spare terminal requirements and earthing provisions shall
comply with (7.4).
4. For applications inside North America the following applies:
a. The Packager shall provide bonding conductors from the engine, generator
and all other package mounted equipment to the baseplate.
b. Two ground bosses, with a NEMA 2-hole pattern, shall be mounted diagonally
on the baseplate for external ground bonding by others.
8.4 NAMEPLATES
1. For applications outside North America the following applies:
a. A list of nameplates, including sizes and character dimensions, shall be
submitted to the Buyer for approval.
b. Text on the nameplates submitted to the Buyer for approval shall be in
English, unless otherwise specified in the requisition.
c. The components of the generator set shall have nameplates in accordance
with the specifications as listed in the requisition.
d. The nameplate described herein shall apply to the complete package.
e. The following information shall be clearly marked on a non-destructible,
corrosion-resistant, indelible name/rating plate attached to a permanent part of
the generator control panel:
i. Manufacturer/ packager’s name and the year package is manufactured
ii. Buyer's order/PO number
iii. Buyer's equipment number
iv. Model number of engine
v. type and serial number of the package;
CAUTION:
SURFACE TEMPERATURE EXCEEDS 60 °C (140 °F).
DO NOT TOUCH.
SERIOUS BURNS CAN OCCUR.
Figure 1 Sign to mount near exposed equipment that can exceed 60 °C (140 °F)
8.6 WELDING
1. Unless otherwise specified in the requisition, all welding, such as welding on
baseplates, piping, flanges, vessels, non-pressure components, supports, control
panels and baseplates shall be performed by welders and weld procedures qualified in
accordance with an recognized standard such as AWS D1.1 for structural steel or
ASME Section IX for pressure vessels and piping.
8.7 PAINTING
1. Unless otherwise specified in the package requisition, all package components which
are susceptible to environmental/external corrosion shall be painted to protect against
corrosion.
Vendor’s proven standard painting is acceptable for packages installed in
services with low humidity.
2. Vendor’s proven Marine grade (sever duty Zinc/Epoxy /Urethane) coating shall be
used for packages installed offshore, in severe services, humid or high chloride
environments.
4. All acoustic enclosure doors shall be fitted with emergency opening bars on the inside.
5. Opening any door for access during generator set operation shall initiate an alarm.
6. Opening any door for access during generator set operation shall not cause a
shutdown of the generator set.
7. For an emergency generator set in an acoustic enclosure, failure of the ventilating air
flow shall not shut down the set.
8. For an emergency generator set in an acoustic enclosure, failure of the ventilating air
flow shall initiate an alarm.
9. Mechanically induced ventilation shall be installed, so as to provide not less than
20 changes of air per hour within the acoustic enclosure, or to limit the temperature
rise within the enclosure to not more than 10 °C (50 °F) above the ambient air
temperature, whichever requires the greater flow rate.
10. The generator set shall run as long as possible in case of failure of the airflow to the
acoustic enclosure or excessive temperature rise in the enclosure.
11. A two-stage filter, comprising an inertial stage followed by a viscous impingement
stage, shall filter ventilation air.
12. The acoustic enclosure shall be fitted with two heat detectors above the engine.
13. Either of two heat detectors above the engine shall shut down the engine upon fire
detection.
14. Initiation of a shutdown shall cause a release of extinguishant into the acoustic
enclosure and simultaneously cause the shutting of a damper in the exhaust air from
the enclosure and shutdown of the ventilating fans.
15. Fire detection and extinction systems shall be physically separate and operate
autonomous for each generator.
16. Unless otherwise approved by the principal, common fire extinguishing system shall
not be used.
17. Emergency and back-up generators shall have dedicated systems.
18. Fire extinguishing systems using carbon dioxide or other asphyxiating gases shall be
inhibited before free access to the acoustic enclosure is allowed.
19. An alarm shall be provided to indicate that the system has been inhibited.
For fire extinguishing systems using water fog, inhibition is not required.
8.8.2 Fire extinguishing system
1. Unless otherwise specified on the requisition, the Manufacturer/Supplier shall provide
a dedicated water mist fire extinguishing system that will be skid mounted and located
adjacent to the main skid.
