DOCUMENT NUMBER DOCUMENT NAME

AD2-C1-00-GHC-PSD-IDM-00693 Demi Water Storage and Distribution System.


System Description
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
2 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

CONTENTS:

1. AIM .........................................................................................................................................3
2. GENERAL DESCRIPTION .....................................................................................................4
2.1 Main functions .............................................................................................................4
2.2 Description .................................................................................................................. 4
2.3 MAIN EQUIPMENT .....................................................................................................5
3. INTERFACES .........................................................................................................................9
3.1 General .......................................................................................................................9
3.2 Support systems .........................................................................................................9
3.3 Dependent systems .................................................................................................... 9
4. OPERATION CONCEPT ...................................................................................................... 10
4.1 NORMAL OPERATION ............................................................................................. 10
4.2 START-UP ................................................................................................................ 10
4.3 SHUTDOWN ............................................................................................................. 11
5. INSTRUMENTATION AND CONTROL................................................................................. 12
5.1 Instrumentation ......................................................................................................... 12
5.2 Control ...................................................................................................................... 12
6. REFERENCE DOCUMENTS ................................................................................................ 24
7. ANNEXES ............................................................................................................................ 26
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
3 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

1. AIM

The aim of this document is to provide a description of the Demineralized Water Storage
and Distribution System for Al Dur II Project, to be erected by SEPCOIII in Bahrain.

This document define the purpose, characteristics, control and protection philosophy for the
above mentioned system.
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
4 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

2. GENERAL DESCRIPTION

2.1 Main functions

The main function of the Demineralized Water Storage and Distribution System is the
storage and supply of demineralized water for the following services:

 Steam/water cycle make up and for system first filling

 GT 11/12/21/22 compressor washing system

 Closed cooling water system filling and make up

 Dillution water for chemical dosing systems

 GT 11/12/21/22 air preheating water system filling

 GRMS water bath heaters filling and sealing of condensate pumps.

 Laboratory

 H2 generators

 ST 10/20 liquid ring vacuum pumps filling

2.2 Description

The system is based on production of demineralized water from 2nd pass RO permeate
provided by the desalination plant. This water is passed through ion exchange resin mixed
beds to produce demineralized water of very high purity.

The system will include the following equipment:

 2 x 50% 2nd pass permeate tanks

 3 x 50% mixed bed polishers


PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
5 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

 2 x 50% demineralized water tanks

 2 x 100% demineralized water distribution pumps

Water is received from the desalination plant at sufficient pressure for filling the two tanks
of 2nd pass permeate based on the level in the tanks. From these tanks, the mixed bed
polisher is fed to produce demineralized water.

The main process of this plant is ion removal/exchange treatment of the 2nd pass permeate
to yield demineralized water. The configuration of the plant is 3 x 50% trains of ion exchange
resins arranged in mixed beds, including also 3 x 50% pumps. Strong acid cation (SAC)
and strong base anion (SBA) resins will be used. Design production cycle between
regenerations is established in a minimum of 72 h for water with TDS content of 20 ppm.
The plant includes regeneration system for exhausted resins by means of hydrochloric acid
and caustic soda. Regeneration system includes chemical storage, metering pumps,
dilution pumps and related piping and instrumentation. Regeneration effluents rejected from
the plant package are discharged to the neutralization plant

The water produced in the mixed beds is used to fill the 2 x 50% demineralized water tanks.
From these tanks, demineralized water is distributed to all the consumers of the plant.

For distribution of demineralized water, there are 2 x 100% capacity demineralized water
distribution pumps. These pumps raise the pressure of the water from the demineralized
water tanks to supply demineralized water to the plant consumers with enough pressure. In
normal operation, only one pump is running while the other is in stand-by mode, ready to
start in case of failure of the running one. The pumps are protected in the suction by
strainers provided with differential pressure transmitter for monitoring and they also include
a minimum recirculation control loop with control valve to ensure pumps are always working
above the minimum required flowrate.

