INSTALLATION NOTES

126
1. BASIC WELD JOINT WILL BE IMPLEMENTED AS A CONNECTION FOR THE
ANGLE BARS IN THE CONDENSER MOUNT.
2. THE THERMAL CAPACITY OF THE EVAPORATOR SHALL BE BASED ON "TD
RATINGS METHOD" AS PER AHRI-STANDARD 420.
301 3. MOTOR BASE AND ALL PERMANENTLY INSTALLED PANELS SHALL BE TYPE
304 STAINLESS STEEL. THE SHIPPING SUPPORTS ARE TO BE CONSTRUCTED
FROM G-325 HOT DIP GALVANIZED STEEL AND SHOULD BE REMOVED AFTER
827 3313 INSTALLATION.
4. FAN MOTORS SHALL BE TOTALLY ENCLOSED AIR OVER DESIGN. FAN MOTOR
BEARINGS SHALL BE PERMANENTLY LUBRICATED WITH GREASE SUITABLE
54 66.7 FOR LOW AMBIENT CONDITIONS. FAN MOTORS SHALL BE PRE-WIRED TO
JUNCTION BOX.
5. THE HEAT EXCHANGER COIL SHALL BE CONSTRUCTED FROM TYPE 304
STAINLESS STEEL TUBING AND ALUMINUM FINS. THE TUBING SHALL BE ROLL
discharge line suction line FORMED, CONTINUOUSLY WELDED AND ANNEALED. THE WELDED TUBE IS
TESTED USING AN EDDY CURRENT DEVICE. THE ROUND TUBING IS FIT INTO
THE ALUMINUM FIN PLATE AND HYDRAULICALLY EXPANDED. THE COIL SHALL
BE EVACUATED AND CHARGED WITH LOW-PRESSURE NITROGEN PRIOR TO
3000 SHIPMENT.
6. DIMENSIONS ARE IN MILLIMETERS
800

flat washer rubber bearing pad


0.5 mm - Thick 1mm - thick
supporting load
GALVANIZED STEEL ANGLE BAR
50mm x 50mm nut anchor bolt to concrete slab

rubber vibration pad for nominal


vibration pad
didtribution of vibration with 0.0254m
CONDENSER SCHEDULE thickness.
TAG NO. me-3215-3
MODEL EFGP 3580.4 concrete ground
REFRIGERANT R22 0.35 - thickness condenser mounted on the concrete wall
COOLING CAPACITY (kW) 252.9
NO. OF FANS 4
AIR FLOW (m³/h)
INLET SIZE (mm)
94612
66.7
3 CONDENSER DETAILS
OUTLET SIZE (mm) 54 M 1 SCALE NTS
PROJECT LEADER INSTRUCTOR PROJECT / LOCATION: GROUP MEMBER PREPARED BY: No. REVISIONS DATE
ST A T E U ENGR. R-DIE BISCOCHO
SHEET CONTENT SHEET NO.

BatStateU AGUSTIN HENRIC FRANCIA


NI
S
TA N G A

VE

R-DIE BISCOCHO DESIGN AND ANALYSIS OF COLD COLD ROOM STORAGE


JOSUA MAGPANTAY
R S IT Y

MECHANICAL ENGINEER STUDENT


BATANGAS STATE UNIVERSITY ENGR. ALLAN B. DE VILLA ROOM STORAGE FOR CHICKEN MEATS
R-DIE BISCOCHO
EQUIPMENT LAYOUT M
BA

PROFESSIONAL MECHANICAL ENGINEER


19 0 3 Alangilan, Batangas City SECTION: ME - 3215 3
PH GROUP NO: 09
I L I PPI N ES MECHANICAL ENGINEERING DEPARTMENT BALAYAN, BATANGAS
DATE SUB: AUGUST 16, 2022