2. Stainless steel 316 fire dampers shall be provided within the acoustic enclosure as
part of the requirements for fire extinguishing system.
3. The extinguishing system shall be constructed with water wetted components
manufactured in 316 SS material.
4. The extinguishing system shall be capable of depressurization and re-filling from the
facility water system.
5. The pressurized water container shall conform to ASME VIII Div. 1.
6. The pressurized water container shall include a level gauge and drain connection.
7. The extinguishing system shall have automatic and manual actuation of extinguishant
discharge that shuts down all equipment within the acoustic enclosure.
8. A manual actuation station for discharge of the extinguishing system shall be located
immediately outside and adjacent to the access way of the acoustic enclosure.
9. Stainless Steel fire dampers shall be provided within the acoustic enclosure.
10. Alarm/light to be provided on the outside of the acoustic enclosure and control panel at
Switch gear room.
11. The extinguishing system shall have a sufficient quantity of extinguishant to enable a
2-shot actuation within a pre-determined time period, if there is still just cause.
12. The extinguishing system shall be equipped with adequate safeguards to prevent
accidental release of extinguishing due to system tests and extended outages of AC
power, compressed air, or other utilities.
13. The fire and gas detection and suppression system shall fully comply with local
regulation and Classification Society Rules as specified in the requisition.
8.10 TROPICALIZATION
1. If an engine is to be installed in a hot and humid (tropical) climate, the engine, cooling
capacity and its electrical and instrumentation shall be designed and preserved to
ensure reliable operation in the specified climate.
8.11 WINTERIZATION
1. If an engine is intended to operate or be required to start automatically in cold
climates, then cold weather protection is required.
Cold climates are typically defined as temperatures low enough that require
protection of lube oil systems, fuel systems, protection from blowing snow, or
other freezing elements. Winterization of the engine is likely to be executed by the
Packager.
2. Winterization of the engine may include oversized oil heaters, heat tracing, package
enclosure, fuel heaters.
2. The engine factory acceptance test (FAT) shall be witnessed by the Principal.
10.3.2 Generator
1. The generator shall be tested according to Manufacturer/Supplier standard
requirements.
2. The generator FAT shall be witnessed by the Principal.
11.1 GENERAL
1. The generator set shall be prepared for shipment after all testing and inspections have
been completed, and the equipment has been painted.
2. The generator set shall be prepared for the type of shipment specified, including
blocking of rotors where necessary.
3. Corrosion-resistant tags attached with stainless steel wire shall identify blocked rotors.
4. The generator set preparation shall make the equipment fitted for 6 months’ (or for a
period as stated in the requisition) outdoor storage from the time of shipment, with no
disassembly required before operation.
5. Internal bracing or supports for shipping shall be clearly identified, preferably by
painting in a distinctive colour.
6. Lifting points and the centre of gravity shall be clearly identified on the equipment
packages.
7. The Packager shall provide a recommended lifting arrangement.
8. The equipment shall be identified by item and serial number.
9. Materials shipped separately from the generator shall be identified by securely
attached corrosion-resistant metal tags indicating the item and serial number of the
equipment for which it is intended.
10. Crated equipment shall be shipped with duplicate packing lists, one inside and one on
the outside of the crate.
11.2 PRESERVATION
1. The Packager shall provide instructions for maintaining the integrity of the preservation
for the period between arrival at site and start-up of the generator set.
2. Exterior machined surfaces shall be coated with a rust preventative, e.g., VCI to
protect against atmospheric corrosion.
3. The interior of all equipment shall be clean, free from scale, welding spatter, and
foreign objects.
4. Mechanical equipment shall be sprayed or flushed with a rust preventative, e.g., VCI
that can be removed with solvent.
5. The rust preventative shall be applied through all openings of the mechanical
equipment while the engine is slow-rolled.
6. Internal steel areas of bearing housings and carbon steel oil systems, auxiliary
equipment and piping (except for cooling water piping) shall be coated with an oil-
soluble rust preventative, e.g., VCI.
7. Preservation agents containing calcium and/or silicone compounds shall not be used
on the generator set as they cause subsequent foaming of the lubricating oil.
8. All coolants shall be drained from the engine, coolers and piping.
9. The interior of the coolant system shall be preserved by a water soluble film.
10. All flanged openings shall be closed with metal closures 5 mm thick, with elastomer
gaskets and at least four full-diameter bolts.