2.3 MAIN EQUIPMENT

In this section most relevant equipment and components of the system are highlighted.
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
6 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

2.3.1. 2nd pass permeate tanks

KKS: 00GHC23BB001 / 00GHC24BB001

Type of equipment: water storage tank (API 650 type)

Maintenance: if needed, during outage of the plant

Control function: N/A

Reference drawings:

 AD2-C1-00-GHC-MDW-LAN-00001 2nd Pass Permeate Tank A/B

2.3.2. Mixed bed polisher

KKS: N/A

Type of equipment: package plant for production of demineralized water by ion exchange
resins

Maintenance: yes, as per vendor maintenance schedule

Control function: N/A

Reference drawings:

 AD2-C1-00-GHC-GGP-WET-00001 System Description

 AD2-C1-00-GHC-GGP-WET-00005 O&M, and start/up commissioning manuals

 AD2-C1-00-GHC-GDW-WET-00501 General arrangement drawings

 AD2-C1-00-GHC-MDW-WET-00502 P&ID

 AD2-C1-00-GHC-MDS-WET-00503 Data sheets for Compressed air vessel

 AD2-C1-00-GHC-MDS-WET-00504 Data sheets for pumps


PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
7 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

 AD2-C1-00-GHC-MDS-WET-00505 Data sheets for Self-cleaning filter

 AD2-C1-00-GHC-MDS-WET-00506 Data sheets for Regeneration dosing system

 AD2-C1-00-GHC-MDS-WET-00507 Data sheets for Mixed Ion-exchanger

 AD2-C1-00-GHC-MDS-WET-00508 Data sheets for Manual valve

 AD2-C1-00-GHC-IDW-WET-06001 Control logic diagrams

 AD2-C1-00-GHC-ILS-WET-06007 List of Process Settings and Alarms

2.3.3. Demineralized water tanks

KKS: 00GHC43BB001 / 00GHC44BB001

Type of equipment: water storage tank (API 650 type)

Maintenance: if needed, during outage of the plant

Control function: N/A

Reference drawings:

 AD2-C1-00-GHC-MDW-LAN-00011 Demineralized Tank A/B

2.3.4. Demineralized water distribution pumps

KKS: 00GHC51AP001 / 00GHC52AP001

Type of equipment: centrifugal pump

Maintenance: as per pump maintenance schedule

Control function: N/A


PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
8 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

Reference drawings:

 AD2-C1-00-YMB-MDS-CWO-03000 Pump datasheet

 AD2-C1-00-YMB-MDW-CWO-03003 Pump curves

 AD2-C1-00-YMB-MDW-CWO-03001 Pump GA drawing


PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
9 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

3. INTERFACES

3.1 General

The interfaces of the Demineralized Water Storage and Distribution System with other
systems or related equipment are described below. The interfaces are classified according
to those that are necessary for the operation of the system (support systems) or according
to those that are provided by the system and are necessary in order to allow other systems
to carry out their functions (dependent systems).

3.2 Support systems

 Mechanical systems

o Compressed Air System. For operation of pneumatic valves.

o Plant Drainage System: for collection of drains of the system.

o Desalination plant. To provide 2nd pass permeate.

 Electrical Systems

o Low voltage system.

o For operation of motorized valves.

o For operation of the demineralized water distribution pumps.

 Control Systems

o Distributed Control System (DCS): To control the system.

3.3 Dependent systems

All the consumers indicated in section 2.1.


PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
10 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

4. OPERATION CONCEPT

4.1 NORMAL OPERATION

Demineralized water is a basic system required in several areas/systems of the plant for
cycle make up, GT compressor washing, filling of closed circuits and other uses. Therefore
this system must be continuously operating.

In normal operation the status of the main equipment and components will be as follows:

 Both 2nd pass permeate tanks will be operating, maintaining the stock of water in the
tanks through the automatic filling system (water provided from desalination plant).

 Mixed bed polisher plant will operate as required to maintain demineralized water
tanks in full condition. As the capacity of the plant is higher than the normal demand
of demineralized water, it is expected that mixed bed polisher plant will operate
intermittently, starting and stoping based on the level in the downstream tanks.

 Both demineralized water tanks will be operating, maintaining the stock of water in
the tanks sending start and stop commands to the mixed bed polisher plant.

