Test Report No.

: M-1454/22 Date : 14/06/2022 ULR - TC669722100001454F


Discipline : Electrical Testing Group : Transformer Oil
Customer Name : The Executive Engineer EHV (O&M) Div. MSETCL Jalna
Customer Address: P) Condition at time of collection
A) Make : Kanohar F) Sample Collection Point : Bottom K) Condition of Sample : Good i) Temp. : 28 0 C
B) Ratio : 132 / 33 kV G) Oil Temp. : 50 0C L) Sr. No. : KT-25000/20 ii) Relative humidity : 36 %
C) Capacity : 25 MVA H) Date of Collection : 14-Jun-22 M) Location of Substation : Tr-1, 132 Kv Rajur Q) Condition at time of testing
0
D) Year of Mfg. : 2008 I) Sample Receipt Date : 14-Jun-22 N) Location of Testing : 132 Kv Rajur i) Temp. : 24 C
E) Date of Comm.: - J) Date of Testing : 14-Jun-22 O) Collection By : Lab ( IS 6855 & IS 9434) ii) Humidity : 39 %
Sr. Method Of Test As Per Characteristics as per IS - Specified Values Results
Name of Test Analysis Remark
No. I.S. 1866:2017 Good Fair Poor SI Units Derived
1. Appearance IS 335 : 2018 Clear Pale Yellow Good
0
2. Density at 29.5 C IS 1448-P-16 : 2014 > 0.89 g/ml 0.816 Good
2
3. Kinematic Viscosity at 270C IS 1448-P-25/Sec-01 : 2018 > 27 mm /s 13 Good
4. Inter Facial Tension IS 6104 : 1971 > 28 22 to 28 < 22 mN/m 34 Good
5. Flash Point IS 1448-P-21 : 2019 Maximum decrease 10% 0C (Min.) 162 Good
0
6. Pour Point IS 1448-P-10/Sec-02 : 2013 > -6 C (Max.) -22 Good
7. Neutralization Value IS 1448-P-2 : 2007 < 0.10 0.10 to 0.20 > 0.20 mgKOH/g 0.099 Good
8. Break Down Voltage IS 6792 : 2017 > 50 40 to 50 < 40 KV
66 Good
64 66 66 70 68 62
9. Dielectric Dissipation Factor at 900C IS 6262 : 1971 < 0.10 0.10 to 0.50 > 0.50 0.020 Good
0
10. Resistivity at 90 C IS 6103 : 1971 >3 0.2 to 3 < 0.2 GΩ m 356.2 Good
11. Water Contents IS 13567 : 2018 < 20 20 to 30 > 30 mg/kg 13 Good
12. Sediment & Sludge IS Annex. C of IS 1866:2017 > 0.02 % Nil Good
13. Dissolved Gas Analysis IS 9434 : 2019 CO CH 4 CO 2 C2 H 4 C 2H 6 C2 H 2 H2
Detection Level of G.C (in µl/l) 25 1 25 1 1 1 5
(BDL : Below Detection Level) Result Derived (in µl/l) 81 BDL 701 BDL BDL BDL BDL
Evaluation - For Sr. No. 1 to 12 Please Refer Table No. 5 - Application and Interpretation of tests (Page No. 1 to 4) of IS 1866 : 2017 / IEC 60422 : 2013.
The Quantity and proportion of Dissolve Gases in the oil are within the limits.

Note : 1) The report relates only to the particular sample received for testing in good condition at BRIS. Ravindra More (Technical Manager)
2) The report cannot be reproduced in part under any circumstances Authorised Signatory
This is computer generated Test Report, no signature is required.