11. Plastic or wooden plates/closures shall not be used.
12. All open ends of drains, vents, instrument tubing and small bore piping connections
shall be capped or plugged with metal caps or plugs.
13. Threaded caps or plugs shall be used for threaded connections.
11.3 BATTERIES
1. Unless otherwise specified on the requisition Nickel-cadmium batteries shall be
supplied dry and discharged, with the electrolyte packed separately.
2. If Lead-acid recombination type batteries are specified in the requisition, they shall
receive a commissioning charge within a period after leaving the factory, as specified
by the Manufacturer/Supplier.
13. DOCUMENTATION
13.1 GENERAL
1. All documents shall be marked in the right-hand bottom corner with the Buyer's order
and item number together with the Packager's references.
2. Packager shall provide all documentation in accordance with the vendor document and
data requirements (VDDR) and as shown in the vendor provided schedule.
3. Packager shall use the sample VDDR included in Appendix D as the basis to prepare
its proposal.
2. The Packager shall submit as a minimum the following information and data:
a. completed technical request for information;
b. piping layout;
c. instrument diagram;
d. general arrangement drawing of all equipment also showing dry and operating
masses, arrangement of components, cable entry details, minimum space
required for erection and maintenance;
e. 3D modelling of the package with standard formatting to allow importing the
model into PDMS or comparable programs.
f. schedule and drawing of electrical, instrument and mechanical termination
points;
g. foundation requirements;
h. baseplate construction data;
i. dynamic performance calculations;
j. torsional and lateral vibration data;
k. structural dynamic calculations for generator set vibration, taking account of
anti-vibration mounts;
l. schematic and connection diagrams of main, control, status indication, alarm,
metering, protection, trip, shutdown and auxiliary circuits;
m. alarm and trip setting schedules;
n. material specifications;
o. equipment lists/parts lists;
p. recommended spare parts lists as defined in the requisition by completing
Shell ESPIR Spreadsheet.
i. Access to the Spreadsheet shall be provided by the Principal.
ii. Buyer shall provide the latest spreadsheet and instruction post award.
q. preservation for shipment procedures;
r. operating manuals incorporating unpacking, depreservation, installation,
commissioning, operating and maintenance instructions and fault finding
procedures;
s. Manufacturer's/Supplier’s proposed service and repair support after warranty;
t. test and inspection procedures;
u. testing programme;
v. certificates of conformity and declarations of compliance for equipment used in
hazardous areas;
w. reports of all tests performed;
x. Contractor shall provide detailed engineering component information
according to the project format as specified in the package requisition.
14. REFERENCES
GFSs specified on a project will be delivered on an as needed basis:
• The parts developed by Shell (together with the Vendor) will be made available by Shell
to the Contractor
• The parts developed by the Vendor (as agreed with Shell standardization Team) will be
made available by the Vendor
In this GFS, reference is made to the following publications:
NOTES: 1. Unless specifically designated by date, the latest edition of each publication
shall be used, together with any amendments/supplements/revisions thereto.
2. The DEPs, SPEPs, GFSs and most referenced external standards are
available to Shell staff on the SWW (Shell Wide Web) at
http://sww.shell.com/standards/.
AMERICAN STANDARDS
ABS Rules for Building and Classing Steel Vessels
www.scribd.com/doc/177008814/ABS-Rules-for-Building-and-
Classing-Steel-Vessels-2014
Pipe flanges and flanged fittings NPS ½ through NPS 24 Metric/Inch ASME B16.5
Standard
Section VIII Division I rules for construction of pressure vessels ASME VIII Div. 1
Section IX qualification standard for welding, brazing, and fuzing ASME Section IX
procedures; welders; brazers; and welding, brazing, and fusing
operators – welding, brazing and fusing qualifications
Standard specification for diesel fuel oils ASTM D975
Standard practice for human engineering design for marine systems, ASTM F1166
equipment, and facilities
Structural welding code – Steel AWS D1.1/D1.1M
Metal-enclosed low-voltage (1000 vac and below, 3200 vdc and IEEE C37.20.1:2015
below) power circuit breaker switchgear
Cylindrical-rotor 50 Hz and 60 Hz synchronous generators rated 10 IEEE C50.13
MVA and above
Issued by: IEEE - The Institute of Electrical and Electronics Engineers, Inc.