 One demineralized water distribution pump will operate continuosly, maintaining the
pressure in the distribution header to supply any demand when required. In case of
low demand, the minimum recirculation control valve will open as required to
maintain the pumps always above the minimum flowrate needed.

4.2 START-UP

For the start up of this system, the following conditions are required:

 Electrical and control systems are operating/available

 Instrument air is operating/available

 Piping distribution system is full of water and air is properly vented from all high
points.
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
11 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

Start up of this system is done automatically and is summarized in the following events:

 2nd pass permeate tanks filling valves of are put in auto to maintain the tanks full
(this requires the desalination plant to be in operation).

 Mixed bed polisher plant is available to be started/stopped as required by the level


of the demineralized water tanks.

 Demineralized water tanks filling valves of are put in auto to maintain the tanks full
(this requires the mixed bed polisher plant to be available).

 One demineralized water distribution pump is started.

 Minimum recirculation control loop is put in auto.

4.3 SHUTDOWN

The shutdown of this system should be done only after all systems are shutdown as this
system provides demineralized water through all the plant.

The shutdown of the system is done automatically and is summarized in the following
events:

 Mixed bed polisher plant is stopped

 Demineralized water distribution pump running is stopped

 Control and on-off valves are positioned in initial/default position


PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
12 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

5. INSTRUMENTATION AND CONTROL

5.1 Instrumentation

Instruments are represented on the following Piping and Instrumentation Diagram (P&ID):

 AD2-C1-00-GHC-PDW-IDM-00691 Demi water storage and distribution system


P&ID

5.2 Control

In this section, descriptive narrative is provided for the control and protection of the system.
For details on the logics of this system refer to the following document:

 AD2-C1-00-GHC-IDW-IDM-06762 Demi Water Storage and Distribution System.


Logic Diagrams.

The below table summarizes the actuators of the system:

KKS Service Type Notes


00GHC21AA101 2nd pass permeate tank On-off motorized
00GHC23BB001 filling valve
valve
00GHC22AA101 2nd pass permeate tank On-off motorized
00GHC24BB001 filling valve
valve
- Mixed bed polisher Package plant
00GHC41AA101 Demineralized water tank On-off motorized
00GHC43BB001 filling valve
valve
00GHC42AA101 Demineralized water tank On-off motorized
00GHC44BB001 filling valve
valve
00GHC51AP001 Demineralized water Pump
distribution pump 1
00GHC52AP001 Demineralized water Pump
distribution pump 2
00GHC56AA201 Demineralized water Pneumatic control
distribution pumps valve
recirculation control valve
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
13 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

5.2.1. Water Treatment System Functional Group (00GHC40EE100)

Water Treatment System functional group is in charge of managing the start/stop or


open/close of each individual device to respond to the measured parameters of the Water
Treatment water.The actuators / drives included in this functional group are shown in the
table of paragraph 5.2.

Water Treatment System Functional Group receives the AUTO order from the Automatic
Plant Sequencer.

The below table summarizes the logic for the Water Treatment System Functional Group:

00GHC40EE100 Water Treatment Plant Functional Group

Manual Reject N/A


Auto permitted Always permitted
On permitted Always permitted
Off permitted Always permitted
Auto Selection Water Treatment Plant Group ON Command from
Automatic Plant Sequencer (00GHC40EE100: XA61, as
pulse)
Auto On command Water Treatment Plant Group ON Command from
Automatic Plant Sequencer (00GHC40EE100: XA61, as
pulse) (for certain time delay)
Auto Off command N/A
Force On N/A
Force Off N/A
No Discrepancy All pump drives and actuators in AUTO
AND
Water Treatment Plant in remote mode
(00GHC40GH001:XA57)
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
14 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

5.2.2. 2nd pass permeate tanks filling valves (00GHC21AA101 / 00GHC22AA101)

These valves open and close based on the level of the corresponding 2nd pass permeate
tank. When the level is below low level, they open to allow the 2nd pass permeate filling the
tank. Once the level reaches the high setting, the valves automatically close, to avoid
overfilling.

In case of very high level in the tank the valves are forced closed and in case of very low
level they are forced open.

