GENERAL NOTES

1. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS


BEFORE EXECUTION OF THE WORK.
2. ALL DIMENSIONS ARE IN FEET & INCHES

3. FIGURED DIMENSIONS SHALL BE FOLLOWED.

4.. THIS DRG. SHOULD BE READ WITH RELEVANT ARCHITECTURAL DRAWINGS

5. ALL REINFORCEMENT SHALL BE OF HIGH YIELD STRENGTH DEFORMED BARS OF


NGL Fe-500 GRADE CONFORMING TO IS: 1786-1985

COLUMN SCHEDULE

DEPTH AS PER SOIL REPORT


COLUMN
6. RCC MEMBER. CONCRETE GRADE. COVER.

U P TO HARD STRATA
FOOTINGS M20 50
COLUMNS M20 40
BEAMS M20 25
COLUMN COLUMN COLUMN COLUMN PEDESTAL

AS PER SITE
OR
TIES PEDESTAL SLAB M20 20

(D)2' MIN
S.No. NO'S REINFORCEMENT REINF,ALONG -B
GROUP SIZE(AxC) SECTION SIZE(ExF) WALLS M20 20

REINF,ALONG -L 7. SAFE BEARING CAPACITY OF SOIL IS CONSIDERED AS 300 KN/Sq.M.


AT A DEPTH OF 6'-0". SITE EXECUTIVES TO VERIFY THE
Ld Ld

D
Y12-6Nos P.C.C 1:4:8
CORRECTNESS OF THE SAME BEFORE EXECUTION OF THE WORK. THE FOUNDATION
SHALL BE PLACED ON FIRM SOIL FREE OF ANY EXPANSIVE SOIL.
1 C1 9 15"X18"

6"
9"X12" TIESY8@8"c/c 8. COVER SPECIFIED SHALL BE PROVIDED TO ALL TYPES OF REINFORCEMENT
SECTION X-X USING DULY CURED WIRED COVER BLOCKS MADE OF SAME GRADE OF CONCRETE
AS THAT OF THE R.C.C MEMBER.

9. SPACER BAR OF 25mm DIA OR DIA OF LARGEST BAR USED AT THE SECTION
Y12-8Nos 3" B 3" SHALL BE PROVIDED AT 1500c/c IN BEAMS WHEREVER TWO OR

3"
MORE LAYERS REINFORCEMENT IS PROVIDED.
2 C2 9"X15" 3 TIESY8@8"c/c 15"X21"
10. FOOTINGS AND COLUMNS ARE DESIGNED FOR G+2 FLOORS ONLY.
2-SETS AS PER ARCHITECTURAL DRAWINGS.

PEDESTAL

Y16- 4Nos + X E
X

REINF ALONG -B
3 C3 9"X15" 4 Y12-4Nos 15"X21"

N
C
COLUMN

F
L
TIESY8@8"c/c
2-SETS
A
REINF ALONG -L

REV. DESCRIPTION BY DATE

3"
ARCHITECT:
M

R.C.C FOOTING SCHEDULE PLAN

S.No. FOOTING PIT SIZE FOOTING SIZE DEPTH BOTTOM REINFORCEMENT


STRUCTURAL CONSULTANTS
F M N L B D ALONG "L" DIRE ALONG "B" DIRE
ALONUM DESIGN
STONE HENGE APARTMENTS,
1 F1 5'-0" 5'-0" 4'-6" 4'-6" 15" Y10-9NO'S Y10-9NO'S # 411, 4th floor,JAWAHAR NAGAR,
RTC X ROADS,Hyderabad-20, A.P,
Tel:9010868666.
2 F2 5'-0" 5'-0" 4'-6" 4'-6" 15" Y10-11NO'S Y10-11NO'S E-Mail: raghu.alonum@gmail.com
OWNER :

3 F3 5'-6" 5'-6" 5'-0" 5'-0" 18" Y10-13NO'S Y10-13NO'S


PROJECT TITLE :

PROPOSED RESIDENTIAL AT BUILDING AT ALWAL

DRAWING TITLE :
COLUMN AND FOOTING DETAILS

DRAWING NO SD-3 REV R0


PROJECT NO 694 CHECKED BY Raghu

SCALE DRAWN BY NK
DATE 03-03-2016 DESIGNED BYEK