BRITISH STANDARDS
Specification for flanges and bolting for pipes, valves and fittings BS 10
INTERNATIONAL STANDARDS
Rotating electrical machines - Part 1: Rating and performance IEC 60034-1
Part 6: Methods of cooling (IC Code) IEC 60034-6
Part 14: Mechanical vibration of certain machines with shaft heights IEC 60034-14
56 mm and higher – measurement, evaluation and limits of vibration
severity
Part 18-1: Functional evaluation of insulation systems – general IEC 60034-18
guidelines
Direct acting indicating analogue electrical measuring instruments IEC 60051
and their accessories, Parts 1 through 9
Explosive atmospheres - Part 15: Equipment protection by type of IEC 60079-15
protection "n"
Basic and safety principles for man-machine interface, marking and IEC 60445
identification – identification of equipment terminals, conductor
terminations and conductors
Degrees of protection provided by enclosures (IP Code) IEC 60529
Electrical Accessories - circuit breakers for overcurrent protection for IEC 60898
household and similar installations
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - IEC 61000-6-2
immunity for industrial environments
Electromagnetic compatibility (EMC) – Part 6-4: Generic standards – IEC 61000-6-4
emission standard for industrial environments
Low-voltage switchgear and controlgear assemblies IEC 61439
Belt drives – pulleys – limiting values for adjustment of centres ISO 155
Belt drives – pulleys – quality, finish and balance ISO 254
Belt-drives – V-ribbed belts, joined V-belts, and V-belts including ISO 1813
wide section belts and hexagonal belts – electrical conductivity of
antistatic belts: characteristics and methods of test
Reciprocating internal combustion engine drive alternating current ISO 8528-1
generating sets Part 1: Application, ratings and performance
Reciprocating internal combustion engines – performance – Part 1: ISO 3046-1
Declarations of power, fuel and lubricating oil consumptions, and test
methods – additional requirements for engines for general use
Part 3: Test measurements ISO 3046-3
Part 4: Speed governing ISO 3046-4
Part 5: Torsional vibrations ISO 3046-5
Part 6: Overspeed protection ISO 3046-6
Part 7: Codes for engine power ISO 3046-7
Belt drives – classical and narrow V-belts – grooved pulleys (system ISO 4183
based on datum width)
Belt drives – classical and narrow V-belts – lengths in datum system ISO 4184
Belt drives – V-belts and V-ribbed belts – calculation of power ratings ISO 5292
Mechanical vibration – Evaluation of machine vibration by ISO 10816-1
1. The project and Engineering Contractor shall apply the standards as been specified
above and no project specific technical standards and/or specifications shall be
made on top of these.
It is recognized that the Engineering Contractor has its own procedures and
standards to manage a project, from that perspective it is allowed to develop a
limited number of project specific standards, specifications, procedures that are
required to manage and administer the project execution.
NOTES: *1. Where a restricted earth-fault relay is used for generator differential protection
the separate stator earth-fault relay may be omitted.
*2. To be provided only where there is continuous parallel operation with public
grid or other generator sets.
*3. Shutdown of engine required in addition to generator trip.
*4. Status indication required on each application.
*5. Mandatory functions.
Hours run X*
Turbocharger speed X H
L
Engine vibration X
Cylinder head vibration(1) X
Turbocharger vibration X H
Fan vibration X H
Start sequence X
Start sequence fail X X
Controls fail X X
Mode of operation X
Crankshaft keyphaser X
Temperature
Lube oil to engine X* H
L(3)
Lube oil to cooler X H
Lube oil from cooler X H
L
Coolant to engine X H
L
Coolant from engine(2) X* H
Air inlet manifold X
Exhaust - each cylinder X XH
XL
Exhaust - turbocharger inlet X
Exhaust - turbocharger outlet X
Main bearings X
Big end bearings X
Turbocharger bearings X
Pressure
Lube oil X* L
Differential Pressure
Lube oil filter X* H
Air filter X* H
Level
Lube oil sump X* L
Coolant X* L
Battery charger on X* L
Instrument power X* L