00GHC21AA101 2nd Pass Permeate Tank 1 Make Up MOV

Manual Reject N/A


Auto permitted Always Permitted
On permitted Always Permitted
Off permitted Always Permitted
Auto Selection Auto Order from Water Treatment Plant System Group
(00GHC40EE100:XA93)
Auto Open command Demi Water System Group ON Command
(00GHC10EE100:XA91)
AND
2nd Pass Permt Tank 1 Level Low
(00GHC23CL901:XH52)
Auto Close command Demi Water System Group OFF Command from
(00GHC10EE100:XA92)
OR
2nd Pass Permt Tank 1 Level High
(00GHC23CL901:XH01)
Force Open 2nd Pass Permt Tank 1 Level Low Low
(00GHC23CL901:XH54)
Force Close 2nd Pass Permt Tank 1 Level High High High
(00GHC23CL901:XH06)
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
15 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

00GHC22AA101 2nd Pass Permeate Tank 2 Make Up MOV

Manual Reject N/A


Auto permitted Always Permitted
On permitted Always Permitted
Off permitted Always Permitted
Auto Selection Auto Ord from Water Treatment Plant System Group
(00GHC40EE100:XA93)
Auto Open command Demi Water System Group ON Command
(00GHC10EE100:XA91)
AND
2nd Pass Permt Tank 2 Level Low
(00GHC24CL901:XH52)
Auto Close command Demi Water System Group OFF Command from
(00GHC10EE100:XA92)
OR
2nd Pass Permt Tank 2 Level High
(00GHC24CL901:XH01)
Force Open 2nd Pass Permt Tank 2 Level Low Low
(00GHC24CL901:XH54)
Force Close 2nd Pass Permt Tank 2 Level High High High
(00GHC24CL901:XH06)

5.2.3. Mixed bed polisher

The mixed bed polisher is a package plant with its own system for control, monitoring and
protection. However, this package has an interface with the DCS in order to exchange
signals as main commands, status of the plant, main alarms, etc. The details of this interface
can be seen in the logic diagrams of the system referenced in section 5.2.

This plant is commanded from the DCS to start and stop based on the level of the
demineralized water tanks. When the level is below low level, the plant is commanded to
start. Once the level reaches the high setting, the plant is commanded to stop, to avoid
overfilling.
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
16 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

For more details of this package refer to the documentation from the vendor included in
section 2.3.2.

00GHC40GH001 Water Treatment Plant System

Start command [[{Demi Water tank 1 Level Low (00GHC43CL901:XH52)


AND
Demi Water Tank1 Makeup MOV Open
(00GHC41AA101:XB81)}
OR
{Demi Water tank 2 Level Low (00GHC44CL901:XH52)
AND
Demi Water Tank2 Makeup MOV Open
(00GHC42AA101:XB81)}]
AND
Water Treatment Plant Ready to Start
(00GHC40GH001:XB84)
AND
Water Treatment Plant Group ON Command
(00GHC40EE100:XA91)
OR
Water Treatment Plant Ready to Start
(00GHC40GH001:XB84)
AND
Water Treatment Plant start Command
(00GHC40GH001:XL91)
AND
NOT Stop Command
(00GHC40GH001:XB92)
Stop command [[{Demi Water Tank1 Makeup MOV NOT Open
(00GHC41AA101:XB81)}
OR
Demi Water tank 1 Level High (00GHC43CL901:XH01)}
AND
{Demi Water Tank2 Makeup MOV Open
(00GHC42AA101:XB81)
OR
Demi Water tank 2 Level High (00GHC44CL901:XH52)}]
OR
(Water Treatment Plant Group OFF Command
(00GHC40EE100:XA92)
OR
Water Treatment Plant stop Command
(00GHC40GH001:XL92)
OR
[{2nd Pass permit Tank1 Level 3LO (00GHC23CL901:XH56)
OR
2nd Pass permit Tank1 Outlet Manual Valve NOT Open
(00GHC23CG301:XL01)}
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
17 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

00GHC40GH001 Water Treatment Plant System

AND
{2nd Pass permit Tank2 Level Low (00GHC24CL901:XH56)
OR
2nd Pass permit Tank2 Outlet Manual Valve NOT Open
(00GHC24CG301:XL01)}]] (with a certain time delay)

5.2.4. Demineralized Water System Functional Group (00GHC10EE100)

Demi Water System functional group is in charge of managing the start/stop or open/close
of each individual device to respond to the measured parameters of the Demineralized
water.The actuators / drives included in this functional group are shown in the table of
paragraph 5.2.

Demineralized Water System Functional Group receives the AUTO order from the
Automatic Plant Sequencer.

The below table summarizes the logic for the Demi Water System Functional Group:

00GHC50EE100 Demi Water System Functional Group

Manual Reject N/A


Auto permitted Always permitted
On permitted Always permitted
Off permitted Always permitted
Auto Selection Demi Water System Group ON Command from
Automatic Plant Sequencer (00GHC50EE100: XA61, as
pulse)
Auto On command Demi Water System Group ON Command from
Automatic Plant Sequencer (00GHC50EE100: XA61, as
pulse) (for certain time delay)
Auto Off command N/A
Force On N/A
Force Off N/A
No Discrepancy All pump drives and actuators in AUTO
AND
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
18 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

2ACT Demi Water pumps manager No Discrepancy


(00GHC50EE100)

5.2.5. Demineralized water tanks filling valves (00GHC41AA101 / 00GHC42AA101)

These valves open and close based on the level of the corresponding demineralized water
tank. When the level is below low level, they open to allow water from the mixed beds
polisher filling the tank. Once the level reaches the high setting, the valves automatically
close, to avoid overfilling.

In case of very high level in the tank the valves are forced closed and in case of very low
level they are forced open.

00GHC41AA101 Demi Water Tank 1 Make Up MOV

Manual Reject N/A


Auto permitted Always Permitted
On permitted Always Permitted
Off permitted Always Permitted
Auto Selection Demi Water System Group Auto Ord from Demi Water
System Group (00GHC50EE100:XA93)
Auto Open command Demi Water System Group ON Command from Demi
Water System Group (00GHC50EE100:XA91)
AND
Demi Water Tank 1 Level Low (00GHC43CL901:XH52)
Auto Close command Demi Water System Group OFF Command from Demi
Water System Group (00GHC50EE100:XA92)
OR
Demi Water Tank 1 Level High (00GHC43CL901:XH01)
Force Open Demi Water Tank 1 Level Low Low
(00GHC43CL901:XH54)
Force Close Demi Water Tank 1 Level High High High
(00GHC43CL901:XH05)
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
19 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

00GHC42AA101 Demi Water Tank 2 Make Up MOV

Manual Reject N/A


Auto permitted Always Permitted
On permitted Always Permitted
Off permitted Always Permitted
Auto Selection Demi Water System Group Auto Ord from Demi Water
System Group (00GHC50EE100:XA93)
Auto Open command Demi Water System Group ON Command from Demi
Water System Group (00GHC50EE100:XA91)
AND
Demi Water Tank 1 Level Low (00GHC44CL901:XH52)
Auto Close command Demi Water System Group OFF Command from Demi
Water System Group (00GHC50EE100:XA92)
OR
Demi Water Tank 2 Level High (00GHC44CL901:XH01)
Force Open Demi Water Tank 1 Level Low Low
(00GHC44CL901:XH54)
Force Close Demi Water Tank 1 Level High High High
(00GHC44CL901:XH05)

5.2.6. Demineralized water Pumps Manager (00GHC50EE200)

Demineralized water Pumps manager’s function is to manage the automatic change over
(ACO) between the Demineralized Water Pumps, to select the lead / lag pump motor and
define the number of required pump motors to be in service following the requirements of
the system.

The below table summarizes the logic for the Demineralized water Pumps Manager (2ACT):

00GHC50EE200 Demi Water Pumps Manager (2ACT)

Change Over N/A


2 Actuators Required N/A
1 Actuators Required ON order from Demi Water System Functional Group
(00GHC50EE100)
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
20 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

00GHC50EE200 Demi Water Pumps Manager (2ACT)

AND
None of the Demi Water pumps in OFF force condition
(00GHC51/52AP001)
0 Actuators Required OFF order from Demi Water System functional group
(00GHC50EE100)
OR
Any of the Demi Water pumps OFF force command
(00GHC51/52AP001)
Fault Demi Water pumps NOT started (00GHC51/52AP001)
AND
[(Demi Water Water pumps NOT in Auto
(00GHC51/52AP001)
OR
(Demi Water pumps Fault (00GHC51/52AP001)
OR
(Demi Water pumps NOT on Permit (00GHC51/52AP001)
OR
(Demi Water pumps OFF force (00GHC51/52AP001)
OR
(Demi Water pumps TRIPPED (00GHC51/52AP001)]
ON Feedback
Demi Water pumps started (00GHC51/52AP001)

5.2.7. Demineralized water distribution pumps 00GHC51/52AP001

There are 2 x 100% demineralized water distribution pumps. In normal operation, one pump
is requested to operate continuously and the other pump is in standby (for automatic start
in case the lead pump fails).

The pump operation is monitored by pressure transmitters in the discharge common


header. In case of very low pressure, the pump is tripped as this may be indicative of some
problems with the running pump.

The pump operation is also monitored by flowrate transmitters in the discharge common
header. In case of very low flow or very high flow, the pump is tripped as this may be
indicative of some problems with the running pump.
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
21 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

00GHC51/52AP001 Demi Water Pump 1/2

Manual Reject N/A


Auto permitted Always Permitted
On permitted Demi Water Tank 1 Outlet Manual Valve Open
(00GHC43CG301:XL01)
AND
Demi Water Tank 1 Level NOT
2LO(00GHC43CL901:XH54)
AND
Demi Water Tank 1 Level NOT Bad Quality
(00GHC43CL901:XM26)
OR
Demi Water Tank 2 Outlet Manual Valve Open
(00GHC44CG301:XL01)
AND
Demi Water Tank 2 Level 2LO(00GHC44CL901:XH54)
AND
Demi Water Tank 2 Level NOT Bad Quality
(00GHC44CL901:XM26)
Off permitted Always Permitted
Auto Selection Demi Water System Group Auto Ord from Demi Water
System Group (00GHC50EE100:XA93)
Auto ON command 2 ACT 2 ACT Demi Water Pump1/2 ON Command.
(00GHC50EE200:XA62/64)
Auto OFF command 2 ACT 2 ACT Demi Water Pump1/2 OFF Command.
(00GHC50EE200:XA61/63)
Force ON N/A
Force OFF [Demi Water Tank 1 Outlet Manual Valve NOT Open
(00GHC43CG301:XL01)
OR
Demi Water Tank 1 Level BDQ (00GHC43CL901:XM26)
OR
Demi Water Tank 1 Level 3LO(00GHC43CL901:XH56)]
AND
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
22 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

00GHC51/52AP001 Demi Water Pump 1/2

[Demi Water Tank 2 Outlet Manual Valve NOT Open


(00GHC44CG301:XL01)
OR
Demi Water Tank 2 Level BDQ (00GHC44CL901:XM26)
OR
Demi Water Tank 2 Level 3LO(00GHC44CL901:XH56)]
Trip Demi Water PPS Discharge Pressure 3LO
(00GHC55CP901:XH56)
OR
Demi Water PPS Discharge flow 3LO
(00GHC55CF901:XH56)
OR
Demi Water PPS Discharge flow 3HI
(00GHC55CF901:XH56)
OR
Demi Water PPS Discharge flow BDQ
(00GHC55CF901:XM26)
AND
Demi Water Pump 1/2 Running (00GHC51/52AP001:XB61)
With some time delay.

5.2.8. Demineralized water distribution pumps recirculation control valve 00GHC56AA201

This control valve is in charge of ensuring the demineralized water distribution pumps are
always working above the minimum flowrate required by the pump.

This valve is part of a control loop with the following characteristics:

 Process variable: demineralized water common header flow rate


(00GHC55CF001/002)

 Final control element: demineralized water distribution pumps recirculation control


valve 00GHC56AA201

 Set point: refer to the system settings given in annex 1.


PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
23 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

00GHC56AA201 Demi Water Pumps Recirculation CV

Manual reject Demi Water discharge flow Bad quality


(00GHC55CF901:XM26)
Auto permitted Always permitted
Modulate permitted Either of the Demi Water Pumps running
(00GHC51/52AP001:XB61)
OR
Demi Water System Group ON command
(00GHC50EE100:XA91)
Auto selection Auto Sel. order from Demi Water functional Group
(00GHC50EE100:XA93)
Remote setpoint SP
Process value Demi Water Pumps discharge flow (00GHC55CF901)
Tracking command N/A
Tracking value N/A
Force open N/A
Force close N/A
Action Reverse
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
24 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

6. REFERENCE DOCUMENTS

Main system documents


AD2-C1-00-GHC-PDW-IDM-00691 Demi water storage and distribution system P&ID
AD2-C1-00-GHC-PCR-IDM-00692 Demi Water Storage and Distribution System. Calculation Note
Control documents
AD2-C1-00-GHC-IDW-IDM-06762 Demi Water Storage and Distribution System Logic Diagrams
AD2-C1-00-YDS-IDW-IDM-06740 Logic Control Diagrams Symbology
AD2-C1-00-YYD-ILS-IDM-06130 Alarms and Set Points List
Other related P&IDs
AD2-C1-00-QFB-PDW-IDM-00621 Compressed air system P&ID
AD2-C1-00-GMA-PDW-IDM-00791 Plant Drainage System P&ID
AD2-C1-00-LC_-PDW-IDM-00741 P&ID CONDENSATE SYSTEM
AD2-C1-00-H-P-DW-BHI-00510 PROCESS & INSTRUMENT DIAGRAM DRAWING FOR HRSG
AD2-C1-00-PG_-PDW-IDM-00761 Closed auxiliary cooling water system P&ID
AD2-C1-00-QC_-PDW-IDM-00801 Chemical dosing system P&ID
AD2-C1-00-NDA-PDW-IDM-00821 GT Air preheater water system P&ID
AD2-C1-00-EK_-PDW-EMR-00508 PID (GRMS)
BH1003-MBA-MFB030-065001 P&ID Manual Compressor cleaning system (GT)
AD2-C1-00-QJG-MDW-BGW-03001 P&ID diagram (H2 generators)
2nd pass permeate tank documentation
AD2-C1-00-GHC-MDW-LAN-00001 2nd Pass Permeate Tank A/B
Water treatment plant (mixed beds) documentation
AD2-C1-00-GHC-GGP-WET-00001 System Description
AD2-C1-00-GHC-GGP-WET-00005 O&M, and start/up commissioning manuals
AD2-C1-00-GHC-GDW-WET-00501 General arrangement drawings
AD2-C1-00-GHC-MDW-WET-00502 P&ID
AD2-C1-00-GHC-MDS-WET-00503 Data sheets for Compressed air vessel
AD2-C1-00-GHC-MDS-WET-00504 Data sheets for pumps
AD2-C1-00-GHC-MDS-WET-00505 Data sheets for Self-cleaning filter
AD2-C1-00-GHC-MDS-WET-00506 Data sheets for Regeneration dosing system
AD2-C1-00-GHC-MDS-WET-00507 Data sheets for Mixed Ion-exchanger
AD2-C1-00-GHC-MDS-WET-00508 Data sheets for Manual valve
AD2-C1-00-GHC-IDW-WET-06001 Control logic diagrams
AD2-C1-00-GHC-ILS-WET-06007 List of Process Settings and Alarms
Demineralized water tank documentation
AD2-C1-00-GHC-MDW-LAN-00011 Demineralized Tank A/B
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
25 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

Demineralized water distribution pumps documentation


AD2-C1-00-YMB-MDS-CWO-03000 Pump datasheet
AD2-C1-00-YMB-MDW-CWO-03003 Pump curves
AD2-C1-00-YMB-MDW-CWO-03001 Pump GA drawing
PROJECT DOCUMENT OWNER

AL DUR II IWPP
OWNER EPC CONTRACTOR DOCUMENT NUMBER DATE

AD2-C1-00-GHC-PSD-IDM-00693 05/02/2020
DOCUMENT NAME PAGE
26 / 26
Demi Water Storage and Distribution System.
System Description Rev.: 1

7. ANNEXES

 Annex 1 - Demineralized water system settings

 Annex 2 - Demineralized water system Functional Diagram